Siemens Sicam P855 7KG85 Series, Sicam P850 7KG85 Series Device Manual

Power Monitoring Device and Power Quality Recorder
SICAM P850/P855 7KG85xx
V2.60
Device Manual
User Information 1 Overview 2 Device Design 3 Measurands and Recording 4 Getting Started 5 Connection Principle 6 Operation at Use of a PC 7 Operation at Use of the Display 8 Time Synchronization 9 Calibration 10 Maintenance, Storage, Transport 11
E50417-H1040-C482-A6
Failures and LED Indications 12 Technical Data 13 Operational Indications 14 Operating Parameters 15
Glossary Index
Disclaimer of Liability
Copyright
This document has been subjected to rigorous technical review before being published. It is revised at regular intervals, and any modifications and amendments are included in the subsequent issues. The content of this document has been compiled for information purposes only. Although Siemens AG has made best efforts to keep the document as precise and up-to-date as possible, Siemens AG shall not assume any liability for defects and damage which result through use of the information contained herein.
This content does not form part of a contract or of business relations; nor does it change these. All obligations of Siemens AG are stated in the relevant contractual agreements.
Siemens AG reserves the right to revise this document from time to time.
Document version: E50417-H1040-C482-A6.02 Edition 10.2018 Version of the product described: V2.60
Copyright Siemens AG 2018. All rights reserved.
The disclosure, duplication, distribution and editing of this document, or utilization and communication of the content are not permitted, unless authorized in writing. All rights, including rights created by patent grant or registration of a utility model or a design, are reserved.
Registered Trademarks
SIPROTEC
TM
and SICAMTM are registered trademarks of
SIEMENS AG. An unauthorized use is illegal.
All other designations in this document can be trademarks whose use by third parties for their own purposes can infringe the rights of the owner.

