Siemens Switch 480V User Manual

480V Metal-Enclosed Switchgear
Siemens low-voltage metal-enclosed switchgear is used in electric power dis­tribution systems for the control and pro­tection of circuits and equipment. The switchgear employs drawout type low voltage power circuit breakers described in Section 4.
LV switchgear is typically installed in:
lighting networks and feeders, power generation and other auxiliaries, and to provide power for machine tools and material handling equipment drivers.
Utility and Co-generation Facilities
— for motor control centers to protect and distribute power to electrical devices such as blowers, compres­sors, fans, pumps, and motors.
Commercial and Residential
Buildings — for protection and distri-
bution of power for lighting, elevators, air conditioning, blowers, fans, motors, and pumps.
General
Available Types:
Type R — indoor (NEMA 1)Type SR — outdoor walk-in (NEMA
3R)
Low-voltage switchgear can be applied on distribution systems with:
3-phase, 3- or 4-wire feeders50 or 60HzVoltages of 208, 240,480, or 600 voltsCurrents up to 5000 amperes
Circuit breakers may be either manually or electrically operated, fused or unfused. The following designations are used:
RL — Standard Interrupting
4
RLE — Extended InterruptingRLI — High InterruptingRLF — Fused Type
Siemens Static Trip III trip units are pro­vided on all low voltage power circuit breakers, except non-automatic circuit breakers. All circuit breakers are UL
480V Metal-Enclosed
Switchgear
Listed. See Tables 4.10 and 4.11 for cir­cuit breaker ratings.
480 Volt Metal-Enclosed Switchgear
Industry Standards
Types R and SR switchgear with power circuit breakers are designed, tested and constructed in accordance with:
ANSI C37.20.1 — Metal-Enclosed
Low Voltage Power Circuit Breaker Switchgear
ANSI C37.50 — Test Procedure for
Low Voltage AC Power Circuit Breakers Used in Enclosures
ANSI C37.51 — Conformance Testing
of Metal-Enclosed Low Voltage AC Power Circuit Breaker Switchgear Assemblies
Applicable standards of IEEE and
NEMA
Applicable requirements of the
National Electric Code (NEC)
UL 1558 — Metal-Enclosed Low
Voltage Power Circuit Breaker Switchgear
Type RL drawout circuit breakers are in accordance with:
ANSI C37.13 — Low Voltage AC
Power Circuit Breakers Used in Enclosures
ANSI C37.16 — Preferred Ratings,
Related Requirements, and Application for Low Voltage Power Circuit Breakers and ACPower Circuit Protectors.
ANSI C37.17 — Trip Devices for AC
and General Purpose DC Low- Voltage Power Circuit Breakers.
UL 1066 — Low Voltage AC and DC
Power Circuit Breakers Used in Enclosures.
Features and modifications required by NEC are incorporated when the assembly is designated as “Service (Entrance) Equipment.”
UL Listing (Optional)
An Underwriters’ Laboratories listing mark (UL label) can be optionally supplied for each vertical section. The specific section must contain only devices which are UL Listed or are UL recognized com­ponents found suitable for the intended use. All circuit breaker drawout elements are UL Listed.
50 CSI Section 16470
Siemens Electrical Products and Systems
Specification Guide
480V Metal-Enclosed Switchgear
Siemens low-voltage metal-enclosed switchgear is used in electric power dis­tribution systems for the control and pro­tection of circuits and equipment. The switchgear employs drawout type low voltage power circuit breakers described in Section 4.
LV switchgear is typically installed in:
lighting networks and feeders, power generation and other auxiliaries, and to provide power for machine tools and material handling equipment drivers.
Utility and Co-generation Facilities
— for motor control centers to protect and distribute power to electrical devices such as blowers, compres­sors, fans, pumps, and motors.
Commercial and Residential
Buildings — for protection and distri-
bution of power for lighting, elevators, air conditioning, blowers, fans, motors, and pumps.

