ClusterController_Modbus-TI-en-18 | Version 1.8 ENGLISH
Legal Provisions SMA Solar Technology AG
Legal Provisions
The information contained in these documents is the property of SMA Solar Technology AG.
Any publication, whether in whole or in part, requires prior written approval by
SMA Solar Technology AG. Internal reproduction used solely for the purpose of product evaluation
or other proper use is allowed and does not require prior approval.
Trademarks
All trademarks are recognized, even if not explicitly identified as such. Missing designations do not
mean that a product or brand is not a registered trademark.
Modbus® is a registered trademark of Schneider Electric and is licensed by the Modbus Organization, Inc.
4 ClusterController_Modbus-TI-en-18 Technical Information
SMA Solar Technology AG Information on this Document
Icon
Explanation
Indicates a hazardous situation that, if not avoided, will result in
death or serious injury.
Indicates a hazardous situation that, if not avoided, can result in
death or serious injury.
Indicates a hazardous situation that, if not avoided, can result in
minor or moderate injury.
Indicates a situation that, if not avoided, can result in property damage.
Information that is important for a specific topic or goal, but is not
safety-relevant.
◻
Indicates a requirement for meeting a specific goal.
1 Information on this Document
Validity
This document is applicable for device type "CLCON-10" and device type "CLCON-S-10"*
(SMA Cluster Controller). It describes the Modbus interface of the SMA Cluster Controller, the
variant of the "Modbus® Application Protocol" implemented by SMA, and the corresponding parameters, measured values and data exchange formats.
* Not available in all countries (see the SMA Cluster Controller product page at
www.SMA-Solar.com)
This document does not contain any information on software which can communicate with the
Modbus interface (see the software manufacturer's manual).
Target Group
This document is intended for qualified persons. Only persons with appropriate skills are allowed to
perform the tasks described in this document (see Section 2.2 "Skills of Qualified Persons", page 7)
Symbols
Technical Information ClusterController_Modbus-TI-en-18 5
Information on this Document SMA Solar Technology AG
Typography
Application
Example
bold
• Elements to be selected
• Elements on a user interface
• File names
• Parameters
• Select Settings.
• Control via communication.
• The file usrprofile.xml
• The values Major and Minor
Complete designation
Designation in this document
Modbus register
Register
Photovoltaic system
PV system
SMA Cluster Controller
Cluster Controller
Abbreviation
Designation
Explanation
GFDI
Ground-Fault Detection and
Interruption
Detection of the grounding error and subsequent interruption of the electric circuit.
PMAX
Set active power limit
The device can generate active power up to
this limit.
Power Balancer
-
The Power Balancer is a function in
Sunny Mini Central devices for controlling
three-phase grid feed-in, for example, to avoid
unbalanced loads.
SMA fieldbus
-
Hardware interface for communication between SMA devices (e.g. Speedwire). For
information on the supported communication
interfaces, refer to the datasheet of the SMA
device being used.
SUSy ID
SMA update system ID
Numeric value that identifies a specific
SMA device type, e.g.
128 = STP nn000TL-10.
Typographies
Nomenclature
Abbreviations
6 ClusterController_Modbus-TI-en-18 Technical Information
SMA Solar Technology AG Safety
Damage to SMA inverters
The parameters of the SMA inverters that can be changed with writable Modbus registers (RW)
are intended for long-term storage of device settings. Cyclical changing of these parameters leads
to destruction of the flash memory of the devices.
• Device parameters must not be changed cyclically.
Contact the SMA Service Line if you would like to automate the remote control of your PV system
(see Section 9 "Contact", page 39).
2 Safety
2.1 Intended Use
The Modbus interface of the SMA Cluster Controller is designed for industrial use and has the
following tasks:
• Remote control of the grid management services of a PV system.
• Remote-controlled querying of the measured values of a PV system.
• Remote-controlled changing of the parameters of a PV system.
The Modbus interface can be used via the protocol Modbus TCP and
by the protocol Modbus UDP.
The enclosed documentation is an integral part of this product:
• Read and observe the documentation.
• Keep the documentation in a convenient place for future reference.
2.2 Skills of Qualified Persons
The activities described in this document must only be performed by qualified persons.
Qualified persons must have the following skills:
• Knowledge of IP-based network protocols
• Training in the installation and configuration of IT systems
• Knowledge of and compliance with this document and all safety information
2.3 Safety Information
This section contains safety information that must be observed at all times when working on or with
the product. To prevent personal injury and property damage and to ensure long-term operation of
the product, read this section carefully and observe all safety information at all times.
Technical Information ClusterController_Modbus-TI-en-18 7
Safety SMA Solar Technology AG
Data security in Ethernet networks
You can connect the Cluster Controller to the Internet. When connecting to the Internet,
there is a risk that unauthorized users can access and manipulate the data of your PV system.
• Take appropriate protective measures, for example:
• Set up a firewall
• Close unnecessary network ports
• Only enable remote access via VPN tunnel
• Do not set up port forwarding at the Modbus port in use
2.4 Information on Data Security
8 ClusterController_Modbus-TI-en-18 Technical Information
SMA Solar Technology AG Product Description
3 Product Description
3.1 Modbus Protocol
The Modbus Application Protocol is an industrial communication protocol that is currently used in
the solar sector mainly for system communication in PV power plants.
The Modbus protocol has been developed for reading data from or writing data to clearly defined
data areas. The Modbus specification does not prescribe what data is within which data area. The
data areas must be defined device-specifically in Modbus profiles. With knowledge of the devicespecific Modbus profile, a Modbus master (e.g. SCADA system) can access the data of a Modbus
slave (e.g. SMA Cluster Controller). Information on firmware versions and device-specific Modbus
registers of SMA products can be found on our product pages or Modbus page at
www.SMA-Solar.com.
The special Modbus profile for SMA devices is the SMA Modbus profile.
3.2 SMA Modbus Profile
The SMA Modbus profile contains definitions for SMA devices. A reduction of the available data
on SMA devices was carried out for the definition and this was then assigned to the corresponding
Modbus registers. The SMA Modbus profile contains, for example, the total and daily energy,
current power, voltage and current levels. The assignment between SMA device data and Modbus
addresses is split into ranges in the SMA Modbus profile and these can be addressed via unit IDs
(see Section 3.5 "Addressing and Data Transmission in the Modbus Protocol", page 12).
To enable access to data of an SMA device, a special gateway is required and this is provided by
way of the Cluster Controller.
