Siemens Switch 480V User Manual

480V Metal-Enclosed Switchgear
Siemens low-voltage metal-enclosed switchgear is used in electric power dis­tribution systems for the control and pro­tection of circuits and equipment. The switchgear employs drawout type low voltage power circuit breakers described in Section 4.
LV switchgear is typically installed in:
lighting networks and feeders, power generation and other auxiliaries, and to provide power for machine tools and material handling equipment drivers.
Utility and Co-generation Facilities
— for motor control centers to protect and distribute power to electrical devices such as blowers, compres­sors, fans, pumps, and motors.
Commercial and Residential
Buildings — for protection and distri-
bution of power for lighting, elevators, air conditioning, blowers, fans, motors, and pumps.
General
Available Types:
Type R — indoor (NEMA 1)Type SR — outdoor walk-in (NEMA
3R)
Low-voltage switchgear can be applied on distribution systems with:
3-phase, 3- or 4-wire feeders50 or 60HzVoltages of 208, 240,480, or 600 voltsCurrents up to 5000 amperes
Circuit breakers may be either manually or electrically operated, fused or unfused. The following designations are used:
RL — Standard Interrupting
4
RLE — Extended InterruptingRLI — High InterruptingRLF — Fused Type
Siemens Static Trip III trip units are pro­vided on all low voltage power circuit breakers, except non-automatic circuit breakers. All circuit breakers are UL
480V Metal-Enclosed
Switchgear
Listed. See Tables 4.10 and 4.11 for cir­cuit breaker ratings.
480 Volt Metal-Enclosed Switchgear
Industry Standards
Types R and SR switchgear with power circuit breakers are designed, tested and constructed in accordance with:
ANSI C37.20.1 — Metal-Enclosed
Low Voltage Power Circuit Breaker Switchgear
ANSI C37.50 — Test Procedure for
Low Voltage AC Power Circuit Breakers Used in Enclosures
ANSI C37.51 — Conformance Testing
of Metal-Enclosed Low Voltage AC Power Circuit Breaker Switchgear Assemblies
Applicable standards of IEEE and
NEMA
Applicable requirements of the
National Electric Code (NEC)
UL 1558 — Metal-Enclosed Low
Voltage Power Circuit Breaker Switchgear
Type RL drawout circuit breakers are in accordance with:
ANSI C37.13 — Low Voltage AC
Power Circuit Breakers Used in Enclosures
ANSI C37.16 — Preferred Ratings,
Related Requirements, and Application for Low Voltage Power Circuit Breakers and ACPower Circuit Protectors.
ANSI C37.17 — Trip Devices for AC
and General Purpose DC Low- Voltage Power Circuit Breakers.
UL 1066 — Low Voltage AC and DC
Power Circuit Breakers Used in Enclosures.
Features and modifications required by NEC are incorporated when the assembly is designated as “Service (Entrance) Equipment.”
UL Listing (Optional)
An Underwriters’ Laboratories listing mark (UL label) can be optionally supplied for each vertical section. The specific section must contain only devices which are UL Listed or are UL recognized com­ponents found suitable for the intended use. All circuit breaker drawout elements are UL Listed.
50 CSI Section 16470
Siemens Electrical Products and Systems
Specification Guide
480V Metal-Enclosed Switchgear
Siemens low-voltage metal-enclosed switchgear is used in electric power dis­tribution systems for the control and pro­tection of circuits and equipment. The switchgear employs drawout type low voltage power circuit breakers described in Section 4.
LV switchgear is typically installed in:
lighting networks and feeders, power generation and other auxiliaries, and to provide power for machine tools and material handling equipment drivers.
Utility and Co-generation Facilities
— for motor control centers to protect and distribute power to electrical devices such as blowers, compres­sors, fans, pumps, and motors.
Commercial and Residential
Buildings — for protection and distri-
bution of power for lighting, elevators, air conditioning, blowers, fans, motors, and pumps.

General

Available Types:
Type R — indoor (NEMA 1)Type SR — outdoor walk-in (NEMA
3R)
Low-voltage switchgear can be applied on distribution systems with:
3-phase, 3- or 4-wire feeders50 or 60HzVoltages of 208, 240,480, or 600 voltsCurrents up to 5000 amperes
Circuit breakers may be either manually or electrically operated, fused or unfused. The following designations are used:
RL — Standard Interrupting
4
RLE — Extended InterruptingRLI — High InterruptingRLF — Fused Type
Siemens Static Trip III trip units are pro­vided on all low voltage power circuit breakers, except non-automatic circuit breakers. All circuit breakers are UL
480V Metal-Enclosed
Switchgear
Listed. See Tables 4.10 and 4.11 for cir­cuit breaker ratings.
480 Volt Metal-Enclosed Switchgear
Industry Standards
Types R and SR switchgear with power circuit breakers are designed, tested and constructed in accordance with:
ANSI C37.20.1 — Metal-Enclosed
Low Voltage Power Circuit Breaker Switchgear
ANSI C37.50 — Test Procedure for
Low Voltage AC Power Circuit Breakers Used in Enclosures
ANSI C37.51 — Conformance Testing
of Metal-Enclosed Low Voltage AC Power Circuit Breaker Switchgear Assemblies
Applicable standards of IEEE and
NEMA
Applicable requirements of the
National Electric Code (NEC)
UL 1558 — Metal-Enclosed Low
Voltage Power Circuit Breaker Switchgear
Type RL drawout circuit breakers are in accordance with:
ANSI C37.13 — Low Voltage AC
Power Circuit Breakers Used in Enclosures
ANSI C37.16 — Preferred Ratings,
Related Requirements, and Application for Low Voltage Power Circuit Breakers and ACPower Circuit Protectors.
ANSI C37.17 — Trip Devices for AC
and General Purpose DC Low- Voltage Power Circuit Breakers.
UL 1066 — Low Voltage AC and DC
Power Circuit Breakers Used in Enclosures.
Features and modifications required by NEC are incorporated when the assembly is designated as “Service (Entrance) Equipment.”
UL Listing (Optional)
An Underwriters’ Laboratories listing mark (UL label) can be optionally supplied for each vertical section. The specific section must contain only devices which are UL Listed or are UL recognized com­ponents found suitable for the intended use. All circuit breaker drawout elements are UL Listed.
50 CSI Section 16470
Siemens Electrical Products and Systems
Specification Guide
480V Metal-Enclosed Switchgear