General

Available Types:
Type R — indoor (NEMA 1)Type SR — outdoor walk-in (NEMA
3R)
Low-voltage switchgear can be applied on distribution systems with:
3-phase, 3- or 4-wire feeders50 or 60HzVoltages of 208, 240,480, or 600 voltsCurrents up to 5000 amperes
Circuit breakers may be either manually or electrically operated, fused or unfused. The following designations are used:
RL — Standard Interrupting
4
RLE — Extended InterruptingRLI — High InterruptingRLF — Fused Type
Siemens Static Trip III trip units are pro­vided on all low voltage power circuit breakers, except non-automatic circuit breakers. All circuit breakers are UL
480V Metal-Enclosed
Switchgear
Listed. See Tables 4.10 and 4.11 for cir­cuit breaker ratings.
480 Volt Metal-Enclosed Switchgear
Industry Standards
Types R and SR switchgear with power circuit breakers are designed, tested and constructed in accordance with:
ANSI C37.20.1 — Metal-Enclosed
Low Voltage Power Circuit Breaker Switchgear
ANSI C37.50 — Test Procedure for
Low Voltage AC Power Circuit Breakers Used in Enclosures
ANSI C37.51 — Conformance Testing
of Metal-Enclosed Low Voltage AC Power Circuit Breaker Switchgear Assemblies
Applicable standards of IEEE and
NEMA
Applicable requirements of the
National Electric Code (NEC)
UL 1558 — Metal-Enclosed Low
Voltage Power Circuit Breaker Switchgear
Type RL drawout circuit breakers are in accordance with:
ANSI C37.13 — Low Voltage AC
Power Circuit Breakers Used in Enclosures
ANSI C37.16 — Preferred Ratings,
Related Requirements, and Application for Low Voltage Power Circuit Breakers and ACPower Circuit Protectors.
ANSI C37.17 — Trip Devices for AC
and General Purpose DC Low- Voltage Power Circuit Breakers.
UL 1066 — Low Voltage AC and DC
Power Circuit Breakers Used in Enclosures.
Features and modifications required by NEC are incorporated when the assembly is designated as “Service (Entrance) Equipment.”
UL Listing (Optional)
An Underwriters’ Laboratories listing mark (UL label) can be optionally supplied for each vertical section. The specific section must contain only devices which are UL Listed or are UL recognized com­ponents found suitable for the intended use. All circuit breaker drawout elements are UL Listed.
50 CSI Section 16470
Siemens Electrical Products and Systems
Specification Guide
480V Metal-Enclosed Switchgear

