Installation Precautions - Adherence to the following will aid in problem-free
installation with long-term reliability: WARNING - Several different sources of power
can be connected to the fire alarm control panel. Disconnect all sources of power
before servicing. Control unit and associated equipment may be damaged by
removing and/or inserting cards, modules, or interconnecting cables while the unit is
energized. Do not attempt to install, service, or operate this unit until manuals are
read and understood. CAUTION - System Re-acceptance Test after Software
Changes: To ensure proper system operation, this product must be tested in
accordance with NFPA 72 after any programming operation or change in site-specific
software. Re-acceptance testing is required after any change, addition or deletion of
system components, or after any modification, repair or adjustment to system
hardware or wiring. All components, circuits, system operations, or software functions
known to be affected by a change must be 100% tested. In addition, to ensure that
other operations are not inadvertently affected, at least 10% of initiating devices that
are not directly affected by the change, up to a maximum of 50 devices, must also be
tested and proper system operation verified. This system meets NFPA requirements
for operation within the range of 0°C-49°C (32°F-120°F) or humidity within the range
of 10%-93% at 30°C (86°F) noncondensing. However, the useful life of the system's
standby batteries and the electronic components may be adversely affected by
extreme temperature ranges and humidity. Therefore, it is recommended that this
system and its peripherals be installed in an environment with a normal room
temperature of 15-27º C/60-80º F. Verify that wire sizes are adequate for all
initiating and indicating device loops. Most devices cannot tolerate more than a 10%
I.R. drop from the specified device voltage. Like all solid state electronic devices,
this system may operate erratically or can be damaged when subjected to lightning
induced transients. Although no system is completely immune from lightning
transients and interference, proper grounding will reduce susceptibility. Overhead or
outside aerial wiring is not recommended, due to an increased susceptibility to
nearby lightning strikes. Consult with the Technical Services Department if any
problems are anticipated or encountered. Remove DC power prior to removing or
inserting circuit boards. Failure to do so can damage circuits. Remove all electronic
assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When
possible, make all cable entries from the sides or rear. Before making modifications,
verify that they will not interfere with battery, transformer, or printed circuit board
location. Do not tighten screw terminals more than 9 in-lbs. Over-tightening may
damage threads, resulting in reduced terminal contact pressure and difficulty with
screw terminal removal. Fire alarm control panels contain static-sensitive
components. Always ground yourself with a proper wrist strap before handling any
circuits so that static charges are removed from the body. Use static suppressive
packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals.
These instructions must be followed to avoid damage to the control panel and
associated equipment. FACP (Fire Alarm Control Panel) operation and reliability
depend upon proper installation.
Equipment used in the system may not be technically compatible with the control. It
is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central
monitoring station may be out of service or temporarily disabled. The most common cause of fire alarm malfunctions, however, is inadequate maintenance. All devices
and system wiring should be tested and maintained by professional fire alarm
installers following written procedures supplied with each device. System inspection
and testing should be scheduled monthly or as required by national and/or local fire
codes. Adequate written records of all inspections should be kept.
Silent Knight Fire Product Warranty and Return Policy
Manufacturer Warranties and Limitation of Liability
2
Section 1
Overview
The Emergency Voice System Packages are a combination of the addressable fire
alarm control panel and voice integration control all in one package. The general idea
of the Emergency Voice System is to activate a message giving building occupants
instructions about an emergency event. This manual contains information on how to
install and operate the following Emergency Voice System Packages:
Model NumberConsists of These Part Numbers
EVS-Series
5820XL-EVS
EVS-RCU
1.1Optional Accessories
This manual also contains information on how to install the following compatible
accessory with the EVS series equipment:
EVS-50W50 watt amplifier with 4 separate audio circuits
EVS-125W125 watt amplifier with 4 separate audio circuits
EVS-CE4Provides four additional audio circuits for each EVS-50W
Adds 24 additional switches to the EVS-VCM or EVS-RVM to manually select various voice
output groups for emergency announcements from the on-board microphone
LS10062-001-SK-E1-1
EVS Series Emergency Voice System Installation Manual
1.2Features
EVS-Series
•The EVS-VCM has a built-in Digital Message Repeater.
•15 recordable one minute messages that can be mapped to eight EVS.
•Single enclosure for system control components.
•SBUS addressable amplifier. The system can support a combination of up to four
EVS-50W 50 watt amplifier or EVS-125W 125 watt amplifiers for a maximum of
500 watts per system.
•On-board supervised microphone.
•5820XL-EVS can support up to four EVS-RCU’s (Remote Command Units).
•Up to 32 mappable speaker circuits using a combination of EVS-50W or EVS125W’s and EVS-CE4’s.
•Supports 25 Vrms or 70.7 Vrms speaker circuits using EVS-50W.
1.3About This Manual
This manual is intended to be a complete reference for all installation and operation
tasks. Please let us know if the manual does not meet your needs in any way. We
value your feedback!
1-2LS10062-001-SK-E
1.3.1Terms Used in this Manual
The following terminology is used with the this system:
TermDescription
EVS
FACPFire Alarm Control Panel
LOC
Mass Notification
EVS-Series
EVS Device
EVS Control
EVS Device Priority
EVS Super User
VBUS
Module
Main control panelRefers to 5820XL-EVS control panel in the EVS-Series cabinet.
Input Point
Input ZoneA protected area made up of input points.
Output Point
(or Output Circuit)
Audio CircuitsAre output groups that are defined as voice output groups.
Group (or “Output Group”)
Output (or “Cadence”)
Pattern
Mapping
Emergency Voice System.The features of the control panel and accessories that
provide Mass Notification functionality as described in UL standard 2572.
Local Operator's Console. The user interface for a Mass Notification System. In
the Silent Knight product line, this would be the interface provided by the 5820XLEVS or the EVS-RCU.
A way of protecting life by relaying specific event information to a building or site
including voice and/or audible and visual signals.
When this is used in a statement, it would indicate the that statement applies to
the 5820XL-EVS control panels.
A LOC or a 5880 module that is programmed as an EVS device. These are used
as inputs for triggering the EVS.
EVS Control is a mode that all EVS Devices need to be in to be able to change
the current state of the EVS. EVS Control is requested by using the EVS Control
Button on LOC stations and is automatically requested for EVS 5880 Device
contact triggers along with the EVS Aux Input triggers of the VCM and RVM.
The priority level which is programmed for ever EVS Device. In order from lowest
to highest; Normal, Medium, High.
A user profile provided option that allows the user to override all EVS Control
rules and gain EVS Control.
The VBUS is an analog voice bus that carries the recorded voice messages from
the EVS-VCM to the EVS-50W/125Ws, or the voice messages generated from a
system microphone to the EVS-50W/125W’s.
The term module is used for all hardware devices except for SLC addressable
devices and notification appliances.
An addressable sensing device, such as a smoke or heat detector or a contact
monitor device.
A notification point or circuit for notification appliances. Relay circuits and
auxiliary power circuits are also considered output points. The output group can
be specifically defined as an output group to be used for voice evacuation circuits.
A group of output points. Operating characteristics are common to all output
points in the group.
The pattern that the output will use, for example, Constant, March Code, ANSI
3.41. Applies to zones and special system events.
Mapping is the process of specifying which outputs are activated when certain
events occur in the system.
