Product Information November, 2001
AS 488/TM M02.02
1 Scope
The product information for the system software M02.01/M01.07 remains valid.
The following information represents a supplement.
The delivery consists of:
6DS2 410-0XX00-0XA0
6DS2 410-0XX00-0XB0
6DS2 410-0XX00-0XC2
(Upgrade / Update)
AS 488/TM Memory Card Diskette 3,5" with AS 488/TM
software
Diskette 3,5" with tools for
installation
Software contract and
Diskette 3,5" with tools for
installation
Software contract
registration card
Product Information Product Information
Note on software protection:
The memory card must be considered as part of the CPU. If the memory card is removed
during current operation, and if the AS 488/TM enters STOP as a result of the software
protection, all modifications to the configuration are lost which have been made in the
meantime and which have not been saved, as well as all modified inputs which have been
made since the last save operation; I/O modules may be reset to the basic status.
Note to the Diskette IBS-Tools + Hinweise (Commissioning Tools + Notes):
Because of space the data on the IBS tool diskette is existing now as a self-extracting exe
file. For extracting please start the file IBS_DISK.EXE! With this the following directory
structure is created on your PC / programming device:
...\IBS_DISK.M2\ASBEDIEN ASBEDIEN V1.08
...\IBS_DISK.M2\ASBEDIEN.NT ASBEDIEN V2.00 for Windows NT
...\IBS_DISK.M2\DOKU Supplementary Documentation (see chapter 1.1)
...\IBS_DISK.M2\PROGRAF AS system file for PROGRAF AS+ (see chapter 1.2)
Product Information November, 2001
AS 488/TM M02.02
1.1 Supplementary Documentation
In addition to the tools required for startup of your AS 488/TM, the commissioning diskette
contains a document file for the service terminal (within the directory ASBEDIEN or
ASBEDIEN.NT):
ASBEDI_E.doc User description for the Commissioning Terminal (IBS terminal)
For further information by seperate ordering to C79000-G8076-C700 please ask your
Siemens sales partner for a document diskette. This information which may be useful
when starting up is found in this file and the following files:
DIODEF_E.doc Description of the pin allocations for the DIO interface module
(for cabinet status signals, such as door contact, fan, etc.)
BUSINI_E.doc Configuration for operating your AS 488/TM on the CS 275
or PROFIBUS-TM system bus
PERPRO_E.doc Configuring the Teleperm M I/O peripherals
DP_PRO_E.doc Configuring the PROFIBUS-DP peripheral
The INI files that need modifying for the parameter settings can be found on the
AS 488/TM memory card or the upgrade/update diskette.
DP_BST_E.doc Description of the standard DP driver blocks
IP262_E.doc Description of the standard driver blocks for IP262
Please print out these document files and add them to your AS 488/TM documents.
Failure to observe the information provided can result in a serious malfunction of the
installation.
If you do not have the corresponding Windows installation on your PC, your local Siemens
representative will be pleased to help you.
Product Information November, 2001
AS 488/TM M02.02
1.2 AS System File for PROGRAF AS+
Your commisioning diskette contains a directory PROGRAF after extracting. This contains
the system file AS.SYS required for PROGRAF AS+.
Copy the file AS.SYS into your PROGRAF PC into the directory
drv:\PROGRAF\USER\
The system file of the AS 488/TM automation system is then known to PROGRAF AS+.
Carry out your PROGRAF AS configuring in the usual manner.
Note:
From PROGRAF AS+ V3.00 onwards, the AS commands FORM, LA, AR, DI and DEL are
also allowed for online structuring.
After "LA,name;" PROGRAF AS+ terminates the coupling to AS 488/TM (message "BUS
STRUCTURING ABORTED"). The coupling must be re-established after the loading and
reset procedure is complete (new ANMS).
Caution:
Under no circumstances should PROGRAF AS+ be stopped while the AS is
being reset, as this causes the bus structuring in the AS to remain active.
If it should happen nonetheless, the user of PROGRAF AS+ should logon on
the same AS.
1.3 Master Type File for COM ET200 / COM PROFIBUS
In the DOKU folder on the IBS tool diskette, there are two files for the ET200 configuration
tool COM ET200 or COM PROFIBUS.