Construction Details

General
General
The Siemens 480 volt switchgear assem­bly consists of one or more metal­enclosed, vertical sections. Normally the end sections are designed to allow for installation of future sections.
Each vertical section consists of up to four individually enclosed breaker or auxil­iary compartments which are sized to provide uniform height.
Included in each assembly are various components such as circuit breakers, instrumentation and control equipment, transformers, relays, three-phase bus work, and all internal wiring, connectors, and other supporting equipment.
In accordance with ANSI C37.20.1, the maximum temperature for parts that are handled is 50°C. The main bus maximum temperature rise is 65°C above 40°C ambient. The temperature rise of the air surrounding the cable connection points is limited to 45°C above 40°C ambient.
Finish
During construction, the structural steel parts, panels, and compartments are all prepared for painting by a five-stage wash system. Standard finish color is light gray ANSI 61. If a different finish color is required, it is applied over the standard finish with conventional spray equipment and is allowed to air cure. The completed finish has a nominal 2 mils dry film thickness.
Assembly Construction
Siemens metal-enclosed power switchgear is constructed of preformed, full-depth, 14-gauge steel sheets bolted together and reinforced with cross-mem­ber braces to form a rigid, self-supporting compact assembly. The top and rear plates, and side sheets are all 14-gauge steel. When two vertical sections are mounted together, two sheets of 14­gauge steel separate adjacent circuit breaker compartments.
Bolted steel / glass polyester compart­ments housing each power circuit break­er are mounted in the vertical section to form the switchgear assembly. This iso­lates the circuit breakers from the bus / cable section and from adjacent circuit breaker compartments.
The bus / cable section includes main horizontal bus, riser bus, connections from the main bus to each set of primary disconnects, and load side copper run­back bus.
Grounded metal barriers can be provided to isolate the main bus from cable con­nections. Barriers are also available to isolate the incoming line to the main cir­cuit breakers from the main load bus of the switchgear.
Inter-Unit Wiring TroughMeter and Auxiliary CompartmentVentilation and Lifting StructureTelescoping Breaker Drawout RailsVentilation Openings (RL-2000, RL-3200, RL-4000
and RL-5000)
4
480V Metal-Enclosed
Switchgear
Siemens Electrical Products and Systems
Specification Guide
51CSI Section 16470
480V Metal-Enclosed Switchgear
Construction Details
General
Main and Ground Bus
The standard main bus is silver-plated copper. Welded aluminum is also avail­able. Provisions for future extension of aluminum main bus conductors include tin plated joints with high tensile strength steel hardware. Tin-plated copper bus is optionally available.
The main three-phase horizontal bus is arranged vertically one phase above the other with edge-to-edge alignment to provide high, short circuit strength. Insulated main and vertical bus are optional.
Main bus ratings available are 1600, 2000, 3200, 4000, or 5000 amperes con­tinuous current. A neutral bus is fur­nished when specified, and can be rated 1600, 2000, 3200, 4000 or 5000 amperes continuous current.
A standard copper ground bus extends through all sections. A cable lug can be mounted to the ground bus in each section.
Minimum bus bracing is 65,000 amperes RMS symmetrical. Higher symmetrical bracings are available based on the low­est breaker short circuit rating in the group.
Load side runbacks for feeder circuits are one-piece copper construction, are insu­lated with sleeve tubing in the main bus area, and are supported by high-strength, glass polyester moldings.
Control Wiring
Standard secondary and control wiring is #14 AWG extra-flexible, stranded copper type SIS. Terminations are made with compression-type, insulated terminals.
For devices not having screw-type termi­nals, tab-type disconnects are used.
Insulation
The insulation used is Pyro-Shield, a fiber­glass-reinforced polyester material that has high impact strength and low mois­ture absorption. Other features include high flame retardance, high resistance to chemical fumes, and long life at high temperatures.
Circuit Breaker Compartments
Typical circuit breaker compartments include primary disconnects, ground dis­connect, drawout rails, and associated interlocks, and secondary disconnects, if appropriate. Telescoping drawout rails allow the breaker to be withdrawn from the compartment without additional extensions or adapters. Compartments for electrically-operated circuit breakers include secondary disconnects and con­trol circuit fuses. Up to three current transformers for metering or relaying can be mounted in each compartment.
Circuit breaker compartment front panels can be used to hold a variety of auxiliary devices such as breaker control switch­es, ammeters, and test blocks.
4
480V Metal-Enclosed
Switchgear
52 CSI Section 16470
Control Circuit Fuses Ground Disconnect Secondary Disconnect Front Panel Devices Primary Disconnect
Circuit Breaker Cell Interior
Siemens Electrical Products and Systems
Specification Guide
TOC Switch Operator Interference Interlock MOC Switch Operator Space Heater Drawout Rails
480V Metal-Enclosed Switchgear
Guide Form Specifications
Options
Switchgear Mounted Hoist
The hoist, optional on type R indoor switchgear, and standard on type SR outdoor switchgear, travels along rails on top of the switchgear to ease breaker handling.
TOC and MOC Switches
The Truck Operated Cell (TOC) Switch provides interlocking control or remote indication of the breaker racking position. The cubicle mounted auxiliary switch or Mechanism Operated Cell (MOC) switch provides interlocking control or remote indication based on the main contact position (open or closed).
The switches have field adjustable con­tacts for simple conversion of contacts from normally open (“a” type) to normal­ly closed (“b” type). Each contact may be adjusted individually without disassembly or removal of wiring.
Typical Outdoor Installation with Liquid Filled Transformer
General
MOC and TOC Switches. TOC Shown with Cover Removed.
Shutters
These provide protection against acciden­tal contact with primary disconnects in a compartment when the breaker is removed.
Wire Trough Covers
Secondary wiring is enclosed within each vertical section in the primary bus and outgoing cable areas.
Key Interlock
This provides a mechanical means for operating circuit breakers and other devices only when predescribed condi­tions are met.
PTS4 Test Set
Set allows testing of the full range of pro­tective settings of Static Trip III trip units.
Metering and Auxiliary Compartments
Compartments are available to house devices such as voltage transformers, metering, control power transformers, and supervisory devices.
Instrument and Control Transformers
Voltage transformers and control power transformers are mounted in auxiliary compartments. These transformers are protected by primary pull-out type cur­rent-limiting fuses and secondary fuses. Current transformers are normally mount­ed on the compartment primary discon­nect studs where they are readily acces­sible. See Tables 4.10, 4.11, 4.12, and
4.13 for available ratings.
Outdoor Switchgear
Type SR outdoor switchgear, available up to 4000 amp, is enclosed in a weather resistant (NEMA 3R) steel housing. All exterior doors extend below the floor line and are gasket sealed.
For protection from snow, rain, and dust, the switchgear rests on a six-inch, formed steel base which provides rigid support and a tight bottom seal. A heavy duty, coal tar emulsion protective under­coating is applied to the underside for protection against moisture and corro­sion. Shielded ventilation housings permit proper air circulation while excluding dust, dirt, and foreign matter.
A lighted, unobstructed service aisle is provided at the front of the switchgear allowing inspection and maintenance without exposure to the elements, An access door equipped with an emer­gency bar release is located at each end of the aisle. A GFI convenience outlet is included.
Accessories
Each switchgear assembly includes the following standard accessories:
Crank for circuit breaker rackingLifting bar assembly for all circuit
breaker types
Spring charging handle for electrically
operated circuit breakers
As an optional accessory, a test cabinet is available for indoor use that is wall mounted with necessary equipment for testing electrically-operated breakers that have been removed from the breaker compartments.
Portable PTS4 Test Set
4
480V Metal-Enclosed
Switchgear
Siemens Electrical Products and Systems
Specification Guide
53CSI Section 16470
480V Metal-Enclosed Switchgear

