Product and Applications Description
The touch panel UP 588 is a multifunctional display/control unit for the EIB. The basis of the device is an
LC display with a resolution of 320 x 240 pixels and an
integrated, resistive matrix with 6 x 10 fields. The display has backlighting available, which is activated during operation and can be switched off automatically
after an adjustable period.
• Touch-Panel UP 588 5WG1 588-2AB01
backlighting green AC 230V
• Touch-Panel UP 588/11 5WG1 588-2AB11
backlighting white AC 230V
• Touch-Panel UP 588/21 5WG1 588-2AB21
backlighting white AC / DC 24V
In connection with the associated application program,
the display unit can be used for the following functions:
the display and operation of up to 70 EIB standard functions on 7 display pages, the display of an alarm page
with 4 alarm signals and 2 text messages as well as the
execution of time-controlled tasks.
The following accessories are required for the touch
panel:
Design frame, aluminium 5WG1 588-8AB01
Application Programs
01 07 Touch-Panel vision 802103
• display and operation of up to 70 EIB standard
functions on 7 display pages
• display of an alarm page with 4 alarm signals and
2 text messages
• execution of time-controlled tasks
• 8 scene with 10 communication objects are possible
• display of date and time
Installation instructions
• The device can be used for permanent interior instal-
lations in dry rooms and for insertion in flush-type
boxes.
Diagram 1: drilling jig for cavity wall box for Touch
panel UP 588
WARNING
V
• The device may only be installed and commissioned
by an authorised electrician.
• The device may only be used in connection with the
named accessories, in particular the flush-type box.
• 230V devices which are not included with supply may
not be inserted in the flush-type box. It is also not
possible to loop through 230V cables.
• The prevailing safety and accident regulations should
be observed.
• The power supply voltage may only be connected to
the supply if the device has been fully installed.
• Electrical isolation should be ensured between the
bus cable and the 230V power supply.
• For planning and construction of electric installations,
the relevant guidelines, regulations and standards of
the respective country are to be considered.
Siemens AG UP 588, 6 pages Technical Manual
Automation and Drives Group
Electrical Installation Technology © Siemens AG 2006 Update: http://www.siemens.de/gamma
P.O.Box 10 09 53, D-93009 Regensburg Subject to change without prior notice
2.3.1.4/1

instabus EIB
Technical Product Information
April 2006
Touch panel UP 588 5WG1 588-2AB01
Touch panel UP 588/11 5WG1 588-2AB11
Touch panel UP 588/21 5WG1 588-2AB21
Accessories: Design frame, anodised aluminium 5WG1 588-8AB01
Technical Specifications
Power supply
• Bus voltage: via the bus line
• External power supply
• Touch-Panel UP 588 and Touch-Panel UP 588/11
230 V AC ±10%, 50/60 Hz
• Touch-Panel UP 588/21
12 - 36V DC, 120mA
10 - 28V AC, 50/60 Hz, 120mA
Operating elements
• Learning button for toggling between
normal/addressing mode
• Resistive matrix with 6 x 10 fields
(touch-sensitive display)
Display elements
• Red programming LED for displaying
normal/addressing mode
• 320 x 240 pixel display with graphic capability and
backlighting
Connections
• Bus line: EIB bus terminal, screwless
0.6 ... 0.8mm ∅ solid
insulation strip length 5mm
• Power supply
Insulation strip length: 6...7mm
The following conductors/conductor cross-sections
are permitted:
- 0.5...2.5mm
- 0.5...1.5mm
Mechanical data
• Housing: plastic
• Dimensions (WxHxD): 190 x 156 x 58mm
• Mounting depth in flush-type box: 52mm
• Installation: screwed into the relevant flush-type box
• Dimensions of relevant flush-type box (WxHxD):
164 x 138 x 65 mm, included with supply
• Weight: approx. 350 g
2
solid
2
finely-stranded
Electrical safety
• Degree of pollution 2
• Type of protection (according to EN 60529): IP 20
• Overvoltage category: III
• Bus: safety extra-low voltage SELV DC 24 V
• Device complies with EN50090-2-2
EMC requirements
Complies with EN 61000-6-1 and EN 61000-6-2
Ambient conditions
• Climatic withstand capability: EN 50090-2-2
• Ambient operating conditions: 0°C to +45°C
• Storage temperature: -25°C to +70°C
• Relative humidity (not condensing): 5 % to 93 %
Markings
KNX/EIB
CE mark
In accordance with the EMC guideline (residential and
functional buildings) and the low voltage guideline
Technical Manual UP 588, 6 pages Siemens AG
Automation and Drives Group
Update: http://www.siemens.de/gamma © Siemens AG 2006 Electrical Installation Technology
Subject to change without prior notice P.O.Box 10 09 53, D-93009 Regensburg
2.3.1.4/2