3.3 User-Defined Modbus Profile
The user-defined Modbus profile enables you to reassign Modbus addresses of the SMA Modbus
profile. One advantage of reassigning Modbus addresses is, for example, that you can arrange
relevant measured values and parameters in sequence for a specific purpose. These addresses can
then be read and written in a single data block.
3.4 PV System Topology
The SMA Modbus profile was developed for a hierarchical system structure. In this structure, the
Cluster Controller is a communication device which is equipped with a Modbus TCP/IP and Modbus UDP/IP interface. All additional SMA devices that are connected to the Cluster Controller via
the SMA fieldbus are subordinate to the Cluster Controller. From the perspective of the Modbus
protocol, the Cluster Controller represents a Modbus slave that provides a gateway to SMA devices. The SMA devices can only be addressed using this gateway per unit ID.
Technical Information ClusterController_Modbus-TI-en-18 9
Product Description SMA Solar Technology AG
Line
Explanation
IP network connection between SCADA system and Cluster Controller
(PV system router)
SMA fieldbus
Logical assignment of SMA device to unit ID
Example 1: PV System Topology from the Perspective of the SMA Devices
10 ClusterController_Modbus-TI-en-18 Technical Information
SMA Solar Technology AG Product Description
Example 2: PV System Topology from the Perspective of the Modbus Protocol
In the following example, an inverter is assigned to a unit ID between 3 and 247 in each case. This
way the inverter data can be addressed in the Modbus protocol. Unit ID 1 represents the gateway
to the Modbus protocol and unit ID 2, the PV system parameters.
Technical Information ClusterController_Modbus-TI-en-18 11
Product Description SMA Solar Technology AG
Unit ID
Explanation
1
This unit ID is reserved for the gateway of the Cluster Controller.
2
This unit ID is reserved for the system parameters.
3 to 247
The unit IDs 3 to 247 are used for addressing individual devices and for the userdefined Modbus profile. Information on firmware versions and device-specific Modbus registers of SMA products can be found on our product pages or Modbus page
at www.SMA-Solar.com. You can change the assignment of these unit IDs (see Section 4.2 "Information on Changing Unit IDs", 17).
255
Devices which are assigned to this unit ID, were connected to the Cluster Controller or
replaced after activation of the Modbus server. The devices cannot be addressed with
this unit ID. You must assign unit IDs from the range 3 to 247 to these devices (see
Section 4.2 "Information on Changing Unit IDs", page 17).
3.5 Addressing and Data Transmission in the Modbus Protocol
3.5.1 Unit IDs
The Unit ID is a superordinate addressing type in the Modbus protocol. The SMA Modbus protocol
has 247 unit IDs, of which, 245 can be assigned to individual devices. If a unit ID is assigned to a
device, then the parameters and measured values of this device can be accessed.
The following table shows an overview of the unit IDs in the SMA Modbus profile:
12 ClusterController_Modbus-TI-en-18 Technical Information
SMA Solar Technology AG Product Description
3.5.2 Assignment of the Modbus Register to Unit IDs
The assignment of the parameters and measured values of the SMA devices to Modbus register
addresses is achieved using assignment tables and is also shown in this document (see Section 5
"SMA Modbus Profile—Assignment Tables", page 23).
In the assignment table "Gateway (unit ID = 1)",the assignment of SMA devices to individual
unit IDs is saved in the Modbus registers from address 42109. Each assignment has an address
range of four Modbus registers, although only the corresponding register is writable with the
unit ID.
In the assignment table "PV System Parameters (unit ID = 2)", parameters and measured values of
the Cluster Controller and the PV system are stored.
In the assignment table "SMA devices (unit ID = 3 to 247)", the parameters and measured values
intended for all SMA devices are stored. The individual SMA devices use a subset of these for their
device-specific parameters and measured values. Information on firmware versions and devicespecific Modbus registers of SMA products can be found on our product pages or Modbus page
at www.SMA-Solar.com.
3.5.3 Modbus Register Address, Register Width and Data Block
A Modbus register is 16 bits wide. For wider data items, connected Modbus registers are used and
considered as data blocks. The number of connected Modbus registers is indicated in the assignment tables. The address of the first Modbus register in a data block is the start address of the data
block.
3.5.4 Address Range for Modbus Register
For addressing Modbus registers, the address range 0 to 0xFFFF is available with 65536 addresses.
3.5.5 Data Transmission
In accordance with the Modbus specification, only a specific volume of data can be transported in
a single data transmission in a simple protocol data unit (PDU). The data also contains functiondependent parameters such as the function code, start address or number of Modbus registers to
be transmitted. The amount of data depends on the Modbus command used and has to be taken
into account during data transmission. You can find the number of possible Modbus registers per
command in section 3.6.
With data storage in the Motorola format "Big Endian", data transmission begins with the high byte
and then the low byte of the Modbus register.
Technical Information ClusterController_Modbus-TI-en-18 13
Product Description SMA Solar Technology AG
Modbus command
Hexadecimal value
Data volume
(number of registers)1
Read Holding Registers
0x03
1 to 125
Read Input Registers
0x04
1 to 125
Write Single Register
0x06
1
Write Multiple Registers
0x10
1 to 123
Read Write Multiple Registers
0x17
Read: 1 to 125, Write: 1 to 121
1
3.6 Reading and Writing of Data
The Modbus interface can be used via the protocol Modbus TCP and by the protocol Modbus
UDP. Using Modbus TCP enables read- and write access (RW) and using Modbus UDP enables
only write access (WO) to the Modbus register.
The following Modbus commands are supported by the implemented Modbus interface:
Error messages on reading or writing individual Modbus registers
If a Modbus register is accessed, which is not contained in a Modbus profile, or if a Modbus command is incorrect, a Modbus exception is generated. Modbus exceptions are also generated when
write access occurs on a read-only Modbus register or read access occurs on a write-only Modbus
register.
Reading or writing of data blocks
To prevent inconsistencies, data blocks of associated registers or register ranges must be read or
written consecutively. The 4 bytes of a 64-bit Modbus register must, for example, be read with an
operation in a 64-bit SMA data type.
Error message on writing multiple Modbus registers as a data block
If multiple registers are written as a data block (Modbus commands 0x10 and 0x17) and an error
occurs during writing, the faulty register as well as all the subsequent registers in the packet will be
rejected. In the event of an error, a Modbus exception will be generated.
Modbus exceptions
For Modbus exceptions, see "Modbus Application Protocol Specification" at
http://www.modbus.org/specs.php.