Construction Details

General
General
The Siemens 480 volt switchgear assem­bly consists of one or more metal­enclosed, vertical sections. Normally the end sections are designed to allow for installation of future sections.
Each vertical section consists of up to four individually enclosed breaker or auxil­iary compartments which are sized to provide uniform height.
Included in each assembly are various components such as circuit breakers, instrumentation and control equipment, transformers, relays, three-phase bus work, and all internal wiring, connectors, and other supporting equipment.
In accordance with ANSI C37.20.1, the maximum temperature for parts that are handled is 50°C. The main bus maximum temperature rise is 65°C above 40°C ambient. The temperature rise of the air surrounding the cable connection points is limited to 45°C above 40°C ambient.
Finish
During construction, the structural steel parts, panels, and compartments are all prepared for painting by a five-stage wash system. Standard finish color is light gray ANSI 61. If a different finish color is required, it is applied over the standard finish with conventional spray equipment and is allowed to air cure. The completed finish has a nominal 2 mils dry film thickness.
Assembly Construction
Siemens metal-enclosed power switchgear is constructed of preformed, full-depth, 14-gauge steel sheets bolted together and reinforced with cross-mem­ber braces to form a rigid, self-supporting compact assembly. The top and rear plates, and side sheets are all 14-gauge steel. When two vertical sections are mounted together, two sheets of 14­gauge steel separate adjacent circuit breaker compartments.
Bolted steel / glass polyester compart­ments housing each power circuit break­er are mounted in the vertical section to form the switchgear assembly. This iso­lates the circuit breakers from the bus / cable section and from adjacent circuit breaker compartments.
The bus / cable section includes main horizontal bus, riser bus, connections from the main bus to each set of primary disconnects, and load side copper run­back bus.
Grounded metal barriers can be provided to isolate the main bus from cable con­nections. Barriers are also available to isolate the incoming line to the main cir­cuit breakers from the main load bus of the switchgear.
Inter-Unit Wiring TroughMeter and Auxiliary CompartmentVentilation and Lifting StructureTelescoping Breaker Drawout RailsVentilation Openings (RL-2000, RL-3200, RL-4000
and RL-5000)
4
480V Metal-Enclosed
Switchgear
Siemens Electrical Products and Systems
Specification Guide
51CSI Section 16470
480V Metal-Enclosed Switchgear
Construction Details
General
Main and Ground Bus
The standard main bus is silver-plated copper. Welded aluminum is also avail­able. Provisions for future extension of aluminum main bus conductors include tin plated joints with high tensile strength steel hardware. Tin-plated copper bus is optionally available.
The main three-phase horizontal bus is arranged vertically one phase above the other with edge-to-edge alignment to provide high, short circuit strength. Insulated main and vertical bus are optional.
Main bus ratings available are 1600, 2000, 3200, 4000, or 5000 amperes con­tinuous current. A neutral bus is fur­nished when specified, and can be rated 1600, 2000, 3200, 4000 or 5000 amperes continuous current.
A standard copper ground bus extends through all sections. A cable lug can be mounted to the ground bus in each section.
Minimum bus bracing is 65,000 amperes RMS symmetrical. Higher symmetrical bracings are available based on the low­est breaker short circuit rating in the group.
Load side runbacks for feeder circuits are one-piece copper construction, are insu­lated with sleeve tubing in the main bus area, and are supported by high-strength, glass polyester moldings.
Control Wiring
Standard secondary and control wiring is #14 AWG extra-flexible, stranded copper type SIS. Terminations are made with compression-type, insulated terminals.
For devices not having screw-type termi­nals, tab-type disconnects are used.
Insulation
The insulation used is Pyro-Shield, a fiber­glass-reinforced polyester material that has high impact strength and low mois­ture absorption. Other features include high flame retardance, high resistance to chemical fumes, and long life at high temperatures.
Circuit Breaker Compartments
Typical circuit breaker compartments include primary disconnects, ground dis­connect, drawout rails, and associated interlocks, and secondary disconnects, if appropriate. Telescoping drawout rails allow the breaker to be withdrawn from the compartment without additional extensions or adapters. Compartments for electrically-operated circuit breakers include secondary disconnects and con­trol circuit fuses. Up to three current transformers for metering or relaying can be mounted in each compartment.
Circuit breaker compartment front panels can be used to hold a variety of auxiliary devices such as breaker control switch­es, ammeters, and test blocks.
4
480V Metal-Enclosed
Switchgear
52 CSI Section 16470
Control Circuit Fuses Ground Disconnect Secondary Disconnect Front Panel Devices Primary Disconnect
Circuit Breaker Cell Interior
Siemens Electrical Products and Systems
Specification Guide
TOC Switch Operator Interference Interlock MOC Switch Operator Space Heater Drawout Rails
480V Metal-Enclosed Switchgear
Guide Form Specifications
Options
Switchgear Mounted Hoist
The hoist, optional on type R indoor switchgear, and standard on type SR outdoor switchgear, travels along rails on top of the switchgear to ease breaker handling.
TOC and MOC Switches
The Truck Operated Cell (TOC) Switch provides interlocking control or remote indication of the breaker racking position. The cubicle mounted auxiliary switch or Mechanism Operated Cell (MOC) switch provides interlocking control or remote indication based on the main contact position (open or closed).
The switches have field adjustable con­tacts for simple conversion of contacts from normally open (“a” type) to normal­ly closed (“b” type). Each contact may be adjusted individually without disassembly or removal of wiring.
Typical Outdoor Installation with Liquid Filled Transformer
General
MOC and TOC Switches. TOC Shown with Cover Removed.
Shutters
These provide protection against acciden­tal contact with primary disconnects in a compartment when the breaker is removed.
Wire Trough Covers
Secondary wiring is enclosed within each vertical section in the primary bus and outgoing cable areas.
Key Interlock
This provides a mechanical means for operating circuit breakers and other devices only when predescribed condi­tions are met.
PTS4 Test Set
Set allows testing of the full range of pro­tective settings of Static Trip III trip units.
Metering and Auxiliary Compartments
Compartments are available to house devices such as voltage transformers, metering, control power transformers, and supervisory devices.
Instrument and Control Transformers
Voltage transformers and control power transformers are mounted in auxiliary compartments. These transformers are protected by primary pull-out type cur­rent-limiting fuses and secondary fuses. Current transformers are normally mount­ed on the compartment primary discon­nect studs where they are readily acces­sible. See Tables 4.10, 4.11, 4.12, and
4.13 for available ratings.
Outdoor Switchgear
Type SR outdoor switchgear, available up to 4000 amp, is enclosed in a weather resistant (NEMA 3R) steel housing. All exterior doors extend below the floor line and are gasket sealed.
For protection from snow, rain, and dust, the switchgear rests on a six-inch, formed steel base which provides rigid support and a tight bottom seal. A heavy duty, coal tar emulsion protective under­coating is applied to the underside for protection against moisture and corro­sion. Shielded ventilation housings permit proper air circulation while excluding dust, dirt, and foreign matter.
A lighted, unobstructed service aisle is provided at the front of the switchgear allowing inspection and maintenance without exposure to the elements, An access door equipped with an emer­gency bar release is located at each end of the aisle. A GFI convenience outlet is included.
Accessories
Each switchgear assembly includes the following standard accessories:
Crank for circuit breaker rackingLifting bar assembly for all circuit
breaker types
Spring charging handle for electrically
operated circuit breakers
As an optional accessory, a test cabinet is available for indoor use that is wall mounted with necessary equipment for testing electrically-operated breakers that have been removed from the breaker compartments.
Portable PTS4 Test Set
4
480V Metal-Enclosed
Switchgear
Siemens Electrical Products and Systems
Specification Guide
53CSI Section 16470
480V Metal-Enclosed Switchgear

