SBUS Address
DIPs
Dead Front Panel
Mounting Holes
SBUS
VBUS
Audio
AUX
Input
AUX
Audio
Trigger
Supervised
Power
ECS-RVM
Limited
EVS-RVM Remote Voice Module
Installation Instructions
The EVS-RVM Remote Voice Module is
contained within the EVS-RCU Remote
Command Unit. It provides a supervised
microphone for live communication and an
interface for the Emergency Voice System.
Note: Installation and wiring of this device must be done in
accordance with NFPA 72 and local ordinances.
Compatibility
The EVS-RVM is compatible with the
IntelliKnight 5820XL-EVS. For programming
and DIP switch settings, refer to Installation
manual for 5820XL-EVS (PN LS10061001SK-E).
Board Layout & Mounting
Figure 1: Back View of EVS-RVM
Specifications
Standby Current: 60 mA
Alarm Current: 80 mA
1. Open the cabinet door and the dead
front panel.
2. Remove AC power and disconnect the
backup batteries from the main control
panel.
3. Mount the EVS-RVM in the middle
section of the dead front on the six
mounting studs. See Figure 1.
Wiring to a FACP
See Figure 2 to properly wire the EVS-RVM
to the F A CP SBUS.
Figure 2: Wiring the EVS-RVM to the FACP
Document PN: LS10065-001SK-E Rev A
ECN: 13-0146
EVS-RVM Remote Voice Module Installation Instructions
Installing the Microphone
To install the microphone:
1. Clip the microphone into the microphone
clip. See Figure 3.
Figure 3: Sliding Microphone into Microphone Clip
2. Insert microphone cord through hole at
the bottom of the dead front panel. See
Figure 4.
See Figure 5.
Figure 5: Installing Strain Relief Clip
4. Push the strain into the hole in the dead
front panel.
5. Restore AC power and reconnect the
backup batteries.
Figure 4: Microphone Cord Inserted Through Dead
Front Panel Hole
3. Attach strain relief clip to microphone
cord. The strain relief clip should have
about 2¾” of microphone cord through it.
2 Document LS10065-001SK-E Rev A