Number of Modbus registers transferable as data block per command
14 ClusterController_Modbus-TI-en-18 Technical Information
SMA Solar Technology AG Product Description
Type
Description
NaN value
S16
A signed word (16-bit).
0x8000
S32
A signed double word (32-bit).
0x8000 0000
STR32
32 byte data field, in UTF8 format.
ZERO
U16
A word (16-bit).
0xFFFF
U32
A double word (32-bit).
0xFFFF FFFF or -1
U32
For status values, only the lower 24 bits of a double word (32bit) are used.
0xFFFF FD or 0xFFFF
FE or -1
U64
A quadruple word (64-bit).
0xFFFF FFFF FFFF
FFFF or -1
Format
Explanation
Duration
Time in seconds, in minutes or in hours, depending on the Modbus register.
DT
Date/time, in accordance with country setting. Transmission as UTC
(seconds since 1970-01-01).
ENUM
Coded numerical values. The breakdown of the possible codes can be found directly
under the designation of the Modbus register in the SMA Modbus profile—assignment
tables (see also Section 8.6 "Frequently Used Number Codes", page 38).
FIX0
Decimal number, commercially rounded, no decimal place.
FIX1
Decimal number, commercially rounded, one decimal place.
3.7 SMA Data Types and NaN Values
The following table shows the data types used in the SMA Modbus profile and compares these to
possible NaN values. The SMA data types are listed in the assignment tables in the Type column.
They describe the data widths of the assigned values:
3.8 SMA Data Formats
The following SMA data formats describe how SMA data is to be interpreted. The data formats are
important, for example, for the display of data or for its further processing. The SMA data formats
are listed in the Format column of the assignment tables.
Technical Information ClusterController_Modbus-TI-en-18 15
Product Description SMA Solar Technology AG
FIX2
Decimal number, commercially rounded, two decimal places.
FIX3
Decimal number, commercially rounded, three decimal places.
FW
Firmware version (see "Firmware version extract" below)
IP4
4-byte IP address (IPv4) of the form XXX.XXX.XXX.XXX.
RAW
Text or number. A RAW number has no decimal places and no thousand or other
separation indicators.
REV
Revision number of the form 2.3.4.5.
TEMP
Temperature values are stored in special Modbus registers in degrees Celsius (°C), in
degrees Fahrenheit (°F), or in Kelvin K. The values are commercially rounded, with
one decimal place.
UTF8
Data in UTF8 format.
Release type
Release-type coding
Explanation
0 N No revision number
1 E Experimental release
2 A Alpha release
3 B Beta release
4 R Release
5 S Special release
> 5
As number
No special interpretation
Firmware version extract, format "FW": From the delivered DWORD, four values are extracted. The values Major and Minor are contained BCD-coded in bytes 1 and 2. Byte 3 contains the
Build value (not BCD-coded). Byte 4 contains the Release Type value according to the following
table:
Example:
Firmware version of the product: 1.5.10.R
Values from DWORD: Major: 1, Minor: 5, Build: 10, Release type: 4
(Hex: 0x1 0x5 0xA 0x4)
16 ClusterController_Modbus-TI-en-18 Technical Information
SMA Solar Technology AG Commissioning and Configuration
Allocation of unit IDs by activation of the Modbus servers
Upon activation of the Modbus servers of the Cluster Controller, unit IDs are assigned to
the SMA devices already connected to the Cluster Controller. The protocol types TCP/UDP
can be activated individually or together. If one or both of the servers are deactivated and
reactivated, the previously assigned Modbus Unit IDs are maintained.
4 Commissioning and Configuration
4.1 Commissioning Steps and Requirements
Requirements:
☐ The devices of the PV system must be connected to the Cluster Controller and the
Cluster Controller must be commissioned (for information on connection and commissioning,
see the Cluster Controller installation manual).
☐ You must log in as installer to the Cluster Controller (for login to or logout of the
Cluster Controller, see the Cluster Controller user manual).
Procedure:
1. Activate the Modbus server(s) and, if required, configure the communication ports
(for Modbus configuration, see the Cluster Controller user manual).
2. Change the unit IDs if, after activation of the Modbus servers, further SMA devices have
been added to the PV system or SMA devices have been replaced (see the following sections).
4.2 Information on Changing Unit IDs
You can change the unit IDs of SMA devices. A change is required, for example, if additional or
changed SMA devices are connected to the Cluster Controller after activation of the Modbus
servers. By way of the automatic detection of the PV system, additional or changed devices are
assigned the Modbus unit ID = 255 (NaN). On the other hand, it may be necessary to change the
unit IDs if a restructuring of the system topology is required, for example, to better map the physical
arrangement of the devices in the Modbus protocol.
Depending on whether you wish to change individual unit IDs or restructure the entire system topology, you have two options:
• Changing Unit IDs via the gateway (recommended for changing individual Unit IDs)
• Changing Unit IDs via an XML file (recommended for restructuring of the system topology)
Both of these methods are described in separate Sections.
Technical Information ClusterController_Modbus-TI-en-18 17
Commissioning and Configuration SMA Solar Technology AG
Accessing the gateway
You access the gateway via the IP address of the Cluster Controller, under the unit ID = 1.
Modbus address
Content
Description
Device #
………
42109
158
SUSy-ID
A
42110
2145600972
Serial number
A
42112
3
Unit ID
A
42113
158
SUSy-ID
B
42114
2145600320
Serial number
B
42116
4
Unit ID
B
42117
158
SUSy-ID
C
42118
2145600934
Serial number
C
42120
255
Unit ID
C
… … …
…
4.3 Changing Unit IDs via the Gateway
4.3.1 Reading Out the Gateway
You can read out the individual unit IDs of the SMA devices from the gateway, for example, using
a SCADA system.
The assignment of the system devices for unit IDs 3 to 247 is stored in the Modbus registers from
address 42109. Each assignment has an address range of four Modbus registers. You can find the
Modbus register of the gateway in Section 5.2 "Gateway", page 24.
Example "Read out additional device from the gateway“
Via automatic detection, an additional SMA device was assigned to unit ID = 255 (indicated with
C in column "Device #" in the following table). The assignments of the gateway were, as follows
here, shown with a SCADA system as a table:
18 ClusterController_Modbus-TI-en-18 Technical Information
SMA Solar Technology AG Commissioning and Configuration
Do not assign unit IDs more than once
You must not assign a Unit ID more than once. In the event of a Modbus query with a unit
ID that has been assigned more than once, the data is read out for the device that is entered with this unit ID in the gateway under the lowest Modbus address.