LV Power Circuit Breakers

The Siemens RL series circuit breakers are designed for up to 600 volt service with current carrying capacities of up to 5000 amperes and interrupting capacities of up to 130,000 amperes unfused or 200,000 amperes fused.
These compact, fast operating circuit breakers incorporate a stored energy closing mechanism, either manually or electrically charged, for fast, positive closing.
A quick-make closing mechanism releas­es the stored energy for high speed clos­ing of the primary contacts. This positive, controlled closing prevents unnecessary arcing between the movable and station­ary breaker contacts and thus lengthens contact and breaker life.
Manual tripping is performed with the push lever on the front of the breaker. Up to three padlocks can be used to lock the breaker contacts in the open position.
Typical Breaker Features
Arc QuenchersMain and Arcing Contact StructuresInductive Tripping SensorsControl WiringInterlocksPosition IndicatorsInterpole BarriersMechanical Trip BarAuxiliary Switches (option)
Each circuit breaker is a complete 3-pole, single-throw element that is mechanically and electrically trip-free, with a Static Trip III overcurrent trip unit.
Tables 4.16 and 4.17 show circuit breaker
4
operating and control data.
Circuit Breaker Racking
Racking is accomplished by turning a racking screw on the front of the breaker and may be done with the compartment door open or closed. The racking screw turns U-shaped brackets on each side of
480V Metal-Enclosed
Switchgear
the breaker which rack the breaker frame in or out of the compartment.
As the racking screw is turned counter­clockwise, the breaker frame moves out of the compartment and disconnects the primary contacts, followed by the sec­ondary contacts. With only the secondary contacts connected (test position), the breaker may be closed and opened for testing without energizing the load. An indicator located on the front of the breaker identifies the position of the breaker in the compartment.
Type RL Circuit Breaker With Static Trip III Trip Unit And Optional Breaker Display Unit (BDU)
Primary Disconnects
Primary current is applied to the circuit breaker through silver plated disconnects. The stationary contacts are mounted through solid Pyro-Shield insulation sheets in the back of the compartments. The movable contacts are mounted on the back of the breaker. Stainless steel springs provide pressure to the finger contacts in the connected position. Low contact resistance is maintained by these self-aligning contacts. The primary con­tacts are positioned so that current can flow only in the connected position. In the test position the contacts are separat­ed a safe distance.
Secondary Disconnects
Secondary circuits are connected to the circuit breaker through silver-plated, slide­type contacts which are located below the arc quenching area to avoid contami­nation from arc product gases. The posi­tion of these contacts is visible with the panel door open. The stationary contacts are silver-plated copper strips mounted on a Pyro-Shield molded base. The con­tacts are recessed to guide the movable, self-aligning contacts and to prevent acci­dental short circuiting. Secondary connec­tions are made automatically in both the connected and test positions.
General
Secondary Disconnects in Cell Left = Communications Right = Breaker Control
Main and Arcing Contacts — Similar Design for all Ratings
54 CSI Section 16470
Siemens Electrical Products and Systems
Specification Guide
480V Metal-Enclosed Switchgear
Sensor Ratings
Frame Size and Max Amp Rating
800
150, 200, 300, 400, 600, 800
1600
2000
150, 200, 300, 400, 600, 800, 1200, 1600
150, 200, 300, 400, 600, 800, 1200, 1600, 2000
4000
3200 1200, 1600, 2000, 3200
1600, 2000, 3200 햲, 4000
5000
5000
Table 4.1 Available Sensor Ratings
Optionally available with integral 200A ground sensor winding to meet NEC 239-95 requirements.
LV Power Circuit Breakers
Ground Connection
A ground contact is located on the circuit breaker to connect with the ground cir­cuit. The breaker is grounded in both the connected and test positions.
Drawout Interlocks
All circuit breakers have drawout inter­locks to:
prevent racking a closed breakerprevent closing breaker until racked to
connected or test position
prevent inserting or withdrawing
breaker from compartment while clos­ing springs are charged
Arc Interruption
When a fault occurs, the main contacts open first, transferring the fault current to the arcing contacts. As the arcing con­tacts open, the thermal and electromag­netic characteristics force the arc into the arc chute, where the metal plates length­en, constrict, and cool the arc.
Current Limiting Fuses
The 800,1600 and 2000 ampere circuit breakers are available with integrally mounted current limiting fuses to increase interrupting rating and / or to limit short circuit (let-through) current. The fuses are bolted in series with the upper set of primary disconnects. The breakers meet all required standards and are UL Listed based on current limiting fuses.
An open fuse tripping device is wired in parallel with the main fuses to insure that the circuit breaker opens if a main fuse interrupts, thus preventing single phasing. This device holds the circuit breaker trip­free until it is reset and also indicates which main fuse has interrupted.
Ground shoe contact Mounting rails Racking position detent Stored energy mechanism position
indicator
Contact position indicator Arc chutes Handle for manually charging stored
energy closing springs (optional on electrically operated breakers)
Inter-phase barriers Racking mechanism shutter (with
packlocking provisions)
Racking position indicator Contact closing release lever
(behind charging handle)
RL Circuit Breaker Features (Electrically Operated Breaker Shown)
General
Clevis attached to racking drive
screw.
Circuit breaker rating nameplate Racking interlock bar Static Trip III trip unit test points Static Trip III overcurrent device Tripping lever (with padlocking
provisions) with guard.
Breaker Display Unit (optional) Power switch for spring charging
motor (electrically operating break­er only)
Spring charging motor (electrically
operated breaker only) Auxiliary switch (optional on man­ually operated breakers)
4
480V Metal-Enclosed
Switchgear
Integrally Fused RLF-800 Circuit Breaker
The higher raed circuit breakers, 3200, 4000 and 5000 ampere, are available with current limiting fuses mounted on a separate drawout carriage, which is key interlocked with the circuit breaker. This allows racking of the fuse carriage with only the associated circuit breaker in the
open position. The carriage mounts in the same vertical section as the circuit break­er element.
Current Sensors
The tripping system of the RL breaker is self-powered from the current sensors mounted on the primary contacts of the breaker element (four-wire ground applica­tions include a fourth sensor mounted in the cable compartment). A signal from the current sensors, proportional to primary current, is applied to the trip device which then operates the actuator to trip the breaker based on a pre-set time delay versus current magnitude relationship.
Siemens Electrical Products and Systems
Specification Guide
55CSI Section 16470
480V Metal-Enclosed Switchgear
T: Long Time
S: Short Time
I: Instantaneous
G: Ground Fault
20, 30, 40, 50, 60 .10, .25, .40
Delay (Seconds @ 6X Setting)
Setting
DelayPickup
(X Sensor Rating)
3.5, 6, 10 17, 30
.5, .55, .6, .65, .7, .75, .8, .85, .9, .95, 1.0
(Seconds)
(Seconds)
(X LT Setting)
0.8, .15, .22 .30, .40
2, 3, 4, 5, 6, 7, 8, 12
DelayPickup
(X Sensor Rating)
(Seconds)
DelayPickup
(% Ground Sensor)
No Intentional Delay
2, 4, 6, 8, 12, 15
Table 4.2 Static Trip III Settings
Pickup is fixed at 1.1 times long time setting.

