Siemens SICAM Q100, 7KG95 Series Device Manual

Preface Open Source Software
Contents
Power Monitoring Device and Class A Power Quality Recorder
SICAM Q100 7KG95xx
V2.00
User Information 1 Overview 2 Device Design 3 Measured Quantities and Recording 4 Energy Management 5 Getting Started 6 Connection Principle 7 Operation at Use of a PC 8 Operation at Use of the Display 9 Time Synchronization 10 Maintenance, Storage, Transport 11
E50417-H1040-C522-A4
Failures and LED Indications 12 Technical Data 13 Operational Indications 14 Operating Parameters 15
Glossary Index
NOTE
For your own safety, please observe the warnings and safety instructions contained in this document.
Disclaimer of Liability
This document has been subjected to rigorous technical review before being published. It is revised at regular intervals, and any modifications and amendments are included in the subsequent issues. The content of this document has been compiled for information purposes only. Although Siemens AG has made best efforts to keep the document as precise and up-to-date as possible, Siemens AG shall not assume any liability for defects and damage which result through use of the information contained herein.
This content does not form part of a contract or of business relations; nor does it change these. All obligations of Siemens AG are stated in the relevant contractual agreements.
Siemens AG reserves the right to revise this document from time to time.
Document version: E50417-H1040-C522-A4.07 Edition 03.2018 Version of the product described: V2.00
Copyright
Copyright Siemens AG 2018. All rights reserved.
The disclosure, duplication, distribution and editing of this document, or utilization and communication of the content are not permitted, unless authorized in writing. All rights, including rights created by patent grant or registration of a utility model or a design, are reserved.
Registered Trademarks
SIPROTEC SIEMENS AG. An unauthorized use is illegal.
All other designations in this document can be trademarks whose use by third parties for their own purposes can infringe the rights of the owner.
TM
and SICAMTM are registered trademarks of