Overview
LS10062-001-SK-E1-3
EVS Series Emergency Voice System Installation Manual
1.4How to Contact Silent Knight
If you have a question or encounter a problem not covered in this manual, contact
Silent Knight Technical Support at 800-446-6444. www.silentknight.com
To order parts, contact Silent Knight Sales at 800-328-0103.
1-4LS10062-001-SK-E
Overview
Limitations of Fire Alarm Systems
Manufacturer recommends that smoke and/or heat detectors be located throughout a
protected premise following the recommendations of the current edition of the
National Fire Protection Association Standard 72 (NFPA 72), manufacturer’s
recommendations, State and local codes, and the recommendations contained in
Guide for the Proper Use of System Smoke Detectors, which is made available at no
charge to all installing dealers. A study by the Federal Emergency Management
Agency (an agency of the United States government) indicated that smoke detectors
may not go off or give early warning in as many as 35% of all fires. While fire alarm
systems are designed to provide warning against fire, they do not guarantee warning
or protection against fire. A fire alarm system may not provide timely or adequate
warning, or simply may not function, for a variety of reasons. For example:
•Particles of combustion or smoke from a developing fire may not reach the
sensing chambers of smoke detectors because:
Barriers such as closed or partially closed doors, walls, or chimneys may inhibit
particle or smoke flow.
Smoke particles may become cold stratify, and not reach the ceiling or upper
walls where detectors are located.
Smoke particles may be blown away from detectors by air outlets.
Smoke particles may be drawn into air returns before reaching the detector.
In general, smoke detectors on one level of a structure cannot be expected to sense
fires developing on another level.
•The amount of smoke present may be insufficient to alarm smoke detectors.
Smoke detectors are designed to alarm at various levels of smoke density. If such
density levels are not created by a developing fire at the location of detectors, the
detectors will not go into alarm.
•Smoke detectors, even when working properly, have sensing limitations.
Detectors that have photoelectric sensing chambers tend to detect smoldering
fires better than flaming fires, which have little visible smoke. Detectors that have
ionizing-type sensing chambers tend to detect fast flaming fires better than
smoldering fires. Because fires develop in different ways and are often
unpredictable in their growth, neither type of detector is necessarily best and a
given type of detector may not provide adequate warning of a fire.
•Smoke detectors are subject to false alarms and nuisance alarms and may have
been disconnected by users. For example, a smoke detector located in or near a
kitchen may go into nuisance alarm during normal operation of kitchen
appliances. In addition, dusty or steamy environments may cause a smoke
detector to falsely alarm. If the location of a smoke detector causes an abundance
of false alarms or nuisance alarms, do not disconnect the smoke detector; call a
professional to analyze the situation and recommend a solution.
•Smoke detectors cannot be expected to provide adequate warning of fires caused
LS10062-001-SK-E1-5
EVS Series Emergency Voice System Installation Manual
by arson, children playing with matches (especially within bedrooms), smoking in
bed, violent explosions (caused by escaping gas, improper storage of flammable
materials, etc.).
•Heat detectors do not sense particles of combustion and are designed to alarm
only when heat on their sensors increases at a predetermined rate or reaches a
predetermined level. Heat detectors are designed to protect property, not life.
•Warning devices (including horns, sirens, and bells) may not alert people or wake
up sleepers who are located on the other side of closed or partially open doors. A
warning device that activates on a different floor or level of a dwelling or structure
is less likely to awaken or alert people. Even persons who are awake may not
notice the warning if the alarm is muffled by noise from a stereo, radio, air
conditioner or other appliance, or by passing traffic. Audible warning devices may
not alert the hearing-impaired (strobes or other devices should be provided to
warn these people). Any warning device may fail to alert people with a disability,
deep sleepers, people who have recently used alcohol or drugs, or people on
medication or sleeping pills.
Please note that:
i)Strobes can, under certain circumstances, cause seizures in people with con-
ditions such as epilepsy.
ii) Studies have shown that certain people, even when they hear a fire alarm sig-
nal, do not respond or comprehend the meaning of the signal. It is the property
owner’s responsibility to conduct fire drills and other training exercises to make
people aware of fire alarm signals and instruct on the proper reaction to alarm
signals.
iii) In rare instances, the sounding of a warning device can cause temporary or
permanent hearing loss.
•Telephone lines needed to transmit alarm signals from a premises to a central
station may be out of service or temporarily out of service. For added protection
against telephone line failure, backup radio transmission systems are
recommended.
•System components, though designed to last many years, can fail at any time. As
a precautionary measure, it is recommended that smoke detectors be checked,
maintained, and replaced per manufacturer’s recommendations.
•System components will not work without electrical power. If system batteries are
not serviced or replaced regularly, they may not provide battery backup when AC
power fails.
•Environments with high air velocity or that are dusty or dirty require more frequent
maintenance.
In general, fire alarm systems and devices will not work without power and will not
function properly unless they are maintained and tested regularly.
While installing a fire alarm system may make the owner eligible for a lower insurance
rate, an alarm system is not a substitute for insurance.
1-6LS10062-001-SK-E
Property owners should
Overview
continue to act prudently in protecting the premises and the people in their premises
and should properly insure life and property and buy sufficient amounts of liability
insurance to meet their needs.
Requirements and recommendations for proper use of fire alarm systems including smoke detectors and other fire alarm devices:
Early fire detection is best achieved by the installation and maintenance of fire
detection equipment in all rooms and areas of the house or building in accordance
with the requirements and recommendations of the current edition of the National Fire
Protection Association Standard 72, National Fire Alarm Code (NFPA 72), the
manufacturer’s recommendations, State and local codes and the recommendations
contained in Guide for the Proper Use of System Smoke Detectors, which is made
available at no charge to all installing dealers. For specific requirements, check with
the local Authority Having Jurisdiction (ex. Fire Chief) for fire protection systems.
Requirements and Recommendations include:
•Smoke Detectors shall be installed in sleeping rooms in new construction and it is
recommended that they shall also be installed in sleeping rooms in existing
construction.
•It is recommended that more than one smoke detector shall be installed in a
hallway if it is more than 30 feet long.
•It is recommended that there shall never be less then two smoke detectors per
apartment or residence.
•It is recommended that smoke detectors be located in any room where an alarm
control is located, or in any room where alarm control connections to an AC
source or phone lines are made. If detectors are not so located, a fire within the
room could prevent the control from reporting a fire.
•All fire alarm systems require notification devices, including sirens, bells, horns,
and/or strobes. In residential applications, each automatic alarm initiating device
when activated shall cause the operation of an alarm notification device that shall
be clearly audible in all bedrooms over ambient or background noise levels (at
least 15dB above noise) with all intervening doors closed.
•It is recommended that a smoke detector with an integral sounder (smoke alarm)
be located in every bedroom and an additional notification device be located on
each level of a residence.
•To keep your fire alarm system in excellent working order, ongoing maintenance is
required per the manufacturer’s recommendations and UL and NFPA standards.
At a minimum the requirements of Chapter 7 of NFPA 72 shall be followed. A
maintenance agreement should be arranged through the local manufacturer’s
representative. Maintenance should be performed annually by authorized
personnel only.
The most common cause of an alarm system not functioning when a fire occurs is
inadequate maintenance. As such, the alarm system should be tested weekly to
LS10062-001-SK-E1-7
EVS Series Emergency Voice System Installation Manual
make sure all sensors and transmitters are working properly.