Preface

Purpose of this Manual
This manual describes the application, functions, installation, commissioning, and operation of the Power Monitoring Device and Power Quality Recorder SICAM P850/P855 7KG85xx.
Target Group
This manual is intended for project engineers, commissioning and operating personnel in electrical systems and power plants.
Scope of Vali dity of this Manual
This manual is valid for the Power Monitoring Device and Power Quality Recorder SICAM P850/P855 7KG85xx.
Further Support
For any questions concerning your system, please contact your Siemens representative.
The Siemens Customer Support Center provides around-the-clock support.
Phone: +49 (180) 524-7000
Fax: +49 (180) 524-2471
Internet: www.siemens.com/powerquality
e-mail: support.energy@siemens.com
Training Courses
If you are interested in our current training program, please contact our training center:
Siemens AG Siemens Power Academy TD
Humboldtstr. 59 D-90459 Nuremberg
Tel.: +49 (911) 433-7415
Fax: +49 (911) 433-5482
Internet: http://www.siemens.com/poweracademy
e-mail: poweracademy@siemens.com
E50417-H1040-C482-A6, Edition 10.2018
3SICAM P850/P855, 7KG85xx, Device Manual
Notes On Safety
This manual is not a complete index of all safety measures required for operation of the equipment (module, device). However, it comprises important information that must be noted for purposes of personal safety, as well as in order to avoid material damage. Information is highlighted and illustrated as follows according to the
degree of danger.
DANGER
DANGER means that death or severe injury will occur if the appropriate safety measures are not taken.
Follow all advice instructions to prevent death or severe injury.
WARNING
WARNING means that death or severe injury can occur if the appropriate safety measures are not taken.
Follow all advice instructions to prevent death or severe injury.
CAUTION
CAUTION means that minor or moderate injury can occur if the appropriate safety measures are not taken.
Follow all advice instructions to prevent minor injury.
NOTICE
NOTICE means that damage to property can occur if the appropriate safety measures are not taken.
Follow all advice instructions to prevent damage to property.
NOTE
is important information about the product, the handling of the product, or the part of the documentation in question to which special attention must be paid.
4 SICAM P850/P855, 7KG85xx, Device Manual
E50417-H1040-C482-A6, Edition 10.2018
Personnel Qualified in Electrical Engineering
Only qualified electrical engineering personnel may commission and operate the equipment (module, device) described in this document. Qualified electrical engineering personnel in the sense of this manual are people who can demonstrate technical qualifications as electrical technicians. These persons may commission, iso­late, ground, and label devices, systems and circuits according to the standards of safety engineering.
Use as Prescribed
The equipment (device, module) must not be used for any other purposes than those described in the Catalog and the Technical Description. If it is used together with third-party devices and components, these must be recommended or approved by Siemens.
If the device is not used in accordance with the Product Information and this manual, the scheduled protection is impaired.
Problem-free and safe operation of the product depends on the following:
Proper transport
Proper storage, setup, and installation
Proper operation and maintenance
When electrical equipment is operated, hazardous voltages are inevitably present in certain parts. If proper ac­tion is not taken, death, severe injury, or property damage can result.
The equipment must be grounded at the grounding terminal before any connections are made.
All circuit components connected to the power supply may be subject to dangerous voltage.
Hazardous voltages may be present in equipment even after the supply voltage has been disconnected (capacitors can still be charged).