LV Power Circuit Breaker Trip Unit

Static Trip®III Trip Unit
Static overcurrent tripping devices have been standard on Siemens circuit break­ers for over thirty years. The Static Trip Ill trip unit features microprocessor-con­trolled tripping, while providing RMS sensing for standard overcurrent protec­tion, and optional metering and communi­cations functions. Located in the lower right side of the breaker, the trip unit is readily accessible for simple reading and adjustment of all settings and indicators. Static Trip III trip units are interchange­able on all ratings of low voltage circuit breakers.
The time / current characteristics of the Static Trip III trip unit are shown on page
62. All communicating Static
Trip III trip units include a local communication port that supports the breaker-mounted display unit or BDU. The BDU features a high-visibility
alpha-numeric display. Real-time metered values, min/max values, event log data and setpoint data can be read on the BDU in straightforward engineering units. Alarm and relay setpoint can be config­ured using the BDU keypad.
This data can also be communicated to other devices or computers for control monitoring via Siemens’ ACCESS sys­tem. See Section 1 of this guide for a thorough description of ACCESS.
4
Static Trip®Ill Trip Unit (right) and Breaker Display Unit (left)
Siemens RMS sensing samples the entire current wave shape and calculates the effective heating value of the current. Static Trip Ill trip units provide accurate protection and avoid unnecessary trips.
General
480V Metal-Enclosed
Switchgear
Harmonics distort the current wave shape and can increase its peak value. Normal peak-sensing units may trip, causing nui­sance shutdowns.
56 CSI Section 16470
Siemens Electrical Products and Systems
Specification Guide
480V Metal-Enclosed Switchgear
Function
Model
III
Table 4.3 Static Trip III Trip Unit Functions
Self-Powered Overcurrent Protection
IIIC IIICP IIICPX
Requires additional compartment mounted devices and wiring to meet specific application.
Supports optional Breaker Display Unit accessory.
Open command uses alarm relay output and restricts use for other alarm functions. Close command requires electrically operated breaker.
Included when ground fault protection specified.
Requires “N” option and neutral current sensor.
Only displayed for four wire systems.
✓✓✓✓
RMS Sensing
✓✓✓✓
Switchable Thermal Memory
✓✓✓✓
Ground Fault Protection
opt opt opt opt
opt opt opt opt
LCD Target
✓✓✓✓
Protective Microprocessor Watchdog
✓✓✓✓
Pickup LEDs Zone Interlocking
(For Short Time and Ground Fault)
opt opt opt opt
Retrofit Universal Mounting Package
opt opt opt
Alarm Relay Output
RS-485 Communications Port
✓✓✓✓
✓✓✓
Breaker Display Unit Port
✓✓✓
Communications Microprocessor Watchdog
✓✓✓
Comm Watch LED
✓✓✓
Backup Shadow Protection
✓✓✓
— —
opt opt opt
opt opt opt
Communication Open/Close/Trip
햲햴
Trip Log
✓✓✓
Trip Unit Status Indication
✓✓✓
Breaker Position Indication
✓✓✓
Breaker Operation Counter
✓✓✓
Event Log
✓✓✓
Phase Current Metering
✓✓✓
Ground Current Metering
✓✓✓
Neutral Current Metering
Min/Max Current Log
✓✓✓
——
Power Metering Functions
✓ ✓
——
Min/Max Power Log
———
Extended Protective Relaying
———
Extended Trip Log
Function
Model
Table 4.5 Functions
Static Trip III Metering
Phase Currents
IIIC IIICP
✓✓
Avg Phase Currents
✓✓ ✓✓
Neutral Current
opt opt
Phase Voltage
Avg Phase Voltage
Line Voltages Avg Line Voltages
Ground Current
kW
Power Factor
kW Demand
kW Hours
kW Hours Reverse
kVA
kVAR
— —
kVAR Hours
✓ ✓
Frequency
Protective Function
Setting Range
Typical Applications
Motors
Table 4.4 Static Trip IIICPX Protective Relay Functions
Current Unbalance 5–50%
5–50% 60–660V 60–660V 10–2000kW
50.0–70.0 Hz
45.0–60.0 Hz
Generators Mains
— —
— —
— — —
✓✓
✓✓
Voltage Unbalance
✓✓
Overvoltage
Undervoltage Reverse Power
Overfrequency
Underfrequency
Shunt Trip (Amperes) Seal-In/Inrush
Operating Voltage Range
Nominal Control Voltage
60 Hz AC
104–127120 1.65/7.7 208–254240 0.71/3.4
DC
28–56 5.45
70–140
48
125 2.76
140–280250 1.85
Table 4.6 Shunt Trip Coil Ratings
LV Power Circuit Breaker Trip Unit
General
RL Breaker Accessories/Modifications
Type RL circuit breakers feature several options, including:
Shunt Trip, (for MO breakers)Operation CounterUndervoltage Trip DeviceElectrically Operated InterlockAutomatic Trip Alarm Contact (with or
without Lockout Bell Alarm)
Tripping Actuator
The tripping actuator is a low energy, flux-shifting device that allows fast action tripping of the breaker.
Shunt Trip
The shunt trip is used to electrically trip the circuit breaker from a remote device, such as pushbutton, switch, or relay. The shunt trip is standard on all electrically operated breakers, optional on manually operated breakers. The shunt trip coil is designed for a momentary duty cycle. Thus, an “a” type auxiliary contact switch is used to interrupt the shunt trip circuit immediately after the breaker is tripped.
Siemens Electrical Products and Systems
Specification Guide
When the coil is energized, the armature picks up and rotates the trip latch, there­by tripping the breaker. A compression spring returns the armature to the normal position.
57CSI Section 16470
4
480V Metal-Enclosed
Switchgear
480V Metal-Enclosed Switchgear
Dropout Voltage
Pickup Voltage
Nominal Control Voltage
60 Hz AC
100120
240 or 480
60
DC
40 24
105
48
125 62
Table 4.7 Undervoltage Trip Ratings
Not available. Use 120 VAC undervoltage device with appropriate 240/120V or voltage transformer in cubicle.
BreakMakeContinuous
Bell Alarm Contact Ratings (Amperes)
Nominal Control Voltage
60 Hz AC
10.0 10.0
10.0
10.0
10.0
10.0
10.0
120 240
DC
0.5
0.5
48
125
0.25
10.0
10.0
0.5
0.5
0.25250
Table 4.9 Ratings
Bell Alarm Contact
Dropout Voltage
Pickup Voltage
Voltage Range
Nominal Control Voltage
60 Hz AC
104 208
120 240
36 72
DC
38 15
100
48
125 38
200250 75
Table 4.8 Interlock Coil Ratings
480V Metal-Enclosed Switchgear
LV Power Circuit Breakers
LV Power Circuit Breakers
General
RL Breaker Accessories / Modifications (cont’d)
Operation Counter
A mechanically-operated, 5-digit non­resetable counter can be mounted beneath the breaker auxiliary switch. The counter is incremented by the action of the auxiliary switch operating mechanism.
Undervoltage Trip Device
The undervoltage trip device protects against a drop in normal bus voltage and functions to directly trip the breaker. Pickup occurs at 85 percent or less of rated value and dropout between 30 and 60 percent of rated value. Pickup and dropout are individually adjustable. Instantaneous or time-delayed operation can be provided. The static timing unit is adjustable from 0.04 to 4 seconds for time delay. This allows the system to distinguish between undervoltage conditions and momentary voltage dips.
If desired, a mechanical lockout option may be provided. This substitutes a manual reset for the automatically reset tripping actuator. In this case the breaker is held trip free until the lockout is manually reset.
Automatic Trip Alarm Contact (with or without Lockout) (Bell Alarm)
The bell alarm contact is operated when the trip actuator operates in response to the Static Trip III trip unit. It indicates when the circuit breaker has tripped as a result of the static trip unit. The contact can control a local or remote auxiliary alarm for indication of an automatic trip or, by wiring in series with a breaker clos­ing coil, for interlocking to prevent circuit breaker closure until the circuit is reset. The contact must be reset manually or electrically (optional). The manually reset switch is available with a single-pole double-throw contact, or two single-pole single-throw contacts. The electrically reset switch is available with a single­pole single-throw contact.
Electrically Operated Interlock
This can be added to interlock two break­ers, preventing both from being closed at the same time. These electromechanical devices add an additional solenoid that must be energized before the breaker
4
can be closed. When the interlock is de­energized, the breaker is held trip-free and cannot be closed electrically or manually. The interlock has a mechanical link that goes to the main shaft of the breaker. The interlock is held in the picked-up position when the breaker is closed. Once closed the interlock can be
480V Metal-Enclosed
Switchgear
de-energized without tripping the breaker. There are no adjustments for pickup or dropout voltages. The interlocks are continuously energized.
58 CSI Section 16470
Current SensorsPT Module (Optional)
RL Circuit Breaker – Rear View
Siemens Electrical Products and Systems
Specification Guide
Ground Shoe ContactPrimary Disconnects
Secondary Disconnects
480V Metal-Enclosed Switchgear
Ratio
600:120 0.6
480:120 0.6
288:120 0.6
0.6
0.6
0.6
1.2
1.2
1.2
100
100
100
WXY
Burden
Accuracy Class at 60 Hz
Volt-Amp Rating
150
150
150
Thermal Rating VA
50/60
50/60
50/60
Hertz
Table 4.10 Voltage Transformers
Ratio
100:5 1.2
150:5 1.2
200:5 1.2
2.4
2.4
1.2
——
B-0.1 B-0.2 B-0.5
Accuracy at 60 Hz Metering Burden (ohms)
B-1.0
———
———
B-2.0
C5
C5
C10
250:5 0.6 1.2
———
C10
300:5 0.6 0.6
——
C10
400:5 0.6 0.6
——
C5
500:5 0.6 0.6
——
C10
600:5 0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.6
C10
800:5
C15
1000:5 C20
1200:5 C20
1500:5 C30
1600:5 C30
2000:5 C5
2500:5 0.3
0.3
0.3
0.3
0.3
0.3
0.3
1.2
1.2
0.6
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.6
1.2
0.3
0.3
0.3
0.3
0.6
0.6
0.3
0.6
0.6
0.6
1.2
1.2
0.6
C10
Relay Class
Table 4.12 Current Transformers for RL-800, RLE-800, RLI-800, RL-1600, RLE-1600, RL-2000, or RLE-2000 Applications
kVA Phase
Single
Primary Voltage
240/480
Secondary Voltage
120/240
Table 4.11 Control Power Transformers—115°C Rise
3
5 10 15
햲 햲
Requires complete compartment.
Breaker compartment will accept 3 CT’s in-line on lower disconnects.
Ratio
1000:5
1200:5
1500:5
B-0.1 B-0.2 B-0.5
Accuracy at 60 Hz Metering Burden (ohms)
B-1.0 B-2.0
C20
C25
C35
2000:5 C25
2500:5 C30
3000:5 C15
3200:5 C20
4000:5
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
C10
5000:5 C10
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3 0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.6
0.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3 0.6
1.2
1.2
Relay Class
Table 4.13 Current Transformers for RL-3200햴, RLE-3200햴, RL-4000햵, RLE-4000햵, or RL-5000햳 Applications
Breaker compartment will accept 3 CT’s in line on lower disconnects.
Breaker compartment will accept 6 CT’s, 3 on lower and 3 on upper disconnects.
Breaker compartment will accept 3 CT’s in staggered arrangement, 2 on lower and 1 on upper disconnects.

