AUTOMATIC VENT DAMPER
INSTALLATION INSTRUCTIONS AND TROUBLESHOOTING GUIDE
For Galaxy, Sentinel
and Sentry Series Boilers
READ AND SAVE THESE INSTRUCTIONS
FOR REFERENCE.
The installation must conform to the requirements of
the authority having jurisdiction or, in the absence of
such requirements, to the National Fuel Gas Code,
ANSI Z223.1-latest edition.
In addition, where required by the authority having
jurisdiction, the installation must conform to American
Society of Mechanical Engineers Safety Code for
Controls and Safety Devices for Automatically Fired
Boilers, No. CSD-1.
THIS MANUAL MUST BE LEFT WITH OWNER AND
SHOULD BE HUNG ON OR ADJACENT TO THE
BOILER FOR REFERENCE.
WARNING
By failing to follow the WARNING instructions listed below, a hazardous condition
such as explosion, carbon monoxide poisoning, fire or all of these could result.
• This device is design certified by C.S.A. for use only on
specific Slant/Fin Corporation gas boiler models. These
boilers must also be equipped with a plate or rating plate
which states that the boiler must* (may*) be used with a
Slant/Fin Corp. automatic vent damper device and indicates
the proper vent damper model or part number (See Table 1).
* Boilers under 300,000 Btu/hr. input MUST use a vent damper.
Note: GG-75 HES (Constant circulation), MAY use a vent
damper.
Boilers with 300,000 Btu/hr. input or greater equipped with IID
(intermittent pilot ignition) MAY use a vent damper.
Boilers with 300,000 Btu/hr. input equipped with continuous
pilot and VR8300A gas valve MAY use a vent damper.
• This device must be installed and inspected annually by a qualified installer in accordance with the Slant/Fin vent damper
installation instructions, Slant/Fin boiler installation instructions
and the vent damper manufacturer's installation instructions
included with this damper. If improperly installed, a hazardous
condition such as explosion or carbon monoxide poisoning could
result. If installed improperly, all vent damper and boiler warranties shall be voided.
The vent damper shipped with your boiler may be a different model than illustrated above.
• Use of this device on boilers other than those indicated above is
not permitted.
• CAUTION: When servicing controls all wires must be labeled
prior to disconnection. Wiring errors can cause improper and
dangerous operation.
• This device must be installed on the outlet end of the draft hood
of the boiler as close to the draft hood as practicable, and without modification of the draft hood (see figures 3 through 7).
• The inlet size of the vent damper must be the same nominal
trade size as the outlet of the draft hood. See Table 1 for the
boiler models and their corresponding vent damper models.
• The device must be located in a venting system or section of a
venting system so that it serves only the single appliance for
which it is installed.
• Clearances of not less than 6 inches (152 mm) must be maintained from combustible materials, with provisions for access.
• If the boiler will not fire, DO NOT jump any of the safety controls
(the vent damper circuit is part of the safety control circuit).
Check page 12 of this manual for troubleshooting guide.
Part No. 41-1676. Printed in U.S.A. 112 Publication No. VD-40, Rev. V
INTRODUCTION
This product is an automatic, motorized stack damper that has been
developed to increase the efficiency of heating systems by reducing
standby losses from the heating apparatus and the conditioned air
space. The damper closes the chimney vent when the burner is off
and fully opens it when combustion is required. The concept is similar
to the opening and closing of a fireplace flue, except that the operation
is completely automatic. An interlock has been added which prevents
burner operation unless the damper is in an open position. A closed
damper substantially reduces standby losses on boilers.
DESCRIPTION
The unit must be installed after the appliance draft diverter and as
close to it as practicable, without modification of the draft hood. When
the damper is in the closed position, it will prevent residual heat in the
heating appliance from being drawn up the chimney vent by its natural
draft. If located within a heated area, a closed damper will also prevent conditioned air from being pulled through the draft diverter and
up the chimney by the same stack effect.
When combustion is required, the damper will rotate to its open position BEFORE an integral end switch activates the burner circuit. If the
damper does not rotate to its open position, the burner circuit will not
be activated.
When the heating requirement has been satisfied, the burner will go
off immediately, and the damper will rotate to its fully closed position.
Potential fuel savings can vary based on the following factors:
1. Geographical location of dwelling
2. The size of heating plant relative to heat loss
of dwelling
3. Location of heating plant within dwelling
4. Diameter of venting system
5. Total height of chimney above heating plant
6. Outdoor temperatures over a given period of time
7. Sustained wind velocities over a given period of time
8. Settings of operating and limit controls on heating plant
9. Source of domestic hot water, temperature of water, and
amount used
10. Room thermostat settings
11. Infiltration factors of dwelling
12. Number of heating zones
13. Day/night thermostats
14. Presence of other vents and exfiltration factors
15. Chimney vent friction
GENERAL INFORMATION
VENT
SIZE
10"
ELECTRICAL
Minimum Wiring
Requirements 24VAC,18 gauge, 90°C
Thermostat Anticipation
Flair0.1 AMP + control circuit
Honeywell Inc. 0.2 AMP + control circuit
Johnson 0.2 AMP + control circuit
Field Controls (Effikal) 0.1 AMP + control circuit
FEATURES
100,000 trouble-free operations in life cycle test • Burner "OFF" before
start of damper close • Normal burner operations with damper disabled open • No burner operation with damper disabled closed •
External damper position indicator • Direct drive, no-linkage and
switch for burner off/on cycle • Low voltage (24V) circuitry compatible
with standing pilot and intermittent ignition devices • CSA
retrofit certification ANSI Z21.66 - latest edition • "Free-wheeling" permits free rotation of vane during installation without motor damage •
Both operator motor and operator control (P.C. board) are replaceable
INSTALLATION INSTRUCTIONS
I. Before you start to install
1. Read this installation manual, vent damper manufacturer’s
instructions, the "WARNING" label attached to the top of the
boiler, the "WARNING" on the wiring diagram and the “DANGER” label on the vent damper carton.