Preface

Purpose of this Manual
This manual describes the application, functions, installation, commissioning, and operation of the Power Monitoring Device and Class A Power Quality Recorder SICAM Q100 7KG95xx.
Target Group
This manual is intended for project engineers, commissioning and operating personnel in electrical systems and power plants.
Scope of Vali dity of this Manual
This manual is valid for the Power Monitoring Device and Class A Power Quality Recorder SICAM Q100 7KG95xx.
Further Support
For any questions concerning your system, please contact your Siemens representative.
The Siemens Customer Support Center provides around-the-clock support.
Phone: +49 (180) 524-7000
Fax: +49 (180) 524-2471
Internet: www.siemens.com/powerquality
e-mail: support.energy@siemens.com
Training Courses
If you are interested in our current training program, please contact our training center:
Siemens AG Siemens Power Academy TD
Humboldtstr. 59 D-90459 Nuremberg
Tel.: +49 (911) 433-7415
Fax: +49 (911) 433-7929
Internet: http://www.siemens.com/poweracademy
e-mail: poweracademy@siemens.com
E50417-H1040-C522-A4, Edition 03.2018
3SICAM Q100, 7KG95xx, Device Manual
Notes On Safety
This manual is not a complete index of all safety measures required for operation of the equipment (module, device). However, it comprises important information that must be noted for purposes of personal safety, as well as in order to avoid material damage. Information is highlighted and illustrated as follows according to the
degree of danger.
DANGER
DANGER means that death or severe injury will occur if the appropriate safety measures are not taken.
Follow all advice instructions to prevent death or severe injury.
WARNING
WARNING means that death or severe injury can occur if the appropriate safety measures are not taken.
Follow all advice instructions to prevent death or severe injury.
CAUTION
CAUTION means that minor or moderate injury can occur if the appropriate safety measures are not taken.
Follow all advice instructions to prevent minor injury.
NOTICE
NOTICE means that damage to property can occur if the appropriate safety measures are not taken.
Follow all advice instructions to prevent damage to property.
NOTE
is important information about the product, the handling of the product, or the part of the documentation in question to which special attention must be paid.
4 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
Personnel Qualified in Electrical Engineering
Only qualified electrical engineering personnel may commission and operate the equipment (module, device) described in this document. Qualified electrical engineering personnel in the sense of this manual are people who can demonstrate technical qualifications as electrical technicians. These persons may commission, iso­late, ground, and label devices, systems and circuits according to the standards of safety engineering.
Use as Prescribed
The equipment (device, module) must not be used for any other purposes than those described in the Catalog and the Technical Description. If it is used together with third-party devices and components, these must be recommended or approved by Siemens.
If the device is not used in accordance with the Product Information and this manual, the scheduled protection is impaired.
Problem-free and safe operation of the product depends on the following:
Proper transport
Proper storage, setup, and installation
Proper operation and maintenance
When electrical equipment is operated, hazardous voltages are inevitably present in certain parts. If proper ac­tion is not taken, death, severe injury, or property damage can result.
The equipment must be grounded at the grounding terminal before any connections are made.
All circuit components connected to the power supply may be subject to dangerous voltage.
Hazardous voltages may be present in equipment even after the supply voltage has been disconnected (capacitors can still be charged).
Equipment with exposed current transformer circuits must not be operated. Prior to disconnecting the equipment, ensure that the current transformer circuits are short-circuited.
The limit values stated in the document may not be exceeded. This must also be considered during testing and commissioning.
E50417-H1040-C522-A4, Edition 03.2018
5SICAM Q100, 7KG95xx, Device Manual
Used Symbols
No. Symbol Description
1 Direct current
IEC 60417-5031
2 Alternating current
IEC 60417-5032
3 Direct and alternating current
IEC 60417-5033
4 Three-phase alternating current
5 Earth (ground) terminal
IEC 60417-5017
6 Protective conductor terminal
IEC 60417-5019
7 Caution, risk of electric shock
8 Caution, risk of danger
ISO 7000-0434
6 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
Statement of Conformity
This product complies with the directive of the Council of the European Communities on the approximation of the laws of the Member States relating to electromagnetic compatibility (EMC Council Directive 2004/108/EC - valid until April 19th, 2016; EMC Council Directive 2014/30/EU ­valid as of April 19th, 2016) and concerning electrical equipment for use within specified voltage limits (Lowvoltage Directive 2006/95/EC - valid until April 19th, 2016; Lowvoltage Directive 2014/35/ EU - valid as of April 20th, 2016).
This conformity has been established by means of tests conducted by Siemens AG according to the Council Directive in agreement with the generic standards EN 61000-6-2 and EN 61000-6-4 for the EMC directives, and with the standard EN 61010-1 for the low-voltage directive.
The device has been designed and produced for industrial use.
The product conforms to the standard IEC 62586-1, Ed. 1.
Further Standards
This product is UL-certified to Standard UL 61010-1, third edition, based on the specification stated in Chapter 13 (Technical Data). UL File No.: E228586
Open-type Measuring Equipment
2UD1
For further information see UL database on the internet: http://ul.com. Chose Online Certifications Directory and insert E228586 under UL File Number.
E50417-H1040-C522-A4, Edition 03.2018
7SICAM Q100, 7KG95xx, Device Manual
8 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018

Open Source Software

The product contains, among other things, Open Source Software developed by third parties. The Open Source Software used in the product and the license agreements concerning this software can be found in the Readme_OSS.
These Open Source Software files are protected by copyright. Your compliance with those license conditions will entitle you to use the Open Source Software as foreseen in the relevant license. In the event of conflicts between Siemens license conditions and the Open Source Software license conditions, the Open Source Soft­ware conditions shall prevail with respect to the Open Source Software portions of the software.
The Open Source Software is licensed royalty-free. Insofar as the applicable Open Source Software License Conditions provide for it you can order the source code of the Open Source Software from your Siemens sales contact - against payment of the shipping and handling charges - for a period of at least 3 years since purchase of the Product. We are liable for the Product including the Open Source Software contained in it pursuant to the license conditions applicable to the Product. Any liability for the Open Source Software beyond the program flow intended for the Product is explicitly excluded. Furthermore any liability for defects resulting from modifi­cations to the Open Source Software by you or third parties is excluded. We do not provide any technical sup­port for the Product if it has been modified.
NOTE
To read the Readme_OSS file, a PDF viewer must be installed on the computer.
E50417-H1040-C522-A4, Edition 03.2018
9SICAM Q100, 7KG95xx, Device Manual
10 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018

