Siemens SLIM Installation Instructions Manual

FRONT
BACK
FAULT
IN - LINE 1
IN - LINE 2
OUT - LINE 1
OUT - LINE 2
Installation Instructions Model SLIM
Loop Isolator Module
OPERATION The Model SLIM Loop Isolator Module from Siemens Building Technologies, Ltd.
isolates short circuits on FS-250C analog loops. By placing devices between SLIMs during installation, a short in the wiring within that group is disconnected from the rest of the loop. The remainder of the devices continue to operate. The SLIM operates in both Class A and Class B circuits.
A yellow LED flashes when a device detects a short circuit. The SLIM then isolates that part of the loop. When the short is removed, the SLIM automatically restores the loop to normal operation. The SLIM does not have a loop address and therefore does not require address programming nor does it reduce the loop capacity below 252 devices.
Figure 1 The SLIM-1 Loop Isolator Module
Remove all system power before installation, first the battery and then the AC.
INSTALLATION The SLIM is a polarity insensitive module. Refer to Figure 1 for the location of the two
input terminals and two output terminals. Line 1 and Line 2 can be either line of the loop.
The SLIM may be used in two circuit configurations as follows:
Class B (See Figure 2) In Class B wiring each SLIM isolates a branch on the circuit. Note that
a short on the main branch causes the entire loop to fail. To prevent this, mount the SLIMs at the enclosure and run each branch independently.
P/N 315-049692C-1
Siemens Building Technologies
Fire Safety
1. All wiring must comply with national and local codes.
2. In order to provide adequate protection, it is recom­mended that you do not install more than 20 devices
ANALOG LOOP
LINE 1
LINE 2
on a single SLIM.
3. Minimum wire gauge is 18 AWG.
4. The total wire resistance (both wires) between SLIMs cannot exceed 20 ohms.
5. Do not install more than 15 SLIMs per FDLC loop.
6. All circuits are supervised.
7. Refer to FDLC Installation
IN IN OUT OUTIN IN OUT OUTIN IN OUT OUT
Instructions, P/N 315­447360FA or the FS-250C Manual, P/N 315-049589C for the list of compatible devices, as applicable.
Figure 2 SLIM Wiring Diagram - Class B Installation
8. All terminals are power limited.
Class A Single Loop (See Figure 3) In Class A wiring the SLIMs are wired in series with the loop wiring.
This results in a single continuous loop. If any group in the loop has a short, that group is lost and a Class A circuit failure results.
1. All wiring must comply with national and local codes.
2. In order to provide adequate protection, it is recom­mended that you do not install more than 20 devices on a single SLIM.
3. Minimum wire gauge is 18 AWG.
4. The total wire resistance (both wires) between SLIMs cannot exceed 20 ohms.
5. Do not install more than 15 SLIMs per FDLC loop.
6. All circuits are supervised.
7. Refer to FDLC Installation Instructions, P/N 315­447360FA or the FS-250C Manual, P/N 315-049589C for the list of compatible devices, as applicable.
8. All terminals are power limited.
The FS-250C displays the message “DLC Open” and “no response” for devices in the groups on the loop that follow the short.
INSIDE ENCLOSURE
TO ANALOG LOOP RETURN
LINE 2 LINE 1
TO ANALOG LOOP FEED
OUTOUT
LINE 1 LINE 2
IN IN OUT OUT IN IN OUT OUT
ININ
OUTOUT
IN IN OUT OUT
ININ
OUTOUT
Figure 3 SLIM Wiring Diagram - Class A Installation (Single Loop)
ININ
Siemens Building Technologies Fire Safety
P/N 315-049692C-12
Loading...
+ 2 hidden pages