SURVIVABILITY:
Per the National Fire Alarm Code, NFPA 72, all circuits necessary for the operation of
the notification appliances shall be protected until they enter the evacuation signaling
zone that they serve. Any of the following methods shall be considered acceptable as
meeting these requirements:
1) A 2-hour rated cable or cable system
2) A 2-hour rated enclosure
3) Performance alternatives approved by Authority Having Jurisdiction
1-8LS10062-001-SK-E
Section 2
Agency Listings, Approvals, and Requirements
2.1Federal Communications Commission (FCC)
1. The following information must be provided to the telephone company before the
FACP can be connected to the phone lines:
AManufacturer:Silent Knight by Honeywell
BModel Number:5820XL-EVS
CFCC registration number:AC6 USA-34758-AL-E
Ringer equivalence:0.8B
DType of jack:RJ31X
EFacility Interface Codes:Loop Start: 02LS2
FService Order Code:9.0F
2. This device may not be directly connected to coin telephone or party line services.
3. This device cannot be adjusted or repaired in the field. In case of trouble with the
device, notify the installing company or return to:
Silent Knight by Honeywell
12 Clintonville Road
Northford, CT 06472-1610
203-484-7161 or 800-328-0103
www.silentknight.com
4. If the FACP causes harm to the telephone network, the telephone company will
notify the user in advance that temporary discontinuance of service may be
required. If advance notice is not practical, the telephone company will notify the
user as soon as possible. Users have the right to file complaints, if necessary, with
the Federal Communications Commission.
5. The telephone company may make changes in its facilities, equipment, operations, or procedures that could affect the operation of the equipment. If this happens, the telephone company will provide advance notice to allow you to make
the necessary modifications to maintain uninterrupted service.
Warning
This device has been verified to comply with FCC Rules Part 15. Operation is subject to the following
conditions: (1) This device may not cause radio interference, and (2) This device must accept any
interference received, including interference that may cause undesired operation.
LS10062-001-SK-E2-1
EVS Series Emergency Voice System Installation Manual
2.2Underwriters Laboratories (UL)
2.2.1Requirements for All Installations
General requirements are described in this section. When installing an individual
device, refer to the specific section of the manual for additional requirements. The
following subsections list specific requirements for each type of installation (for
example, Central Station Fire Alarm systems, Local Protected Fire Alarm systems,
and so on).
1. All field wiring must be installed in accordance with NFPA 70 National Electric
Code.
2. Use the addressable smoke detectors specified in FACP installation manual.
3. Use UL listed notification appliances compatible with the FACP from those specified in the Appendix at the back of this manual.
4. UL installations using Class B wiring for the speaker circuit require the use of an
EOL resistor assembly.
5. A full system checkout must be performed any time the panel is programmed.
2.2.2Requirements for Central Station Fire Alarm
Systems
1. Use both phone lines. Enable phone line monitors for both lines.
2. You must program a phone number and a test time so that the FACP sends an
automatic daily test to the central station.
3. Do not use the ground start option.
4. The AC Loss Hours option must be set from 1-3 hours.
5. The Attempts to Report option must be set for 5.
2.2.3Requirements for Local Protected Fire Alarm
Systems
At least one UL listed supervised notification appliance must be used.
2-2LS10062-001-SK-E
Agency Listings, Approvals, and Requirements
2.2.4Requirements for Remote Station Protected Fire
Alarm Systems
1. Do not exceed the current load restrictions shown in FACP installation manual.
2. The AC Loss Hours option must be set from 1-3 hours.
The EVS-Series Control is UL listed as a voice evacuation unit for use in NFPA 72
systems. If the EVS-Series Control and its accessories are to be used as part of a UL
installation, carefully read the UL requirements in this section. For more information
on NFPA 72 standards, refer to the NFPA National Fire Alarm Code.
LS10062-001-SK-E2-3
EVS Series Emergency Voice System Installation Manual
2-4LS10062-001-SK-E
Section 3
Before you Begin Installation
This section of the manual is intended to help you plan your tasks to complete the
installation. Pleas read this section thoroughly, especially if you are installing a EVSSeries control for the first time.
3.1Environmental Specifications
It is important to protect the control panel from water. To prevent water damage, the
following precautions should be FOLLOWED when installing the units:
•Mount in indoor, dry environments only
•Do not mount directly on exterior walls, especially masonry walls (condensation)
•Do not mount directly on exterior walls below grade (condensation)
•Protect from plumbing leaks
•Protect from splash caused by sprinkler system inspection ports
•Do not mount in areas with humidity-generating equipment (such as dryers,
production machinery)
When selecting a location to mount the control panel, the unit should be mounted
where it will NOT be exposed to temperatures outside the range of 0°C-49°C (32°F120°F) or humidity outside the range of 10%-93% at 30°C (86°F) noncondensing.
3.2Wiring Specifications
Induced noise (transfer of electrical energy from one wire to another) can interfere
with telephone communication or cause false alarms. To avoid induced noise, follow
these guidelines:
•Isolate input wiring from high current output and power wiring. Do not pull one
multi-conductor cable for the entire panel. Instead, separate the wiring as follows:
High voltageAC power Terminals
SLC loopsPhone line circuits
Audio input/output NAC1 through NAC4
Notification circuits
SBUS
Relay circuits
•Do not pull wires from different groups through the same conduit. If you must run
them together, do so for as short a distance as possible or use shielded cable.
Connect the shield to earth ground at the panel. You must route high and low
voltages separately.
LS10062-001-SK-E3-1
EVS Series Emergency Voice System Installation Manual
SBUS
Devices
Flexputs / NACs
VBUS
AC
Relays
SLC
Devices
5820XL-EVS
•Route the wiring around the inside perimeter of the cabinet. It should not cross the
circuit board where it could induce noise into the sensitive microelectronics or pick
up unwanted RF noise from the high speed circuits. See Figure 3-1 for an
example.
High frequency noise, such as that produced by the inductive reactance of a speaker
or bell, can also be reduced by running the wire through ferrite shield beads or by
wrapping it around a ferrite toroid.
Figure 3-1 Wire Routing Example
Note: All circuits are power limited except the battery and AC cabling. Maintain 1/4 inch spacing be-
tween high and low voltage circuits and between power-limited and non-power limited circuits.
3-2LS10062-001-SK-E
Before you Begin Installation
3.3SBUS Specifications
Refer to Section 4 of the FACP’s installation manual for SBUS wiring details.
EVS-Series Model NumberFACP Installation Manual
5820XL-EVSLS10061-001SK-E
3.4Electrical Specifications
Table 3-1: EVS-50W AC Current Draw
ModuleVoltage
EVS-50W 25V120V 60 Hz350 mA1100 mA
EVS-50W 70V120V 60 Hz350 mA1200 mA
Table 3-2: EVS-125W AC Current Draw
ModuleVoltage
EVS-125W 25V120V 60 Hz300 mA2200 mA
Standby
Current
Standby
Current
Alarm
Current
Alarm
Current
LS10062-001-SK-E3-3
EVS Series Emergency Voice System Installation Manual
3-4LS10062-001-SK-E
Section 4
EVS Device Installation
Caution!
To avoid the risk of electrical shock and damage to the unit, power should be OFF at the
control panel while installing or servicing.
4.1Mounting the Cabinet
This section provides instructions on how to install the EVS series cabinet for surface
or recessed mounting. Refer to Section 3.1 when choosing a mounting location.