Contents

Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Open Source Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1 User Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2 Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
2.1 Device Versions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
2.2 Ordering Information, Scope of Delivery and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3 Device Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
3.1 Mechanical Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.2 Display and Softkeys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
4 Measured Quantities and Recording. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.1 Power Quality Measuring System and Recording System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.1.1 Measuring System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.1.2 Flicker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.1.3 Transients . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
4.1.4 Mains Signalling Voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
4.1.5 Rapid Voltage Change . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
4.1.6 Harmonic Power and Harmonic Angles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
4.1.7 Recording of Measured Quantities and Events. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
4.2 Measured Quantities. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
4.2.1 Measured Quantities Depending on the Connection Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
4.2.2 Data Availability of Measured Quantities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
4.2.3 Recording and Evaluation of Measured Quantities. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
4.3 Display of Measured Quantities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
4.3.1 Measured Quantities and Operational Measurement Uncertainty acc. to IEC 62586-1 Product Stand­ard, Class A, and Standards IEC 61000-4-30, Ed. 3 and IEC 61000-4-7 and IEC 61000-4-15 . . . 75
4.3.2 Measured Quantities and Operational Measurement Accuracy acc. to IEC 61557-12. . . . . . . . . . 77
4.3.3 Accuracy of the Frequency Measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
5 Energy Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
5.1 Load-Profile Determination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
5.1.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
5.1.2 Methods of Load-Profile Determination. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
5.1.3 Historical Load-Profile Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
5.1.4 Current Load-Profile Data at the Communication Interfaces and in the User Interface . . . . . . . . . 84
5.1.5 Synchronization of the Load Profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
5.2 Tariffs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
6 Getting Started. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
6.1 Unpacking, Inspecting the Delivery, Installing, and Changing the Battery . . . . . . . . . . . . . . . . . . . . . . 90
E50417-H1040-C522-A4, Edition 03.2018
11SICAM Q100, 7KG95xx, Device Manual
6.2 Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
6.2.1 General Assembly Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
6.2.2 Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
6.3 Electrical Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
6.3.1 Safety Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
6.3.2 Electrical Connection of SICAM Q100 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
6.4 System Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
6.5 Access Rights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
6.6 Meaning of the LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
6.7 Commissioning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
6.7.1 Initial Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
6.7.2 Changes During Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
6.7.3 Starting the Device with the Default IP Address. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
7 Connection Principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
7.1 Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
7.2 Communication Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
7.2.1 Ethernet Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
7.2.2 RS485 Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
7.3 Connection Types and Connection Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
7.3.1 Using SICAM Q100 in the Power Systems IT, TT, and TN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
7.3.2 Examples – Standard Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
7.3.3 Example - Special Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
8 Operation at Use of a PC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
8.1 General Usage Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
8.2 Start and Design of the User Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
8.2.1 Initial Start of the Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
8.2.2 Enabling JavaScript . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
8.2.3 Changing the Buffer Mechanism . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
8.2.4 Changing the Compatibility Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
8.2.5 Changing the Security Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
8.2.6 Number of Connections via HTML . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
8.2.7 Layout of the User Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
8.2.8 Starting the User Interface during Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
8.3 Configuration of the Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
8.3.1 Device Configuration Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
8.3.2 Access to the Passive Set of Parameters by Multiple Users . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
8.3.3 Setting the Operational Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
8.3.4 HMI. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
8.3.5 Energy Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
8.3.6 Recording and Reporting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
8.3.7 Setting Administrative Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185
12 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
8.4 Value View and Evaluation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 222
8.4.1 Process Connections and Automation Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 222
8.4.2 Evaluation and Data Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 233
8.5 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 249
8.5.1 Firmware Upload. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250
8.5.2 Formatting the SD Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 252
8.5.3 Presets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 253
8.5.4 Message Logs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257
8.5.5 Evaluation and Data Management – Transient Detection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 262
8.5.6 Diagnosis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 263
8.6 AC Calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 266
8.7 Example of a Parameterization and Measured Value Evaluation. . . . . . . . . . . . . . . . . . . . . . . . . . . . 267
8.7.1 Task Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 267
8.7.2 Initial Situation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 267
8.7.3 Parameterization as Defined by the Task . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 269
8.7.4 Performing the Measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 274
8.8 Flowchart of Modbus RTU Master and Modbus Gateway Parameterization . . . . . . . . . . . . . . . . . . . 275