VT, CPT, CT Data

Technical
4
480V Metal-Enclosed
Switchgear
Siemens Electrical Products and Systems
Specification Guide
59CSI Section 16470
480V Metal-Enclosed Switchgear
Frame Size Amperes
800
1600
2000
RL-800
600 635 2200
Breaker Type
Rated Volts
Rated Max. Volts
Voltage Ratings
Without Instantaneous Trip Amperes
With Instantaneous Trip Amperes
Short Circuit Rating Symmetrical Current
Short Time Rating Symmetrical Amperes
Insulation Level Dielectric Withstand Volts
30,00030,00030,000
Continuous Current Rating Amperes
75–800
RLE-800 42,00065,00042,000 75–800
RLI-800 22,00042,00022,000 75–800
RL-1600
RLE-1600
RL-2000
RLE-2000
3200
RL-3200
RLE-3200
4000
RL-4000
RLE-4000
RL-50005000
50,00065,00050,000 75–1600 65,00065,00065,000 75–1600 65,00065,00065,000 75–2000 85,00085,00085,000 75–2000 65,00085,00065,000 600–3200 85,00085,00085,000 600–3200 85,000100,00085,000 800–4000
100,000100,000100,000 800–4000
85,000100,00085,000 2500–5000
800
1600
2000
RL-800
480 508 2200
30,00030,00030,000 75–800
RLE-800 42,00065,00042,000 75–800
RLI-800 22,000100,00022,000 75–800
RL-1600
RLE-1600
RL-2000
RLE-2000
3200
RL-3200
RLE-3200
4000
RL-4000
RLE-4000
RL-50005000
50,00065,00050,000 75–1600 65,00065,00065,000 75–1600 65,00065,00065,000 75–2000 85,000100,00085,000 75–2000 65,00085,00065,000 600–3200 85,00085,00085,000 600–3200 85,000100,00085,000 800–4000
100,000100,000100,000 800–4000
85,000100,00085,000 2500–5000
800
1600
2000
RL-800
240 and 208
254 2200
30,00042,00030,000 75–800
RLE-800 42,00065,00042,000 75–800
RLI-800 22,000100,00022,000 75–800
RL-1600
RLE-1600
RL-2000
RLE-2000
3200
RL-3200
RLE-3200
4000
RL-4000
RLE-4000
RL-50005000
50,00065,00050,000 75–1600 65,00065,00065,000 75–1600 65,00065,00065,000 75–2000 85,000100,00085,000 75–2000 65,00085,00065,000 600–3200 85,00085,00085,000 600–3200 85,000130,00085,000
800–4000
100,000130,000100,000
800–4000
85,000100,00085,000 2500–5000
Table 4.14 Type RL Low-Voltage Power Circuit Breaker Ratings At 50 / 60 Hertz
480V Metal-Enclosed Switchgear
LV Power Circuit Breakers
LV Power Circuit Breakers Ratings
Technical
4
480V Metal-Enclosed
Switchgear
60 CSI Section 16470
Siemens Electrical Products and Systems
Specification Guide
Description
Time from Energizing Shunt Trip Coil Unit (Cycles):
Contacts Part Open
RL-800 RLE-800 RLI-800 RLF-800
RL-1600 & 2000 RLE-1600 & 2000 RLF-1600 & 2000
RL-4000 & 5000 RLE-4000 RLF-4000 & 5000
RL-3200 RLE-3200 RLF-3200
Type
2.0–3.01.0–3.01.25–3.01.5 –3.0
3.0–4.02.2–3.52.2 –3.52.2– 3.7Contacts Fully Open
Time from Energizing Closing Control Relay Until (Cycles):
Contacts Touch 2.5 – 5.52.2–5.02.0 –5.02.5– 5.0
Minimum Voltage 22191715
2.5 – 5.72.5–5.72.3 –5.32.8– 5.3Contacts Fully Close
Length of Break, Inches (mm)
Between Main Contacts 1.00 (25 mm)1.00 (25 mm)1.00 (25 mm)1.00 (25 mm)
1.10 (28 mm)1.10 (28 mm)1.10 (28 mm)1.10 (28 mm)Between Arcing Contacts
Average Spring Charging Time (Seconds):
Nominal Voltage 15131210
10888Maximum Voltage
Table 4.16 Type RL Circuit Breaker Operating Data (60 Hertz Basis)
480V Metal-Enclosed Switchgear
Frame Size Amperes
800 1600 2000
3200
RLF-800
208
to
600
600
Type
Rated Volts
Rated Max. Volts
Voltage Ratings
Range of Fuse Rating Amperes
Short Circuit Ratings Symmetrical Amps
Insulation Level Dielectric Withstand Volts
250–1600
Continuous Current Rating Amperes
75–800 RLF-1600 RLF-2000
800–3000
2000–5000
200,0002200
2200
75–1600
4000 75– 2000
600–3200
RLF-3200 & RFC-3200 Fuse Carriage
200,000
4000–60002200 800–4000200,000
RLF-4000 & RFC-4000 Fuse Carriage
4000
5000–60002200 2500–5000200,000
RLF-5000 & RFC-5000 Fuse Carriage
5000
Table 4.15 Type RLF Fused Circuit Breaker Ratings At 50/60 Hertz
Description Nominal Control Voltage Spring Charge Motor Voltage Range
Voltage Rating
120 VAC 240 VAC 48 VDC 125 VDC 250 VDC
Table 4.17 Type RL Circuit Breaker Control Data
104–127 100–140 200 –280208–254 38 –56
Shunt Trip and Closing Coil Voltage Range (at Coil)
104–127 70–140 140 –280208 –254 28 –56
Tripping Coil Current (Seal-in / Inrush) — Amperes
1.65/7.7 2.76 1.850.71/3.4 5.45
Closing Coil Current (Seal-in / Inrush) — Amperes Y-Relay Current (Max. Value — Amperes)
1.65/7.7 2.76 1.850.71/3.4 5.45
Current of Spring Charge Motor:
Cutoff Value — Amperes Inrush Value — Amperes
0.48 0.45 0.210.36 1.16
0.026 0.02 0.010.015 0.15
3.3 3.97 1.921.75 7.5
LV Power Circuit Breakers Ratings
Technical
Siemens Electrical Products and Systems
Specification Guide
4
480V Metal-Enclosed
Switchgear
61CSI Section 16470
480V Metal-Enclosed Switchgear
LV Power Circuit Breakers
Time/Current Characteristics of Static Trip®III Trip Unit
Technical
4
480V Metal-Enclosed
Switchgear
62 CSI Section 16470
Siemens Electrical Products and Systems
Specification Guide
480V Metal-Enclosed Switchgear
RL-800
150 (68)
45 (20)
140 (64)
RLE-800
180 (82)
45 (20)
170 (64)
RLI-800
185 (84)
45 (20)
175 (80)
RL-1600
190 (86)
45 (20)
180 (82)
RLE-1600
195 (89)
45 (20)
185 (84)
RL-2000
220 (100)
45 (20)
210 (95)
RL-3200
300 (136)
50 (23)
290 (132)
RL-4000
360 (164)
50 (23)
350 (159)
RL-5000
445 (202)
55 (25)
425 (193)
RLE-2000
225 (102)
45 (20)
215 (98)
RLE-3200
305 (139)
50 (23)
295 (134)
RLE-4000
365 (166)
50 (23)
355 (161)
Operation Manual Electrical Additional
Weight for Shipping
Element Type
Table 4.19 Breaker Element Weight in lbs. (kg)
RLF-800
205 (93)
45 (20)
195 (89)
RLF-1600
320 (145)
45 (20)
310 (141)
RLF-2000
335 (152)
45 (20)
325 (148)
RLF-3200
330
(150)
50 (23)
290
(132)
RFC-3200
50 (23)
390
(177)
450
(205)
475 (217)
55 (25)
RLF-4000
360
(100)
45 (20)
350
(95)
RLF-5000
445
(202)
55 (25)
425
(193)
RFC-4000
50 (23)
RFC-5000
Operation Manual Electrical Additional
Weight for Shipping
Element Type
Table 4.20 Fused Element Weight in lbs. (kg)
For use with RLF-3200 breaker.
For use with RLF-4000 breaker.
For use with RLF-5000 breaker.
Fuses mounted on separate drawout carriage and located in separate compartment. For total weight, add weight of breaker element and separate fuse carriage.
550 (250)
500 (227)
61 (1549)
55 (1397)Outdoor
Indoor
Dimension A in Inches (mm)
Weight in lbs. (kg)
Table 4.18

Weights and Dimensions

Dimensions
Siemens 480 volt switchgear can be configured in many ways by combining different section types. Up to five vertical sections plus a transition section can be shipped together as a unit. If all vertical sections are not to be shipped as a unit, specifications need to be provided that describe the limiting factors (e.g., low door or narrow hallway).
Normal indoor vertical sections are 101 in. (2565 mm) high and 60 in. (1524 mm) deep. A top-mounted hoist, which is shipped as an accessory in a separate container, adds 2 in. (51 mm) for a total installed height of 103 in. (2616 mm).
The outdoor switchgear assembly contains the indoor assembly in an out­door housing. The overall height is 113 in. (2870 mm) and the depth is 119.40 in. (3033 mm).
The major assembly sections include: Transition Sections — used as transi-
tion to liquid filled transformer or to outdoor dry type transformers.
Auxiliary Sections — used as incom-
ing bus duct or cable entrance when a main breaker is not used.
Main Sections — used to contain
main breaker and may house metering and feeder breakers.
Feeder Sections — used to contain
feeder breakers and other equipment such as instrumentation.
Tie Sections — used to contain tie
breaker and other equipment such as feeder breakers.
Transition Section For Liquid Filled and Outdoor Dry Type Transformers
Siemens Electrical Products and Systems
Specification Guide
4
480V Metal-Enclosed
Switchgear
63CSI Section 16470
480V Metal-Enclosed Switchgear
R30R22
Indoor Outdoor
1000 (455) 1200 (545) 2000 (909) 2400 (1091)
Table 4.21 Weight in lbs. (kg)
Auxiliary Section
R30R22
Indoor Outdoor
1400 (636) 1900 (864) 2400 (1091) 3100 (1409)
R36
2210 (1005)
Table 4.22 Connection Weights in lbs. (kg)
Breaker Section and
Weights shown do not include weight of circuit breaker removeable elements. All weights are approximate based on aluminum bus. For outdoor lineup, add 1200 lb (545 kg) to total weight of individual sections for end walls and hoist.