4.1.1Preventing Water Damage
Water damage to the fire system can be caused by moisture entering the cabinet
through the conduit. Conduits that are installed to enter the top of the cabinet are
most likely to cause water problems. Installers should take reasonable precautions to
prevent water from entering the cabinet. Water damage is not covered under
warranty.
4.1.2Surface Mounting
The Cabinet can be mounted on the wall surface by using the mounting holes in the
back of the cabinet (see 4.1).
The EVS-RCU Remote Command Unit is a combination EVS-RVM Remote Voice
Module and its associated 5860 annunciator. The EVS-RCU is compatible with the
Silent Knight 5820XL-EVS. For more information, refer to Installation manual for the
5820XL-EVS (PN LS10061-001SK-E).
Cabinet dimensions are 20" W x 26½” H x 4.6" D.
1. Insert two screws level with each other, 14" apart for the top cabinet key shaped
holes. See Figure 4-1.
2. Hang the cabinet onto the two screws. Tighten the screws down.
3. Insert two screws into the two bottom mounting holes and tighten them snug to
the cabinet.
If you need to remove the cabinet door and the dead front panel, see Section 4.1.3.1
LS10062-001-SK-E4-1
EVS Series Emergency Voice System Installation Manual
Key Shaped Holes
Bottom Mounting Holes
20"
26-1/2”
for instructions.
Figure 4-1 5820XL-EVS and EVS-RCU Cabinet Mounting Holes
4-2LS10062-001-SK-E
EVS Device Installation
Side View of Cabinet
Sheet Rock
Sheet Rock
Mounting
Studs
Cabinet
Mounting Hole
Trim Ring
Mounting
Hole
Cabinet
Mounting Hole
and Trim Ring
Trim Ring
1.5 to 1.75"
Trim Ring
Mounting
Hole
4.1.3Recessed Mounting
This section describes how to recess mount the cabinet into a wall. To recess mount
the cabinet you will need to have the optional trim ring P/N VIP-TR (ordered
separately).
Follow these steps to recess mount the cabinet:
1. Remove the cabinet door and the dead front panel. See Section 4.1.3.1.
2. Cut a recess hole. There should be 1.5" to 1.75" of cabinet extruding from the
wall, this should be measured from either the top edge or bottom edge to the exterior side of the sheet rock. (See Figure 4-2.)
Important!
Do not insert the cabinet deeper than recommend above. If the cabinet is mounted to deep you will
not be able to re-attach the door assembly.
3. Mount the cabinet to wall studs by inserting a screw through the cabinets side
mounting holes into the wall stud.
Figure 4-2 Detail of Flush Mounting with Trim Ring
LS10062-001-SK-E4-3
EVS Series Emergency Voice System Installation Manual
Trim Ring
Cabinet
4. Place the trim ring around the cabinet. See Figure 4-3.
Figure 4-3 Trim Ring Around cabinet
5. Secure the trim ring to the cabinet using the self-tapping sheet metal screws from
the inside of the cabinet into the trim ring.
6. Re-attach the cabinet door assembly.
4.1.3.1Cabinet Door and Dead Front Removal
While installing the cabinet it may be necessary to remove the cabinet door and the
dead front panel. This section provides instructions on how to remove the door and
dead front panel.
1. Disconnect the SBUS connection between the EVS-VCM and the FACP. See
Section 4.3.2.
2. Disconnect VBUS wiring from EVS-VCM. See Section 4.5.5.
4-4LS10062-001-SK-E
EVS Device Installation
Cabinet Door
Dead
Front Panel
Dead Front
Panel Screws
Cabinet Door
Hex Nuts
3. Using a Phillips head screw driver, remove the six screws that hold the dead front
panel in place. See Figure 4-4.
Figure 4-4 Cabinet Door and Dead Front Panel Removal
4. Using a 1/4” Hex drive, remove the six Hex nuts that hold the cabinet door in
place. See Figure 4-4.
Re-Attaching the Cabinet Door
To re-attach the cabinet door reverse the procedure in section 4.1.3.1.
4.2Connecting AC Power and Batteries
Refer to the FACP’s installation manual for proper AC power connections.
EVS Series Model NumberFACP Installation Manual
5820XL-EVSLS10061-001SK-E
LS10062-001-SK-E4-5
EVS Series Emergency Voice System Installation Manual
AUX
SBUS Address
DIPs
Dead Front Panel
Mounting Holes
Not
Used
VBUS
USB
SBUS
Audio
Trigger
AUX
Audio
Input
EVS-SW24
Connector
4.3The EVS-VCM
The EVS-VCM Voice Control Module is contained within the Silent Knight EVS Series
panel enclosure. It provides a supervised microphone for live communication and an
interface for the Emergency Voice System. This section provides information on how
to install or remove the EVS-VCM to the control cabinet and how to make the proper
wiring connections.
4.3.1EVS-VCM Board Layout
The following is description of the EVS-VCM voice control module components.
Figure 4-5 Back View of EVS-VCM
4-6LS10062-001-SK-E
EVS Device Installation
Dead Front
Panel
Dead Front
Panel
EVS (1-8) Activate
OPG Select
EVS Control LED
EVS Control
Button
Buttons
Buttons
Mounting
Holes
Mounting
Holes
ALL CALL
Button
NON-ACTIVE
CALL Button
ALL CALL
NON-ACTIVE
CALL
Figure 4-6 Front View EVS-VCM
LS10062-001-SK-E4-7
EVS Series Emergency Voice System Installation Manual
FACP
EVS-VCM
Supervised
Power Limited
4.3.2Connecting the EVS-VCM to the SBUS
Refer to Figure 4-7 to properly connect the EVS-VCM to the FACPs SBUS.
Figure 4-7 SBUS Connections
See Section 4.9 to set SBUS addressing.
4.3.3Installing the Microphone
To install the microphone follow these steps:
1. Clip the microphone into the micro phone clip. See Figure 4-8.
Figure 4-8 Sliding Microphone into Microphone Clip
4-8LS10062-001-SK-E
EVS Device Installation
2-3/4”
2. Insert Microphone cord through hole at the bottom of the dead front panel. See
Figure 4-9.
Figure 4-9 Microphone Cord Inserted Through Dead Front Panel Hole
3. Attach strain relief clip to microphone cord. The strain relief clip should have about
2-3/4” of micro phone cord through it. See Figure 4-10.
Figure 4-10 Installing Strain Relief Clip
4. Push the strain relief into the hole in the dead front panel.
LS10062-001-SK-E4-9
EVS Series Emergency Voice System Installation Manual
4.3.4To Remove the EVS-VCM
To remove the EVS-VCM follow these steps:
1. Remove AC power and disconnect batteries from the main control panel.
2. Disconnect the SBUS connections from the SBUS terminals on the EVS-VCM.
See Figure 4-7.
3. Disconnect any devices connected to the VBUS. See Figure 4-5.
4. Unplug the Microphone from the microphone connector. See Figure 4-11.
Figure 4-11 Back View of Dead Front Panel
5. Remove the six 1/4 hex nuts that hold the EVS-VCM in place.
6. Lift the EVS-VCM off of the dead front panel.
4-10LS10062-001-SK-E
EVS Device Installation
Mounting
Studs
Mounting
Studs
4.4Installing the EVS-SW24 Switch Expander
The EVS-SW24 adds 24 switches to the EVS-Series controls for a total of 40 (with
the 16 Non-EVS switches on the EVS-VCM).
This section provides instruction on how to properly install the EVS-SW24.
