Siemens UP 237K, UP 254K Technical Product Information

GAMMA instabus
Technical Product - Information
February 2014
Temperature Controller UP 237K 5WG1 237-2KB_1
UP 254K 5WG1 254-2KB_3

Product and Application Description

The room temperature controller UP 237K and UP 252K are available in the following colors, matching the design of the wall switch design line DELTA i-system or DELTA style:
DELTA i-system Temperature Controller UP 237K titanium white 5WG1 237-2KB11 aluminum metallic 5WG1 237-2KB31
DELTA style Temperature Controller UP 254K titanium white/ metallic silver 5WG1 254-2KB13 platinum metallic 5WG1 254-2KB43
The room temperature controls UP 237K and UP 254K are especially designed for usage in rooms which are heated and/or cooled and whose temperatures are con­trolled depending on up to four room operating modes (comfort mode, pre-comfort mode, energy-savings mode and protection mode). As required, a parameter can be used to set that the controller does not consider all four operating modes but rather only three (comfort mode, energy-savings mode and protection mode). The room temperature control can be used a a two-point control (thermostat) or as a continuous control (P or PI control). These Room temperature controller can only function together with the necessary Bus Transceiver Module (BTM) UP 117 and the associated application program.
LED displays
Along with a button and a rotary knob on its upper edge, the clear and self-explanatory user interface contains 5 green illuminating light emitting diodes (LED) to display whether "manual operation" is activated as well as the current room operating mode and two red illuminating LEDs and 2 duo-color illuminating LEDs on the left edge. The duo-color LEDs are used to display whether the heating valve (LED is lit in red) or the cooling valve (LED is lit in yellow) is open. If these LEDs are not illuminated, then both valves are closed. A red LED is used to display whether a window is open or whether a dew point alarm is pending.
Button
Briefly
pressing the button on the control causes switch­ing in automatic mode (the LED for the display of manual operation is not lit) each time between "comfort mode" and "pre-comfort mode" (with four operating modes) or between "comfort mode" and "energy-savings mode" (with three operating modes). Moreover briefly
pressing the button during active energy-savings or protection mode starts a "comfort prolongation". Pressing and hold­ing down (e.g.> 1 s, but < 3 s) the button during continu­ous comfort prolongation can cause this to end at any time and jump back to the room operating mode before the start of the comfort prolongation. Holding down the button for a longer time (> 3 s) can cause switching from automatic to manual operation. In manual operation every room operating mode can be permanently activated and not changed by a bus tele­gram. If manual operation is activated, then each time the button is pressed briefly the light display of the cur­rent operating mode wanders gradually from the current position to the next operating mode symbol until the ex­treme right or left position is reached and from there back again. If during a waiting time of around 3 seconds no renewed brief
pressing of the button occurs, then the displayed room operating mode will be activated and this reported by the Bus. If the button in "manual operation" is pressed for a very long (> 3 s) time, then the system will be switched to automatic operation and at the same time to comfort mode. If a presence detector is installed, then a brief
pressing of the button in automatic operation
is ignored.
Note: Via a parameter setting the switching of room control modes and an activation of on-site comfort prolongation can be locked by the button.
Rotary knob
The control is supplied with two rotary knobs: one insert­ed in the control for shifting the basic target value to a higher or lower value and a second for directly setting the target value in the range of 16 to 26 °C. If instead of shifting the target value with the adjustable shifting range, direct target value setting in degrees Cel­sius is desired, then the inserted rotary knob should be exchanged with the delivered rotary knob and the pa­rameter "target value setting" should be switched t o "di­rectly in °C" in the "Functions / objects" parameter win­dow.
Note: Via a parameter setting the setting of setpoint value re­spectively setpoint value shifting can be locked by the rotary control.
Siemens AG UP 237K, UP 254K, 5 pages Technical-Manual Infrastructure & Cities Sector, Building Technologies Control Products and Systems ã Siemens AG 2014 Update: http://www.siemens.com/gamm a P. O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice.
2.8.2.8/1
GAMMA instabus
Technical Product-Information
February 2014
Temperature Controller UP 237K 5WG1 237-2KB_1
UP 254K 5WG1 254-2KB_3
Commissioning
For commissioning a control with the help of ETS (Engi­neering Tool Software), the control together with the suitable DELTA frame must first be inserted into a Bus Transceiver Module (BTM) UP 117 which serves to sup­ply power to the control and to transmit data via the KNX Bus. After removing the rotary knob for target value shifting, the recess for the commissioning button and the com­missioning LED of the control are visible.
Note:
The bus transceiver module UP 117 and the asso­ciated DELTA frame are not supplied and must be or­dered separately.
With the help of ETS, the application program can be se­lected, the specific parameter and addresses assigned and transferred into the room temperature controls UP 237K and UP 254K.

