Siemens VALVEGYR LDU11.323A17, VALVEGYR LDU11.523A17, VALVEGYR LDU11.523A27, VALVEGYR LDU11.323A27 User Manual

CC1N7696en
20.04.2016
Building Technologies Division
7
696
VALVEGYR®
Valve Proving System for automatic Shutoff Valves
LDU11...
The LDU11... valve proving system is designed for use with shutoff valves in con- nection with gas burners and gas appliances. In the event of inadmissible leakage, the system prevents the burner from starting up. The LDU11... system conforms to the requirements of EN1643 covering automatic shutoff valves for use with gas burners and gas appliances to EN161.
The LDU11... and this Data Sheet are intended for use by OEMs which integrate the valve proving system in their products.
2/21
Building Technologies Division CC1N7696en
20.04.2016
Use
The LDU11... is designed for automatic gas valve proving (leakage test) based on the pressure proving principle. It is for use on gas-fired combustion plant with or without vent pipe to atmosphere. In the case of plants with no vent pipe where EN standards apply, the notes given in «Connection examples without vent pipe to atmosphere» must be observed.
Used in connection with 1 or 2 commercially available pressure switches, valve proving is automatically initiated with every burner startup, either
- prior to burner startup
- during the prepurge time if it lasts a minimum of 60 seconds
- immediately after a controlled shutdown, or
- on completion of the burner control’s control sequence, e.g. at the end of the
postpurge time
The valve proving test is based on the 2-stage pressure proving principle:
1. The valve on the mains side is tested by evacuating the test space and by monitoring the atmospheric pressure in it.
2. The valve on the burner side is checked by pressurizing the test space and by moni­toring the gas pressure.
If the pressure increases excessively during the first test phase called «Test1», or de-
creases excessively during the second test phase called «Test2», the LDU11.... will in-
hibit burner startup and initiate lockout. In that case, the lockout reset button will light up to indicate the fault. Remote indication of the fault is also possible. A program indicator, which stops whenever a fault occurs, indicates which of the valves is leaking. The LDU11... can be reset either on the unit itself or via an electric remote reset facility.
Warning notes
To avoid injury to persons, damage to property or the environment, the following warning notes must be observed.
Do not open, interfere with or modify the control unit.
All activities (mounting, installation and service work, etc.) must be carried out by
qualified staff
Before making any wiring changes in the connection area, completely isolate the
plant from mains supply (all-polar disconnection). Ensure that the plant cannot be in­advertently switched on again and that it is indeed dead. If not observed, there is a risk of electric shock hazard
Ensure protection against electric shock hazard by providing adequate protection for
the valve proving system’s connection terminals
Each time work has been carried out (mounting, installation, service work, etc.),
check to ensure that wiring is in an orderly state
Press the lockout reset button only manually (applying a force of no more than 10 N)
without using any tools or pointed objects
Do not press the lockout reset button on the unit for more than 10 seconds since
longer presses will destroy the lockout relay
Fall or shock can adversely affect the safety functions. Do not put such units into
operation, even if they do not exhibit any damage
Mounting notes
Ensure that the relevant national safety regulations are complied with
3/21
Building Technologies Division CC1N7696en
20.04.2016
Installation notes
Live and neutral conductors must not be interchanged
Standards and certificates
Applied directives:
 Low-voltage directive 2014/35/EC  Directive for gas-fired appliances 2009/142/EC  Directive for pressure devices 97/23/EC and
2014/68/EC (2016-07-16)
Electromagnetic compatibility EMC (im-
munity) *)
2014/30/EC
*) The compliance with EMC emission requirements must be checked after the valve monitoring system is
installed in the equipment
Compliance with the regulations of the applied directives is verified by the adherence to the following standards / regulations: Safety and control devices for gas burners and gas burning ap-
pliances - Valve proving systems for automatic shut-off valves
DIN EN 1643
The relevant valid edition of the standards can be found in the declaration of con­formity!
Note on DIN EN 60335-2-102 Household and similar electrical appliances - Safety - Part 2-102: Particular requirements for gas, oil and solid-fuel burning appliances having electrical connections. The electrical connections of the LDU11 and the AGM comply with the requirements of EN 60335-2-102.
EAC Conformity mark (Eurasian Conformity mark)
ISO 9001:2008 ISO 14001:2004 OHSAS 18001:2007
Certified complete with plug-in base:
Type reference
LDU11.323A17 --- x x x --- x LDU11.323A27 --- x --- x --- x LDU11.523A17 x --- x x x --­LDU11.523A27 x --- --- x --- ---
4/21
Building Technologies Division CC1N7696en
20.04.2016
Life cycle
LDU11... has a designed lifetime* of 250,000 burner startup cycles which, under normal operating conditions in heating mode, correspond to approx. 10 years of usage (starting from the production date given on the type field). This lifetime is based on the endurance tests specified in standard EN298 and the table containing the relevant test documenta­tion as published by the European Association of Component Manufacturers (Afecor) (www.afecor.org
).
The designed lifetime is based on use of the LDU11... according to the manufacturer’s Data Sheet. After reaching the designed lifetime in terms of the number of burner startup cycles, or the respective time of usage, the LDU11... is to be replaced by authorized personnel.
* The designed lifetime is not the warranty time specified in the Terms of Delivery
Disposal notes
The unit contains electric and electronic components and must not be disposed of to­gether with domestic waste. Local and currently valid legislation must be complied with.