Modbus address
Designation
After detection
Modified
42117
SUSy-ID
158
158
42118
Serial number
2145600934
2145600934
42120
Unit ID
255 (NaN)
5
4.3.2 Changing A Unit ID in the Gateway
You change a unit ID by writing it to the relevant Modbus address. All three of the Modbus registers that belong to a device-unit-ID assignment must be transmitted in a single data block, although
only the register with the unit ID is writable. For the following example, this means that all the data
of the three Modbus addresses 42117, 42118 and 42120 must be contained in the data block.
Example "Changing A Unit ID in the Gateway"
The following table shows an example of assignment of a device to a unit ID. An inverter was
subsequently detected with SUSy ID = 158 and serial number 2145600934, as the third device in
the PV system (Modbus addresses 42117 to 42120). The unit ID of this device was manually set to
5:
Technical Information ClusterController_Modbus-TI-en-18 19
Commissioning and Configuration SMA Solar Technology AG
Uploading and downloading XML files
For more information on uploading and downloading XML files via the user interface, see
the SMA Cluster Controller user manual.
XML tag or attribute
Explanation
<device…/>
Within the tag "Device" is the assignment of a device to a unit ID.
regoffs=”aaa“
Number of the device in file sysplant.xml. The number must not necessarily be assigned sequentially. There are four Modbus register addresses between two devices. Regoffs = 0 defines the first device under
the Modbus address 42109, Regoffs = 244 the last device under the
Modbus address 43085.
susyid=”bbb“
SUSy ID of the device
4.4 Changing Unit IDs via the XML File usrplant.xml
4.4.1 Overview
The Cluster Controller stores the assignments of the devices of the PV system to unit IDs in the file
sysplant.xml. This file contains an excerpt of the gateway (see Section 5.2 "Gateway (Unit ID =
1)", page 24). If new SMA devices are added or if SMA devices are replaced, these are respectively added to the available XML structure of this file with unit ID = 255 by the Cluster Controller.
You can define your own variant of this file in the file usrplant.xml. You can use
sysplant.xml as a template for usrplant.xml.
You can download the file sysplant.xml from the Cluster Controller.
The file usrplant.xml must be activated in the Cluster Controller. Once the file usrplant.xml is
activated, the file sysplant.xml is not taken into consideration for the duration of the activation.
4.4.2 Structure of the XML File usrplant.xml
The files sysplant.xml and usrplant.xml have the same tag structure.
The basic structure of the files is as follows:
To activate the file usrplant.xml, upload the file to the Cluster Controller. All the specifications in
the file are checked. If the file contains no errors, its contents are entered into the system.
A changed usrplant.xml becomes effective a few seconds after it is activated. Once the file
usrplant.xml is activated, the file sysplant.xml is not taken into consideration for the duration of
the activation.
Deactivating the file usrplant.xml:
To deactivate the file usrplant.xml, upload a version of this file containing no device tags to the
Cluster Controller. Both of the following lines show the structure of such a usrplant.xml file:
Without the device tags in the file usrplant.xml, the system returns to the specifications saved in
the file sysplant.xml. A changed usrplant.xml becomes effective a few seconds after it is saved
to the Cluster Controller.
Technical Information ClusterController_Modbus-TI-en-18 21
Commissioning and Configuration SMA Solar Technology AG
Save data prior to restoring default settings
By resetting the Cluster Controller to default settings, the user-defined PV system topology
usrplant.xml and the user-defined Modbus profile usrprofile.xml are deleted. Save these files
before resetting.
4.5 Resetting the Cluster Controller to the Default Settings
By resetting the Cluster Controller to the default settings, the previously assigned unit IDs are deleted and reassigned – file sysplant.xml is therefore rewritten. As a result, all connected SMA devices are assigned a new unit ID.
For further information on resetting to default settings and saving XML files, refer to the
SMA Cluster Controller user manual.
22 ClusterController_Modbus-TI-en-18 Technical Information
SMA Solar Technology AG SMA Modbus Profile—Assignment Tables
Information
Explanation
ADR (DEC)
Decimal Modbus address (see Section 3.5.3 "Modbus Register Address,
Register Width and Data Block", page 13 onwards)
Description/
number code(s)
Short description of the Modbus register and the number codes used.
CNT
Number of assigned Modbus registers.
Type
Data type, e.g. V32 = 32 bits without prefix (see Section 3.7 "SMA Data
Types and NaN Values", page 15).
Format
Data format of saved value, e.g. DT = date, FIX n = output with n decimal
places, TEMP = output as temperature (see Section 3.8 "SMA Data Formats", page 15).
Access
Access type:
RO: Read only (only Modbus TCP)
RW: Read and write (only Modbus TCP). With Modbus UDP, all RW
registers are write-only (WO register).
WO: Write only (Modbus TCP and Modbus UDP)
If an access type is not allowed, a Modbus exception is generated in the
event of access with an access type that is not allowed.
5 SMA Modbus Profile—Assignment Tables
5.1 Information on the Assignment Tables
The following subsections are sorted by unit ID. Each contains a table of the Modbus addresses
which can be accessed using this unit ID. The tables present the following information:
Technical Information ClusterController_Modbus-TI-en-18 23
SMA Modbus Profile—Assignment Tables SMA Solar Technology AG
ADR (DEC)
Description/number code(s)
CNT (WORD) Type Format Access
30001
Version number of the SMA Modbus profile
2
U32
RAW
RO
30003
SUSy ID (of the Cluster Controller)
2
U32
RAW
RO
30005
Serial number (of the Cluster Controller)
2
U32
RAW
RO
30007
Modbus data change: meter value is increased by
the Cluster Controller if new data is available.