Auxiliary / Breaker Section Dimensions

Dimensions
Auxiliary Sections — Front Views
Dimensions in Inches (mm)
Main Breaker Sections — Front Views
Feeder Breaker Sections and Combinations — Front Views
Breaker Designations
4
A = RL- 800 / 1600 / 2000,
RLF- 800 / 1600 / 2000, RLE- 800 / 2000햳, RLI-800
B = RL- 3200 C = RLF- 3200 in one cell, with
fuse drawout (RFC-3200) in other cell
D = RLF- 4000 in one cell, with
fuse drawout (RFC-4000)
480V Metal-Enclosed
Switchgear
E = RL- 4000, RLE-4000
in other cell
F = RLF- 5000 in one cell with
fuse drawout (RFC-5000) in other cell
G = RL- 5000
22 in. (559 mm) compartment only.
64 CSI Section 16470
Tie Breaker Sections and Combinations — Front Views
Feeder breakers located above tie breaker must be electrically on opposite side of tie breaker from feeder breaker which is located below the breaker.
Siemens Electrical Products and Systems
Specification Guide
480V Metal-Enclosed Switchgear

Indoor Floor Plan, Side View

Indoor Floor Plan
Dimensions
Dimensions in Inches (mm)
This transition required for liquid filled and outdoor dry type transformers only.Cable space is 13.2 in. (335 mm) in depth for bottom entry with circuit breaker in bottom compartment. (Refer to side view.)
Indoor Side View
Switchgear (Up to 4000A)
Switchgear (5000A) Dimensions in Inches (mm)
4
480V Metal-Enclosed
Switchgear
Bolting Arrangement
Siemens Electrical Products and Systems
Specification Guide
65CSI Section 16470
480V Metal-Enclosed Switchgear

Outdoor Floor Plan, Side View

Outdoor Floor Plan
Dimensions
Dimensions in inches (mm)
Cable space is 22.4 in. (569 mm) depth for
bottom entry with circuit breaker in bottom compartment.
4
480V Metal-Enclosed
Switchgear
30.0” (762 mm) Door Hinges on Extension
Dimensions in inches (mm)
Bolting Arrangement
Outdoor Bolting Arrangement
Type SR
(Side View)
66 CSI Section 16470
Siemens Electrical Products and Systems
Specification Guide
480V Metal-Enclosed Switchgear