Equipment with exposed current transformer circuits must not be operated. Prior to disconnecting the equipment, ensure that the current transformer circuits are short-circuited.
The limit values stated in the document may not be exceeded. This must also be considered during testing and commissioning.
E50417-H1040-C482-A6, Edition 10.2018
5SICAM P850/P855, 7KG85xx, Device Manual
Used Symbols
No. Symbol Description
1 Direct current
IEC 60417-5031
2 Alternating current
IEC 60417-5032
3 Direct and alternating current
IEC 60417-5033
4 Three-phase alternating current
5 Earth (ground) terminal
IEC 60417-5017
6 Protective conductor terminal
IEC 60417-5019
7 Caution, risk of electric shock
8 Caution, risk of danger
ISO 7000-0434
6 SICAM P850/P855, 7KG85xx, Device Manual
E50417-H1040-C482-A6, Edition 10.2018
Statement of Conformity
This product complies with the directive of the Council of the European Communities on the approximation of the laws of the Member States relating to electromagnetic compatibility (EMC Council Directive 2004/108/EC - valid until April, 19th of 2016, Low Voltage Directive 2014/35/EU ­valid from April, 20th of 2016) and concerning electrical equipment for use within specified voltage limits (Low-voltage Directive 2006/95/EC - valid until April, 19th of 2016, Low Voltage Directive 2014/ 35/EU - valid from April, 20th of 2016).
This conformity has been established by means of tests conducted by Siemens AG according to the Council Directive in agreement with the generic standards EN 61000-6-2 and EN 61000-6-4 for the EMC directives, and with the standard EN 61010-1 for the low-voltage directive.
The device has been designed and produced for industrial use.
The product conforms to the standard IEC 61557-12.
Further Standards
This product is UL-certified to Standard UL 61010-1, third edition, based on the specification stated in Chapter 13 (Technical Data). UL File No.: E228586
Open-type Measuring Equipment
2UD1
For further information see UL database on the internet: http://ul.com. Chose Online Certifications Directory and insert E228586 under UL File Number.
E50417-H1040-C482-A6, Edition 10.2018
7SICAM P850/P855, 7KG85xx, Device Manual
8 SICAM P850/P855, 7KG85xx, Device Manual
E50417-H1040-C482-A6, Edition 10.2018

Open Source Software

The product contains, among other things, Open Source Software developed by third parties. The Open Source Software used in the product and the license agreements concerning this software can be found in the Readme_OSS.
These Open Source Software files are protected by copyright. Your compliance with those license conditions will entitle you to use the Open Source Software as foreseen in the relevant license. In the event of conflicts between Siemens license conditions and the Open Source Software license conditions, the Open Source Soft­ware conditions shall prevail with respect to the Open Source Software portions of the software.
The Open Source Software is licensed royalty-free. Insofar as the applicable Open Source Software License Conditions provide for it you can order the source code of the Open Source Software from your Siemens sales contact - against payment of the shipping and handling charges - for a period of at least 3 years since purchase of the Product. We are liable for the Product including the Open Source Software contained in it pursuant to the license conditions applicable to the Product. Any liability for the Open Source Software beyond the program flow intended for the Product is explicitly excluded. Furthermore any liability for defects resulting from modifi­cations to the Open Source Software by you or third parties is excluded. We do not provide any technical sup­port for the Product if it has been modified.
E50417-H1040-C482-A6, Edition 10.2018
9SICAM P850/P855, 7KG85xx, Device Manual
10 SICAM P850/P855, 7KG85xx, Device Manual
E50417-H1040-C482-A6, Edition 10.2018

