Slant/Fin SE-245 User Manual

CONTENTS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PAGE
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Installation Requirements
Boiler Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Boiler Foundation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Chimney Requirements . . . . . . . . . . . . . . . . . . . . . . . . 4
Minimum Clearance . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Draft Hood . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Vent Damper Installation. . . . . . . . . . . . . . . . . . . . . . 5,6
Electrical Controls and Wiring . . . . . . . . . . . . . . . . . . . 7
Boiler Water Temperature Control. . . . . . . . . . . . . 11-15
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . 16
Boiler Room Air Supply and Ventilation . . . . . . . . . . . 17
Water Piping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Operating Instructions
Filling and Venting Water Systems. . . . . . . . . . . . . . . 17
Initial Start, Safety and Lighting Instructions . . . . . . . 20
Burner Adjustment, Checking Gas Input . . . . . . . . . . 20
Care and Maintenance
General Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . 21
Water Level Check. . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Annual Inspection and Cleaning . . . . . . . . . . . . . . . . 22
Safety Check for Control Systems . . . . . . . . . . . . . . . 22
Protection from Freezing/Water Treatment. . . . . . . . . 22
Keeping Area Clear . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Troubleshooting Guide . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Piping a Heating-Cooling System. . . . . . . . . . . . . . . . . . 24
Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Appendix A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Printed in U.S.A. 1213 Publication No. SE-41 Rev. C Part No. 46-0601
HOT WATER MODELS SE-70 THROUGH SE-245
INSTALLATION AND OPERATING INSTRUCTIONS
GAS-FIRED CAST-IRON BOILERS FOR NATURAL AND L.P. PROPANE GASES
SENTINEL
The installation must conform to the requirements of the authority having jurisdiction or, in the absence of such require­ments, to the National Fuel Gas Code, ANSI Z223.1-lates edition. The installation must also conform to the additional requirements in this Slant/Fin Instruction Book.
In addition, where required by the authority having jurisdic­tion, the installation must conform to American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers, No. CSD-1. If there is any conflict in the above requirements, then the more stringent requirement will apply.
This manual must be left with owner and should be hung on or adjacent to the boiler for reference.
WARNING
This boiler, gas piping and accessories must be installed, connected, serviced and repaired by a trained, experienced service technician, familiar with all precautions required for gas-fired equipment and licensed otherwise qualified, in compliance with the authority having jurisdiction.
Heating Contractor
Address
Phone Number
Boiler Model Number
Boiler Serial Number
Installation Date
This manual must be left with
owner and should be hung on or
adjacent to the boiler for reference.
WARNING
SEE “WARNING” ON PAGE 4 FOR LIQUEFIED
PETROLEUM (L.P.) PROPANE GAS-FIRED BOILERS
IMPORTANT
READ ALL OF THE FOLLOWING WARNINGS
AND STATEMENTS BEFORE READING THE
INSTALLATION INSTRUCTIONS
2
Sentinel
Dimensions MODEL SE-70 to SE-245
SE-70 3 111⁄8"175⁄8"4493⁄4"55⁄8"61⁄4" 250 SE-105 4 14
1
8"205⁄8"5511⁄4"71⁄8"61⁄4" 310
SE-140 5 17
1
8"235⁄8"5513⁄4"85⁄8"61⁄4" 365
SE-175 6 20
1
8"265⁄8"6513⁄4"101⁄8"61⁄4" 425
SE-210 7 23
1
8"295⁄8"7533⁄4"115⁄8"63⁄4" 485
SE-245 8 26
1
8"325⁄8"7533⁄4"131⁄8"63⁄4" 545
Boiler Model
Gas
Typ e
2000 3000 4000 5000 6000 7000 8000 9000 10000
Orifice
Size for
Sea
Level
Orifice Sizes for High Altitudes
Includes 4% Reduction for Each 1000 Feet
Elevation - Feet
No. of
Sect.
Dimensions
(Inches)
ABCDEG
Approx.
