Siemens UP 520/31 Technical Product Information

GAMMA instabus
Technical Product Information
February 2010
Blind actuator UP 520/31 5WG1 520-2AB31
Siemens AG UP 520/31, 4 pages Technical Manual Industry Sector, Building Technologies Low Voltage Distribution © Siemens AG 2010 Update: http://www.siemens.com/gamma PO Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.10.1.18/1
Product and Function Description
Photo
The blind actuator receives telegrams from sensors via the Instabus and controls a shutter or blind motor with its output. Both travel directions are mechanically interlocked. With sun protection or positioning telegrams, the actuator offers moreover the possibility of moving shutters, blinds and slats into any desired position. On reception of a storm warning, the actuator is capable of moving shutters or blinds into a predefined safety position and to lock them up in this position.
In addition, the device has two extension inputs that depending on parameter settings, can act directly on the output (local operation, see “state of delivery”) or alternatively also as binary inputs on the Instabus. The connected potential-free switch or push button contacts are read in via a common reference potential on the actuator. As binary input, telegrams can be transmitted for switching or dimming, for Venetian blind control, value setting or scene recall / save.
State of delivery:
When delivered, the switching state of the outputs is undefined.
On application of the bus voltage, the relays will switch off.
With the bus voltage applied, the extension inputs control the relays of the actuator as follows:
input Operation behavior
short stop / slat up
A
long move up
short stop / slat down
B
long move down
Simultaneous actuation of A and B is not possible
Application program
12 A1S2 Shutter, 2x Input 207301
2 binary inputs
o ON / OFF / TOGGLE switching o Value setting o Dimming o Blind / Shutter – control o Scene control o Inputs blocking function o Behavior on bus power restoration
1 channel with additional functions
o Sun protection function o Safety function o Adjustable response after bus voltage
failure
o Adjustable response to bus voltage return o Adjustable priority of sun protection
function and manual operation
GAMMA instabus
Technical Product Information
February 2010
Blind actuator UP 520/31 5WG1 520-2AB31
Technical Manual UP 520/31, 4 pages Siemens AG Industry Sector, Building Technologies Update: http://www.siemens.com/gamma © Siemens AG 2010 Low Voltage Distribution Subject to change without further notice PO Box 10 09 53, D-93009 Regensburg
2.10.1.18/2
Technical specifications
Power supply
Carried out via the bus line
Power consumption: typically 150 mW
Outputs
Number: 1 output, potential-free relay contact (µ-contact)
Rating voltage: AC 230V,
Switching power: max. 1 motor 1000 VA
Switching behavior: Can be parameter set, depending
on function
Contacts
Output: Contact the load on H07V-K 1,5 mm
2
with the
attached clamps.
Inputs and bus line: Line YY 6x0.6 mm
Approx. 33cm pre-assembled, can be laid to max. 5m
Mechanical specifications
Casing: plastic
Dimensions: d =53mm, height = 28 mm
Weight: approx. 88g
Mounting: in box mounts, Ø 60mm, depth: 40mm
Electrical safety
Degree of pollution (to IEC 60664-1): 2
Protection class (to EN 60529): IP 20
Protection class (to IEC 61140): III
Overvoltage category class (to IEC 60664-1): III
Bus: safety extra low voltage SELV DC 24V
Device complies with EN 50090-2-2 and IEC 60664-1
Reliability
Failure rate: 170 fit at 40°C
EMC criteria
Complies with EN 61000-6-2, EN 61000-6-3 and EN
50090-2-2
Environmental specifications
Climatic conditions: EN 50090-2-2
Ambient temperature in operation: - 5 ... + 45 °C
Storage temperature: - 25 ... + 70 °C
(Storage above + 45°C reduces the service life)
Relative humidity (non-condensing): 5% to 93%
Markings
• KNX EIB
CE mark
to EMC directive (residential and functional building)
Location and functioning of the display and operating elements
PKBK
EIB+ / RD EIB- / BK A / GN com / WH B / YE com / BN
Prog.
U 230V
n
~
Figure 1: Location of the indicating and operating elements
X Connector cables low voltages
Red: Bus (+) Black: Bus (-) Green: input A White: Reference potential (com) Yellow: Input B
Brown: Reference potential (com) Y Connector cables load black: L // brown: Up // pink: Down Z Program button / -LED (red)