9 Operation at Use of the Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 277
9.1 General Operating Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 278
9.2 Starting Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 280
9.3 Display Content . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 281
9.4 Parameterization. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 283
9.4.1 Menu Tree of the Main Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 283
9.4.2 Measured Quantities Submenus. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 284
9.4.3 Submenus for Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 286
9.4.4 Menu Tree of the Settings Submenu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 287
9.4.5 User-defined Screens Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 299
10 Time Synchronization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 301
10.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 302
10.2 Internal Time Keeping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 302
10.2.1 Time Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 302
10.2.2 Status Bits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 302
10.3 External Time Synchronization per NTP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 303
10.4 External Time Synchronization via Fieldbus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 304
10.5 Internal Time Synchronization via RTC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 304
11 Maintenance, Storage, Transport. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 305
11.1 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306
11.2 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306
11.3 Transport . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306
12 Failures and LED Indications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307
12.1 General Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308
E50417-H1040-C522-A4, Edition 03.2018
13SICAM Q100, 7KG95xx, Device Manual
12.2 Commissioning during Failures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 309
12.2.1 Automatic Start of the Boot Loader . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 309
12.2.2 Manual Start of the Boot Loader . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310
12.3 Indications Signaled by LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 312
12.4 Troubleshooting and Repair. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 317
13 Technical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 319
13.1 General Device Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 320
13.1.1 Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 320
13.1.2 Inputs and Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 321
13.1.3 Communication Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 323
13.1.4 Environmental Conditions and Climatic Stress Tests. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 325
13.1.5 General Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 326
13.2 Test Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 327
13.2.1 Electrical Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 327
13.2.2 Mechanical Stress Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 329
13.2.3 Safety Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 329
13.3 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 330
14 Operational Indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 333
15 Operating Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 337
15.1 Process Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 338
15.1.1 AC Measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 338
15.1.2 Binary Inputs U1/U2 and U3/U2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 339
15.1.3 Binary Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 341
15.1.4 LEDs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 343
15.2 Automation Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 344
15.2.1 Limit Violation 1-8 and 9-16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 345
15.2.2 Group Indications 1-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 346
15.3 HMI. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 347
15.3.1 Display Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 347
15.3.2 User-Defined Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 347
15.4 Energy Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 350
15.4.1 Load Profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 350
15.4.2 Tariffs (TOU) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 350
15.5 Recording and Reporting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 351
15.5.1 Event Recorders. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 351
15.5.2 Trigger Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 352
15.5.3 Recorder Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 353
15.5.4 Mains Signalling Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 354
15.5.5 Memory Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 354
15.5.6 Report Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 355
15.5.7 Recording Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 356
15.5.8 Transient Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 356
14 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
15.6 Administrative . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 357
15.6.1 Time Synchronization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 357
15.6.2 Ethernet Communication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 358
15.6.3 Communication Serial. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 360
15.6.4 Modbus Slave Devices 1 – 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 362
15.6.5 SICAM Subdevices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 366
15.6.6 Device and Language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 369
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 371
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 375
E50417-H1040-C522-A4, Edition 03.2018
15SICAM Q100, 7KG95xx, Device Manual
16 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
1 User Information
Application
The SICAM Q100 is a multifunctional device for the detection, processing, and evaluation of measured quan­tities and events according to IEC 61000-4-30, class A, power quality (PQ) standard. The energy management functions also allow determining load profiles and setting up to 6 tariffs. The device is used on all voltage levels of power supply systems. SICAM Q100 is used in 1-phase systems and in 3-wire and 4-wire systems (with neu­tral conductor). The device is mainly used by power utilities but also in other industrial and commercial sectors.
In addition to the measuring function, SICAM Q100 features various recorders (for example, measured value recorders) to record the measured quantities and the load profile in programmable time intervals. Long-term data and events are analyzed and output as report according to power quality standards, for example EN
50160.
The input circuits for voltage measurement are galvanically isolated and can be used in IT, TT, and, TN networks. To ensure galvanic separation for current measurements, the lines connected to the current measuring inputs are galvanically separated from the current transformers.
The measurements are obtained from the alternating quantities of current and voltage supplied to the AC inputs. When no external voltage and current transformers are used, the device can process rated input alternating voltages of up to V
The integrated web server can be used to set the parameters and display the measured values on HTML pages from the connected computer. With the internal graphic display, a limited parameterization via softkeys can be carried out on the front panel and measured values can be output via the display.
= 230 V (110 V for UL condition) and rated input alternating currents up to 5 A.
P-N