2
U32
RAW
RO
30051
Device class:
8000 = All devices
8001 = PV inverter
8002 = Wind power inverter
8007 = Battery inverter
8033 = Load
8064 = Sensor technology general
8065 = Energy meter
8128 = Communication products
2
U32
ENUM
RO
30193
UTC system time (s)
2
U32
DT
RO
30513
Total energy fed in across all line conductors, in Wh
(accumulated values of the inverters)
4
U64
FIX0
RO
30517
Energy fed in on current day across all line conductors, in Wh (accumulated values of the inverters)
4
U64
FIX0
RO
30775
Current active power on all line conductors (W),
accumulated values of the inverters
2
S32
FIX0
RO
30805
Reactive power on all line conductors (var),
accumulated values of the inverters
2
S32
FIX0
RO
5.2 Gateway (Unit ID = 1)
In the following table you can find the parameters and measured values provided by the gateway,
which you can access under unit ID = 1as well as the assignment of the SMA devices to the
unit IDs. You can access the gateway via the IP address of the Cluster Controller:
24 ClusterController_Modbus-TI-en-18 Technical Information
SMA Solar Technology AGSMA Modbus Profile—Assignment Tables
34653
Digital input group 1, coded
as status:
311 = Open
2055 = DI1
2056 = DI1 DI2
2057 = DI1 DI2 DI3
2058= DI1 DI2 DI3 DI4
2059 = DI1 DI2 DI4
2060 = DI1 DI3
Technical Information ClusterController_Modbus-TI-en-18 25
SMA Modbus Profile—Assignment Tables SMA Solar Technology AG
Unit ID = 255
For unit ID = 255, observe Section 4.3 "Changing Unit IDs via the Gateway", page 18.
Modbus exception on accessing empty assignments
If, in the address range 42109 to 43088, individual Modbus registers or a data block are
accessed which do not contain any assignment of unit IDs to SMA devices, a Modbus exception is generated.
ADR (DEC)
Description/number code(s)
CNT (WORD) Type Format Access
30193
UTC system time, in s
2
U32
DT
RO
30513
Total energy fed in across all line conductors, in Wh
(accumulated values of the inverters)
4
U64
FIX0
RO
30517
Energy fed in on current day across all line conductors, in Wh (accumulated values of the inverters)
4
U64
FIX0
RO
30775
Current active power on all line conductors (W),
accumulated values of the inverters
2
S32
FIX0
RO
30805
Reactive power across all line conductors (VAr)
(accumulated values of the inverters)
2
S32
FIX0
RO
31235
Active power setpoint Digital I/O in %
2
U32
FIX2
RO
31237
Active power setpoint Analog input in %
2
U32
FIX2
RO
31239
Active power setpoint in %s
2
U32
FIX2
RO
5.3 System Parameters (Unit ID = 2)
In the following table , you can find the PV system parameters that you can access using unit ID =
2. The system parameters represent measured values and parameters of the Cluster Controller and
also PV system devices that are connected via the Modbus protocol. Parameters such as time
settings are transferred by the Cluster Controller to the devices of the PV system and there, depending on the device type, processed further. Measured values such as energy meter values are queried by the devices and made available as accumulated values:
26 ClusterController_Modbus-TI-en-18 Technical Information
SMA Solar Technology AGSMA Modbus Profile—Assignment Tables
Specification Modbus Electric utility company
31241
Active power setpoint in %s
Specification Modbus Direct marketing
2
U32
FIX2
RO
31243
Resulting setpoint in %
(minimum value definition of all specifications)
2
U32
FIX2
RO
31249
Current utility grid export active power P in W (actual
value of the active power fed in at the grid-connection
point; measured with an external measuring device).
2
S32
FIX0
RO
31251
Current utility grid export reactive power Q in VAr
(actual value of the reactive power fed in at the gridconnection point; measured with an external measuring device).
2
S32
FIX0
RO
34609
Ambient temperature (°C)
2
S32
TEMP
RO
34611
Highest measured ambient temperature (°C)
2
S32
TEMP
RO
34613
Total irradiation on the sensor surface (W/m²)
2
U32
FIX0
RO
34615
Wind speed (m/s)
2
U32
FIX1
RO
34617
Humidity (%)
2
U32
FIX2
RO
34619
Air pressure (Pa)
2
U32
FIX2
RO
34621
PV module temperature (°C)
2
S32
TEMP
RO
34623
Total irradiation on the external irradiation sensor/pyranometer (W/m²)
2
U32
FIX0
RO
34625
Ambient temperature (°F)
2
S32
TEMP
RO
34627
Ambient temperature (K)
2
S32
TEMP
RO
34629
PV module temperature (°F)
2
S32
TEMP
RO
34631
PV module temperature (K)
2
S32
TEMP
RO
34633
Wind speed (km/h)
2
U32
FIX1
RO
34635
Wind speed (mph)
2
U32
FIX1
RO
34637
Analog current input 1 (mA)
2
S32
FIX2
RO
34639
Analog current input 2 (mA)
2
S32
FIX2
RO
Technical Information ClusterController_Modbus-TI-en-18 27
SMA Modbus Profile—Assignment Tables SMA Solar Technology AG
34641
Analog current input 3 (mA)
2
S32
FIX2
RO
34643
Analog current input 4 (mA)
2
S32
FIX2
RO
34645
Analog voltage input 1 (V)
2
S32
FIX2
RO
34647
Analog voltage input 2 (V)
2
S32
FIX2
RO
34649
Analog voltage input 3 (V)
2
S32
FIX2
RO
34651
Analog voltage input 4 (V)
2
S32
FIX2
RO
34653
Digital input group 1, coded
as status:
311 = Open
2055 = DI1
2056 = DI1 DI2
2057 = DI1 DI2 DI3
2058= DI1 DI2 DI3 DI4
2059 = DI1 DI2 DI4
2060 = DI1 DI3
Reading and setting the time zone (see Section 8.5
"Number Codes of the Time Zones", page 36).
2
U32
ENUM
RW
40005
Automatic daylight saving time conversion active:
1129 = Active
1130 = Not active
2
U32
ENUM
RW
28 ClusterController_Modbus-TI-en-18 Technical Information
SMA Solar Technology AGSMA Modbus Profile—Assignment Tables
40493
Direct marketer:
Active power setpoint P, in % of the maximum active
power (PMAX) of the PV plant.
Value range:
-100.00% to < 0% = Load
0% = No active power
< 0% to +100.00% = Generator
1
S16
FIX2
WO
41167
Active power setpoint in % (manual specification)
2
U32
FIX2
RO
Technical Information ClusterController_Modbus-TI-en-18 29
User-Defined Modbus Profile SMA Solar Technology AG
XML tag or attribute
Explanation
<virtual_modbusprofile>
</virtual_modbusprofile>
A user-defined Modbus profile is created within this XML structure.
<channel />
Within a channel tag, a Modbus address of a unit ID is redefined:
unitid="aaa"
Specifies the unit ID of the device whose Modbus addresses are to be
used as a source. Possible unit IDs for individual devices are 3 to 247.
source=”bbbbb”
Specifies a Modbus address of the devices selected under "unitid",
whose parameters or measured values are to be used as source (see
Section 5 "SMA Modbus Profile—Assignment Tables", page 23).