Contents

Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Open Source Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1 User Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2 Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2.1 Device Versions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2.2 Ordering Information, Scope of Delivery and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
3 Device Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
3.1 Mechanical Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.2 Display and Softkeys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
3.3 Electrical Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
4 Measurands and Recording . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.1 Measuring and Recording System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.1.1 Functioning of the Measuring System according to IEC 61000-4-30 . . . . . . . . . . . . . . . . . . . . . . . 30
4.1.2 Recording of Measurands and Events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
4.2 Measurands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
4.2.1 Measurands in 1-phase Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
4.2.2 Measurands in 3-wire and 4-wire Networks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
4.2.3 Measurands Depending on the Connection Type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
4.2.4 Data Availability. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
4.3 Display of Measurands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
4.3.1 Measurands and Operational Measurement Uncertainty acc. to IEC 62586-1 Product Standard,
Class S, and Standards IEC 61000-4-30, Ed. 2 and IEC 61000-4-7 and IEC 61000-4-15. . . . . . . 65
4.3.2 Measurands and Operational Measurement Uncertainty acc. to IEC 61557-12. . . . . . . . . . . . . . . 66
4.3.3 Accuracy of the Frequency Measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
5 Getting Started. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
5.1 Unpacking, Inspecting the Delivery, and Installing the Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
5.2 Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
5.2.1 General Assembly Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
5.2.2 Environmental Protection Hints. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
5.2.3 Assembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
5.3 Electrical Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
5.3.1 Safety Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
5.3.2 Electrical Connection of SICAM P850/P855 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
5.4 System Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
5.5 Access Rights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
E50417-H1040-C482-A6, Edition 10.2018
11SICAM P850/P855, 7KG85xx, Device Manual
5.6 Meaning of the LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
5.7 Commissioning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
5.7.1 Initial Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
5.7.2 Changes During Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
5.7.3 Starting the Device with the Default IP Address. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
6 Connection Principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
6.1 Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
6.2 Communication Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
6.2.1 Ethernet Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
6.2.2 RS485 Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
6.3 Connection Types and Connection Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
6.3.1 Using SICAM P850/P855 in the Power Systems IT, TT, and TN. . . . . . . . . . . . . . . . . . . . . . . . . . 89
6.3.2 Connection Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
6.3.3 Examples - Standard Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
6.3.4 Example - Special Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
7 Operation at Use of a PC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
7.1 General Usage Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
7.2 Start and Design of the User Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
7.2.1 Initial Start of the Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
7.2.2 Enabling JavaScript . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
7.2.3 Changing the Buffer Mechanism . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
7.2.4 Changing the Compatibility Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
7.2.5 Changing the Security Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
7.2.6 Number of Connections via HTML . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
7.2.7 Layout of the User Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
7.2.8 Starting the User Interface during Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
7.3 Configuration of the Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
7.3.1 Device Configuration Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
7.3.2 Access to the Passive Set of Parameters by Multiple Users . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
7.3.3 Setting the Operational Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
7.3.4 HMI. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
7.3.5 Recording and Reporting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
7.3.6 Setting Administrative Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
7.4 Value View and Evaluation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 176
7.4.1 Process Connections and Automation Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 176
7.4.2 Evaluation and Data Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
7.5 Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
7.5.1 Firmware Upload . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192
7.5.2 Formatting the SD Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194
7.5.3 AC Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
7.5.4 Presets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
7.5.5 Message Logs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
7.5.6 Diagnosis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201
12 SICAM P850/P855, 7KG85xx, Device Manual
E50417-H1040-C482-A6, Edition 10.2018
7.6 Example of a Parameterization and Measured Value Evaluation for SICAM P855 . . . . . . . . . . . . . . 204
7.6.1 Task Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 204
7.6.2 Initial Situation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 204
7.6.3 Parameterization as Defined by the Task . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 206
7.6.4 Performing the Measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211
8 Operation at Use of the Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
8.1 General Operating Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214
8.2 Starting Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 216
8.3 Display Content . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217
8.4 Parameterization. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219
8.4.1 Menu Tree of the Main Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219
8.4.2 Measurands Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220
8.4.3 Submenus for Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 222
8.4.4 Menu Tree of the Settings Submenu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
8.4.5 User-defined Screens Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 234
9 Time Synchronization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235
9.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 236
9.2 Internal Time Keeping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 236
9.2.1 Time Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 236
9.2.2 Status Bits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 236
9.3 External Time Synchronization per NTP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 237
9.4 External Time Synchronization via Fieldbus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 238
9.5 Internal Time Synchronization via RTC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 238
10 Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239
10.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 240
10.2 Calibrating the Alternating Voltage Measuring Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241
10.3 Calibrating the Alternating Current Measuring Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 244
10.4 Calibrating the Measuring Voltage Input of Neutral Conductor VN . . . . . . . . . . . . . . . . . . . . . . . . . . 247
10.5 Calibrating the Phase Angle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250
11 Maintenance, Storage, Transport. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 253
11.1 7KG85xxMaintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 254
11.2 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 254
11.3 Transport . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 254
12 Failures and LED Indications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255
12.1 General Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 256
12.2 Commissioning during Failures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257
12.2.1 Automatic Start of the Boot Loader. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257
12.2.2 Manual Start of the Boot Loader . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 258
12.3 Indications Signaled by LEDs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259
12.4 Troubleshooting and Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 264
E50417-H1040-C482-A6, Edition 10.2018
13SICAM P850/P855, 7KG85xx, Device Manual
13 Technical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 265
13.1 General Device Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 266
13.1.1 Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 266
13.1.2 Inputs and Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 267
13.1.3 Communication Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 269
13.1.4 Environmental Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 271
13.1.5 General Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 271
13.2 Test Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 272
13.2.1 Electrical Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 272
13.2.2 Mechanical Stress Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 274
13.2.3 Climatic Stress Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 275
13.2.4 Safety Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 275
13.3 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 276
14 Operational Indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 281
15 Operating Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 285
15.1 Process Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 286
15.1.1 AC Measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 286
15.1.2 Binary Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 287
15.1.3 LEDs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 289
15.2 Automation Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 290
15.2.1 Limit Violation 1-8 and 9-16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 290
15.2.2 Group Indications 1-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 291
15.3 HMI. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 292
15.3.1 Display Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 292
15.3.2 User Defined Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 293
15.4 Recording and Reporting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 294
15.4.1 Event Recorders. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 294
15.4.2 Trigger Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 294
15.4.3 Recorder Management. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 296
15.4.4 Memory Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 298
15.4.5 Report Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 299
15.4.6 Recording Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300
15.5 Administrative. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 301
15.5.1 Time Synchronization. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 301
15.5.2 Ethernet Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 302
15.5.3 OPC UA PubSub (MQTT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 303
15.5.4 Communication Serial . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 304
15.5.5 Device and Language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306
Glossary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307
Index. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 311
14 SICAM P850/P855, 7KG85xx, Device Manual
E50417-H1040-C482-A6, Edition 10.2018