Follow these steps to install the EVS-SW24:
1. Open Cabinet door and dead front panel.
2. Remove AC power from the main control panel.
3. Disconnect the backup batteries.
4. Install the EVS-SW24 on the six mounting studs located on the inside of the dead
front panel. See Figure 4-12.
Figure 4-12 Mounting Location for the EVS-SW24
5. Secure the switch expander to the dead front panel using the supplied six 1/4”
Hex nuts.
LS10062-001-SK-E4-11
EVS Series Emergency Voice System Installation Manual
Wiring Harness
6. Connect one end of the wiring harness (P/N 130398 supplied) to the EVS-VCM
and the other end to the EVS-SW24 as shown in Figure 4-13.
Figure 4-13 Wiring Harness Connection
7. Restore AC power.
8. Reconnect backup batteries.
4-12LS10062-001-SK-E
EVS Device Installation
VBUS
In
Out
SBUS
SBUS
ID DIPs
Audio Circuits
Audio
Expander
AC Transformer
Connector
Battery
Connector
4.5Installing the EVS-50W
This section provides information on how to install the EVS-50W for use with the
EVS-Series products.
4.5.1EVS-50W Board Layout
Figure 4-14 shows the location of terminals, DIPs, and Expander connection, used in
the installation of the EVS-50W.
Figure 4-14 Components Layout of EVS-50W
LS10062-001-SK-E4-13
EVS Series Emergency Voice System Installation Manual
Key Holes
Bottom Mounting
Holes
4.5.2Mounting the EVS-50W
The EVS-50W is equipped with a separate enclosure. Refer to Section 4.1 when
selecting a mounting location for the EVS-50W.
The panel should be accessible to main drop wiring runs. It should be mounted as
close to the center of the building as possible and located within a secured area, but
should be accessible for testing and service.
Mount the control panel cabinet so it is firmly secured to the wall surface. When
mounting on concrete, especially when moisture is expected, attach a piece of 3/4inch plywood to the concrete surface and then attach the cabinet to the plywood. Also
mount any other modules to the plywood.
The cabinet can be surface or flush-mounted. If you will be flush-mounting the
cabinet, the hole for the enclosure should be 14½” W x 24¾” H x 3-7/16” D (36.8cm
W x 62.9cm H x 8.73cm D). Do not flush-mount in a wall designated as a fire break.
The Outside dimensions of the cabinet are 16" W x 26 ¼” H x 4-1/8” D (40.64cm W x
66.68cm H x 10.48cm D).
Follow these steps to properly mount the cabinet.
1. On the mounting surface install two screws level with each other 11" apart.
Figure 4-15 Cabinet Flush Mount Dimensions and Mounting Hole Locations
2. Install the cabinet onto the two mounting screws and tighten the screws.
3. Insert two screws into the two bottom mounting holes.
4-14LS10062-001-SK-E
EVS Device Installation
4.5.3Wiring Specifications
All wiring and devices installed in the system must meet the standards described in
National Electrical Code (NFPA 70), NFPA Standard 72, and Life Safety Code (NFPA
101).
To avoid induced noise (transfer of electrical energy from one wire to another), keep
input wiring isolated from high-current output and power wiring. Avoid pulling one
multi-conductor cable for the entire panel.
Instead, separate the wiring as follows:
1/4” spacing must be maintainedInput/Output Type:Wiring
between each of these circuit
types;
as well as between power limitedPower-Limited:SBUS, VBUS
and non power-limited circuits.Audio:Speaker
DO NOT pull wires from different groups through the same conduit.
For the same reasons, wiring within the cabinet should be routed around the
perimeter of the cabinet. It should not cross the printed circuit board where it could
induce noise into the sensitive microelectronics or pick up unwanted RF noise from
the high speed circuits.
Non Power-Limited:AC power, Standby batteries
LS10062-001-SK-E4-15
EVS Series Emergency Voice System Installation Manual
High frequency noise, such as that produced by the inductive re-actance of a speaker
or bell, can also be reduced by running the wire through ferrite beads or by wrapping
it around a ferrite toroid core. Figure 4-16 provides an example.
Figure 4-16 Wire Routing Example for EVS-50W
4.5.4Speaker Wiring
Each EVS-50W supplies four NAC (Notification Appliance Circuit) for speaker
connection. The speaker circuit can be supervised and wired Class B (Style Y) or
Class A (Style Z). The speaker circuit is capable of 50 watts of power at 25 Vrms or
70.7 Vrms.
4-16LS10062-001-SK-E
EVS Device Installation
4.5.4.1Wiring Lengths
Table 4-1 Wire Lengths
Number Of SpeakersTotal LoadWire Distance in Feet
@1/2 W@1 WVrmsWatts18 AWG16 AWG14 AWG12 AWG
10525Vrms 5W39006200986015680
70Vrms250003970063200100520
201025Vrms 10W2125338053758540
70Vrms15200241503840061100
301525Vrms 15W1460232036905870
70Vrms11000175002780044200
402025Vrms 20W1100175027804420
70Vrms8500135102150034175
522625Vrms 26W760120019203050
70Vrms610097001540024520
804025Vrms 40W55087513902200
70Vrms410065001036016480
1005025Vrms 50W45071511301800
70Vrms35005560885014070
Note: The above table assumes a uniform distribution of the speakers, and that a max of 20% voltage
drop on the last speaker is allowed.
LS10062-001-SK-E4-17
EVS Series Emergency Voice System Installation Manual
15k EOL
UL Listed
Supervised
Power Limited
Supervised
Power Limited
4.5.4.2Class B (Style Y)
Figure 4-17 illustrates how to wire speakers to the control panel using Class B (Style
Y) supervision.
Figure 4-17 Class B (Style Y) Speaker Configuration
4.5.4.3Class A (Style Z)
Figure 4-18 illustrates how to wire speakers to the control panel using Class A (Style
Z) wiring.
Figure 4-18 Class A (Style Z) Speaker Configuration
4-18LS10062-001-SK-E
EVS Device Installation
To Next EVS-50W
UL Listed 15k
EOL
EVS-VCM
EVS-50W
EVS-50W
Supervised
Power Limited
at Last panel
on the VBUS
VBUS Connections
3 Vrms, 5 mA max.
4.5.5VBUS Wiring
The VBUS is an analog voice bus that carries the recorded voice messages from the
EVS-VCM to the EVS-50W’s, or the voice messages generated from a system
microphone to the EVS-50W’s. The maximum resistance on the VBUS is 20.
Connect the VBUS from the EVS-VCM to the EVS-50W’s as shown in Figure 4-19.
LS10062-001-SK-E4-19
Figure 4-19 VBUS Wiring
EVS Series Emergency Voice System Installation Manual
Supervised
Power Limited
Control
Panel
Supervised
Power Limited
To Next
EVS-50W
(Max. 8)
Control
Panel
4.5.6SBUS Wiring
This section contains information on how to connect EVS-50Ws (up to 4) onto the
main control SBUS. Refer to Section 3.3 for SBUS specifications. Wire the SBUS as
shown in Figure 4-20 or Figure 4-21.
Figure 4-20 SBUS Connections of the EVS-50W
Figure 4-21 Connecting Multiple EVS-50Ws to the SBUS
See Section 4.9 for information on setting SBUS addresses.
4-20LS10062-001-SK-E
EVS Device Installation
Threaded
Mounting Studs
4.5.7Connecting AC Power
The AC inputs are rated as 120 VAC, 60 Hz (transformer P/N 115061).
