Simer Pumps 2520ULST User Manual

©2008 SIM813 (1/17/08)
OWNER’S MANUAL
Condensate Pumps
NOTICE D’UTILISATION
Pompes de récuération des eaux condensées
MANUAL DEL PROPIETARIO
Bombas de condensado
For further operating, installation, or maintenance assistance:
Call 1-800-468-7867
English . . . . . . . . . . . . . . . Pages 2-6
Installation/Fonctionnement/Pièces
Pour plus de renseignements concernant l’utilisation, l’installation ou l’entretien,
Composer le
1 (800) 468-7867
Français . . . . . . . . . . . . Pages 7-11
Instalación/Operación/Piezas
Para mayor información sobre el funcionamiento, instalación o mantenimiento de la bomba:
Llame al 1-800-468-7867
Español . . . . . . . . . . .Paginas 12-16
Model 2520ULST
293 Wright St., Delavan, WI 53115
Phone:
1-800-468-7867 1-800-546-7867
Fax:
1-800-390-5351
5499 1006
Safety 2
For parts or assistance, call Simer Customer Service at 1-800-468-7867 / 1-800-546-7867
READ ALL INSTRUCTIONS BEFORE STARTING INSTALLATION
General Safety Information
Electrically powered condensate pumps normally give many years of trouble-free service when correctly installed, maintained, and used. However, unusual cir­cumstances (interruption of power to the pump, algae/debris in the reservoir, electrical or mechanical fail­ure in the pump, etc.), may prevent your pump from functioning normally. Consequently, any condensate pump installed in an area susceptible to water damage must be connected to a failure alarm or water sensing device or include an auxiliary safety shutoff switch acti­vated by high water in the pump reservoir and connect­ed to the thermostat of the furnace/AC unit. See the “Troubleshooting Chart” in this manual for information about common condensate pump problems. For more information, see your dealer or call customer service at 1-800-468-7867.
1. Drain all water from system before servicing.
2. Periodically inspect reservoir, pump, and system com­ponents. Keep free of debris and foreign objects. Perform routine maintenance as required.
3. When installing an electrically driven pump, follow all electrical and safety codes that apply.
4. Make certain power source conforms to requirements of your equipment.
5. Protect electrical cord from sharp objects, hot sur­faces, oil, and chemicals. Avoid kinking cord. Replace or repair damaged or worn cords immediately.
6. Personal Safety: a. Wear safety glasses at all times when working with
pumps.
b. Keep work area clean, uncluttered and properly
lighted – replace all unused tools and equipment. c. Keep visitors at a safe distance from work area. d. Make workshop child-proof – with padlocks, master
switches, and by removing starter keys.
Risk of electric shock. If your basement has water or moisture on floor, do not walk on wet area until all power has been turned off. If shut-off box is in basement, call electric company to shut-off service to house, or call your local fire department for instructions. Failure to follow this warning can result in fatal electrical shock.
When pump is plugged in, do not handle pump, cord, or plug with wet hands or when standing on a wet or damp surface or in water. Unplug pump before servicing it or doing any maintenance on it.
ATTACH ORIGINAL RECEIPT HERE FOR WARRANTY CONSIDERATION.
SIMER warrants to the original consumer purchaser (“Purchaser”) of its products that they are free from defects in material or workmanship. If within twelve (12) months from the date of the original consumer purchase any such product shall prove to be defective, it shall be repaired or replaced at
SIMER’s option, subject to the terms and conditions set forth below. Your original receipt of purchase is required to determine warranty eligibility.
Exceptions to the Twelve (12) Month Warranty
Product/Model No. Warranty Period
M40P, M40, BW85P, CM10, CMK 90 days
2330, 2300, 2310, 2955, 2956, 2957, 2960, A5500, 2520ULST 2 Years
4" Submersible Well Pumps, 3984, 3983, 2975PC, 2958, 2985, 3075SS 3 Years
Pre-Charge Water System Tank, 3986, 3985, 2956 5 Years
3988, 3995, 3997, 3963 Lifetime
General Terms and Conditions
Purchaser must pay all labor and shipping charges necessary to replace product covered by this warranty.This warranty shall not apply to acts of God, nor shall it apply to products which, in the sole judgement of SIMER, have been subject to negligence, abuse, accident, misapplication, tampering, alteration; nor due to improper installation, operation, maintenance or storage; nor to other than normal application, use or service, including but not limited to, operational failures caused by corrosion, rust or other foreign materials in the system, or operation at pressures in excess of recommended maximums.
Requests for service under this warranty shall be made by returning the defective product to the Retail outlet or to SIMER as soon as possible after the discovery of any alleged defect. SIMER will subsequently take corrective action as promptly as reasonably possible. No requests for service under this warranty will be accepted if received more than 30 days after the term of the warranty.
This warranty sets forth SIMER’s sole obligation and purchaser’s exclusive remedy for defective products. SIMER SHALL NOT BE LIABLE FOR ANY CONSEQUENTIAL, INCIDENTAL, OR CONTINGENT DAMAGES WHATSOEVER. THE FOREGOING WARRANTIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER EXPRESS WARRANTIES. IMPLIED WARRANTIES, INCLUDING
BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, SHALL NOT EXTEND BEYOND THE DURATION OF THE APPLICABLE EXPRESS WARRANTIES PROVIDED HEREIN.