1 User Information

Application
The multifunctional SICAM P850/P855 devices record and process measurands and events according to IEC 61000-4-30 Power Quality (PQ) standard. The devices are used on all voltage levels of power-supply systems. SICAM P850/P855 devices are used in 1-phase systems, 3-phase systems, and 4-phase systems (with neutral conductor). The devices are used primarily in power utilities but also in other industrial and commercial applications.
In addition to the measuring function, SICAM P850/P855 features various recorders (average, min and max values) to record the measurements in programmable time intervals. Waveform capture is available in both devices. For recording functionality the devices feature a 2-GB memory for data storage.
In SICAM P855 additionally, long-term data for power quality evaluation and events are analyzed and output as report according to power quality standards, for example, EN 50160 and flexible data export in PQDIF, COMTRADE or CSV.
The input circuits for voltage measurement are galvanically isolated and can be used in IT, TT, and, TN networks. To ensure galvanic separation for current measurements, the lines connected to the current measuring inputs are galvanically separated from the current transformers.
The measurements are obtained from the alternating quantities of current and voltage supplied to the AC inputs. When no external voltage and current transformers are used, the device can process rated input alternating voltages of up to V and rated input alternating currents up to 5 A.
= 400 V (347 V for UL condition) and V
P-N
= 690 V (600 V for UL condition)
P-P
Measurands
The integrated web server can be used to set the parameters and display the measured values on HTML pages from the connected PC or notebook. The softkeys located on the front of devices with an optional display enable a limited parameterization and measured value output on the display.
An Ethernet interface and an optional RS485 interface are available for communicating with the control center and other process automation systems. The RS485 interface supports the transmission of operating measured values, counts and messages. The Modbus RTU or IEC 60870-5-103 communication protocol can be used, depending on the device variant.
The following measurands can be recorded or calculated from the measured quantities:
Alternating voltage and alternating current
Unbalanced of alternating voltage and alternating current
Active, reactive, and apparent power
Active, reactive, and apparent energy
Power frequency
Phase angle
Power factor and active power factor
THDS (Subgroup Total Harmonic Distortion) of alternating voltage and alternating current
Harmonics of alternating voltage and alternating current
Flicker acc. to IEC 61000-4-15 (only SICAM P855)
E50417-H1040-C482-A6, Edition 10.2018
15SICAM P850/P855, 7KG85xx, Device Manual
1 User Information
The uncertainty of operational measurements of the measurands is defined as per IEC 62586-1 product standard, class S (leading standard), the IEC 61000-4-30 power quality standard, and the IEC 61557-12 standard.
For detailed information on measurands and measurements, see Chapter 4.2 and the technical data in Chapter 13.1.
Functionality of the Recorders in SICAM P850
The recorders are capable of recording both measurands and events in parameterizable time intervals. The following recorder types are used in SICAM P850:
Measurement recorder: recording parameterized periods, for example, 10-second frequency, aggregation of current, power etc.
Fault recorder: Recording of sampled values of voltage and current using programmable triggers.
The device features a 2-GB memory for storing the recorder data.
Functionality of the Recorders in SICAM P855
The recorders are capable of recording both measurands and events in parameterizable time intervals. The following recorder types are used in SICAM P855:
Measurement recorder: recording of PQ measurands (acc. to IEC 61000-4-30) and non-PQ measurands over parameterized periods, for example, 10-second frequency, aggregation of voltage, current, power etc.
Trend recorder: long-term recording and monitoring of the voltage change history over a parameterized period of time in programmable tolerance ranges; 1/2 RMS values
Fault recorder: Recording of sampled values of voltage and current using programmable triggers.
Event recorder: recording of voltage events, frequency events, and voltage unbalance events
The device features a 2-GB memory for storing the recorder data.
Communication
To communicate with the systems control and other process automation equipment, the device features an Ethernet interface and optionally an RS485 interface.
Ethernet supports the device parameterization, the transmission of measured data, counter values and indications/events, and the time synchronization via NTP. The communication protocols are HTTP, Modbus TCP and IEC 61850.
The RS485 interface supports the transmission of the measured data, counter values and indications, and the time synchronization. Depending on the device version, you can use either the Modbus RTU or the IEC 60870-5-103 communication protocol.
Time Synchronization
During operation SICAM P850/P855 needs the date and time for all time-relevant processes. This ensures that a common time basis exists when communicating with peripheral devices and enables time stamping of the process data. The following types of time synchronization can be executed:
External time synchronization via Ethernet NTP (preferred)
External time synchronization via fieldbus using the Modbus RTU or the IEC 60870-5-103 communication protocol
Internal time synchronization via RTC (if external time synchronization is not available)
Parameterization
Parameters are set using an internal Web browser with HTML pages from the connected PC or notebook. Internet Explorer 6 (or higher) is required for this purpose. Devices featuring a display offer a limited parameterization function using the front softkeys.
16 SICAM P850/P855, 7KG85xx, Device Manual
E50417-H1040-C482-A6, Edition 10.2018

2 Overview

2.1 Device Versions 18
2.2 Ordering Information, Scope of Delivery and Accessories 21
E50417-H1040-C482-A6, Edition 10.2018
17SICAM P850/P855, 7KG85xx, Device Manual
2 Overview

