Slant-Fin VHS-180, VHS-30 User Manual

®
VICTORY II
This manual must be left with owner and should be hung on or adjacent to the boiler for reference.
HOT WATER MODELS VHS-30 THROUGH VHS-180
GAS-FIRED CAST-IRON BOILERS FOR NATURAL AND L.P. PROPANE GASES
Models with Intermittent Pilot System – Spark Ignition
INSTALLATION AND OPERATING INSTRUCTIONS
Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page
Dimensions, Rating and Orifice Sizes . . . . . . . . . . . . . . . . . . .2
Installation Requirements:
Boiler Location and Foundation . . . . . . . . . . . . . . . . . . . . .3
Minimum Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Boiler Room Air Supply and Ventilation . . . . . . . . . . . . . . .4
Flue Gas Venting Requirements . . . . . . . . . . . . . . . . . . . . . . .4
Category
Category
Venting System Regular Inspection . . . . . . . . . . . . . . . . . . . .14
Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Water Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Piping a Heating-Cooling System . . . . . . . . . . . . . . . . . . . . .18
Operating Instructions:
Safety Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Care and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Sequence of Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
General Troubleshooting Guide . . . . . . . . . . . . . . . . . . . . . . .24
Appendix A and B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
The venting system of this boiler is under positive pres­sure when it is connected to the outdoors with 3" diameter pipe. Leakage from this system can be hazardous and if not avoided can result in death or serious injury. In addi­tion to the recommendations within this manual and the User’ blower to the outdoor discharge, must be carefully checked annually by a qualified service agency.
II and III Venting:
Venting Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Flue Length Restriction . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
I Venting:
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Vent Connector Material . . . . . . . . . . . . . . . . . . . . . . . . . .10
Venting Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Filling and Venting Water Systems . . . . . . . . . . . . . . . . . .18
Initial Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Operating Instruction . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Burner Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
WARNING
s Information Manual, the venting system, from the
IMPORTANT
READ ALL OF THE FOLLOWING
WARNINGS AND STATEMENTS
BEFORE READING THE
INSTALLATION INSTRUCTIONS
WARNING
PROPANE GAS-FIRED BOILERS
Installation location ONLY as permitted in paragraph entitled "LIQUEFIED PETROLEUM (L.P.) PROPANE GAS-FIRED BOILER LOCATION" on page 3 of this instruction book. The above warning does not apply to fired boilers.
The installation must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1-latest edition. The installation must also conform to the additional requirements in this Slant/Fin Instruction Book.
In addition where required by the authority having juris­diction, the installation must conform to American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers, No. CSD-1.
WARNING
This boiler, gas piping and accessories must be installed, connected, serviced and repaired by a trained, experienced service technician, familiar with all precautions required for gas-fired equipment and licensed or otherwise qualified, in compliance with the authority having jurisdiction.
NATURAL gas-
Heating Contractor
Address
Phone Number
Boiler Model Number
Boiler Serial Number
Installation Date
Publication No. VHS-40 Part No. 44-0831 Printed in U.S.A.404
F
igure 1. Views - Dimensions - Data
LEFT END VIEW FRONT VIEW RIGHT END VIEW
VI
CTORY
II V
HS Models
NOTE: Height dimensions increase by 13⁄4" and depth increases to 221⁄4" when combustible floor kit is used.
Figure 2. Base Assembly Victory II - VHS Boiler
Boiler Model
Input
Btuh
No. of
Sections
VHS-30 30,000 2 8
VHS-60 60,000 3 11
VHS-90 90,000 4 14
VHS-120 120,000 5 17
VHS-150 150,000 6 20
VHS-180 180,000 7 23
AB
1
8"14
1
8" 175⁄8" 250
1
8"20
1
8"23
1
8"26
1
8"29
Water (lb.)
5
8" 190
5
8" 310
5
8" 365
5
8" 425
5
8" 485
Approx.
Total Wt.
Full of
Gas manifold
Orifice Sizes for High Altitudes
Inc
ludes 4% Reduction for Each 1000 Feet
Elevation — Feet
3000 4000 5000 6000 7000 8000 9000 10000
Gas
Type
Orifice
Siz
e for
Sea Le
vel
2000
Natural #49 50 50 50 51 51 51 52 52 52
Propane #57 58 59 59 60 60 61 62 63 63
Bur
ners
Pilot
Burner access door
Gas valve
Orifice sizes indicated for sea level above are factory installed in boiler unless otherwise specified by the local authority. Orifice table is based on a higher heating value between 1000 Btuh and 1010 Btuh for Natural Gas (See page 19, if local higher heating value exceeds these numbers). See page 19, for burner input adjustment.