Some states do not allow the exclusion or limitation of incidental or consequential damages or limitations on how long an implied warranty lasts, so the above limitations or exclusions may not apply to you. This warranty gives you specific legal rights and you may also have other rights which vary from state to state.
SIMER • 293 Wright Street • Delavan, WI U.S.A. 53115
Phone: 1-800-468-7867/1-800-546-7867 • Fax: 1-800-390-5351
E-Mail: info@simerpumps.com • Web Site: http://www.simerpumps.com
For parts or assistance, call Simer Customer Service at 1-800-468-7867 / 1-800-546-7867
Installation 3
Fire and explosion hazard. Do not use this
pump to pump flammable or explosive liquids. Use pump only with liquids compatible with pump component materials. Do not use pump in explosive atmospheres.
Risk of flooding. If for any reason property
damage or personal injury can result from an inoperative or leaking pump, an auxiliary switch backup system and/or an alarm should be installed with pump.
INSTALLATION
Electrical shock and carbon monoxide hazards. When mounting the pump on the side of the furnace, make sure that the mounting holes clear the heat exchanger and all wiring. The mounting screw for
the pump should touch only the pump reservoir flange and the exterior sheet metal on the furnace. If in doubt or if this is confusing, consult a qualified HVAC serviceman or the furnace manufacturer.
Make sure that the tubing to the pump intake is fastened securely so that it cannot come out of the pump intake port. Check for local code requirements. You must com­ply with codes.
Check local codes for discharge water requirements. Run the discharge line to a point outside the house if possible. To do this easily, you may be able to run the condensate discharge line out through the wall along the AC freon line. Use the existing line if possible (when replacing an existing pump).
Clamping the plastic discharge line to the check valve with a 1/2" hose clamp (purchase separately) will help to keep it in place, especially with older tubing (plastic tubing tends to harden as it gets older).
Common locations for the end of the discharge line are: A. Out a window or along the air conditioner freon line
to the outdoors.
B. To a floor drain (leave an air gap between the end of
the tube and the drain).
C. To a laundry tub or sink (leave an air gap above the
tub drain).
Mount pump on side of furnace (or on floor or wall).
1
Run plastic tubing as shown into pump’s drain inlet hole(s).
2
Run tubing as shown from hose barb on pump discharge to floor drain or laundry tub.
3
Pump must be level!
From A.C. Unit
Gas Condensing Furnace
Mount Pump
Pump can also be installed on wall or floor. Allow at least 6-1/2” vertical clearance to allow tank removal.
below all Heater and A.C. Drains
At least 6-1/2”
5490 0906
Ceiling and Joists
Discharge tube should slope down toward outlet if possible
3/8" ID Tubing To Floor Drain or Laundry Tub.
Do not kink tube!
1/2" Hose Clamp
5492 0906
Cut tubing at an angle so that bottom of reservoir doesn't close it.
Be sure tubing does not interfere with float.
AC Unit
Furnace Condensate Drain
Plastic Tubing
Condensate Drain
5491 0906
1
2
1-1
" above bottom of reservoir
For parts or assistance, call Simer Customer Service at 1-800-468-7867 / 1-800-546-7867
Installation 4
With the unit plugged in and the discharge line installed, fill the pump reservoir until the pump starts. Allow it to pump down and shut itself off automatically to verify proper operation through one complete cycle.
Safety Switch:
Most models include an automatic safety switch which should be wired to activate an alarm or to cut off power in the event of high water in the condensate reservoir.
If you must run additional wire from the low voltage safety switch to the alarm or to the control wiring of your furnace/AC unit, use at least 18 gauge (AWG) copper wire rated at 105° C. Make connections with wire nuts as shown.
If your installation allows interruption of heating or cool­ing, follow procedure 1, below.
If your installation does not allow interruption of heating or cooling, follow procedure 2, “Safety Switch Sounds Alarm”.
Risk of electrical shock. Disconnect power to furnace/AC unit and be sure condensate pump is unplugged before starting procedure.
1. Safety Switch Shuts Down Furnace/AC
A. Make sure the pump is unplugged. B. Find the red wire in the bundle from the thermostat
and disconnect it from the furnace/AC unit.
C. Connect the red wire to one of the white wires
from the safety switch as shown in Figure 1.
D. Connect the other white wire from the switch to the
furnace/AC terminal strip where the red wire from
the thermostat was connected. E. Plug in the pump. F. The furnace/AC will now operate as long as the
condensate pump empties the reservoir. If the reser-
voir overfills, the switch will open and cut off the
power to the furnace/AC.
Risk of freezing/overheating. This installa-
tion will shut down the furnace/AC unit if the water level in the pump reservoir rises to within about 1/2" from the top of the reservoir (thereby stopping the production of condensate and preventing flooding), but it will not allow the furnace/AC unit to restart until the condensate pump reservoir is emptied. It should be monitored so that in case of high water in the reservoir, corrective action can be taken before freezing/overheating occurs.