2.1 Device Versions

2.1 Device Versions
The multifunctional SICAM P850/P855 devices are used to detect, calculate, evaluate, display, and transmit measured electrical quantities such as alternating current, alternating voltage, power values etc.
SICAM P850 devices feature memory options for recorder functions such as mean values, minimum and maximum values, and fault records. SICAM P855 device additionally feature memory options for event recorder and trend record.
Consistent Device Properties
All devices consistently feature the following properties:
Device type:
Plastic case 96 mm x 96 mm x 100 mm (W x H x D)Web server for parameterization, visualization, and data managementGalvanically isolated voltage measuring inputs
Input and output circuits:
4 inputs for alternating voltage measurements3 inputs for alternating current measurements2 individually programmable binary outputs
Measurements:
Voltage VCurrent IBasic frequency fActive power P (class 0.2S)Reactive power QApparent power SActive power factor cos phiMeasurement up to the 40th harmonic of voltage and currentLimit violationsEnergy measurements
Other
Transmitting measured values using communication protocolsInternal 2-GB memory (SD card)UL Listing
Variants
SICAM P850/P855 is available in different variants:
Device type:
Panel flush mounting device with display for measured values and parameterizationDIN rail device without display
Communication via Ethernet
Only Modbus TCP protocolModbus TCP protocol or IEC 61850 server protocol
Serial communication
With RS485 interface:
- with Modbus RTU protocol
- with Modbus RTU protocol and IEC 60870-5-103 protocol
Without RS485 interface
18 SICAM P850/P855, 7KG85xx, Device Manual
E50417-H1040-C482-A6, Edition 10.2018
Degree of protection of front
SICAM P850/P855 as DIN Rail Device, Terminal Side
SICAM P850/P855 as DIN Rail Device,
with RS485 Interface
DIN Rail Side
IP20 for DIN rail devices without displayIP40 or IP51 for panel flush mounting devices with display
Additional measurands:
Minimum/mean/maximum values
Data export acc. to IEEE Std. 1159-3
COMTRADE dataCSV data
Other Special Functions of SICAM P855
Additional measurands:
Power Quality measurements acc. to IEC 61000-4-30Event detection, for example VFlicker acc. to IEC 61000-4-15
Evaluations
Output of power quality reports
Data export acc. to IEEE Std. 1159-3
PQDIF data
2 Overview
2.1 Device Versions
dips
SICAM P850/P855 Variant, DIN Rail Device
Figure 2-1 SICAM P850/P855 Variant, DIN Rail Device
E50417-H1040-C482-A6, Edition 10.2018
19SICAM P850/P855, 7KG85xx, Device Manual
2 Overview
SICAM P850/P855 for Panel Flush Mounting, Display Side
SICAM P850/P855 for Panel Flush Mounting, Terminal Side,
with RS485 Interface
SICAM P850/P855 for Panel Flush Mounting, Display Side
SICAM P850/P855 for Panel Flush Mounting, Terminal Side, with RS485 Interface
2.1 Device Versions
SICAM P850/P855 Variant with Graphic Display without Cover, Panel Flush Mounting
Figure 2-2 SICAM P850/P855 Variant with Graphic Display without Cover
SICAM P850/P855 Variant with Graphic Display and Cover, Panel Flush Mounting
Figure 2-3 SICAM P850/P855 Variant with Graphic Display and Cover
20 SICAM P850/P855, 7KG85xx, Device Manual
E50417-H1040-C482-A6, Edition 10.2018