2
VI
CTORY
II V
HS Models
INSTALLATION REQUIREMENTS
The installation must conform to the requirements of the a
uthority having jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1­latest edition.
T
his installation must also conform to the additional require­ments in this Slant/Fin Instruction Book.
N
ATURAL GAS-FIRED BOILER LOCATION
Provide a level, solid foundation for the boiler. Location should be as near as possible to chimney or outside wall so that the flue pipe from boiler is short and direct. (See Appen­dix A for vent terminal location restrictions.) The location should also be such that the gas ignition system components are protected from water (dripping, spraying, rain, etc.) during appliance operation and service (circulator replacement, con­densate trap, control replacement, etc.).
WARNING LIQUEFIED PETROLEUM (L.P.) PROPANE GAS-FIRED BOILER LOCATION
REQUIRES SPECIAL ATTENTION
Liquefied Petroleum (L.P.) propane gas is
heavier than air.
Therefore, propane boilers, piping, valves should NOT be installed in locations where propane leaking from defective equipment and piping will "pool" in a basement or other space below the leak.
A spark or flame from the boiler or other source may ignite the accumulated propane gas causing an explosion or fire. Provide a level, solid foundation for the boiler. Location should be as near the chimney as possible so that the flue pipe from boiler to chimney is short and direct.
The UNIFORM MECHANICAL CODE may be in effect in your geographic area.
The following precautions are cited by the 1994 UNIFORM MECHANICAL CODE, section 304.6:
"LPG Appliances. Liquefied petroleum gas-burning appliances shall not be installed in a pit, basement or similar location where heavier-than-air-gas might collect. Appliances so fueled shall not be installed in an above­grade under-floor space or basement unless such loca­tion is provided with an approved means for removal of
unburned gas." Consult Chapter 5 of the 1994 UNIFORM MECHANICAL CODE for design criteria of the "approved" means for removal of unburned gas.
MINIMUM CLEARANCES FROM COMBUSTIBLE CONSTRUCTIONS
A. Minimum clearances to the exterior surfaces of the boiler
shall be as follows: M
INIMUM ALCOVE AND CLOSET CLEARANCE
For Combustible Recommended
Surf
ace Construction for Service
F
ront 6" 18" Rear 6" 18" Left Side 6" 18" Right Side 12" 24" Top 12" 12" Flue Connector:
Enclosed — 6" 6" Unenclosed — 2" 6"
B. Provide accessibility clearance of 24" on sides requiring
servicing and 18" on sides used for passage.
C. All minimum clearances shown above must be met. This
may result in increased values of some minimum clear­ances in order to maintain the minimum clearances of others.
D. Clearance from hot water pipes shall be 1 inch**.
**
At points where hot w the clearance at the opening through the finished floor boards or wall or ceiling boards may be not less than 1/2 inch. Each such opening shall be covered with a plate of uncombustible material.
ater pipes emerge from a floor, wall or ceiling,
BOILER FOUNDATION
A. Provide a solid, level foundation, capable of supporting
the weight of the boiler filled with water, and extending at least 2" past the jacket on all sides. See dimensions of
boilers, page 2. B. For installation on non-combustible floors only*. C. If boiler is to be located over buried conduit containing
electric wires or telephone cables, consult local codes or
the National Board of Fire Underwriters for specific
requirements.
* Installation on combustible flooring allowed only with proper Com-
bustible Floor Kit. Kit part number is printed on boiler rating plate. In no case may the boiler be installed on carpeting.
Figure 3.
SAFETY
KEEP THE BOILER AREA CLEAR AND FREE FROM COMBUSTIBLE MATERIALS, GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQUIDS.
3
VI
CTORY
II V
HS Models
BOILER ROOM AIR SUPPLY AND VENTILATION
An ample supply of air is required for combustion and venti­l
ation. When buildings are insulated, caulked and weather­stripped, now or later on, direct openings to outside may be required and should be provided. If the boiler is not near an o
utside wall, air may be ducted to it from outside wall openings.
Provisions for combustion and ventilation air must be made in accordance with section 5.3, Air for Combustion and Venti­lation, of the National Fuel Gas Code, ANSI Z223.1-latest e
dition, or applicable provisions of the local building codes. The following recommendation applies to buildings of ener­gy-saving construction, fully caulked and weatherstripped.
INSTALLATION IN ENCLOSED BOILER ROOM REQUIRES TWO UNOBSTRUCTED OPENINGS FOR PASSAGE OF AIR INTO THE BOILER ROOM:
Air drawn horizontally from outdoors DIRECTLY
1.
through an outside wall;
the floor and one louvered opening near the ceiling, each opening with a minimum FREE air passage area of 1
square inch per 4000 Btuh of total appliances’ input.
