GAMMA instabus
Technical Product Information
February 2010
Blind actuator UP 520/31 5WG1 520-2AB31
Technical Manual UP 520/31, 4 pages Siemens AG
Industry Sector, Building Technologies
Update: http://www.siemens.com/gamma © Siemens AG 2010 Low Voltage Distribution
Subject to change without further notice PO Box 10 09 53, D-93009 Regensburg
2.10.1.18/2
Technical specifications
Power supply
• Carried out via the bus line
• Power consumption: typically 150 mW
Outputs
• Number: 1 output, potential-free relay contact (µ-contact)
• Rating voltage: AC 230V,
• Switching power: max. 1 motor 1000 VA
• Switching behavior: Can be parameter set, depending
on function
Contacts
• Output: Contact the load on H07V-K 1,5 mm
2
with the
attached clamps.
•
Inputs and bus line: Line YY 6x0.6 mm
Approx. 33cm pre-assembled, can be laid to max. 5m
Mechanical specifications
• Casing: plastic
• Dimensions: d =53mm, height = 28 mm
• Weight: approx. 88g
• Mounting: in box mounts, Ø 60mm, depth: 40mm
Electrical safety
• Degree of pollution (to IEC 60664-1): 2
• Protection class (to EN 60529): IP 20
• Protection class (to IEC 61140): III
• Overvoltage category class (to IEC 60664-1): III
• Bus: safety extra low voltage SELV DC 24V
• Device complies with EN 50090-2-2 and IEC 60664-1
Reliability
Failure rate: 170 fit at 40°C
EMC criteria
• Complies with EN 61000-6-2, EN 61000-6-3 and EN
50090-2-2
Environmental specifications
• Climatic conditions: EN 50090-2-2
• Ambient temperature in operation: - 5 ... + 45 °C
• Storage temperature: - 25 ... + 70 °C
(Storage above + 45°C reduces the service life)
• Relative humidity (non-condensing): 5% to 93%
Markings
• KNX EIB
CE mark
• to EMC directive (residential and functional building)
Location and functioning of the display and
operating elements
PKBK
EIB+ / RD
EIB- / BK
A / GN
com / WH
B / YE
com / BN
Prog.
U 230V
n
~
Figure 1: Location of the indicating and operating elements
X Connector cables low voltages
Red: Bus (+)
Black: Bus (-)
Green: input A
White: Reference potential (com)
Yellow: Input B
Brown: Reference potential (com)
Y Connector cables load
black: L // brown: Up // pink: Down
Z Program button / -LED (red)