2.2 Ordering Information, Scope of Delivery and Accessories

2.2 Ordering Information, Scope of Delivery and Accessories
Ordering Information
2 Overview
E50417-H1040-C482-A6, Edition 10.2018
21SICAM P850/P855, 7KG85xx, Device Manual
2 Overview
2.2 Ordering Information, Scope of Delivery and Accessories
Use the following ordering code to order SICAM P850/P855 devices:
Figure 2-4 Ordering Code for SICAM P850/P855
22 SICAM P850/P855, 7KG85xx, Device Manual
E50417-H1040-C482-A6, Edition 10.2018
Scope of Delivery
The delivery comprises the following components depending on the ordering code:
SICAM P850/P855 according to ordering code (see Figure 2-4)
Battery (insulated in the battery compartment of the device)
Product Information E50417-B1050-C482
Accessories
You can order the following accessories:
Device Manual E50417-H1040-C482 (download available at http://www.powerquality.de)
RS485 bus terminating plug 220 in a 9-pin D-sub connector plug: 7XV5103-5AA00
Sockets for alternating voltage inputs
2 Overview
2.2 Ordering Information, Scope of Delivery and Accessories
Order via:
Phoenix Contact GmbH & Co. KG
Item number: 1700734
Product name: GMSTB 2,5 HCV/ 4-ST-7,62 BK TS
Minimum order quantity: 50 pieces
Various cables as listed in the following tables:
Table 2-1 RS485-Y Bus Cable (2-Wire, Shielded, with 9-Pin D-sub Connector Plugs)
Cable Length Order No.
1 m 7XV5103-0AA01
3 m 7XV5103-0AA03
5 m 7XV5103-0AA05
10 m 7XV5103-0AA10
Table 2-2 RS485 Bus Extension Cable (2-Wire, Shielded, with 9-Pin D-sub Connector Plugs)
Cable Length Order No.
10 m 7XV5103-1AA10
20 m 7XV5103-1AA20
30 m 7XV5103-1AA30
40 m 7XV5103-1AA40
50 m 7XV5103-1AA50
E50417-H1040-C482-A6, Edition 10.2018
23SICAM P850/P855, 7KG85xx, Device Manual
2 Overview
2.2 Ordering Information, Scope of Delivery and Accessories
Table 2-3 Ethernet Patch Cable (Double Shielded (SFPT), LAN Connector Plugs on Both Sides)
Cable Length Order No.
0.5 m 7KE6000-8G-D00-0AA5
1.0 m 7KE6000-8G-D00-1AA0
2.0 m 7KE6000-8G-D00-2AA0
3.0 m 7KE6000-8G-D00-3AA0
5.0 m 7KE6000-8G-D00-5AA0
10.0 m 7KE6000-8G-D01-0AA0
15.0 m 7KE6000-8G-D01-5AA0
20.0 m 7KE6000-8G-D02-0AA0
24 SICAM P850/P855, 7KG85xx, Device Manual
E50417-H1040-C482-A6, Edition 10.2018

3 Device Design

3.1 Mechanical Design 26
3.2 Display and Softkeys 27
3.3 Electrical Design 28
E50417-H1040-C482-A6, Edition 10.2018
25SICAM P850/P855, 7KG85xx, Device Manual
3 Device Design
RJ45 with
4LEDs
2LEDs
RS485
Cover of battery compartment
Terminal block for
Default IP address Default subnet mask
LED RUN
LED ERROR
LED H1
LED H2
Softkeys
F1 to F4
Terminal blocks for
measurements (voltage, current)
power supply
Terminal block for binary outputs
Display
Terminal side
Display side

3.1 Mechanical Design

3.1 Mechanical Design
The electrical modules are installed in a plastic case with the dimensions 96 mm x 96 mm x 100 mm (W x H x D).
In panel flush mounting devices, the display side accommodates the display, 4 softkeys located below and 4 LEDs of which the H1, H2, and ERROR LEDs can be parameterized. The ERROR LED can only be parameterized for error messages.
The device top side holds the RJ45 Ethernet plug connector with 2 LEDs. 4 additional LEDs are identical to the LEDs on the display side. At the cover of the battery compartment there is a labeling strip for the configurable LEDs H1/H2 and a battery symbol that indicates the polarity. The label is also located on the top side and provides among other information the most important rated data of the device. A lithium battery is located under the removable cover of the battery compartment.
SICAM P850/P855 devices can also contain a D-sub connector plug as RS485 interface (see Figure 3-1) as shown in the ordering information (see Chapter 2.2).
26 SICAM P850/P855, 7KG85xx, Device Manual
Figure 3-1 Layout of the Panel Flush Mounting Version of SICAM P850/P855 with Display
NOTE
DIN rail devices have a DIN rail support instead of the display. Therefore, this device side is referred to as the DIN rail side.
E50417-H1040-C482-A6, Edition 10.2018
3.2 Display and Softkeys
MAX MENU
Voltage ph-n MAX 1.1
n 2.00 V Date/Time
c 229.00 V Date/Time
b 231.00 V Date/Time
a 230.00 V Date/Time
Title
Display area
Softkey functions
Softkeys F1 to F4
Display
The layout of the display is shown in the following figure.
3 Device Design