1 User Information

To communicate with the systems control and other process automation equipment and to transmit operational measured values, metered values, indications, load profiles, etc., the device features an Ethernet interface and an RS485 interface.
Measured quantities:
Alternating voltage and alternating current
Unbalanced of alternating voltage and alternating current
Active, reactive, and apparent power
Active, reactive, and apparent energy
Power frequency
Phase angle
Power factor and active power factor
THDS (Subgroup Total Harmonic Distortion) of alternating voltage and alternating current
Harmonics and interharmonics of alternating voltage and alternating current
Flicker acc. to IEC 61000-4-15
Transients
Mains signalling voltage (MSV)
The uncertainty of operational measurements of the measured quantities is defined as per IEC 62586-1 product standard, class A (leading standard), the IEC 61000-4-30 power quality standard, and the IEC 62586-1, Ed. 1 standard.
For detailed information on measured quantities and measured values, see Chapter 4.2 and the technical data in Chapter 13.1.
E50417-H1040-C522-A4, Edition 03.2018
17SICAM Q100, 7KG95xx, Device Manual
1 User Information
Functionality of the Recorders
The recorders are capable of recording measured quantities, events, and load profiles in parameterizable time intervals. The following recorder types are used:
Measurement recorder: recording of PQ measured quantities acc. to IEC 61000-4-30 (for example, frequency, voltage magnitude, etc.) and non-PQ measured quantities (for example, currents, power, etc.) over parameterized periods, for example, 10-second frequency, aggregation of voltage, current, power etc.
Trend recorder: long-term recording and monitoring of the voltage change history over a parameterized period of time in programmable tolerance ranges; 1/2 cycle RMS values
Fault recorder: recording of sampled values of voltage and current using programmable triggers, maximum 256 samples per cycle
Event recorder: recording of maximum 256 frequency events and voltage-unbalance events each, as well as voltage events of which the maximum counter depends on the memory configuration
Mains signalling voltage recorder: recording of mains signalling voltage on the supply voltage.
The device features a 2-GB memory for storing the recorder data.
Energy Management
As part of the energy management, SICAM Q100 records load profiles according to the Fixed Block and Rolling Block method for all power quantities. Additionally, it is possible to calculate up to 6 tariffs (TOU = Time of Use). The synchronization is made with external or internal triggers.
Communication
SICAM Q100 has an Ethernet interface and an electric RS485 interface.
Ethernet supports the device parameterization, transmission of measured data, metered values, load profiles, and indications/events and the time synchronization with NTP. The communication protocols used are HTTP, Modbus TCP, and IEC 61850 server.
The RS485 interface supports the transmission of measured data, metered values, load profiles, and indica­tions and the time synchronization. The communication protocol is Modbus RTU.
The integrated Ethernet switch in the device allows cascading further network components (SICAM subdevices) via a Y cable and integrating them in an existing network with IEC 61850 or another Ethernet pro­tocol.
Time Synchronization
During operation SICAM Q100 needs the date and time for all time-relevant processes. This ensures that a common time basis exists when communicating with peripheral devices and enables time stamping of the process data. The following types of time synchronization can be executed:
External time synchronization via Ethernet NTP (preferred)
External time synchronization via fieldbus using the Modbus RTU communication protocol
Internal time synchronization via RTC (if external time synchronization is not available)
Parameterization
Parameters are set using an internal Web browser with HTML pages from the connected computer. Internet Explorer 6 (or higher) is required for this purpose. Devices featuring a display offer a limited parameterization function using the front softkeys.
18 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
2 Overview
2.1 Device Versions 20
2.2 Ordering Information, Scope of Delivery and Accessories 22