APPROX SHIP WT.
(WITH HARNESS) IN LBS.
4"
5"
6"
7"
8"
9"
3.5
3.5
4.5
4
5
6
7
2. Perform pre-installation inspection as required by ANSI specification Z21.66. See manufacturer’s vent damper instructions.
3. Turn off all electrical power, gas supply and wait for system to
cool (for previous installed boilers).
4. Select a proper, convenient location
(see figures 3, 4, 6 and 7).
5. Carefully unpack the unit. DO NOT FORCE IT OPEN OR
CLOSED! Forcing the damper may damage the gear train and
void the warranty.
WARNING—DANGER
Once you have begun vent damper installation procedure, DO NOT
restore electric power and gas supply until installation and inspection
have been completed (in order to prevent the main burners from operating). DO NOT operate the boiler until the vent damper harness
"RECEPTACLE B" is plugged into "MALE PLUG" (as described in the
installation instructions), and the vent damper installation and checkout procedures have been completed. Failure to observe this warning
may create a hazardous condition that could cause an explosion or
carbon monoxide poisoning.
II. Now, proceed as follows for Boilers with input under 300,000
Btu/hr.:
1. Remove the front cover of the boiler (Galaxy models only)
exposing the wiring compartment. With all electrical power to
boiler off, locate “MALE PLUG”. Refer to the wiring diagram
attached to boiler. A copy of the wiring diagram may also be
found in the boiler installation manual. To find the correct wiring
diagram in installation manual, match the number found in the
lower right hand corner of the boiler wiring diagram with the
identical number on one of the diagrams in the manual.
2. This device must be installed on top of the draft hood or diverter in position as shown in figures 3, 4, 5, 6 and 7. The vent
damper must be installed so that the damper position indicator
is in a visible location after installation for position indicator
description. The arrow imprint on the damper should point in
direction of vent gas flow (towards chimney). Flue pipe (other
than flue collector on boiler) insertion depth for the male end
should not exceed one inch into the vent damper. Be sure the
vent damper is well seated and fasten with 3 sheet metal
screws. Screws should be no longer than 1/2 inch.
3. Be sure that undersized vent pipe does not block move-
ment of damper vane
4. NOTE:
Galaxy 300,000 Btu/hr. Standing Pilot boilers, and Intermittent
Pilot (IID) boilers 300,000 Btu/hr and larger may
have a vent
damper (see page 1). They are factory wired with “MALE
PLUG” and “RECEPTACLE A”. To install the vent damper, cut
the RED wire connected between number 3 and 4 of
“RECEPTACLE A” (the only wire connected to this receptacle)
and then disconnect “RECEPTACLE A” from “MALE PLUG”.
Remove “RECEPTACLE A” from job site and discard. Boilers
that must have a vent damper (boilers with input under
300,000 Btu/hr.) are factory wired with “MALE PLUG” only.
5. a) Galaxy boilers: Attach the flexible metallic conduit vent
damper harness to the right hand side of the jacket by
passing the free end (“RECEPTACLE B”) of the harness
through the 7/8" diameter hole in the top of the jacket, and
using the BX connector at the free end of the metallic conduit, fasten to jacket. Connect “RECEPTACLE B” into
“MALE PLUG” (see correct wiring diagram). Attach the
other side of the vent damper harness to vent damper operator (if not attached) and connect Molex connector to operator receptacle. For more information, see Galaxy installation manual, GG-40.
b) Sentry and Sentinel boilers: All Slant/Fin Sentry and
Sentinel boilers are supplied with vent damper. “MALE
PLUG” and “RECEPTACLE B” are in control box. For vent
damper installation instruction see Sentry installation
manual, S-40 or Sentinel installation manual SE-40.
6. All Slant/Fin Corp. Galaxy steam boilers equipped with inter-
mittent pilot ignition and continuous (standing) pilot systems
are factory wired except for the wires to the low water cut-off
and pressure cut-off. Wire these controls with wire provided
with boiler (see boiler wiring diagram on boiler). Then follow
previous instructions shown in 4 and 5 above.
7. Follow instruction for electrical wiring in boiler installation manual (Galaxy, GG-40; Sentry, S-40 or Sentinel SE-40) or restore
electrical power and turn on gas supply (for previously installed
boilers). See wiring diagram attached to the boiler or in boiler
installation manual.