Guide Form Specifications

Specifications
This equipment specification guide provides information for describing a typical metal enclosed low voltage power circuit breaker switchgear assembly. Items or features that are non-standard but required for a specific application are preceded by (option). Items preceded or followed by a blank (__) require that additional data be provided in order to complete the specification.
General
The equipment to be supplied shall be metal enclosed low-voltage power circuit breaker switchgear with drawout circuit breaker elements. All power circuit breakers and assemblies shall be produced by a single manufacturer and shall be designed, tested and manufac­tured in accordance with the standards referenced in this specification.
Codes and Standards
The switchgear assemblies and power cir­cuit breakers shall comply with the codes and standards as indicated. Copies of cer­tified design tests shall be furnished if requested to confirm compliance.
ANSI / IEEE C37.13 — Low­Voltage AC Power Circuit Breakers Used in Enclosures
ANSI C37.16 — Low-Voltage Power Circuit Breakers and AC Power Circuit Protectors — Preferred Ratings, Related Requirements, and Application Recommendations
ANSI C37.17 — Trip Devices for AC and General Purpose DC Low­Voltage Power Circuit Breakers
ANSI / IEEE C37.20.1 — Metal­Enclosed Low-Voltage Power Circuit-Breaker Switchgear
ANSI / IEEE C37.27 — Application Guide for Low-Voltage AC Nonintegrally Fused Power Circuit Breakers (Using Separately Mounted Current Limiting Fuses)
ANSI C37.50 — Standard Test Procedures for Low-Voltage AC Power Circuit Breakers Used in Enclosures.
ANSI C37.51 — Standard Conformance Test Procedures for Metal Enclosed Low-Voltage AC Power Circuit-Breaker Switchgear Assemblies
ANSI / NEMA 250 — Enclosures for Electrical Equipment (1000 Volts Maximum)
NEMA SG 3 — Low-Voltage Power Circuit Breakers
NEMA SG 5 — Power Switchgear Assemblies
(option) NEMA 210 — Secondary Unit Substations
UL 1066 — Low-Voltage AC and DC Power Circuit Breakers Used in Enclosures
(Option) UL 1558 — Metal-Enclosed Low-Voltage Power Circuit Breaker Switchgear
Assembly
The switchgear assembly shall be Siemens Type R and is to be located indoors, with a NEMA 1 enclosure, (option) outdoor, NEMA 3R per specifications below and constructed of multiple, metal-enclosed, ventilated sections. The front of each verti­cal section is to contain three or four com­partments with 14 gauge steel side sheets and compartment barriers of 11 gauge steel. A double thickness of 14 gauge steel is to be provided between vertical sec­tions. The side sheets shall be full height and depth to provide a full metal barrier separating the rear cable compartments between sections. End sections shall include provisions for main bus extension and installation of future vertical sections. The design shall incorporate preformed steel channels, angles, and side sheets bolted together and reinforced to form a rigid, self-supporting, compact assembly.
Horizontal barriers are to be provided to form individual circuit breaker or metering com­partments. Circuit breaker compartments are to be barriered from the bus compart­ment through a primary disconnect assem­bly. Each circuit breaker or metering com­partment shall be provided with a hinged front door secured with rotary latches requir­ing no tools to operate.
Circuit breaker compartments shall include stationary primary contact disconnects. The primary disconnects shall be copper, silver-plated at connection points and shall be of one piece construction. The upper set of disconnects shall bolt directly to the main bus and, for feeder circuit breakers, the lower set shall extend to the rear cable area and shall be insulated where they pass through the main bus compartment. Primary disconnects shall be sized for the maximum continuous current of the circuit breaker which will be located in the com­partment. Interlocks shall be provided which will prevent a circuit breaker ele­ment of the incorrect frame size or inter­rupting rating from being inserted into the compartment. A stationary circuit breaker frame grounding contact shall be provided which shall be visible with the circuit breaker installed in any position.
Secondary control contacts, when required, shall be located in the circuit breaker compartment and shall be of the sliding contact, silver-plated copper design. Barriers shall be provided between terminal points. The secondary control contacts shall engage the drawout circuit breaker element in the connected and test positions.
Control circuit fuses for electrically oper­ated circuit breakers shall be located on the side of the circuit breaker compart­ment and shall be contained in a dead­front, pull-out fuse block with a clear cover. Withdrawing the cover from the fuse block shall automatically remove the control circuit fuses and hold them cap­tive. The fuse block cover shall include provisions for being installed in the reverse position in order to maintain the open control circuit for testing or mainte­nance purposes while continuing to hold the fuses captive.
All control wiring within the assembly shall be continuous and shall terminate on each end at a suitable terminal block. Control wiring shall be 14 gauge, strand­ed, type SIS, and shall be labeled at each end with sleeve type wire markers. Wire markers shall be machine imprinted with the wire name as indicated on the wiring diagrams. Wrap on wire markers will not be accepted. Terminals shall be insulated locking fork or ring tongue type except where connecting to components that do not accept these terminations. Control wiring for external connections shall be terminated in the rear cable area for ease of access. (Option) Metal covers shall be provided over control wiring troughs where they pass through the power cable termination area. (Option) Metal covers shall be provided over terminal blocks located in the power cable termi­nation area.
Bus
Main bus shall be three-phase, ___ wire ___ ampere copper with silver-plated connection joints (option) aluminum with welded connection points (option) copper with tin-plated connection points. (Option) Neutral bus rating shall be ___% of the main bus current rating and shall be located centrally in the structure for ease of terminating cables whether entering from above or below. 600 volt clearances shall be maintained in all hori­zontal and vertical buses such that insula­tion is not required. The main horizontal bus shall be run in a vertical, edge-to­edge arrangement for high short circuit strength. Access to the rear cable termi­nation area shall be possible without
4
480V Metal-Enclosed
Switchgear
Siemens Electrical Products and Systems
Specification Guide
67CSI Section 16470
480V Metal-Enclosed Switchgear
Guide Form Specifications
Specifications