2 Overview

E50417-H1040-C522-A4, Edition 03.2018
19SICAM Q100, 7KG95xx, Device Manual
2 Overview

2.1 Device Versions

2.1 Device Versions
SICAM Q100 is a multifunctional device for the detection, calculation, recording, evaluation, display, and trans­mission of measured electrical quantities with the following properties:
Consistent Device Properties
All devices consistently feature the following properties:
Device type:
Power Monitoring Device and Class A Power Quality Recorder with measured value recorders and
internal 2 GB memory
Panel flush mounting device with display for measured values and parameterizationPlastic case 96 mm x 96 mm x 100 mm (W x H x D)Web server for parameterization, visualization, and data managementGalvanically isolated voltage measuring inputsTransmitting measured values using communication protocols
Input and output circuits:
4 inputs for alternating voltage measurements4 inputs for alternating current measurements2 binary inputs for example, for synchronization pulses of the load profile or external triggers2 binary outputs
Measurement acc. to standard IEC 61000-4-30, class A
Measured quantities
Voltage VCurrent ISystem frequency f (fundamental)Active power P (accuracy class 0.2S; ANSI C12.20 current class 2 and current class 10)Reactive power QApparent power SEnergy measurements WActive power factor cos Measurement up to the 63th harmonics/49th interharmonics of voltage and currentFlicker acc. to IEC 61000-4-15Mains signalling voltageHarmonics phase angles, harmonic power
Measurements for evaluation and supervision
Minimum/mean/maximum valuesEvent detection, for example voltage dips, voltage swells, voltage interruptionsLimit violationsEnergy management (load profiles and tariffs)Transient detection
Data export
CSV dataPQDIF data
IEEE1159.3: PQDIF for PQ records (events, measurements, records)
COMTRADE data
IEC 60255-24/IEEE Std C37.111: Measuring relays and protection equipment – Part 24: Common
format for transient data exchange (COMTRADE for power systems) for fault records
20 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
Variants
SICAM Q100
, Display Side
SICAM Q100
with RS485 Interface, Terminal Side
2 Overview
2.1 Device Versions
Internal Ethernet switch
Certificates
CE certificationUL certification
Evaluations
Output of power quality reports
SICAM Q100 is available in different variants:
Communication via Ethernet
Only Modbus TCP protocolModbus TCP protocol or IEC 61850 server protocol
Serial communication
Without RS485 interfaceWith RS485 interface:
- Modbus RTUslave protocol
- Modbus RTU master protocol and gateway function
Degree of protection of front
IP40
SICAM Q100
Figure 2-1 SICAM Q100
E50417-H1040-C522-A4, Edition 03.2018
21SICAM Q100, 7KG95xx, Device Manual
2 Overview
Measurings, Monitoring, Recording and Power Quality (PQ) Functions
Measurements acc. to standard IEC 61000-4-30, class A Measured quantities: V, I, f, P, Q, S, W, cos phi, Flicker
Measurement min/max/mean values Measur em en t s t ill 63th harmonics (current, v olt age) Limit violations Energy management: Load profiles and tariffs Transient det ec t ion
Recorder for Power Quality measured values Event recording, visualisation Online PQ reporting e.g. acc. to EN 50160
Description
Power Monitoring Device and Power Quality Recorder, Class A
Order No. / MLFB
Device ty pe
Dimensions 96 mm x 96 mm x 100 mm Panel mounted instrument with graphical display 4 Inputs for AC voltage measurements 4 Inputs for AC current measurements 2 Binary inputs 2 Binary outputs Web server for parameterization , visualization and data management Ethernet switch Internal memory 2 GB
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1AAA
-
5-97KG
Degree of Pr ot ec t ion of Fr on t
IP40
SICAM Q100
CE Certification and UL C ertificat ion
Serial I nt er f ace and Comm uni cat ion Prot ocol
Without RS485 – Modbus RTU slave, and
Modbus RTU master and gateway function
Ethernet Interface and Comm uni c at ion Prot ocol, RJ45
Modbus TCP IEC 61850 server and Modbus TCP
A0
0 3
1
0 2
01

