SilentKnight B200SR-LF User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
I56-4152-002R
B200SR-LF Low Frequency Intelligent Sounder Base
SPECIFICATIONS
Base Diameter: 6.875” (17.46 cm) Base Height (less sensor): 2.0” (5.08 cm) Weight: 0.6 lb. (272 gm) Operating Temperature Range: Refer to applicable sensor Operating Temperature Range using the Base/Sensor Cross Reference Chart at systemsensor.com Operating Humidity Range: 10% to 93% relative humidity (non-condensing)
External Supply Electrical Ratings
External Supply Voltage: 16 to 33 VDC (VFWR) Standby Current: 1mA maximum VDC Alarm Current: 65 mA maximum @ 33.0 VDC 90 mA maximum @ 24.0 VDC 125 mA maximum @16.0 VDC
SLC Electrical Ratings
SLC Operating Voltage: 15 to 32 VDC SLC Standby Current: Refer to applicable sensor specification Sound Output Greater than 85 dBA minimum measured in a UL reverberant room at 10 feet, 24 Volts (in continuous tone)
BEFORE INSTALLING
NOTICE: This manual should be left with the owner/user of this equipment.
IMPORTANT: The detector used with this base must be tested and maintained
regularly following NFPA 72 requirements. The detector should be cleaned at least once a year.
GENERAL DESCRIPTION
The B200SR-LF low frequency sounder base generates a low frequency tone around 520 Hz. Studies have shown that low frequency audible devices that operate around 520 Hz are more effective in waking individuals in sleeping areas. It offers maximum flexibility in configuration and operation to meet or exceed the requirements of UL268 and UL464.
The sounder base is capable of producing either the distinctive three-pulse temporal pattern (ANSI Temporal 3) fire alarm signal now required by NFPA 72 for commercial and residential applications or a continuous tone by simply removing the included jumper from the device. Additionally, the B200SR-LF is designed to be compatible with existing installations of B501-Series sounder bases.
The sounder base is intended for use with intelligent systems. The sounder base requires an external 24 VDC power supply. The connections for the external power supply and the communication loop are isolated to prevent electrical interaction between them. Refer to the panel manual for maximum allowable number of units per loop.
NOTE: For NFPA72 Installations, the Temporal 3 tone should be used for public mode evacuation. NOTE: When not used as a supplementary evacuation system, the external 24 VDC supply shall be treated as a component of the main power supply system and shall fall under the requirements of the main power supply system per NFPA 72.
WIRING GUIDELINES
All wiring must be installed in compliance with the National Electrical Code and the local codes having jurisdiction and must not be of such length or wire size which would cause the base to operate outside of its published specifica­tions. The conductors used to connect smoke sensors to control panels and accessory devices should be color coded to reduce the likelihood of wiring errors. Improper connections can prevent a system from responding properly in the event of a fire.
Wire sizes up to 12 AWG (2.5 mm2) may be used with the base. The sounder base will be shipped with the screw terminals set for 14 AWG wiring. If 12 AWG wire is to be used, back out the screws to allow the wire to fit beneath the clamping plates. For best system performance, the power (+ and -) wires and the communication circuit wires should be twisted pair or shielded cable installed in a separate grounded conduit to protect the communication loop from electrical interference.
Make wire connections by stripping about 3/8” of insulation from the end of the wire. Then, slide the bare end of the wire under the appropriate clamping plate (See Figure 1), and tighten the clamping plate screw. Do NOT loop the wire under the clamping plate (See Figure 2) The wiring diagram for a typical 2-wire intelligent system is shown in Figure 4.
For system monitoring - for terminals 4 and 5, do not use looped wire under termi­nals. Break wire run as shown in Figure 2 to provide monitoring of connections.
B200SR-LF TERMINALS
No. Function
1. Not Used
2. Positive (+) Comm. Line In and Out
3. Negative (-) Comm. Line In and Out
4. External Supply Positive (+)
5. External Supply Negative (-)
6. Sounder Base Interconnect
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
CAUTION
SS-450-013 1 I56-4152-002R
Location of jumper–
3
4
FIGURE 1:
1
FIGURE 2:
1. If configured as in Figure 4 and 5, reverse the polarity of the external 24VDC
2
5
6
supply. If configured as in Figure 5, turn on the Intelligent Relay Module. All B200SR-LF bases on the loop should sound.
2. Latch the sensor LED on from the control panel. That individual sensor’s B200SR-LF should sound.
When performing maintenance on connected smoke sensors, carefully note the location and address of each removed sensor.
FIGURE 3: MOUNTING
remove to enable
continuous tone
C0471-08
C0473-00
MOUNTING
Mount the B200SR-LF mounting plate directly to an electrical box. The plate will mount directly to 4˝ square (with and without plaster ring), 4˝ octagon, 3
1
/2˝ octagon, single gang or double gang junction boxes.
1. Connect field wiring to terminals, as shown in Figure 1 and 2.
2. Attach the mounting plate to the junction box as shown in Figure 3.
3. To mount the sounder base, hook the tab on the sounder base to the groove on the mounting plate.
4. Then, swing the sounder base into position to engage the pins on the product with the terminals on the mounting plate.
5. Secure the sounder base by tightening the mounting screws.
6. Install a compatible smoke sensor as described in the installation manual for the sensor.
TAMPER RESISTANT FEATURE
NOTE: Do not use the tamper-resist feature if the removal tool is to be used. This detector base includes a tamper-resist feature that prevents its removal from the base without the use of a tool. To activate this feature, break the tab from the detector base as shown in Figure 6A. Then, install the detector. To remove the detector from the base once the tamper-resist feature has been activated, insert a small-bladed screwdriver into the slot from the top and press down on the lever (see Figure 6B). This allows the detector to be rotated counterclockwise for removal. The tamper-resist feature can be defeated by breaking and removing the plastic lever from the base. However, this prevents the feature from being used again.
