SilentKnight EVS-CE4 User Manual

EVS-CE4 Installation Instructions
Mounting Screws
Mounting Screws
EVS-CE4 Connector
EVS-50W Audio Expander
Specifications
The EVS-CE4 adds four audio circuits to the EVS-50W or EVS-125W. The EVS-CE4 mounts inside the EVS-50W or EVS-125W cabinet
Note: Installation and wiring of this device must be done in
Compatibility
The EVS-CE4 is compatible with the IntelliKnight 5820XL-EVS. For more information, refer to Installation manual for 5820XL-EVS (PN LS10061-001SK-E).
Board Layout & Mounting
1. Remove AC power from the EVS-50W or EVS-125W control panel and disconnect the backup batteries.
2. Using the four supplied screws, mount the EVS-CE4 in the EVS-50W or EVSĀ­125W cabinet as shown in Figure 1.
Standby Current: 20 mA Alarm Current: 180 mA
Wiring
1. Connect the supplied audio expander cable harness (PN 130426) from the connector labeled Audio Expander on the EVS-50W or EVS-125W to the connector on the EVS-CE4. See Figure 2.
Figure 1: Mounting the EVS-CE4
Figure 2: Audio Expander Wire Harness Connections
2. Wire speakers for Class B (Style Y) supervision as shown in Figure 3 or for Class A (Style Z) wiring as shown in
P/N LS10070-001SK-E Rev A1
ECN 13-0704
EVS-CE4 Installation Instructions
Figure 4.
Figure 3: Class B (Style Y) Speaker Configuration
Figure 4: Class A (Style Z) Speaker Configuration
3. Restore AC power and reconnect the backup batteries.
2 P/N LS10070-001SK-E Rev A1