Air drawn horizontally through HORIZONTAL
2.
DUCTS; one opening near the floor and one opening near the ceiling, each opening with a minimum FREE air passage area of appliances’ input.
3.
Air drawn VERTICALLY from outdoors; one opening at the floor and one opening at the ceiling, each opening with a minimum FREE air passage area of inch per 4000 Btuh of total appliances’ input.
4. Air drawn from inside the building; one opening near
the floor and one opening near the ceiling, each opening with a minimum FREE air passage area of
inch per 1000 Btuh of total appliances’ input.
1 square inch per 2000 Btuh of total
one louvered opening near
1 square
1 square
FLUE GAS VENTING REQUIREMENTS
T
he Victory IIseries boiler is a high efficiency, mechanically
i
nduced draft boiler and, therefore, requires different venting
arrangements than natural draft, lower efficiency boilers.
T
HE FOLLOWING INSTRUCTIONS MUST BE CAREFULLY READ AND FOLLOWED IN ORDER TO AVOID ANY HAZ­ARDOUS CONDITIONS DUE TO IMPROPER INSTALLA­TION OF THE FLUE GAS VENTING SYSTEM.
The vent piping installation MUST be in accordance with these instructions and with ANSI Z223.1-latest edition NATIONAL FUEL GAS CODE, Part 7, Venting of Equipment. O
ther local codes may also apply and must be followed. Where there is a conflict between these requirements, the more stringent case shall apply.
The use of a vent damper is NOT permitted on this boiler series.
Approved Venting Applications
Victory II model VHS-90 through 180 are Category III and VHS-30 and 60 are Category be vented by proper 3" diameter venting system (see Cate­gory
II and III venting - page 5). Models VHS-90 through 180 are also Category when using a minimum of 5" diameter connector and vented into a natural draft chimney or Type “B” vent using a 3"x5" diameter vent adapter (see Category
II boilers, these boilers must
I boilers
I venting - page 10).
IF BOILERS ARE INSTALLED ADJACENT TO OTHER FUEL BURNING EQUIPMENT, THE AREA OF FREE OPENINGS MUST BE APPROPRIATELY INCREASED TO ACCOMMODATE THE ADDITIONAL LOAD.
Openings must never be reduced or closed. If doors or win­dows are used for air supply, they must be locked open. Pro­tect against closure of openings by snow and debris. Inspect frequently.
No mechanical draft exhaust or supply fans are to be used in or near the boiler area.
The flow of combustion and ventilating air to the boiler must not be obstructed.
4
VI
CTORY
II V
HS Models
Figure 4. Vent Sealing Instructions
(Consult vent manufacturer’s instructions.)
CATEGORY II AND III VENTING
1. Vent Material
A) The vent system for horizontal or vertical venting (Category II and III) must be UL listed single wall 3" diameter AL29-4Csstainless steel material. The follow­ing manufacturers’ systems are approved for use within a specified minimum and maximum equivalent vent length for each model. Proper adapter must be used as a connector between Victory
II boilers flue collar and
venting system as shown below:
Manufacturer Type/System Adapter Part Sealant
No.
Heat-F
ab
.
Inc. Saf-T Vent Not Required RTV 106 or Dow
Heat-F
ab
. Inc. Saf-T Vent Not Required Not Required
ProTech System, FasNSeal FSA-SLB-3 Not Required
Inc.
Fle
x-L StaR-34 SRASFA3 GE-1S806
International, Inc.
Z-Flex, Inc. Z-Vent O2SVSSLA2 GE, RTV 106
EZ Seal
Corning 732
Heat-Fab Part Numbers for various items of vent system are listed in Slant/Fin Part List, Publication No. VHS-10PL.
B) When joining the various components of the above
listed vent systems, the manufacturers’ instructions should be closely followed to insure proper sealing.
C) Use sealant specified by vent system manufacturer
for sealing of pipe and fittings. See Figure 4 for proper application of vent pipe sealing for Safe-T vent
system by Heat-Fab. Inc. D) All vent connections must be liquid and pressure tight E) Flue vent system CANNOT be cut to length. Consult
manufacturer’s instructions. For Heat-Fab system, use
slip joint connector to adjust pipe lengths dimensions. F) DO NOT use plastic or galvanized flue pipe.
2. Flue Length Restriction
Maximum and minimum equivalent flue length for different s
ystems are given in the tables on page 6. Equivalent flue length is sum of straight flue lengths and equivalent length of elbows. The vent termination is in addition to the a
llowed equivalent lengths.