Total Wt.
Full of
Water (lb.)
Natural 47 48 48 49 49 49 50 50 51 51
Propane 56 56 56 57 57 57 58 59 59 60
CHIMNEY RECOMMENDATIONS HEIGHT:15 ft. (minimum) from draft hood skirt to top of chimney. INSIDE DIAMETER: Same as dimension C (or larger). NOTE: Larger chimney may be required if two or more boilers or a boiler and another appli­ance are vented to a single chimney.
Orifice indicated for sea level above are factory installed in boiler unless otherwise specified by the local authority. See on page 15 for burner input adjustment.
3
Sentinel
The installation must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1-latest edition.
This installation must also conform to the additional requirements in this Slant/Fin Instruction Book.
NATURAL GAS-FIRED BOILER LOCATION
Provide a level, solid foundation for the boiler. Location should be as near as possible to chimney or outside wall so that the flue pipe from boiler is short and direct.
The location should also be such that the gas ignition system components are protected from water (dripping, spraying, rain, etc.) during appliance operation and service (circulator replace­ment, condensate trap, control replacement, etc.).
BOILER FOUNDATION
A. Provide a solid, level foundation, capable of supporting the
weight of the boiler filled with water, and extending at least 2” past the jacket on all sides. See dimensions of boiler, page 2.
B. For installation on non-combustible floors only. The
Combustible Floor Kit part number printed on the boiler rating plate is the only one to be used when installing on com­bustible floors. The boiler must not be installed on carpeting.
C. If boiler is to be located over buried conduit containing electric
wires or telephone cables, consult local codes or the National Board of Fire Underwriters for specific requirements.
INSTALLATION REQUIREMENTS
Base Assembly Sentinel Boiler
Gas Valve
Burners Pilot
Burner
Access
Door
4
Sentinel
SAFETY
KEEP THE BOILER AREA CLEAR AND FREE FROM COMBUSTIBLE MATERIALS, GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQUIDS.
DRAFT HOOD
The draft hood supplied with SE models is part of the listed boiler assembly. DO NOT alter the hood. See dimensions, page 2.
Attach the hood to the boiler flue outlet. Connect flue pipe full size of hood outlet. Vent damper must be installed on the out­let side of the hood. See Vent Piping, below.
VENT PIPING
A. Vent piping installation must be in accordance with ANSI
Z223.1-latest edition, National Fuel Gas Code, Venting of Equipment. Other local codes may also apply and must be followed.
B. Boiler vent pipe must be the full diameter of the boiler
outlet. See dimensions, page 2.
C. If more than one appliance vents into a common breeching,
the area of the breeching must be equal to the area of the largest vent plus 50% of the area of the additional vent areas. Vent connectors serving appliances vented by natural draft shall not be connected into any portion of mechanical draft systems operating under positive pressure. Horizontal breeching or vent pipe should be as high as possible, consis­tent with codes, so that vertical vents from appliances will have a high rise above draft diverter openings. All horizontal runs must slope upwards not less than 1/4 inch per foot of run. Horizontal portions of the venting system must be
SENTINEL SERIES
MINIMUM CLEARANCES FOR COMBUSTIBLE CONSTRUCTION. MINIMUM ALCOVE AND CLOSET CLEARANCE.
Front 6” Rear 6” Left Side 6” Right Side 12” Top (above boiler) 28” Flue Connector 6”
MINIMUM CLEARANCES FOR COMBUSTIBLE CONSTRUCTIONS
A. Minimum boiler clearances shall be as follows: B. Provide accessibility clearance of 24” on sides requiring
servicing and 18” on sides used for passage.
C. All minimum clearances shown above must be met. This may
result in increased values of some minimum clearances in order to maintain the minimum clearances of others.
D. Clearance from hot water pipes shall be 1 inch**.
** At points where hot water pipes emerge from a floor, wall or ceiling, the
clearance at the opening through the finished floor, wall or ceiling boards may not be less than 1/2 inch. Each such opening shall be covered with a plate of non-combustible material.