LV Power Circuit Breakers

The Siemens RL series circuit breakers are designed for up to 600 volt service with current carrying capacities of up to 5000 amperes and interrupting capacities of up to 130,000 amperes unfused or 200,000 amperes fused.
These compact, fast operating circuit breakers incorporate a stored energy closing mechanism, either manually or electrically charged, for fast, positive closing.
A quick-make closing mechanism releas­es the stored energy for high speed clos­ing of the primary contacts. This positive, controlled closing prevents unnecessary arcing between the movable and station­ary breaker contacts and thus lengthens contact and breaker life.
Manual tripping is performed with the push lever on the front of the breaker. Up to three padlocks can be used to lock the breaker contacts in the open position.
Typical Breaker Features
Arc QuenchersMain and Arcing Contact StructuresInductive Tripping SensorsControl WiringInterlocksPosition IndicatorsInterpole BarriersMechanical Trip BarAuxiliary Switches (option)
Each circuit breaker is a complete 3-pole, single-throw element that is mechanically and electrically trip-free, with a Static Trip III overcurrent trip unit.
Tables 4.16 and 4.17 show circuit breaker
4
operating and control data.
Circuit Breaker Racking
Racking is accomplished by turning a racking screw on the front of the breaker and may be done with the compartment door open or closed. The racking screw turns U-shaped brackets on each side of
480V Metal-Enclosed
Switchgear
the breaker which rack the breaker frame in or out of the compartment.
As the racking screw is turned counter­clockwise, the breaker frame moves out of the compartment and disconnects the primary contacts, followed by the sec­ondary contacts. With only the secondary contacts connected (test position), the breaker may be closed and opened for testing without energizing the load. An indicator located on the front of the breaker identifies the position of the breaker in the compartment.
Type RL Circuit Breaker With Static Trip III Trip Unit And Optional Breaker Display Unit (BDU)
Primary Disconnects
Primary current is applied to the circuit breaker through silver plated disconnects. The stationary contacts are mounted through solid Pyro-Shield insulation sheets in the back of the compartments. The movable contacts are mounted on the back of the breaker. Stainless steel springs provide pressure to the finger contacts in the connected position. Low contact resistance is maintained by these self-aligning contacts. The primary con­tacts are positioned so that current can flow only in the connected position. In the test position the contacts are separat­ed a safe distance.
Secondary Disconnects
Secondary circuits are connected to the circuit breaker through silver-plated, slide­type contacts which are located below the arc quenching area to avoid contami­nation from arc product gases. The posi­tion of these contacts is visible with the panel door open. The stationary contacts are silver-plated copper strips mounted on a Pyro-Shield molded base. The con­tacts are recessed to guide the movable, self-aligning contacts and to prevent acci­dental short circuiting. Secondary connec­tions are made automatically in both the connected and test positions.
General
Secondary Disconnects in Cell Left = Communications Right = Breaker Control
Main and Arcing Contacts — Similar Design for all Ratings
54 CSI Section 16470
Siemens Electrical Products and Systems
Specification Guide
Loading...
+ 14 hidden pages