2.2 Ordering Information, Scope of Delivery and Accessories

2.2 Ordering Information, Scope of Delivery and Accessories
Ordering Information
Use the following ordering code to order SICAM Q100 devices:
Figure 2-2 Ordering Code for SICAM Q100
22 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
Scope of Delivery
The delivery comprises the following components depending on the ordering code:
SICAM Q100 according to ordering code (see Figure 2-2)
Battery (insulated in the battery compartment of the device)
Mounting element
Product Information
Accessories
You can order the following accessories:
Device Manual E50417-H1040-C522 (download available at http://www.siemens.com/powerquality)
RS485 bus terminating plug 220 in a 9-pin D-sub connector plug: 7XV5103-5AA00
Connectors for alternating voltage inputs
2 Overview
2.2 Ordering Information, Scope of Delivery and Accessories
Order via:
Phoenix Contact GmbH & Co. KG
Item number: 1700734
Product name: GMSTB 2,5 HCV/ 4-ST-7,62 BK TS
Minimum order quantity: 50 pieces
Various cables as listed in the following tables:
Table 2-1 RS485-Y Bus Cable (2-Wire, Shielded, with 9-Pin D-sub Connector Plugs)
Cable Length Order No.
1 m 7XV5103-0AA01
3 m 7XV5103-0AA03
5 m 7XV5103-0AA05
10 m 7XV5103-0AA10
Table 2-2 RS485 Bus Extension Cable (2-Wire, Shielded, with 9-Pin D-sub Connector Plugs)
Cable Length Order No.
10 m 7XV5103-1AA10
20 m 7XV5103-1AA20
30 m 7XV5103-1AA30
40 m 7XV5103-1AA40
50 m 7XV5103-1AA50
E50417-H1040-C522-A4, Edition 03.2018
23SICAM Q100, 7KG95xx, Device Manual
2 Overview
2.2 Ordering Information, Scope of Delivery and Accessories
Table 2-3 Ethernet Patch Cable (Double Shielded (SFPT), LAN Connector Plugs on Both Sides)
Cable Length Order No.
0.5 m 7KE6000-8G-D00-0AA5
1.0 m 7KE6000-8G-D00-1AA0
2.0 m 7KE6000-8G-D00-2AA0
3.0 m 7KE6000-8G-D00-3AA0
5.0 m 7KE6000-8G-D00-5AA0
10.0 m 7KE6000-8G-D01-0AA0
15.0 m 7KE6000-8G-D01-5AA0
20.0 m 7KE6000-8G-D02-0AA0
24 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
3 Device Design
3.1 Mechanical Design 26
3.2 Display and Softkeys 27