Example: Boiler Model VHS-180 is to be installed at sea level with 2 elbows using Heat-Fab vent system. Maximum straight run would be: 40 - 2 x 3 = 34ft. If same boiler is to be installed in Colorado Springs (5,980 ft. altitude), the maxi­mum straight run would be: 20 - 2 x 3 = 14 ft.
3. Installation A. Horizontal Venting:
Figures 5 and 6 show typical horizontal venting. For combustible wall passage of vent piping a U.L. listed thimble must be used. See Figures 5 and 6 for wall thimble Part Numbers and more information.
B. Vertical Venting:
Figure 7 shows typical vertical venting. A fire stop is required for each ceiling and floor penetration. An existing chimney (see Figure 8) may be used as a chase for vertical venting. Other appliances CANNOT be vented into the same chimney or vent pipe within the chimney.
For both, horizontal and vertical venting, the following points MUST be followed: A. All Victory
II boilers are equipped with a built-in con­densation drain and trap. The trap loop must be filled with water. DO NOT operate the boiler without filling the trap with water to prevent flue gas discharge into space. The drain should extend to a floor drain or to a container which may require emptying periodically.
B. The horizontal vent pipe must be sloped upward from
the boiler at a pitch of at least 1/4" per 1 foot of run, so that the condensate from the vent system runs to the drain trap.
C. The horizontal vent pipes must be supported with pipe
straps at intervals no greater than indicated by vent pipe manufacturer’s instructions. The vertical portion vent pipe also must be supported per manufacturer’s instructions.
D. Minimum clearances of vent pipes from combustible
constr
uctions must be maintained (see Page 3).
E. Common venting with other appliances or another Vic-
tory
II boiler is NOT allowed.
F. The vent piping must terminate with a screened elbow
or tee. See Figures 5 and 6 for horizontal and 7 and 8 for vertical termination information. A cap termination may be used for vertical venting.
G. See Appendix A for vent system location and conden-
sation drain requirements.
H. For roof passage of vent piping a U.L. listed roof flash-
ing must be used.
s
: AL 29-4C is a registered trademark of Allegheny Ludlum Corp.
5
Heat-Fab Saf-T Vent System
Max. Equivalent Length (Ft.)
Equivalent
0 to Boiler Model No.
VHS-30, 40 40 40 3 2 60, 90 and 120
VHS-150 40 40 20 3 2
VHS-180 40 20 20 3 2
5500 Ft.
Altitudes
5500 to 7000 Ft. Altitudes
7000 to 10,000 Ft. Altitudes
Length of each 90° Elbow, Ft.
Minimum Length, Ft.
ProTech FasNSeal System
Max. Equivalent Length (Ft.)
Equivalent
Boiler Model No.
0 to
5500 Ft.
Altitudes
5500 to 7000 Ft. Altitudes
7000 to 10,000 Ft. Altitudes
Length of each 90° Elbow, Ft.
Minimum Length, Ft.
VI
CTORY
II V
HS Models
VHS-30, 30 30 30 6 2 60, 90 and 120
VHS-150 30 30 15 6 2
VHS-180 30 15 15 6 2
Flex-L StaR-34 and Z-Flex Z-Vent System
Max. Equivalent Length (Ft.)
Equivalent
0 to Boiler Model No.
VHS-30, 35 35 35 6 2 60, 90 and 120
VHS-150 35 35 18 6 2
VHS-180 35 18 18 6 2
5500 Ft.
Altitudes
5500 to 7000 Ft. Altitudes
7000 to 10,000 Ft. Altitudes
Length of each 90° Elbow, Ft.
Minimum Length, Ft.
Note: Vent termination is in addition to the allowed equivalent length.
6
VI
CTORY
II V
HS Models
VICTORY II HORIZONTAL (SIDEWALL) VENTING
All joints must be liquid and pressure tight. Use U/L listed single wall 3" dia.
AL29-4C* S.S. venting materials
Figure 5
* Definition of Snow Line: Knowledge of local conditions will reveal the maximum height that repeated
snowfalls accumulate to. The height should be used as the SNOW LINE.
Figure 6
* Definition of Snow Line: Knowledge of local conditions will reveal the maximum height that repeated
sno
wfalls accumulate to. The height should be used as the SNOW LINE.
: AL 29-4C IS A REGISTERED
*
TRADEMARK OF ALLEGHENY LADLUM CORP.
44vh40-6 REV.A
7
VI
CTORY
II V
HS Models
Figure 7.
8
VI
CTORY
II V
HS Models
Figure 8.
9
Loading...
+ 18 hidden pages