The master type-file ‘SI8050AX.2MH’ must be copied to the MASTERS directory of the
installed COM PROFIBUS. Its contents specify the AS 488/TM as the host system and the
module card IF964 as the DP master. The bitmap file ‘AS488TM.BMP’ must be copied into
the BITMAPS directory. Once COM PROFIBUS is started, the ‘Read in type files’ menu
item or the ‘Read in GSD files’ menu item from within the ‘file’ menu need be activated
only once (see also DP_PRO_D.doc).
Note: In the case of COM PROFIBUS, these files are already supplied from V3.1
onwards.
Product Information November, 2001
AS 488/TM M02.02
2 Commissioning
The Memory Card contains the entire system software for AS 488/TM. It responds with the
version ID M02.02 .
To perform an upgrade or update from diskette, an AS 488/TM memory card must be
available.
The upgrade procedure is performed offline with a PC or a programming device having a
compatible MC interface (e.g. PG740).
The update procedure is performed either from the IBS terminal (online) or from a
programming device having a compatible MC interface (e.g. PG740).
A description of the upgrade procedure is provided under heading 2.2 in this document, of
the update procedure under heading 2.3 .
Caution:
The file RM3_PC1.SYS on the memory card must
never
be deleted or
overwritten, as this would mean that the memory card would no longer be
bootable!
If this happens nevertheless, the memory card can be restored on a
programming device with the help of the upgrade diskette (see chapter 2.2.1).
Notes:
The V.24 serial interfaces of the AS 488/TM and the PCs are non-isolated. With a distance
of more than 10m between the earthable point of the AS and the earthable point of the
PC's protective conductor an electrical isolation of the interface has to be planned.
Further electronic switches for multiplication of the PC's serial interfaces are not suitable
for the commissioning terminal because of the interruption of telegrams at any point. We
recommend the use of the integrated software switch for up to four AS interfaces.
Product Information November, 2001
AS 488/TM M02.02
2.1 Startup by Commissioning Terminal
The extracted IBS tool diskette contains your local tool in the directory ASBEDIEN. Install
this on your PC to be used for commissioning of the AS 488/TM according to the
installation instructions in the document file ASBEDI_E.DOC in the directory ASBEDIEN,
and connect your PC to the serial commissioning interface of your AS 488/TM via a serial
interface.
For operation under Windows 3.1, a PIF file is delivered with the software. This contains
the following settings: run in full screen mode, exclusive foreground execution, foreground
priority very high.
For operation under Windows 95, the following setting should be specified: idle time
activity very low; no screen saver.
Alternatively the new NT version can be used (see chapter 4.2).
Using your "Commissioning terminal" installed in this manner and the commands of the
ASBEDIEN input program you can operate and monitor your AS 488/TM for install and
diagnostic like an AS 235 and also access all data on the memory card inserted in the
AS 488/TM.
Read the parameter files which have to be processed to enable parameterization from the
memory card into a file on your PC using the command "COPY_PC ...". You can modify
this file on your PC according to your system configuration using the ASCII editors which
can be executed under DOS, and then write them back onto your memory card using the
ASBEDIEN command "COPY_TM ...".
Note:
Before starting the UPGRADE/UPDATE activities, please ensure that a current backup of
the customer's system and any files that are to be modified exists. This will allow the
previous software version to be restored in the even of unforeseen circumstances. The
files on the memory card are not write protected, so care should be taken when accessing
the memory card.
To back up the files from the memory card to your archive, use the ASBEDIEN command
"COPY_PC ...".
2.1.1 Upgrade / Update Data
The data for the upgrade/update procedure is existing on the upgrade diskette as selfextracting exe file. For extracting please start the file UPGRADE.EXE! If the pre-adjusted
path is kept, the following directory structure is created on your PC / programming device:
C:\UPGRADE Upgrade batch
C:\UPGRADE\AS_SW.202 AS system software M02.02
C:\UPGRADE\CP5412 Files for operating the system bus with CP5412
C:\UPGRADE\INI Initialization files for restoring
C:\UPGRADE\RMOS32 Programs for formatting procedure
C:\UPGRADE\Update_M.108 Data for update to M01.08
If a different path as C:\ has been selected while extracting, the environment variable
UP_DRIVE has to be changed in UPGRADE.BAT.