3 Device Design

E50417-H1040-C522-A4, Edition 03.2018
25SICAM Q100, 7KG95xx, Device Manual
3 Device Design
RJ45 with
4LEDs
2LEDs
Cover of battery compartment
Terminal block for
Default IP address Default subnet mask
LED RUN
LED ERROR
LED H1
LED H2
Softkeys
F1 to F4
Terminal blocks for
measurements (voltage, current)
power supply
Binary inputs
Display
Terminal side
Display side
D sub (RS485)
Binary outputs

3.1 Mechanical Design

3.1 Mechanical Design
The device is designed for panel flush mounting. The electrical modules are installed in a plastic case with the dimensions 96 mm x 96 mm x 100 mm (W x H x D).
The display side of the device contains the display, 4 softkeys located below and 4 LEDs of which the H1, H2, and ERROR LEDs can be parameterized. The ERROR LED can only be parameterized for error messages.
The device top side holds the RJ45 Ethernet plug connector with 2 LEDs. 4 additional LEDs are identical to the LEDs on the display side. At the cover of the battery compartment there is a labeling strip for the configurable LEDs H1/H2 and a battery symbol that indicates the polarity. The label is also located on the top side and provides among other information the most important rated data of the device. A lithium battery is located under the removable cover of the battery compartment.
SICAM Q100 devices can also contain a D-sub connector plug as RS485 interface (see Figure 3-1) as shown in the ordering information (see Chapter 2.2).
26 SICAM Q100, 7KG95xx, Device Manual
Figure 3-1 Layout of SICAM Q100
E50417-H1040-C522-A4, Edition 03.2018
3.2 Display and Softkeys
Title
Display area
Softkey functions
Softkeys F1 to F4
Display
The layout of the display is shown in the following figure.
3 Device Design

3.2 Display and Softkeys

Softkeys
Figure 3-2 Display and Softkeys
The top line (title) shows the name of the current display in the display area. The display area below shows parameter settings, measured values, and graphic pictures.
The bottom line shows the 4 current functions of the softkeys below the display used to set the parameters.
The 4 softkeys on the display side are used to make the desired entries at the device.
To call and activate the IP address, press softkey F4 (for > 3 s, see Figure 3-2) on the right during system startup if necessary. The IP address and the standard subnet mask are imprinted on the side panel of the device (see Figure 3-1).
Chapter 9 gives a detailed description of the softkey functions.
E50417-H1040-C522-A4, Edition 03.2018
27SICAM Q100, 7KG95xx, Device Manual
3 Device Design
3.2 Display and Softkeys
28 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
4 Measured Quantities and Recording
4.1 Power Quality Measuring System and Recording System 30
4.2 Measured Quantities 39
4.3 Display of Measured Quantities 75

4 Measured Quantities and Recording

E50417-H1040-C522-A4, Edition 03.2018
29SICAM Q100, 7KG95xx, Device Manual
4 Measured Quantities and Recording

4.1 Power Quality Measuring System and Recording System

4.1 Power Quality Measuring System and Recording System

4.1.1 Measuring System

SICAM Q100 devices measure the power quality according to IEC 61000-4-30 in 1-phase or multi-phase distribution systems.
The basic measuring interval for determining the values for mains voltage, harmonics of mains voltage, and mains voltage unbalance is 10 cycles for 50 Hz distribution systems or 12 cycles for 60 Hz distribution systems.
A overview of the measured quantities demanded in according to IEC 61000-4-30, their measurement uncertainty and measurement ranges is represented in the Chapter 4.3.1.

4.1.2 Flicker

The flicker measurement is performed according to IEC 61000-4-15.
The short-term flicker value Pst and long-term flicker value Plt are determined for phase-to-ground voltages and delta voltages. The flicker measurement is performed on all 3 voltage channels.
Flickers appear with a frequency from 0.005 to 35 Hz. The instantaneous flicker value is displayed in perceptibility units P.
SICAM Q100 measures the following flicker types:
Short-term flicker value Pst, determined over 10 min (short-term flicker), fixed
Long-term flicker value Plt, over 2 h (12 Pst values), fixed
Perceptibility Pinst
30 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018