5/21
Building Technologies Division CC1N7696en
20.04.2016
Mechanical design
- Plug-in design
- Exchangeable unit fuse (including spare fuse)
- Made of impact-proof and heat-resistant black plastic
- Lockout reset button with viewing window showing:
– The fault signal lamp – The lockout indication
- Coupled to the program spindle
- With transparent lockout reset button
- Easy-to-remember symbols indicating the type of fault and the time lockout occurred
- Synchronous motor of the sequence switch with gear train and step action sequence switch
- Camshaft with 15 nonadjustable cams
- Program indicator at the head of the camshaft
- 1 main and 1 auxiliary relay
- Lockout relay can be electrically reset from a remote location and provides the «Lockout» and «Reset» functions
- Unit fuse and spare fuse
All electrical components are interconnected via printed circuits.
Type summary
Type reference Mains voltage t3 t4
LDU11.323A17 AC 100...110 V 2.5 s 2.5 s LDU11.323A27 AC 220...240 V 2.5 s 2.5 s LDU11.523A17 ¹) AC 100...110 V 5 s 5 s LDU11.523A27 ¹) AC 220...240 V 5 s 5 s
t3 Filling the test space t4 Evacuating the test space
¹)
Valve opening times do not conform to EN1643
Ordering
Valve proving system LDU11... (without plug-in base) refer to «Type summary»
Plug-in base not included in the delivery, must be ordered as a separate item!
Connection accessories for medium-capacity refer to Data Sheet N7230
- Plug-in base AGM11 with Pg11 threads for cable entry glands
- Plug-in base AGM11.1 with M16 threads for cable entry glands
PTC resistor (AC 230 V) AGK25
- For load on terminal 4 of LMG2...
Valve proving system LDU11...
Housing
Legend
6/21
Building Technologies Division CC1N7696en
20.04.2016
Technical data
Mains voltage
- LDU11.323A27
- LDU11.323A17
A
C 220 V –15 %...AC 240 V +10 %
A
C 100 V –15 %...AC 110 V +10 %
- LDU11.523A27 ¹)
- LDU11.523A17 ¹)
A
C 220 V –15 %...AC 240 V +10 %
A
C 100 V –15 %...AC 110 V +10 %
¹)
Valve opening times do not conform to EN 1643
Mains frequency 50...60 Hz ±6 % Unit fuse (built-in) T6.3H250V to DIN EN 60127 Primary fuse (external) Max. 10 A (slow) Weight
A
pprox. 1000 g
Power consumption
- During the test
- During operation
A
pprox. AC 3.5 VA
A
pprox. AC 2.5 VA Mounting position Optional Degree of protection IP40 (to be ensured through mounting),
except the connection area (terminal base)
Safety class
I
Perm. input current at terminal 1 Max. 5 A (peak current 20 A / 20 ms) Perm. current rating of control terminals Max. 4 A (peak current 20 A / 20 ms) Required current rating of pressure switch (DW)
Min. 1 A, AC 250 V
Storage
DIN EN 60721-3-1 Climatic conditions Class 1K3 Mechanical conditions Class 1M2 Temperature range -20...+60 °C Humidity <95 % r.h.
Transport
DIN EN 60721-3-2 Climatic conditions Class 2K2 Mechanical conditions Class 2M2 Temperature range -50...+60 °C Humidity <95 % r.h.
Operation
DIN EN 60721-3-3 Climatic conditions Class 3K5 Mechanical conditions Class 3M2 Temperature range -20...+60 °C Humidity <95 % r.h.
Caution! Condensation, formation of ice and ingress of water are not permitted!
General unit data LDU11...
Environmental conditions
7/21
Building Technologies Division CC1N7696en
20.04.2016
Function
During the first phase of the valve proving test called «Test1», atmospheric pressure must exist in the length of pipe between the valves to be tested. In plants with a vent pipe to atmosphere, atmospheric pressure is available if the valve proving test is made prior to or during the prepurge time. In plants without vent pipe, atmospheric pressure is made available as the valve proving system opens the valve on the burner side during evacuat­ing the test space (t4). If the valve proving test LDU11... is performed after burner opera­tion, the valve on the burner side after the controlled shutdown can be kept open until evacuating the test space (t4) has elapsed, thus lowering the pressure in the test space and making certain its gas content is burnt off in the combustion chamber during the postpurge time. Prerequisite for this procedure is a suitable control program of the burner control as provided by burner controls type LFE..., LFL..., LGK... or LEC...
The test space is closed off after evacuation. During the first test phase «Test1», which then follows, the LDU11... checks with the pressure switch if the atmospheric pressure in the test space is maintained. If the valve on the mains side is leaking, causing the pres­sure to rise above the switching point of the pressure switch, the LDU11... will trigger an alarm and initiate lockout. The program indicator then stops to indicate «Test1».
If the pressure does not increase because the valve closes correctly, the LDU11... con­tinues its program with the second test phase «Test2». For that purpose, the valve on the mains side is opened during filling the test space (t3) so that the test space is pressurized («filling» the test space). During the second test phase – if the valve on the burner side is leaking – this pressure must not fall below the switching point of the pressure switch. If it does, the LDU11... will initiate lockout also, thus preventing the burner from starting up.
On successful completion of the second test phase, the LDU11... closes the internal control loop between terminals 3 and 6 (circuit path: terminal 3 - contact (ar2) - terminals 4 and 5 - contact III - terminal 6). This control loop is normally included in the burner con­trol’s start control loop.
After the control loop has been closed, the programming mechanism of the LDU11... returns to its start position to switch itself off. During these so-called idle steps, the posi­tions of the programming mechanism’s control contacts remain unchanged.
Loading...
+ 14 hidden pages