To install the AC transformer into the EVS-50W cabinet follow these steps:
1. Open the cabinet door.
2. To access cabinet interior, open dead-front panel by removing the upper screw
and the mid-door retaining screw.
3. Mount the transformer onto the threaded cabinet transformer mounting studs
using the supplied locking hex nuts as shown in Figure 4-22.
Figure 4-22 Transformer Mounting
LS10062-001-SK-E4-21
EVS Series Emergency Voice System Installation Manual
4. Connect AC to the Transformer as Shown in Figure 4-23.
Figure 4-23 AC Connections
5. Plug the transformer output to the AC connector on the control panel as shown in
Figure 4-23.
4-22LS10062-001-SK-E
EVS Device Installation
4.5.8Backup Battery for EVS-50W
The following steps explain how to connect the batteries (refer to Figure 4-24):
1. Connect the black wire of the battery harness to the (-) side of the battery #2.
2. Connect the jumper wire provided form the positive (+) side of battery #2 to the
negative side of battery #1.
3. Connect the red wire from the battery harness to the positive (+) side of battery
#1.
Figure 4-24 Battery Connections to the EVS-50W
LS10062-001-SK-E4-23
EVS Series Emergency Voice System Installation Manual
4.5.9Calculating Current Draw and Standby Battery
This section helps you determine the current draw and standby battery needs for your
installation (18 Ampere Hours max. will fit in cabinet). Complete the remaining
instructions in Table 4-2.
Batteries larger than 18 AH will not fit in the main control cabinet, and must be
housed in the RBB Accessory Battery Cabinet. Maximum of 33 Amp Hours per
system.
Table 4-2: Current Draw Calculations
Device
EVS-50W 25V1
EVS-50W 70.7V1
EVS-CE40 or 1
ACurrent Subtotals:mAmA
Notification DevicesRefer to device manual for number of devices and current ratings.
BCurrent Subtotals:mAmA
C Total current rating of all devices in system (Line B) X 0.001AA
D Number of standby hours (24 or 60 for NFPA 72)H
E Multiply line C (standby current) and D:Total standby AHAH
F Alarm sounding period in hours (For example, 5 minutes = 0.0833 hours):H
G Multiply line C (alarm current) and F:Total alarm AHAH
H Add lines E and G (AH = Ampere Hours):Total AH requiredAH
No. of
Devices
Current Per Device
Standby: 85 mA85 mA
Alarm: 525 mA525 mA
Standby: 100 mA100 mA
Alarm: 580 mA580 mA
Standby: 20 mA20mA
Alarm (All Channels): 180 mA180 mA
Standby
Current
Alarm
Current
4-24LS10062-001-SK-E
EVS Device Installation
AC Connector
VBUS Out
VBUS IN
SBUS
Audio
Expander
Audio Circuits
Battery
Connector
4.6Installing the EVS-125W
This section provides information on how to install the EVS-125W for use with EVSseries products.
4.6.1EVS-125W Board Layout
Figure 4-25 shows the location of terminals, DIPs, and Expander connections used in
the installation of the EVS-125W.
Figure 4-25 Components Layout of EVS-125W
LS10062-001-SK-E4-25
EVS Series Emergency Voice System Installation Manual
Bottom Mounting Holes
Key Holes
Board mounting
bracket
4.6.2Mounting the EVS-125W
The EVS-125W is equipped with a separate enclosure. Refer to Section 4.1 when
selecting a mounting location for the EVS-125W.
The panel should be accessible to main drop wiring runs. It should be mounted as
close to the center of the building as possible and located within a secured area, but
should be accessible for testing and service.
Mount the control panel cabinet so it is firmly secured to the wall surface. When
mounting on concrete, especially when moisture is expected, attach a piece of 3/4inch plywood to the concrete surface and then attach the cabinet to the plywood. Also
mount any other modules to the plywood.
The cabinet can be surface or flush-mounted. If you will be flush-mounting the
cabinet, the hole for the enclosure should be 14 ½” W x 24 ¾” H x 3-7/16” D (36.8cm
W x 62.9cm H x 8.73cm D). Do not flush-mount in a wall designated as a fire break.
The Outside dimensions of the cabinet are 16" W x 26 ¼” H x 4-1/8” D (40.64cm W x
66.68cm H x 10.48cm D).
Follow these steps to properly mount the cabinet.
1. On the mounting surface install two screws level with each other 11" apart.
Figure 4-26 Cabinet Flush Mount Dimensions and Mounting Hole Locations
2. Install the cabinet onto the two mounting screws and tighten the screws.
3. Insert two screws into the two bottom mounting holes.
4-26LS10062-001-SK-E
EVS Device Installation
4.6.3Wiring Specifications
All wiring and devices installed in the system must meet the standards described in
National Electrical Code (NFPA 70), NFPA Standard 72, and Life Safety Code (NFPA
101).
To avoid induced noise (transfer of electrical energy from one wire to another), keep
input wiring isolated from high-current output and power wiring. Avoid pulling one
multi-conductor cable for the entire panel.
Instead, separate the wiring as follows:
1/4” spacing must be maintainedInput/Output Type:Wiring
between each of these circuit
types;
as well as between power limitedPower-Limited:SBUS, VBUS
and non power-limited circuits.Audio:Speaker
DO NOT pull wires from different groups through the same conduit.
For the same reasons, wiring within the cabinet should be routed around the
perimeter of the cabinet. It should not cross the printed circuit board where it could
induce noise into the sensitive microelectronics or pick up unwanted RF noise from
the high speed circuits.
Non Power-Limited:AC power, Standby batteries
LS10062-001-SK-E4-27
EVS Series Emergency Voice System Installation Manual
To AC
VBUS
In & Out
SBUS
Audio
Circuits
Audio Circuits
Audio
Circuits
Battery Connection
EVS-CE4
High frequency noise, such as that produced by the inductive reactance of a speaker
or bell, can also be reduced by running the wire through ferrite beads or by wrapping
it around a ferrite toroid core. Figure 4-27 provides an example.
Figure 4-27 Wire Routing Example for EVS-125W
4.6.4Speaker Wiring
Each EVS-125W supplies four NAC (Notification Appliance Circuit) for speaker
connection. The speaker circuit can be supervised and wired Class B (Style Y) or
Class A (Style Z). Speaker circuit 1 is capable of 100 watts of power at 25 Vrms.
Speaker circuit 2-4 are capable of 50 watts (each) at 25 Vrms.
4-28LS10062-001-SK-E
EVS Device Installation
4.6.4.1Wiring Lengths
Table 4-3 Wire Lengths
Number Of SpeakersTotal LoadWire Distance in Feet
@1/2 W@1 WVrmsWatts18 AWG16 AWG14 AWG12 AWG
10525Vrms 5W39006200986015680
201025Vrms 10W2125338053758540
301525Vrms 15W1460232036905870
402025Vrms 20W1100175027804420
522625Vrms 26W760120019203050
804025Vrms 40W55087513902200
1005025Vrms 50W45071511301800
1507525Vrms 75W3004767531200
20010025Vrms 100W225357565900
25012525Vrms 125W180285452720
Note: The above table assumes a uniform distribution of the speakers, and that a max of 20% voltage
drop on the last speaker is allowed.
