Siemens XLD-1 Installation Instructions Manual

Installation Instructions
Model XLD-1 Analog Loop Driver
OPERATION
The Model XLD-1 from Siemens Building Technolo­gies, Inc. is an optional MXL network module that connects XL3 analog addressable devices to the MXL System. The module uses four consecutive network addresses on the System. Devices connected to the XLD-1 circuits are supervised by the MXL Control Panel.
Each of the XLD-1 circuits supports up to 30 alarm causing, trouble causing, and supervisory type devices, as well as intelligent output de­vices. Each device has its own address. The sensitivity of any analog smoke detector is checked and adjusted from the Control Panel. Sensitivity, as well as other device information, is displayed at the Control Panel. The XLD-1 also supports the use of relay bases.
Each XLD-1 circuit can be wired in either a Class B or Class A configuration. When using Class B, T­tapping is permitted with no loss of supervision.
The XLD-1 module has an on-board micro­processor which provides it with the ability to function and to initiate alarm conditions even if the
Fire Safety
MXL main processor fails. The module also has four LEDS, which can indicate alarm, trouble, transmit, or ground fault. (Refer to Figure 1.)
For additional information on the MXL/MXLV System, refer to the MXL/MXLV Manual, P/N
315-092036.
INSTALLATION
Remove all system power before installa­tion, first battery and then AC. (To power up,
connect the AC first and then the battery.)
The XLD-1 installs into the MXL optional MOM-4 card cage where it plugs into one full width slot. The XLD-1 can be installed in either of the full width slots of the MOM-4 (See Figure 2). The slot determines whether the device loops are avail­able on TB1 or TB2 of the MOM-4.
Before installing the XLD-1 in the MOM-4, set the network address using switch S1 (Refer to Figure 1 for the location of S1). Set it to the lowest of the four corresponding addresses selected for it in the CSG-M. (The lowest address may be odd or
Siemens Building Technologies, Inc. 8 Fernwood Road Florham Park, New Jersey 07932
P/N 315-093385-8
Figure 1
XLD-1 Board
Siemens Building Technologies, Ltd. 2 Kenview Boulevard Brampton, Ontario L6T 5E4 Canada
even.) Follow the appropriate switch positions in Table 1 on the back page to set the address (See NOTE below).
The table below illustrates sample XLD-1 module addresses:
XLD-1 at Module
Addresses 3, 4, 5, and 6
Loop 1 Loop 4
XLD-1 at Module
Addresses 15, 16, 17, and 18
Loop 1 Loop 4
NOTE: To open a dipswitch, press down on the side of the dipswitch marked OPEN. To close a dipswitch, press down on the side of the dipswitch opposite the side marked OPEN.
To open a slide switch, push the slide to the side opposite the side marked ON. To close a slide switch, push the slide to the side marked ON.
Devices
003-01 to 003-30 006-01 to 006-30
Devices
015-01 to 015-30 018-01 to 018-30
After the address is set, install the XLD-1 in the MOM-4, being sure that the module is riding in the card guides and is firmly seated in the card edge connector. Eliminate all troubles from each XLD-1 before installing the next one.
Electrical connections for the four addressable initiating zones are shown in Figure 3.
Compatible Devices
1. All circuits are power limited to NFPA 70 per Article 760. Each detector or group of detectors must use a 2-wire circuit of at least 18 AWG thermoplastic fixture wire enclosed in conduit, or 18 AWG limited energy shielded cable without conduit, if permitted by local building codes.
2. No end of line device is required for these initiating loops.
3. Up to 30 devices can be used per loop. See the Compatibility Table for the XLD-1 for a list of compatible devices. Use any combi­nation of those listed.
4.
The compatibility identifiers for the compatible devices are the model numbers listed in the
Compatibility Table
5. Total circuit resistance must not exceed 100 ohms. Maximum capacitance:
0.4uF, between loop+ and loop–
0.8uF, between loop+ and chassis
0.8uF, between loop– and chassis
6. T-tapping is not allowed on Class A loops.
FULL
WIDTH
SLOT
.
FULL WIDTH SLOT
Electrical Ratings
(Refer to Figure 3)
tnerruCeludoMCDV5evitcAAm0
tnerruCeludoMCDV42evitcA
tnerruCeludoMCDV42ybdnatS
Initiating circuits
28 V unfiltered full wave rectified peak (Alarm and Supervisory) 40mA max per circuit (0-30 devices in alarm)
Battery Calculations
XLD-1 Module Current: 215mA Device Current: 1.1mA per device
+Am022
ecivedrepAm1.1
+Am022
e
civedrepAm1.1
2
Figure 2
Slots for the XLD-1
Loading...
+ 2 hidden pages