SilentKnight EVS-VCM User Manual

SBUS Address DIPs
Dead Front Panel
Mounting Holes
SBUS
VBUS
Audio
AUX Input
AUX Audio
Trigger
Supervised Power
Limited
EVS-VCM
EVS-VCM Voice Control Module Installation Instructions
The EVS-VCM Voice Control Module is contained within the Silent Knight EVS Series panel enclosure. It provides a supervised microphone for live communication and an interface for the Emergency Voice System.
Note: Installation and wiring of this device must be done in
accordance with NFPA 72 and local ordinances.
Compatibility
The EVS-VCM is compatible with the IntelliKnight 5820XL-EVS. For programming and addressing, refer to Installation manual for 5820XL-EVS (PN LS10061-001SK-E).
Board Layout & Mounting
1. Open the cabinet door and the dead front panel.
2. Remove AC power and disconnect the backup batteries from the main control panel.
Mount the EVS-VCM in the middle section of the dead front on the six mounting studs. See Figure 1.
Figure 1: Back View of EVS-VCM
Specifications
Standby Current: 60 mA Alarm Current: 80 mA
Wiring to a FACP
See Figure 2 to properly wire the EVS-VCM to the F A CP SBUS.
Figure 2: Wiring the EVS-VCM to the FACP
Document LS10067-001SK-E Rev A
ECN: 13-0146
EVS-VCM Voice Control Module Installation Instructions
2-3/4”
Installing the Microphone
To install the microphone:
1. Clip the microphone into the microphone clip. See Figure 3.
Figure 3: Sliding Microphone into Microphone
Clip
2. Insert microphone cord through hole at the bottom of the dead front panel. See Figure 4.
See Figure 5.
Figure 5: Installing Strain Relief Clip
4. Push the strain into the hole in the dead front panel.
5. Restore AC power and reconnect the backup batteries.
Figure 4: Microphone Cord Inserted Through
Dead Front Panel Hole
3. Attach strain relief clip to microphone cord. The strain relief clip should have about 2¾” of microphone cord through it.
2 Document LS10067-001SK-E Rev A