reaching over the main and vertical bus. Bus bracing shall be equal to the short circuit interrupting rating of the lowest rated non-fused circuit breaker applied in the assembly. A 0.25 in. (6 mm) by 2.00 in. (51 mm) copper ground bus will be provid­ed. Barriers shall be provided which isolate the rear cable termination compartment from the adjacent vertical section. (Option) Barriers shall be provided to isolate the rear cable area from the main bus area. (Option) Barriers shall be provided to sepa­rate the incoming line connections from the main horizontal and vertical bus.
Circuit Breakers
Circuit breakers shall be Siemens Type RL and shall be either electrically or manually operated as indicated on the data sheets (or drawings). Minimum interrupting rat­ings will be as defined on the data sheets (or drawings) and shall meet or exceed the interrupting ratings as defined by ANSI standards. (Option) Fused circuit breakers are to be the integrally fused type through the 2000 ampere frame size. 3200 and 4000 ampere frame sizes are to be sup­plied with separate drawout fuse carriages which are mounted in the same vertical section as the circuit breaker element and are to be key interlocked with the circuit breaker element such that the fuse carriage cannot be withdrawn unless the circuit breaker is locked in the open position. All fused circuit breakers are to be equipped with blown fuse lockout devices to prevent single phasing. The application of fused circuit breakers shall not reduce the amount of rear cable termination space which would have been provided with non­fused circuit breakers.
Circuit breakers are to be 600 volt class
4
with nominal ratings as dictated by the system voltage. Circuit breakers shall be three-pole, single-throw, operated by a stored energy mechanism, with arc quenchers, main and arcing contact struc­ture, a three-phase solid state trip overcur­rent trip unit, trip actuator, three single ratio tripping sensors, and primary disconnect-
480V Metal-Enclosed
Switchgear
ing devices. In addition, the circuit breaker element shall have connected, test, and disconnected position indicators, spring charged/discharged indicators, and circuit breaker open or closed indicators all of which shall be visible to the operator with the compartment door closed. It shall be possible to rack the circuit breaker element from the disconnect to the connected posi­tion with the compartment door closed. Interlocks will be provided that prevent racking a circuit breaker unless the circuit breaker is open and that prevent closing a circuit breaker unless it is in the connected or test position.
Solid State Trip Units
Solid state trip units shall be Siemens
Static Trip III (basic device)
(Option) Static Trip IIIC (adds communications capability)
(Option) Static Trip IIICP (adds communications and power metering)
(Option) Static Trip IIICPX (adds communications, power metering, and relaying functions)
Trip units shall be interchangeable so that any trip unit can be used with any frame size circuit breaker. The basic trip unit shall be a self powered, micro-processor based device that measures true RMS currents. Long time, short circuit or ground fault trip indication shall be maintained for a mini­mum of 48 hours without the need for a separate battery or relay. Peak sensing devices will not be accepted. All adjust­ment setting switches shall be digitally encoded type with gold contacts. (Note: Refer to catalog section SGBR-3169B for specifications on the Siemens Static Trip III trip unit family and all associated options).
Instrumentation and Metering
A wide variety of user defined metering and instrumentation options are available. They include Siemens 4720, 4700 & 4300 power meters, Siemens Static Trip III trip units, and traditional analog devices. For more detailed specification information on Siemens devices refer to bulletins SGFL 3181B, 3161A, and 3151B for 4720, 4700, and 4300 power meters, respectively; and SGBR-3169B Static Trip III Micro-processor Based Tripping System. If one of the options selected requires separate voltage and current transformers, such as the Siemens 4700 power meter, the following may be used to define these devices.
Current transformers shall have standard accuracy class ratings as defined by ANSI C37.20.1 and shall be mounted directly on the stationary primary disconnects in the circuit breaker compartment. Voltage trans­formers shall have a minimum 150VA thermal rating and shall be located in a metal enclosed metering compartment and shall be protected on the primary side with current limiting fuses.
Outdoor
(Option) Outdoor, NEMA 3R, walk-in, weatherproof construction is to be provided. The complete assembly is to rest on a formed steel base provided under each vertical section and running perpendicular to the depth of the switchgear. The under­side of the enclosure and base structure is to be undercoated with coal tar emulsion material.
Front and rear doors are to be gasketed and hinged. Front doors, located at each end, are to include panic release door hard­ware, three point latches, and provision for padlocking. Rear doors shall be bolted. All exterior hardware shall be stainless steel.
An indoor access aisle approximately 42 in. (1067 mm) deep and accessible from either door is to be provided at the front of the switchgear line-up for inspection and testing of the circuit breakers and associat­ed equipment. A hand-operated traveling hoist, mounted above the switchgear is to be provided for changeout of circuit break­ers. The aisle is to have an extension on each end to accommodate end unit doors that have instrumentation and metering, and to provide additional space for circuit breaker handling.
The switchgear is to include space heaters to prevent condensation of moisture. The aisle shall be provided with incandescent lights, convenience receptacle, and an ON / OFF switch at each end to control the lights.
Finish
During construction, the structural steel parts, panels, and compartments shall be prepared for painting by a five-stage wash system consisting of an alkaline cleaner, fresh water rinse, iron phosphate treat­ment, fresh water rinse, and non-chromate sealer. After cleaning and stabilization, the steel parts shall be coated with a ther­mosetting polyester powder applied with electrostatic equipment at a nominal 2 mils dry film thickness and then cured at 425 degrees Fahrenheit for 20 minutes. Paint color shall be ANSI 61 light gray. The paint finish shall have a pencil hardness of 2H, a gloss as defined by ANSI D523-78 of 45­55%, a salt spray rating per ASTM B-117­73 of 600 hours, and shall be outdoor rated per UL1332.
Accessories
The following accessories are to be provided:
crank for racking circuit breakers
lifting yoke for circuit breakers
container of touch-up paint
(optional) portable test set, type PTS4
overhead hoist for indoor switchgear
(optional) test cabinet
Testing
Production tests in accordance with ANSI C37.20.1, ANSI C37.50, ANSI C37.51 and NEMA SG 5 shall be performed on the completed assembly. Certified copies of these tests shall be furnished upon request.
68 CSI Section 16470
Siemens Electrical Products and Systems
Specification Guide
Loading...