Siemens TCF2, TCF3 Installation Instructions Manual

Page 1
Item: Instructions for Installation of Circuit Breaker
Plug-In Adapters. Cat. No.’ s TCF2 (2-Pole) and TCF3 (3-Pole). For use with: SIEMENS
®
FD Frame Circuit Break­ers and Molded Case Switches in conjunction with plug-in-tulip connector assemblies. Cat. No.’s PC4753, PC4754 and PM4754
Siemens Energy & Automation, Inc. Bellefontaine, Ohio 43311 U.S.A.
Installation Instructions
Hazardous voltage. Will cause death or serious injury.
Turn OFF and lock out all power supplying this device before installing or servicing accessory.
SAFETY INSTRUCTIONS
BREAKERS TYPES
FJ6(ETI), F6, HF6, FM6, FMK, CLF(ETI), HFJ6, (H)(H)FXD6(ETI), FD6, (H)(H)FD6, CFD6(ETI), FFC, FFF
NOTE: This instruction outlines the recommended installation procedure.
Page 1 of 3 Pc. No. 410902A01
Remove Pressure Wire Connectors From Breaker If Present
2. Place tulip clip assembly (6) on back of breaker
in recess provided in base molding. Secure in place with 5/16 flatwashers (7), lockwashers (8) and 5/16 - 18 X 1 1/2 round head screws (9) furnished. (Exception - on CLF and CFD break­ers use 2” long screws on load side.) Torque screws to 5-6 lb-Ft. [6.78-8.13 N/m] to assure a good electrical connection. Repeat this proce­dure for the remaining tulip clip assemblies.
3. Slide upper end shields (10) and insert lower
end shields (1 1) with beveled end facing breaker and press into slots provided at line and load end of breaker.
4. Add accessory label (12) to top of breaker as
indicated in Fig. 4.
1. Circuit Breaker Preparation
The circuit breaker should be in the OFF/”O” position before installing the plug-in-tulip adapter kit. Turn off and lock out all power supplying this device before installing. Verify that
NO
age is present before proceeding with task.
volt-
Install As Shown
Fig. 4
Page 2
Siemens Energy & Automation, Inc. Bellefontaine, OH 43311 U.S.A.
Page 2 of 3
Pc. No. 410902A01
Installation Instructions
TCF2
4 x 10
4 x 7 4 x 8
4 x 9a
4 x 11
1 x 12
4 x 6
Hazardous voltage. Will cause death or severe injury .
Turn OFF and lock out all power supplying this device before installing or servicing accessory.
1.50”
5.00-6.00 Ft.-lbs.
6.78-8.13 N/m
FJ6(ETI), F6, FM6, FMK, HF6,HFJ6(H)(H)FXD(ETI), FD6, (H)(H)FD6, FFC, FFF
6 x 7
6 x 8
6 x 9a
TCF3
6 x 11
6 x 6
6 x 10
1 x 12
1.50”
Page 3
Siemens Energy & Automation, Inc. Bellefontaine, OH 43311 U.S.A.
Page 3 of 3
Pc. No. 410902A01
© Siemens Energy & Automation, Inc.
Installation Instructions
Hazardous voltage. Will cause death or severe injury .
Turn OFF and lock out all power supplying this device before installing or servicing accessory.
4 x 10
2 x 9a
4 x 8
2 x 9b
5.00-6.00 Ft.-lbs.
6.78-8.13 N/m
1.50”
4 x 7
4 x 1 1
TCF2
4 x 6
1 x 12
TCF3
6 x 11
6 x 6
6 x 10
1 x 12
3 x 9a
1.50”
6 x 7
6 x 8
3 x 9b
2.00”
2.00”
CLF(ETI) CFD6(ETI)