6 User-Defined Modbus Profile
With the user-defined Modbus profile, the Modbus addresses that are available in the SMA Modbus profile for the individual unit IDs can be assigned to different Modbus addresses. You can use
the entire Modbus address range from 0 to 65535. One advantage of the user-defined Modbus
profile can be that the measured values and parameters relevant for controlling your system can be
applied to consecutive Modbus addresses. These addresses can then be read or written in a single
data block.
The user-defined Modbus profile can be called up via the gateway like an additional device and
has a separate unit ID which you can define between 3 and 247 (see Section 3.5.1 "Unit IDs",
page 12).
6.1 Structure of the XML File for the User-Defined
Modbus Profile
The user-defined Modbus profile is created in the file usrprofile.xml .
The basic structure of the XML file is as follows:
<?xml version=“1.0“ encoding=“UTF-8“?>
<virtual_modbusprofile>
<channel unitid=”aaa” source=”bbbbb” destination=”ccccc” />…<!—End of the instructions-->
</virtual_modbusprofile>
Legend for XML tags and attributes:
30 ClusterController_Modbus-TI-en-18 Technical Information
SMA Solar Technology AGUser-Defined Modbus Profile
destination="ccccc"
Specifies the new Modbus address at which the parameter or measured
value is to be accessed (0 to 65535). Note the number of Modbus
registers that are stored at the original address. The destination registers
must not overlap. If incomplete Modbus registers are called up later, a
Modbus exception is generated. If register addresses are called up,
which are not filled with values, NaN is returned.
<!--xyz-->
Comments out the range xyz, for example, to deactivate an instruction.
ADR (DEC)
Description/number code(s)
CNT (WORD) Type Format Access
30775
AC active power across all line conductors (W)
2
S32
FIX0
RO
30805
Reactive power across all line conductors (VAr)
2
S32
FIX0
RO
30813
Apparent power across all line conductors (VA)
2
S32
FIX0
RO
Modbus exceptions
For Modbus exceptions, see "Modbus Application Protocol Specification" at
http://www.modbus.org/specs.php.
6.2 Example of a User-Defined Modbus Profile
The Modbus registers for apparent power, active power and reactive power of the devices stored
under unit IDs 3 and 4 are to be retrievable in a user-defined Modbus profile from address 0 at
consecutive Modbus addresses (the following table is an excerpt from the SMA Modbus profile):
The exact appearance of the XML file follows from the example:
<?xml version=“1.0“ encoding=“UTF-8“?>
Technical Information ClusterController_Modbus-TI-en-18 31
User-Defined Modbus Profile SMA Solar Technology AG
Uploading and downloading XML files
For more information on uploading and downloading XML files via the user interface, see
the SMA Cluster Controller user manual.
6.3 Activating and Deactivating User-Defined Modbus Profile
To activate your user-defined Modbus profile, upload the file usrprofile.xml to the Cluster Controller, restart it, and activate the user-defined Modbus profile as described below.
If the usage of the user-defined Modbus profile on the Cluster Controller is deactivated, the userdefined assignments are lost and only the SMA Modbus profile remains active.
Activating A User-Defined Modbus Profile
You activate a user-defined Modbus profile by creating a device entry with the attribute "susyid=0"
in file usrplant.xml (you can find more information on the file usrplant.xml in Section 4.4
"Changing Unit IDs via the XML File usrplant.xml", page 20).
Example:
The following device entry activates a user-defined Modbus profile that is entered as the tenth
device in the gateway.
<device regoffs=”9“ susyid=”0“ serial=”0“ unitid=”100“ />
Deactivating A User-Defined Modbus profile
You deactivate a user-defined Modbus profile by commenting out in its device line in the file
usrplant.xml and re-uploading this to the Cluster Controller (for more information on the
usrplant.xml file, see Section 4.4 "Changing Unit IDs via the XML File usrplant.xml", page 20).
In the following example, you can see a commenting out applied to the line with the user-defined
Modbus profile:
32 ClusterController_Modbus-TI-en-18 Technical Information
SMA Solar Technology AG Troubleshooting
The event numbers of the SMA devices cannot be decrypted with the number
codes in this document.
The event numbers of the SMA devices are device-specific and cannot be decrypted with
the number codes in this document.
To decrypt the event numbers of low or medium-power inverters, you require additional
information (operating parameters/measured values, see Technical Description "Measured
Values and Parameters" at www.SMA-Solar.com).
To decrypt the event numbers of central inverters, contact the SMA Service Line (see Section
9 "Contact", page 39).
7 Troubleshooting
You can find information on error analysis of the SMA Modbus profile in Section 3.6 "Reading and
Writing of Data", page 14.
For troubleshooting of the SMA devices, go to Modbus address 30197 and use the event numbers
displayed here.
Technical Information ClusterController_Modbus-TI-en-18 33
Technical Data SMA Solar Technology AG
Device type
Maximum number of SMA devices
CLCON-10
75
CLCON-S-10
25
Network protocol
Communication port, default setting
TCP
502
UDP
502
Using free communication ports
You should only use free communication ports. The following range is generally available:
49152 to 65535.
You can find more information on occupied ports in the database "Service Name and
Transport Protocol Port Number Registry" at http://www.iana.org/assignments/servicenames-port-numbers/service-names-port-numbers.xml.
Changing the communication port
If you change one of the communication ports of the Cluster Controller, you must also
change the corresponding communication port of a connected Modbus master system.
Otherwise the Cluster Controller can no longer be accessed via the Modbus protocol.
8 Technical Data
8.1 Supported SMA Inverters
All inverters with integrated or retrofitted Speedwire/Webconnect interfaces are supported.
Information on whether an inverter has an integrated Speedwire/Webconnect interface or can be
retrofitted with a Speedwire/Webconnect interface can be found on the product page of the respective inverter at www.SMA-Solar.com.
8.2 Number of SMA Devices
The following table contains details on the maximum number of SMA devices that can be operated
with the Cluster Controller.
8.3 Modbus Communication Ports
The following table shows the default settings of the supported network protocols:
34 ClusterController_Modbus-TI-en-18 Technical Information
SMA Solar Technology AG Technical Data
Damage to SMA inverters
The parameters of the SMA inverters that can be changed with writable Modbus registers (RW)
are intended for long-term storage of device settings. Cyclical changing of these parameters leads
to destruction of the flash memory of the devices.
• Device parameters must not be changed cyclically.