NOTICE: When installing the pump in a new home or after a renovation project, be sure that debris in the duct work does not get into the reservoir; it will clog the system.
2. Safety Switch Sounds Alarm
A. Make sure the pump is unplugged. B. Remove the two screws holding the motor cover to
the pump deck. Remove the cover.
C. Do not disturb the two yellow wires going through
the deck and into the motor (they are potted into the top of the motor so there are no wire ends visi­ble) .
D. Remove the white wire from the bottom terminal
(NC or Normally Closed) on the end of the safety switch and reattach it to the upper terminal (NO or Normally Open) on the end of the switch.
E. Run the white switch wires out through the notch
in the motor cover and replace the motor cover. Make sure all wires (power cord and safety switch) run through the notch. Hook the cover under the catch on the deck and secure it with two screws.
F. Connect the white wires from the safety switch to
the alarm of your choice (purchase separately). Consult the alarm manufacturer’s instructions for correct connections to the alarm.
G. Plug in the pump.
Figure 1: Low Voltage Auxiliary Safety Switch connection for Furnace/AC shutdown installation.
Hazardous voltage. Plug pump into a 115-volt outlet. Pump is double insulated; grounding is not required.
4
Plug pump into a 115-volt outlet
that carries power that will not be interrupted. Do not connect pump to a fan or limit control circuit or the like.
Some Models include an auxiliary safety switch. Connect switch as explained in "Safety Switch".
5493 0906
From ThermostatWire Nut
Condensate Pump
Red
White
White
White
Furnace/A.C.
Green
Yellow
Installation / Maintenance 5
For parts or assistance, call Simer Customer Service at 1-800-468-7867 / 1-800-546-7867
H. Risk of Flooding. With installation
No. 2 (“Safety Switch Sounds Alarm”), the alarm is activated when the water level in the reservoir is within about 1/2" of the top of the reservoir. However,
the furnace/AC unit will continue to pro­duce condensate because the alarm will not shut it down.
Monitor the installation so that in case of high water level in the condensate reservoir you can take action before the reservoir overflows and flooding occurs.
Testing Auxiliary Safety Switch:
NOTICE: Some appliances may not start immediately
due to a built-in delay circuit that prevents rapid cycling of the compressor.
1. Start appliance.
2. Unplug the condensate pump so that it cannot pump out.
3. Pour water into the pump reservoir until it is almost full.
4. As the water rises in the reservoir, the safety switch should shut down the appliance or set off the alarm (depending on the installation procedure used).
5. Plug in the condensate pump and allow it to empty the reservoir. As the water level goes down in the reservoir, the safety switch should reset, allowing the appliance to start or shutting off the alarm.
MAINTENANCE
1. Disconnect the power to the furnace/AC unit and unplug the pump.
2. Disconnect the tubing to the pump. Drain the tubing into a container.
3. Remove the two mounting screws and remove the pump from the furnace or wall. Dump the reservoir into a floor drain or container.
4. After you have dumped the pump, remove the four screws securing the reservoir to the pump deck. Lift the deck/pump assembly off of the reservoir.
5. Turn the deck/pump assembly upside down and remove the five screws holding the impeller cover to the motor.
6. Remove the impeller cover. The rotor/ impeller assembly may come out with it. If not, pull it out of the rotor chamber in the motor. (You may have to pull it hard to get it out against the magnetism in the motor windings.)
7. Clean the impeller, rotor, rotor cavity, and O-Ring. Use a rag to clean the O-Ring groove in the impeller cover and the sealing surface on the bottom of the motor block.
8. Clean out the reservoir.
9. Reassemble the impeller and the impeller cover; tighten the screws carefully. Do not overtighten!
10. Turn everything right side up and reassemble the reservoir to the deck. Be sure the impeller cover fits into the molded ring in the bottom of the reservoir. Fasten the reservoir with the four screws at the corners.
11. Reinstall the pump on the furnace.
12. Plug in the pump, fill the reservoir, and run the pump through one complete pump-down cycle to be sure it works correctly.
13. The pump is ready for operation.
CLEANING THE CHECK VALVE
1. Unplug the condensate pump.
2. Remove the discharge line from the check valve.
3. Use a 9/16" wrench to remove the check valve from the pump deck.
4. Inspect the valve for obstructions or damage. Clean or replace it as needed.
5. Thread the valve back into the pump discharge by hand, plus 1/2 turn with the wrench. NOTICE: Don’t overtighten the valve, as over­tightening can distort the O-Ring that seals the valve, causing leaks.
6. Plug in the pump, fill the reservoir, and run the pump through one complete pump-down cycle to be sure it works correctly.
7. The pump is ready for operation.
Figure 2: Low Voltage Auxiliary Safety Switch connec­tion for alarm circuit installation (does not shut down furnace/AC unit).
1. Move white lead from NC terminal to NO terminal as shown.
White
Common
White
NO
NC
3
2
C
1
2. Connect both white leads to alarm with wire nuts as shown
Alarm
White
White
NO
NC
3
2
C
1
Common
Safety SwitchSafety Switch
Loading...
+ 11 hidden pages