LS10062-001-SK-E4-29
EVS Series Emergency Voice System Installation Manual
15k EOL
UL Listed
Supervised
Power Limited
Supervised
Power Limited
4.6.4.2Class B (Style Y)
Figure 4-28 illustrates how to wire speakers to the control panel using Class B (Style
Y) supervision.
Figure 4-28 Class B (Style Y) Speaker Configuration
4.6.4.3Class A (Style Z)
Figure 4-29 illustrates how to wire speakers to the control panel using Class A (Style
Z) wiring.
Figure 4-29 Class A (Style Z) Speaker Configuration
4-30LS10062-001-SK-E
EVS Device Installation
UL Listed 15k
EOL
on the last panel
Supervised
Power Limited
EVS-VCM
EVS-125W
EVS-125W
To next
EVS-125W
of the VBUS
4.6.5VBUS Wiring
The VBUS is an analog voice bus that carries the recorded voice messages from the
EVS-VCM to the EVS-125Ws, or the voice messages generated from a system
microphone to the EVS-125Ws. The maximum resistance on the VBUS is 20.
Connect the VBUS from the EVS-VCM to the EVS-125Ws as shown in Figure 4-30.
Figure 4-30 VBUS Wiring
LS10062-001-SK-E4-31
EVS Series Emergency Voice System Installation Manual
Supervised
Power Limited
Supervised
EVS-125W
EVS-VCM
EVS-125W
To next EVS-125W (Max 4)
Power Limited
4.6.6SBUS Wiring
This section contains information on how to connect EVS-125Ws (up to 4) onto the
main control SBUS. Refer to Section 3.3 for SBUS specifications. Wire the SBUS as
shown in Figure 4-31 or Figure 4-32.
Figure 4-31 SBUS Connections of the EVS-125W
Figure 4-32 Connecting Multiple EVS-125Ws to the SBUS
See Section 4.9 for information on setting SBUS addresses.
4-32LS10062-001-SK-E
EVS Device Installation
4.6.7Connecting AC Power
At installation, connect the AC terminals to the power source as shown in Figure 4-
33. It may be necessary for a professional electrician to make this connection.
The AC terminals are rated as 120 VAC, 60 Hz.
Figure 4-33 AC Connection
LS10062-001-SK-E4-33
EVS Series Emergency Voice System Installation Manual
4.6.8Backup Battery for EVS-125W
The following steps explain how to connect the batteries (refer to Figure 4-34):
1. Connect the black wire of the battery harness to the (-) side of the battery #2.
2. Connect the jumper wire provided form the positive (+) side of battery #2 to the
negative side of battery #1.
3. Connect the red wire from the battery harness to the positive (+) side of battery
#1.
Figure 4-34 Battery Connection to EVS-125W
4-34LS10062-001-SK-E
EVS Device Installation
4.6.9Calculating Current Draw and Standby Battery
This section helps you determine the current draw and standby battery needs for your
installation (18 Ampere Hours maximum will fit in cabinet). Complete the remaining
instructions in Table 4-4.
Batteries larger than 18 AH will not fit in the main control cabinet, and must be
housed in the RBB Accessory Battery Cabinet. Maximum of 35 amp hr for the
system.
Table 4-4: Current Draw Calculations
Device
EVS-125W1
EVS-CE40 or 1
ACurrent Subtotals:mAmA
Notification DevicesRefer to device manual for number of devices and current ratings.
BCurrent Subtotals:mAmA
C Total current rating of all devices in system (Line B) X 0.001AA
D Number of standby hours (24 or 60 for NFPA 72)H
E Multiply line C (standby current) and D:Total standby AHAH
F Alarm sounding period in hours (For example, 5 minutes = 0.0833 hours):H
G Multiply line C (alarm current) and F:Total alarm AH
H Add lines E and G (AH = Ampere Hours):Total AH requiredAH
No. of
Devices
Current Per Device
Standby: 375 mA375 mA
Alarm: 700 mA700 mA
Standby: 20 mA
Alarm (All Channels): 180 mAmA
Standby
Current
Alarm
Current
AH
LS10062-001-SK-E4-35
EVS Series Emergency Voice System Installation Manual
Mounting
Screws
Mounting
Screws
EVS-CE4
4.7Installing the EVS-CE4
The EVS-CE4 adds four audio circuits to the EVS-50W or EVS-125W. The EVS-CE4
mounts inside the EVS-50W or EVS-125W cabinet
Follow these steps to install the EVS-CE4:
1. Using the four supplied screws mount the EVS-CE4 in the EVS-50W or EVS125W cabinet as shown in Figure 4-35.
Figure 4-35 Mounting the EVS-CE4
4-36LS10062-001-SK-E
EVS Device Installation
EVS-CE4
Connector
EVS-125W
Audio
Expander
2. Connect the audio expander cable harness (P/N 130426) from the connector
labeled “Audio Expander” on the EVS-50W/EVS-125W to the connector on the
EVS-CE4 as shown in Figure 4-36.
EVS Series Emergency Voice System Installation Manual
VBUS
Microphone
Connector
SBUS Address
DIPs
AUX
Dead Front Panel
SBUS
Audio
Input
AUX
Audio
Trigger
Mounting Holes
EVS-SW24
Connector
Not
Used
4.8Installing the EVS-RVM
The EVS-RVM Remote Voice Module is contained within the EVS-RCU Remote
Command Unit. It provides a supervised microphone for live communication and an
interface for the Emergency Voice System.
4.8.1EVS-RVM Board Layout
The following is description of the EVS-RVM remote voice module components.
Note: The EVS-VCM and EVS-RVM circuit boards look similar, but they are not interchangeable. The
EVS-VCM is mounted in the 5820XL-EVS and the EVS-RVM is mounted in the EVS-RCU cabinet.
Figure 4-37 Back View of EVS-RVM
4-38LS10062-001-SK-E
EVS Device Installation
Dead Front
Panel Mounting
Holes
Dead Front
Panel Mounting
Holes
OPG Select Buttons
EVS (1-8) Activate
Buttons
EVS Status
ALL CALL
Button
NON-ACTIVE
& Alarm LEDs
EVS Control
Button
EVS Control
LED
ALL CALL
NON-ACTIVE
CALL
CALL Button
Figure 4-38 Front View EVS-RVM
LS10062-001-SK-E4-39
EVS Series Emergency Voice System Installation Manual
FACP
Supervised
Power Limited
EVS-RVM
From Previous
SBUS Device
Annunciator
EVS-RVM
4.8.2Wiring the EVS-RVM
1. Refer to Figure 4-39 to properly connect the EVS-RVM to the FACPs SBUS.
Figure 4-39 SBUS Connections
2. See Section 4.9 to set SBUS addressing.
3. Connect the SBUS to the annunciator and EVS-RVM. See Figure 4-40.
Figure 4-40 SBUS Wiring for EVS-RVM
4-40LS10062-001-SK-E
EVS Device Installation
EVS-RVM
EVS-125W
EVS-VCM
VBUS Connections
3 VMS, 5 mA max.
15k Resistor
on last device
4. Set the SBUS address on the annunciator and the EVS-RVM board. See Section
4.9.
5. Connect the EVS-RVM to the VBUS and EVS-125W.
Figure 4-41 VBUS and EVS-125W Wiring for EVS-RVM
LS10062-001-SK-E4-41
EVS Series Emergency Voice System Installation Manual
4.8.3Installing the Microphone
To install the microphone follow these steps:
1. Clip the microphone into the micro phone clip. See Figure 4-42.
Figure 4-42 Sliding Microphone into Microphone Clip
2. Insert Microphone cord through hole at the bottom of the dead front panel. See
Figure 4-43.