Contact the SMA Service Line if you would like to automate the remote control of your PV system
(see Section 9 "Contact", page 39).
8.4 Data Processing and Time Behavior
In this Section, you can find typical data processing and reaction times of the Cluster Controller
Modbus interface and time details for saving parameters in SMA devices.
Signal run time through the Cluster Controller
The signal run time through the Cluster Controller is a maximum of 100 ms.
The signal run time is the time required by the Cluster Controller to process incoming Modbus
commands and to forward them to the devices in the PV system.
Data transfer interval via the Modbus protocol
For system stability reasons, the time period between data transfers via the Modbus protocol must
be at least ten seconds. No more than 30 parameters and measured values should be transmitted
per inverter. Note the maximum number of SMA devices according to Section 8.2 "Number of
SMA Devices", page 34.
Physical reaction time of the inverters
The physical reaction time of the inverters is typically approximately one second, depending on the
inverters used.
The physical reaction time is the time between the changing of setpoints in the inverters until their
physical implementation. Such a change would be, for example, changing cos φ.
Reaction time of the Modbus interface
The reaction time of the Modbus interface is five to ten seconds.
The reaction time of the Modbus interface is the time between the arrival of the parameter specifica-
tions in the inverters until the corresponding measured values are provided to the Modbus interface
of the Cluster Controller. Due to this reaction time, parameter specifications can only be displayed
via a Modbus master system (e.g. a SCADA system) at a corresponding or larger interval.
Technical Information ClusterController_Modbus-TI-en-18 35
Technical Data SMA Solar Technology AG
City/Country
Code
Time zone
Abu Dhabi, Muscat
9503
UTC+04:00
Adelaide
9513
UTC+09:30
Alaska
9501
UTC-09:00
Amman
9542
UTC+02:00
Amsterdam, Berlin, Bern, Rome,
Stockholm, Vienna
9578
UTC+01:00
Arizona
9574
UTC-07:00
Astana, Dhaka
9515
UTC+06:00
Asuncion
9594
UTC-04:00
Athens, Bucharest, Istanbul
9537
UTC+02:00
Atlantic (Canada)
9505
UTC-04:00
Auckland, Wellington
9553
UTC+12:00
Azores
9509
UTC-01:00
Baghdad
9504
UTC+03:00
Baku
9508
UTC+04:00
Bangkok, Hanoi, Jakarta
9566
UTC+07:00
Beirut
9546
UTC+02:00
Belgrade, Bratislava, Budapest,
Ljubljana, Prague
9517
UTC+01:00
Bogotá, Lima, Quito
9563
UTC-05:00
Brasilia
9527
UTC-03:00
Brisbane
9525
UTC+10:00
Brussels, Copenhagen, Madrid,
Paris
9560
UTC+01:00
Buenos Aires
9562
UTC-03:00
Canberra, Melbourne, Sydney
9507
UTC+10:00
Caracas
9564
UTC-04:30
Casablanca
9585
UTC+00:00
Cayenne
9593
UTC-03:00
Chennai, Kolkata, Mumbai, New
Delhi
9539
UTC+05:30
Chicago, Dallas, Kansas City,
Winnipeg
9583
UTC-06:00
Chihuahua, La Paz, Mazatlán
9587
UTC-07:00
Darwin
9506
UTC+09:30
Denver, Salt Lake City, Calgary
9547
UTC-07:00
Dublin, Edinburgh, Lisbon, London
9534
UTC+00:00
Yerevan
9512
UTC+04:00
Fiji, Marshall Islands
9531
UTC+12:00
Georgetown, La Paz, San Juan
9591
UTC-04:00
Greenland
9535
UTC-03:00
Guadalajara, Mexico City,
Monterrey
9584
UTC-06:00
Guam, Port Moresby
9580
UTC+10:00
Harare, Pretoria
9567
UTC+02:00
Hawaii
9538
UTC-10:00
Helsinki, Kiev, Riga, Sofia, Tallinn,
Vilnius
9532
UTC+02:00
Hobart
9570
UTC+10:00
Indiana (East)
9573
UTC-05:00
International Date Line (West)
9523
UTC-12:00
Irkutsk
9555
UTC+08:00
Islamabad, Karachi
9579
UTC+05:00
Yakutsk
9581
UTC+09:00
Yekaterinburg
9530
UTC+05:00
Jerusalem
9541
UTC+02:00
Kabul
9500
UTC+04:30
Cairo
9529
UTC+02:00
Cape Verde Islands
9511
UTC-01:00
Katmandu
9552
UTC+05:45
Caucasus Standard Time
9582
UTC+04:00
Krasnoyarsk
9556
UTC+07:00
Kuala Lumpur, Singapore
9544
UTC+08:00
Kuwait, Riyadh
9502
UTC+03:00
Magadan, Solomon Islands, New
Caledonia
9519
UTC+11:00
Manaus
9516
UTC-04:00
Midway Islands, Samoa
9565
UTC-11:00
Minsk
9526
UTC+02:00
Mid-Atlantic
9545
UTC-02:00
Monrovia, Reykjavík
9536
UTC+00:00
8.5 Number Codes of the Time Zones
The following table contains the most important time zones and their number codes in the SMA
Modbus profile. If the location is known, you can determine the numerical key (code) and the time
zone. In the tables in Section 5 "SMA Modbus Profile—Assignment Tables", from page 23, with
specification of the time zone, this table is referenced.
36 ClusterController_Modbus-TI-en-18 Technical Information
SMA Solar Technology AGTechnical Data
Montevideo
9588
UTC-03:00
Moscow, St. Petersburg, Volgograd
9561
UTC+03:00
Nairobi
9524
UTC+03:00
Newfoundland
9554
UTC-03:30
New York, Miami, Atlanta, Detroit,
Toronto
9528
UTC-05:00
Novosibirsk
9550
UTC+06:00
Nuku'alofa
9572
UTC+13:00
Osaka, Sapporo, Tokyo
9571
UTC+09:00
Pacific (U.S., Canada)
9558
UTC-08:00
Beijing, Chongqing, Hong Kong,
Ürümqi
9522
UTC+08:00
Perth
9576
UTC+08:00
Petropavlovsk-Kamchatsky
9595
UTC+12:00
Port Louis
9586
UTC+04:00
Santiago
9557
UTC-04:00
Sarajevo, Skopje, Warsaw, Zagreb
9518
UTC+01:00
Saskatchewan
9510
UTC-06:00
Seoul
9543
UTC+09:00
Sri Jayawardenepura
9568
UTC+05:30
Taipei
9569
UTC+08:00
Tashkent
9589
UTC+05:00
Teheran
9540
UTC+03:30
Tbilisi
9533
UTC+04:00
Tijuana, Lower California (Mexico)
9559
UTC-08:00
Ulan Bator
9592
UTC+08:00
West-Central Africa
9577
UTC+01:00
Windhoek
9551
UTC+02:00
Vladivostok
9575
UTC+10:00
Yangon (Rangoon)
9549
UTC+06:30
Central America
9520
UTC-06:00
Technical Information ClusterController_Modbus-TI-en-18 37
Technical Data SMA Solar Technology AG
Event Numbers
The event numbers displayed by the inverters under the Modbus address 30197 are devicespecific. You cannot decrypt the event numbers with the number codes in this document (see
Section 7 "Troubleshooting", page 33).