WARNING
SPECIAL ATTENTION FOR LIQUEFIED PETROLEUM
(L.P.) PROPANE GAS-FIRED BOILER INSTALLATIONS
LPG appliances (boilers) shall be installed in accordance with applicable provisions of NFPA 58 ( Liquefied Petroleum Gas Code) latest edition for installations in US and CAN/CGA B149.1 latest edition for installations in Canada.
Liquefied Petroleum (LP) propane gas is heavier than air therefore Propane gas accumulate at floor level. If you sus­pect a leak, do not attempt to operate boiler. A spark or flame from the appliance (boiler) or other sources may ignite the accumulated propane gas causing an explosion or fire. It is recommended that inspections for gas leaks be performed periodically by licensed professional and that leak detection devices be installed as a further safety measure.
CHIMNEY REQUIREMENTS
A. Sentinel boilers may be vented into a masonry vitreous tile-
lined chimney or type “B” venting system NOT EXPOSED to the OUTDOORS below the roof line. Venting and sizing of venting system must be in accor­dance with the National Fuel Gas Code ANSI Z223.1, NFPA 54, -latest edition which will be referred to as the National Fuel Gas Code. Local codes apply. If a masonry chimney is exposed to the outdoors on one or more sides below the roof line (exterior chimney), ONE of the following options apply:
1. Chimney must be re-lined with a metallic liner. When this is done, the chimney will be considered NOT exposed to the outdoors and the requirements of the National Fuel Gas Code for NON-exposed chimneys and/or local codes will apply.
2. If an exposed tile-lined chimney is to be used WITH­OUT a metallic liner, the boiler must first meet the requirements of the National Fuel Gas Code:
B. If an existing boiler is removed from a common venting
system, the common venting system may be too large for proper venting of the remaining appliances connected to the common vent. Follow the test procedure shown in Appendix “A” on page 19 of this manual to insure proper operation of venting system and appliances.
C. Inspect for proper and tight construction. Any restrictions
or obstructions must be removed. An existing chimney may require cleaning.
D. Chimney or vent must extend at least 3 feet above any
ridge within 10 feet of the chimney.
5
Sentinel
supported to prevent sagging by securing each joint with metal screws and by providing hanger spaced no greater than 5 feet apart. D. Vent or breeching into chimney should not be inserted past
the inside wall of the chimney liner.
E. All venting means should be inspected frequently. See
Care and Maintenance and separate User's Information Manual.
VENT DAMPER INSTALLATION The vent damper referred to in the following instructions is the Slant/Fin Corporation vent damper.
This device is design certified by A.G.A. for use ONLY on spe­cific Slant/Fin Corp. gas boiler models. These boilers must also be equipped with a label which states that the boiler must be used with a Slant/Fin Corp. automatic vent damper device and indicates the proper vent damper model number. A. INSTALLATION INSTRUCTIONS BEFORE YOU START TO
INSTALL
1. Read this installation manual, the "DANGER" label attached to the top of the boiler, the "WARNING" on the wiring diagrams, vent damper carton and operator cover.
2. Perform pre-installation inspection as required by ANSI specification Z21.66. (See Vent Damper Instructions.)
3. Select a proper, convenient location for vent damper. Vent damper may be installed vertical or horizontal on all models (see figures 1 and 2).
4. Carefully unpack the unit. DO NOT FORCE IT OPEN OR CLOSED! Forcing the damper may damage the gear train and void the warranty.
Figure 1. Vertical installation of vent damper on
Sentinel “SE” boilers
Figure 2. Horizontal or sloping installation of vent damper
Figure 3.
* Install operator in any position as shown above. DO NOT install the operator above the vent pipe (to avoid excessive heat) or below the vent pipe (to avoid possible condensation damage).