Application program

The "0705 CO Room Temperature Control H+K 803002" application program supports the following functions:

· Switching between automatic / manual operation and
switching the room operating mode with the button,
· Target value shifting or target value setting in °C with
the rotary knob,
· Status display with LEDs:
- Displays (green) for manual operation and the cur-
rent room operating mode (comfort, pre-comfort, energy-savings and protection mode),
- Displays (red/yellow), whether the heating or cooling
valve is open,
- Displays (red) for dew point alarm and open window.
· Room temperature control, adjustable as:
- heating only, cooling only, heating and cooling, each selectable as
- heating with two-point control,
- heating with PI control,
- heating with PI control and sequence control (e.g. with floor and radiator heating),
- cooling with two-point control,
- cooling with PI control,
- cooling with PI control and sequence control.
(e.g. with cooling ceiling and supply air cooler). The following partial functions are part of room tempera­ture control:
- Room temperature measurement using the internal
temperature sensor with Offset setting,
- Room temperature measurement using an external
temperature sensor with Offset setting,
- Computation of current room temperature actual
value (internal and external sensors weighted),
- With target value shifting: Basic target value as-
signment via parameter setting and/or via Bus,
- With target value shifting: Computation of current
room temperature target value from basic target val­ue and shifting,
- time-restricted removal of night sinking or the pro-
tection mode (comfort prolongation),
- with presence detection via the Bus, switching to the
"comfort" operating mode occurs,
- Dew point mode can be activated via the Bus,
- Evaluation of the window conditions via the Bus,
- Frost protection / heat protection are reported via
the Bus,
- PI control for heating / cooling with constant regulat-
ing variable-output (in %) or toggling regulating vari­ables-output (on / off).
- Separated or joint regulating variable output for
heating and cooling,
- Separated regulating variable output for basic level
and auxiliary level for 2-level heating or cooling,
- Switching the desired effect and scaling the regulat-
ing variable for heating/cooling is possible,
- Maximal and minimal regulating variable for heat-
ing/cooling possible,
- Operating condition (control status) can be read out
via the Bus,
Technical Data

Power supply

· via the flush-mounted bus transceiver module UP 117

Operating elements

· 1 rotary button for manual adjustment of the setpoint (control range and type of adjustment dependent on the parameter setting and type of rotary button)
· 1 button for toggling of the room operating mode and vice versa

Display elements

· 5 green LED`s for the current operating mode (com­fort , pre-comfort, energy-saving, protection mode) and for manual mode
· 2 red LED`s for dew point alarm and open window
· 2 red/yellow LED`s for Heating / cooling mode

Temperature measurement

· Measuring range: 0 ... + 40 °C
· Resolution: 0.08 K
· Accuracy of the sensor temperature: ± 1.0 K under reference conditions, ± 2.0 K under ambient conditions and in measuring
range

Connections

· 10-pole plug-in connector for connection with the bus transceiver module UP 117
Technical-Manual UP 237K, UP 254K, 5 pages Siemens AG
Update: http://www.siemens.com/gamm a ã Siemens AG 2014 Control Products and Systems
Subject to change without further notice. P. O. Box 10 09 53, D-93009 Regensburg
Infrastructure & Cities Sector, Building Technologies
2.8.2.8/2