Code
Meaning
51
Closed
276
Instantaneous value
295
MPP
303
Off
308
On
309
Operation
311
Open
336
Contact the manufacturer
337
Contact the installer
338
Invalid
381
Stop
455
Warning
461
SMA (manufacturer specification)
1041
Leading
1042
Lagging
1069
Reactive power/voltage characteristic curve Q(V)
1070
Reactive power Q, direct setpoint
1071
Reactive power const. Q (kVAr)
1072
Reactive power Q, setpoint via system control
1073
Reactive power Q(P)
1074
cos φ, direct setpoint
1075
cos φ, setpoint via system control
1076
cos φ(P) characteristic curve
1077
Active power limitation P, in W
1078
Active power limitation P (%) of PMAX
1079
Active power limitation P via system control
1387
Reactive power Q, setpoint via analog input
1388
cos φ, setpoint via analog input
1389
Reactive power/voltage characteristic curve Q(U)
with hysteresis and deadband
1390
Active power limitation P via analog input
1391
Active power limitation P via digital inputs
1392
Error
1393
Wait for PV voltage
1394
Wait for valid AC grid
1395
DC section
1396
AC grid
1455
Emergency switch
1466
Waiting
1467
Starting
1468
MPP search
1469
Shutdown
1470
Disturbance
1471
Warning/error e-mail OK
1472
Warning/error e-mail not OK
1473
System info e-mail OK
1474
System info e-mail not OK
1475
Error e-mail OK
1476
Error e-mail not OK
1477
Warning e-mail OK
1478
Warning e-mail not OK
1479
Wait after grid interruption
1480
Wait for electric utility company
8.6 Frequently Used Number Codes (ENUM)
The following table contains number codes which, as function coding in data format ENUM, are
frequently used in the SMA Modbus profile.
38 ClusterController_Modbus-TI-en-18 Technical Information
SMA Solar Technology AGContact
Danmark
Deutschland
Österreich
Schweiz
SMA Solar Technology AG
Niestetal
Sunny Boy, Sunny Mini Central,
Sunny Tripower:
+49 561 9522-1499
Monitoring Systems
(Kommunikationsprodukte):
+49 561 9522-2499
Fuel Save Controller
(PV-Diesel-Hybridsysteme):
+49 561 9522-3199
Sunny Island, Sunny Boy Storage,
Sunny Backup, Hydro Boy:
+49 561 9522-399
Sunny Central,
Sunny Central Storage:
+49 561 9522-299
SMA Online Service Center
www.SMA-Service.com
Belgium
Belgique
België
Luxemburg
Luxembourg
Nederland
SMA Benelux
BVBA/SPRL
Mechelen
+32 15 286 730
SMA Online Service
Center
www.SMA-Service.com
Česko
Magyarország
Slovensko
SMA Service Partner
TERMS a.s.
+420 387 6 85 111
SMA Online Service
Center
www.SMA-Service.com
Türkiye
SMA Service Partner
DEKOM Ltd. Şti.
+90 24 22430605
SMA Online Service
Center
www.SMA-Service.com
9 Contact
If you have technical problems with our products, please contact the SMA Service Line. We require
the following information in order to provide you with the necessary assistance:
• Modbus master software or hardware used
• Software version of your SMA Cluster Controller
• Type of communication interface between the SMA Cluster Controller and the inverters
• Type, serial numbers, and software version of the inverters connected to your PV system
Technical Information ClusterController_Modbus-TI-en-18 39
Contact SMA Solar Technology AG
France
SMA France S.A.S.
Lyon
+33 472 22 97 00
SMA Online Service Center :
www.SMA-Service.com
Ελλάδα
Κύπρος
SMA Service Partner
AKTOR FM.
Αθήνα
+30 210 8184550
SMA Online Service Center
www.SMA-Service.com
España
Portugal
SMA Ibérica Tecnología Solar,
S.L.U.
Barcelona
+34 935 63 50 99
SMA Online Service Center
www.SMA-Service.com
United
Kingdom
SMA Solar UK Ltd.
Milton Keynes
+44 1908 304899
SMA Online Service Center
www.SMA-Service.com
Italia
SMA Italia S.r.l.
Milano
+39 02 8934-7299
SMA Online Service Center
www.SMA-Service.com
Bulgaria
România
Slovenija
Hrvatska
SMA Service Partner
Renovatio Solar
+40 372 756 599
SMA Online Service Center
www.SMA-Service.com
United Arab
Emirates
SMA Middle East LLC
Abu Dhabi
+971 2234 6177
SMA Online Service Center
www.SMA-Service.com
India
SMA Solar India Pvt. Ltd.
Mumbai
+91 22 61713888
SMA Solar (Thailand) Co., Ltd.
+66 2 670 6999
대한민국
SMA Technology Korea Co.,
Ltd.
서울
+82-2-520-2666
40 ClusterController_Modbus-TI-en-18 Technical Information
SMA Solar Technology AGContact
South Africa
SMA Solar Technology
South Africa Pty Ltd.
Cape Town
08600SUNNY
(08600 78669)
International:
+27 (0)21 826 0600
SMA Online Service Center
www.SMA-Service.com
Argentina
Brasil
Chile
Perú
SMA South America SPA
Santiago de Chile
+562 2820 2101
Australia
SMA Australia Pty. Ltd.
Sydney
Toll free for Australia:
1800 SMA AUS
(1800 762 287)
International:
+61 2 9491 4200
Other countries
International
SMA Service Line
Niestetal
00800 SMA SERVICE
(+800 762 7378423)
Technical Information ClusterController_Modbus-TI-en-18 41
SMA Solar Technology
www.SMA-Solar.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.