6
Sentinel
WARNING—DANGER
Once you have begun vent damper installation procedure, DO NOT restore electric power and gas supply until installa­tion and inspection have been completed (in order to prevent the main burners from operating). DO NOT operate the boiler until the vent damper harness is plugged into vent damper operator. Failure to observe this warning may create a hazardous condition that could cause an explosion or carbon monoxide poisoning.
B. 1. This device must be installed after the boiler draft hood
(between the draft hood outlet and the connector to the outdoor chimney or vent) as close to the draft hood as practicable, and without modification of the draft hood or the vent damper. (See figure 1 and 2.)
2. The inlet size of the vent damper must be the same nominal trade size as the outlet of the draft hood.
3. This device must be located in a venting system or sec­tion of a venting system so that it serves only the single appliance for which it is installed. (See figure 3.)
4. Clearances of not less than 6 inches (152MM) must be maintained from combustible materials, with provisions for service access.
C. AFTER INSTALLATION:
1. Operate system through two complete cycles to check for opening and closing in proper sequence, and proper burner operation. DAMPER MUST BE IN OPEN POSI­TION WHEN BOILER MAIN BURNERS ARE
OPERATING.
2. Perform installation checks as required by ANSI specifi­cation Z21.66. (See Vent Damper Instructions.)
3. Check the troubleshooting section if problems arise with the installation.
GAS PIPING
A. Local installation codes apply. The pipe joint compound used
on threads must be resistant to the action of liquefied petrole­um gases.
B. The gas supply line to the boiler should be run directly from
the meter for natural gas or from the fuel tank for L.P. propane gas. See page 2 for location of union and manual main shutoff valve that may be specified locally. Selecting pipe size for natural gas:
1. Measure or estimate the length of piping from the meter to the installation site.
2. Consult gas supplier for heating value of gas (BTU/cu. ft.).
3. Divide boiler rated input by heating value to find gas flow in piping (cu. ft. per hour).
4. Use table A to select proper pipe size.
Example: Boiler model SE-175 is to be installed. Distance from gas meter to the boiler is 20 ft. Heating value of natural gas is 1020 BTU/cu. ft. Select proper pipe size.
Gas flow = 175,000 BTU/hour
= 171.5 cu. ft. per hour
1020 BTU/cu.ft.
At 20 ft. length of pipe, match required capacity from Table A (choose higher capacity, in this case is 190 cu. ft. per hour). Required pipe size is 3/4". Improper gas pipe sizing will result in pilot flame outages, insufficient heat and other installation difficulties. For more information and also if other appliances are to be attached to the piping system, see Appendix C of National Fuel Gas Code ANSI Z223.1-latest edition.
C. The boiler and its gas connection must be leak tested
before placing the boiler in operation. Use liquid soap solu­tion for all gas leak testing. DO NOT use open flame. This boiler and its individual shutoff valve must be discon­nected from the gas supply piping system during any pres­sure testing of that system at test pressures in excess of 1/2 PSIG. This boiler must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping sys­tem at test pressures equal to or less than 1/2 PSIG. This boiler must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 PSIG.
D. All gas piping used should be inspected thoroughly for
cleanliness before makeup. A sediment trap must be pro­vided, as illustrated on page 2.
E. The minimum and maximum gas supply pressure (at the
inlet of gas valve) are shown on the boiler rating plate for the type of gas used. Gas supply pressure should never be less than minimum or more than maximum pressure when the boiler or any other appliance is turned on or off.
1/2 3/4 1 1-1/4 1-1/2 10 132 278 520 1050 1600 20 92 190 350 730 1100 30 73 152 285 590 890 40 63 130 245 500 760 50 56 115 215 440 670 60 50 105 195 400 610 70 46 96 180 370 560 80 43 90 170 350 530 90 40 84 160 320 490
100 38 79 150 305 460
Length of Pipe in Feet
Gas Flow In Piping -- cu. ft. per hr.
Iron Pipe Size (IPS)—inches
At pressure drop of 0.3 in. water, specific gravity = 0.60.
Table A.