TESTING AND MAINTENANCE
Sensors and bases must be tested after installation and as an integral part of a periodic maintenance program. Test the B200SR-LF as follows:
NOTE: Before testing, notify the proper authorities that the smoke sensor system is undergoing maintenance and, therefore, will be temporarily out of service. Disable the system undergoing maintenance to prevent unwanted alarms.
C0891-10
SS-450-013 2 I56-4152-002R
INTELLIGENT
ALENT)
FIGURE 4: WIRING DIAGRAM
INTELLIGENT
DETECTOR ACTIVATES SOUNDER BASE(S) - (COMPLIES WITH UL268)
UL has approved grouping for up to six B200SR-LF low frequency sounder bases. When wired as a group, any detector in the group that has been activated by the panel will cause other B200SR-LF units in the group to sound. This type of “local” grouping is accomplished by wiring the grouped devices together using terminal 6, Sounder Base Interconnect, as shown in the diagram. This interconnect can also be used to attach B200SR-LF devices to System Sensor B501-Series sounder bases. Some Fire Alarm Control Panels (FACP) support the grouping of sounder bases via software in lieu of the Sounder Base Interconnect.
NOTE: A local grouping of horns via the sounder base interconnect is not supervised, therefore the groups can only be used as a supplementary evacuation system. It is not acceptable to group horns via the sounder base interconnect for primary alarm signaling. Sounder bases which are grouped via software are not subject to this limitation and may be used as part of the primary alarm signaling.
RA
MONITOR MODULE
(+) SLC
(–) SLC
SUP (–)
SUP (+)
UL LISTED
EOL
RESISTOR
47k
END OF LINE RELAY
(EOLR-1 OR EQUIVALENT)
C0970-14
CLASS A OPTIONAL WIRING
(–) SLC
(+) SLC
CONTROL PANEL
U.L. LISTED COMPATIBLE
USED
(+) POWER
(–) POWER
UL LISTED 24V
POWER SUPPLY
EXT +
SLC –
FIRST
SOUNDER
BASE
EXT –
RA
CLASS A OPTIONAL WIRING
SLC +
NOT
* GROUPING OF UP TO 6 MODEL B200SR-LF LOW FREQUENCY SOUNDER BASES
TO OPTIONAL REMOTE
ANNUNCIATOR
MODEL RA400Z/100Z
USED
SLC +
NOT
SECOND
SOUNDER
BASE
OPTIONAL SOUNDER INTERCONNECT*
USED
NOT
EXT +
EXT –
SLC –
RA
SLC +
SOUNDER
LAST
BASE
EXT –
EXT +
SLC –
FIGURE 5: WIRING DIAGRAM DETECTOR ACTIVATES SOUNDER BASE(S);
INTELLIGENT RELAY MODULE ACTIVATES ALL SOUNDER BASES - (COMPLIES WITH UL 268 AND UL 464)
UL has approved grouping for up to six B200SR-LF low frequency sounder bases. When wired as a group, any detector in the group that has been activated by the panel will cause other B200SR-LF units in the group to sound. This type of “local” grouping is accomplished by wiring the grouped devices together using terminal 6, Sounder Base Interconnect, as shown in the diagram. Some Fire Alarm Control Panels support the grouping of sounder bases via software in lieu of the Sounder Base Interconnect.
NOTE: A local grouping of horns via the sounder base interconnect is not supervised, therefore the groups can only be used as a supplementary evacuation
system. It is not acceptable to group horns via the sounder base interconnect for primary alarm signaling. Sounder bases which are grouped via software are not subject to this limitation and may be used as part of the primary alarm signaling.
MONITOR MODULE
(+) SLC
CONTROL PANEL
U.L. LISTED COMPATIBLE
UL LISTED 24V
POWER SUPPLY
(–) SLC
(+) SLC
(+) POWER
(–) POWER
INTELLIGENT
RELAY MODULE†
COMM 2
NC 2
NO 2
COMM 1
NC 1
(–) SLC
(+) SLC
NO 1
†THIS IS A STANDARD RELAY
MODULE CONFIGURED TO
REVERSE THE POWER
USED
SLC +
NOT
FIRST
SOUNDER
BASE
* GROUPING OF UP TO 6 MODEL B200SR-LF LOW FREQUENCY SOUNDER BASES
OPTIONAL SOUNDER INTERCONNECT*
USED
NOT
EXT +
EXT –
SLC –
RA
SLC +
LAST
SOUNDER
BASE
TO OPTIONAL REMOTE
ANNUNCIATOR
MODEL RA400Z/100Z
SLC –
EXT –
EXT +
RA
(–) SLC
SUP (–)
UL LISTED
RESISTOR
EOL
47k
SUP (+)
END OF LINE RELAY
(EOLR-1 OR EQUIV
C0970-15
SS-450-013 3 I56-4152-002R
BREAK TAB AT
USE SMALL-BLADED
FIGURE 6A:
PLASTIC LEVER
FIGURE 6B:
DOTTED LINE BY TWISTING TOWARD CENTER OF BASE.
SLOT
SCREWDRIVER TO PUSH PLASTIC LEVER IN DIRECTION OF ARROW.
C0144-00
C1082-01
Please refer to insert for the Limitations of Fire Alarm Systems
System Sensor warrants its enclosed smoke detector base to be free from defects in mate­rials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this smoke detector base. No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the repair or replacement of any part of the smoke detector base which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid to: System Sensor, Returns
THREE-YEAR LIMITED WARRANTY
SS-450-013 4 I56-4152-002R ©2014 System Sensor
Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
Loading...