3.2 Display and Softkeys

Figure 3-2 Display and Softkeys
The top line (title) shows the name of the current display in the display area. The display area below shows parameter settings, measured values, and graphic pictures.
The bottom line shows the 4 current functions of the softkeys below the display used to set the parameters.
Softkeys
The 4 softkeys on the display side are used to make the desired entries at the device.
To call and activate the IP address, press softkey F4 (for > 3 s, see Figure 3-2) on the right during system startup if necessary. The IP address and the standard subnet mask are imprinted on the side panel of the device (see Figure 3-1).
Chapter 8 gives a detailed description of the softkey functions.
E50417-H1040-C482-A6, Edition 10.2018
27SICAM P850/P855, 7KG85xx, Device Manual
3 Device Design
4 x AC
voltage
measuring
inputs
Terminal
Power
supply
Terminal
3 x AC current
measuring
inputs
Terminal
2 x Binary
outputs
Terminal
ADC
LED Ethernet
RS485
interface
D-Sub
DSP
DisplaySoftkeys

3.3 Electrical Design

3.3 Electrical Design
SICAM P850/P855 contains the following electrical modules depending on the device version:
Digital signal processor (DSP)
Display and Softkeys (optional)
4 inputs for alternating voltage measurements
3 inputs for alternating current measurements
2 binary outputs
Supply voltage
Ethernet interface
Serial RS485 interface (optional)
Figure 3-3 Block Diagram SICAM P850/P855 with Display (Optional) and RS485 Interface (Optional)
28 SICAM P850/P855, 7KG85xx, Device Manual
E50417-H1040-C482-A6, Edition 10.2018

4 Measurands and Recording

4.1 Measuring and Recording System 30
4.2 Measurands 43
4.3 Display of Measurands 65
E50417-H1040-C482-A6, Edition 10.2018
29SICAM P850/P855, 7KG85xx, Device Manual
4 Measurands and Recording
RTC
10-minute
limit
k
10-minute interval (x+1)
j
10/ 12 pe riods
i
1
2 3
Over la pping a rea
10-minute interval (x)
10 /12 peri ods
10/ 12 pe riods 10/12 pe riods
10 /12 periods
10 / 12 per iods

4.1 Measuring and Recording System

4.1 Measuring and Recording System

4.1.1 Functioning of the Measuring System according to IEC 61000-4-30

SICAM P850/P855 devices measure the power quality according to IEC 61000-4-30 in 1-phase or multi-phase distribution systems. The measuring system is implemented according to class A. In terms of functional scope, measuring ranges, and accuracy, the SICAM P850/P855 devices are class S.
The basic measuring interval for determining the values for mains voltage, harmonics of mains voltage, and mains voltage unbalance is a 10-period time interval for 50-Hz distribution systems or a 12-period time interval for 60-Hz distribution systems. The measurement of the 10-/12-period time intervals is resynchronized at each RTC 10-minute limit.
Subsequently, the values for the 10-/12-period time intervals are aggregated over additional time intervals (for example, 10-minute interval at SICAM P850/P855).
10-Minute Interval (SICAM P850/P855)
The value aggregated in a 10-minute interval is tagged with the absolute time (for example 01:10:00). The time at the end of the aggregation interval is indicated as the time qualifier. The values for the 10-minute time interval are calculated without interruption from the 10-/12-period time intervals.
Each 10-minute interval begins at an RTC 10-minute limit. At this 10-minute limit, the 10-/12-period time intervals are aggregated over a 10-minute interval. The last 10-/12-period time interval in a 10-minute aggregation interval overlaps in time at an RTC 10-minute limit. Each overlapping 10-/12-period time interval (for the overlapping area, see Figure 4-1) is included in the aggregation interval of the preceding 10-minute interval.
The aggregation interval enables the power system quality to be evaluated according to EN 50160. The aggregation interval can be adjusted to other applications using a parameter. A shorter aggregation interval increases the storage capacity required for measured values and reduces the maximum possible recording time in the memory.
30 SICAM P850/P855, 7KG85xx, Device Manual
Figure 4-1 Synchronization of the Aggregation Intervals for Class A
E50417-H1040-C482-A6, Edition 10.2018