7
Sentinel
ELECTRICAL WIRING
DANGER: Before wiring, always turn off electric power supply,
otherwise shock or death can result.
1. Power Supply
A separately fused circuit is recommended. Use a standard 15 Amp. fuse or breaker and 14 gauge conductors in BX cable or circuit.
Provide disconnect means and overload protection as required. See boiler wiring diagram (Figure 4).
Boiler must be electrically grounded in accordance with requirements of the authority having jurisdiction, or, in the absence of such requirements, with the National Electrical Code, ANSI/NFPA 70-latest edition.
2. Power Connection
Connect hot and neutral to L1 and L2 terminal of the boiler control (See figure 4). Connect ground wire to ground screw inside boiler control.
3. Thermostat Connections
Thermostat connections must be to T and TV screw terminals of boiler temperature control (See Figure 4).
Thermostat Heat Anticipator Adjustments
If the 24v room thermostat that controls this boiler has an adjustable heat anticipator, connect entire system to thermostat and run the system while measuring the current
drawn through the thermostat wires. Set the heat anticipator at the value measured. The set current should match power requirements by zone valves and relays. Add an additional 0.1 Amp to the measured currrent for vent damper. Refer to the manufacturer’s instruction of zone valve, vent damper and relays. Also, see instructions with the thermostat.
4. Multi Zoning
For pump zoning system, see Figures 5 and 6, for zone valve system, see Figure 7. DO NOT use control transformer to power external accessories like zone valve and relays, overload and/or burned-out transformer and boiler malfunction can result.
5. Indirect External Water Heater
If system includes indirect water heater, the indirect signal must be separated from heating zones(s) system. See figure 6 and 8. Follow steps below: a. Connect end switch of the indirect water heater relay
to I1 and !2 of the boiler temperature control.
b. Connect end switch of the heating zones(s) relays to
T and TV of the boiler temperature control.
c. Power DHW and heating zone(s) circulators through end
switch relays as sgown on figure 6. Do not connect heating zone(s) circulators to C1 and C2 of the control.
Note: For single heating zone with external indirect water heaters, see figure 9.
Figure 4
WIRING DIAGRAM FOR SENTRY & SENTINEL BOILERS WITH VESTIBULE
HYDROLEVEL HYDROSTAT CONTR OL
YELLOW
YELLOW
24V
THERMOSTAT
K C A L B
I
HOT
120V/60Hz
NEUTRAL
JUNCTION
BOX
WIRE LEGEND: FACTORY WIRED FIELD WIRED, FIELD SUPPLI ED
: PROVIDE DISCONNECT MEANS AND
I
OVERLOAD PROTECTION AS REQUIRED IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED. IT MUST BE REPLACED WITH TYP 105` OR ITS EQUIVALENT.
CAUTION:
LABEL ALL WIRE PRIOR TO DISCONNCTION WHEN SERVICING CONTROLS.
WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION. "VERIFY PROPER OPERATION AFTER SERVICING".
MODEL 3200
Z T TV
LO TEMP
C2 B1
L2
L1 C1
N
E
E
T
E
T
I
I
E
H
H
R
W
W
G
CIRCULATOR
PLUG
K C A L B
ECONOMY
HI TEMP
I2
B2
I1
RED
BLOCKED VENT SAFETY SWITCH
BLUE
RED RED
ROLL-OUT SWITCH
ELECTRIC
IGNITION
PILOT
IGNITER CABLE
PILOT GAS PIPE
VENT DAMPER
HARNESS
IGNITION MODULE
24V(GND)
24V
GND
MV
MV/PV
PV
GND
(BURNER)
GAS VALVE
PV
MV-PVMV
GREEN
BLK
WHITE
RED
46 1115 000
8
Sentinel
Figure 5. Multizoning of Sentinel boilers pump zoning system using R845A relay.
Figure 6. Multizoning with indirect water heater pump zoning system using R882A/B relays.
Loading...
+ 18 hidden pages