Figure 4-43 Microphone Cord Inserted Through Dead Front Panel Hole
4-42LS10062-001-SK-E
EVS Device Installation
2-3/4”
3. Attach strain relief clip to microphone cord. The strain relief clip should have about
2-3/4” of micro phone cord through it. See Figure 4-44.
Figure 4-44 Installing Strain Relief Clip
4. Push the strain into the hole in the dead front panel.
4.8.4To Remove the EVS-RVM
To install the EVS-RVM follow these steps:
1. Remove AC power and disconnect batteries from the main control panel.
2. Disconnect the SBUS connections from the SBUS terminals on the EVS-RVM.
See Figure 4-39.
3. Disconnect any devices connected to the VBUS. See Figure 4-37.
LS10062-001-SK-E4-43
EVS Series Emergency Voice System Installation Manual
4. Unplug the Microphone from the microphone connector. See Figure 4-45.
Figure 4-45 Back View of Dead Front Panel
5. Remove the six 1/4 hex nuts that hold the EVS-RVM in place.
6. Lift the EVS-RVM off of the dead front panel.
4-44LS10062-001-SK-E
EVS Device Installation
4.9Addressing SBUS Devices
When installing a hardware module (such as, 5815XL, 5824, 5860, 5496,
5895XL, 5865-3 or 5865-4, EVS-50W, EVS-125W, EVS-VCM, and EVS-RVMs), you
must use the DIP switches on the module to assign an ID# to the module.
Figure 4-46 shows all possible DIP switch positions and their correlation to a
numerical ID. For example, to select ID 2, place DIP switch 2 in the up position.
Figure 4-46 Possible Module Addresses
More information regarding EVS and EVS operations, Please refer to Section 9 of
FACP’s installation manual.
EVS Series Model NumberFACP Installation Manual
5820XL-EVSLS10061-001SK-E
LS10062-001-SK-E4-45
EVS Series Emergency Voice System Installation Manual
4-46LS10062-001-SK-E
Silent Knight Fire Product Warranty and Return Policy
General Terms and Conditions
•All new fire products manufactured by Silent Knight have a limited warranty period
of 36 months from the date of manufacture against defects in materials and
workmanship. See limited warranty statement for details.
•This limited warranty does not apply to those products that are damaged due to
misuse, abuse, negligence, exposure to adverse environmental conditions, or
have been modified in any manner whatsoever.
Repair and RMA Procedure
•All products that are returned to Silent Knight for credit or repair require a RMA
(Return Authorization) number. Call Silent Knight Customer Service at
800-328-0103 or 203-484-7161 between 8:00 A.M. and 5:00 P.M. EST, Monday
through Friday to obtain a return authorization number.
•Silent Knight Technical Support is available at 800-446-6444 between 8:00 A.M.
and 5:00 P.M. CST, Monday through Friday.
•All returns for credit are subject to inspection and testing at the factory before
actual determination is made to allow credit.
•RMA number must be prominently displayed on the outside of the shipping box.
See return address example under Advanced Replacement Policy.
•Included with each return should be: a packing slip that has the RMA number, a
content list, and a detailed description of the problem.
•All products returned to Silent Knight must be sent freight pre-paid. After product
is processed, Silent Knight will pay for shipping product back to customer via UPS
ground.
•Return the Silent Knight product circuit board only. Products that are returned in
cabinets will be charged an additional $50 to cover the extra shipping and
handling costs over board only returns. Do not return batteries. Silent Knight has
the authority to determine if a product is repairable. Products that are deemed unrepairable will be returned to the customer.
•Product that is returned that has a board date code more than 36 months from
date of manufacture will be repaired and the customer will be assessed the
standard Silent Knight repair charge for that model.
Advanced Replacement Policy
•Silent Knight offers an option of advance replacement for fire product printed
circuit boards that fail during the first 6 months of the warranty period. These items
must be returned with transportation charges prepaid and must be accompanied
by a return authorization.
•For advance replacement of a defective board, contact your local Silent Knight
distributor or call Silent Knight at 800-328-0103 to obtain a RMA (Return
Authorization) number and request advanced replacement.
•A new or refurbished board will be shipped to the customer. The customer will
initially be billed for the replacement board but a credit will be issued after the
repairable board is received at Silent Knight. All returned products must comply
with the guidelines described under “General Terms and Conditions” and “Repair
and RMA Procedure”.
•The defective board must be returned within 30 days of shipment of replacement
board for customer to receive credit. No credit will be issued if the returned board
was damaged due to misuse or abuse.
•Repairs and returns should be sent to:
Silent Knight / Honeywell
Attn: Repair Department
12 Clintonville Road
Northford, CT 06472
USA
RA Number:___________________
Manufacturer Warranties and Limitation of Liability
Manufacturer Warranties. Subject to the limitations set forth herein, Manufacturer
warrants that the Products manufactured by it in its Northford, Connecticut facility and
sold by it to its authorized Distributors shall be free, under normal use and service,
from defects in material and workmanship for a period of thirty six months (36)
months from the date of manufacture (effective Jan. 1, 2009). The Products
manufactured and sold by Manufacturer are date stamped at the time of production.
Manufacturer does not warrant Products that are not manufactured by it in its
Northford, Connecticut facility but assigns to its Distributor, to extent possible, any
warranty offered by the manufacturer of such product. This warranty shall be void if a
Product is altered, service repaired by anyone other than Manufacturer or its
authorized Distributors. This warranty shall also be void if there is a failure to maintain
the Products and the systems in which they operate in proper working conditions.
MANUFACTURER MAKES NO FURTHER WARRANTIES, AND DISCLAIMS ANY
AND ALL OTHER WARRANTIES, EITHER EXPRESSED OR IMPLIED, WITH
RESPECT TO THE PRODUCTS,TRADEMARKS, PROGRAMS AND SERVICES
RENDERED BY MANUFACTURER INCLUDING WITHOUT LIMITATION,
INFRINGEMENT, TITLE, MERCHANTABILITY, OR FITNESS FOR ANY
PARTICULAR PURPOSE. MANUFACTURER SHALL NOT BE LIABLE FOR ANY
PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS
A RESULT OF, PERSONAL, COMMERCIAL OR INDUSTRIAL USES OF ITS
PRODUCTS.
This document constitutes the only warranty made by Manufacturer with respect to its
products and replaces all previous warranties and is the only warranty made by
Manufacturer. No increase or alteration, written or verbal, of the obligation of this
warranty is authorized. Manufacturer does not represent that its products will prevent
any loss by fire or otherwise.
Warranty Claims. Manufacturer shall replace or repair, at Manufacturer's discretion,
each part returned by its authorized Distributor and acknowledged by Manufacturer to
be defective, provided that such part shall have been returned to Manufacturer with
all charges prepaid and the authorized Distributor has completed Manufacturer's
Return Material Authorization form. The replacement part shall come from
Manufacturer's stock and may be new or refurbished. THE FOREGOING IS
DISTRIBUTOR'S SOLE AND EXCLUSIVE REMEDY IN THE EVENT OF A
WARRANTY CLAIM.
Warn-HL-08-2009.fm
Silent Knight
12 Clintonville Road
Northford, CT 06472-1610
203-484-7161
Fax: 203-484-7118
www.silentknight.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.