Overview1
Technical Data2
Functions3
Operation and Display4
Installation and Wiring5
Communication6
Maintenance7
Ordering Number8
E50417-H8940-C562-3
NOTE
For your own safety, observe the warnings and safety instructions contained in this document, if available.
Disclaimer of Liability
This document has been subjected to rigorous technical review
before being published. It is revised at regular intervals, and any
modifications and amendments are included in the subsequent
issues. The content of this document has been compiled for
information purposes only. Although Siemens AG has made best
efforts to keep the document as precise and up-to-date as possible,
Siemens AG shall not assume any liability for defects and damage
which result through use of the information contained herein.
This content does not form part of a contract or of business
relations; nor does it change these. All obligations of Siemens AG
are stated in the relevant contractual agreements.
Siemens AG reserves the right to revise this document from time to
time.
The disclosure, duplication, distribution and editing of this document, or utilization and communication of the content are not permitted, unless authorized in writing. All rights, including rights
created by patent grant or registration of a utility model or a design,
are reserved.
Registered Trademarks
SIPROTEC®, DIGSI®, SIGUARD®, SIMEAS®, and SICAM® are
registered trademarks of Siemens AG. Any unauthorized use is
illegal. All other designations in this document can be trademarks
whose use by third parties for their own purposes can infringe the
rights of the owner.
Document Version: V01.10.01
Release date:
06.2018
Siemens Power Automation Ltd.Order No.: E50417-H8940-C562-4
Preface
Purpose of this manual
This manual describes the functions, operation, installation, and commissioning of devices 3-phase Current
Power Meter-> In particular, one will find:
• Information regarding the configuration of the scope of the device and a description of the device functions
> Chapter 3;
• Instructions for Operation and Display > Chapter 4;
• Technical Data > Chapter 2;
T arget Audience
Protection engineers, commissioning engineers, personnel concerned with adjustment, checking, and service
of selective protective equipment, automatic and control facilities, and personnel of electrical facilities and
power plants.
Additional Support
Should further information on the System SICAM be desired or should particular problems arise which are not
covered sufficiently for the purchaser's purpose, the matter should be referred to the local Siemens representative.
Our Customer Support Center provides a 24-hour service.
Phone: +49 (180) 524-7000
Fax: +49 (180) 524-2471
E-mail: support.energy@siemens.com
Notes on Safety
This document is not a complete index of all safety measures required for operation of the equipment
(module or device). However, it comprises important information that must be followed for personal safety, as
well as to avoid material damage. Information is highlighted and illustrated as follows according to the degree
of danger:
DANGER
DANGER means that death or severe injury will result if the measures specified are not taken.
✧ Comply with all instructions, in order to avoid death or severe injuries.
WARNING
WARNING means that death or severe injury may result if the measures specified are not taken.
✧ Comply with all instructions, in order to avoid death or severe injuries.
SICAM P35 P36, 3-phase Multi-Function Power Meter, User Manual
E50417-H8940-C562-4, Release Date 06.2018
3
Preface
CAUTION
CAUTION means that medium-severe or slight injuries can occur if the specified measures are not taken.
✧ Comply with all instructions, in order to avoid moderate or minor injuries.
NOTICE
NOTICE means that property damage can result if the measures specified are not taken.
✧ Comply with all instructions, in order to avoid property damage.
NOTE
Important information about the product, product handling or a certain section of the documentation which
must be given particular attention.
Qualified Electrical Engineering Personnel
Only qualified electrical engineering personnel may commission and operate the equipment (module, device)
described in this document. Qualified electrical engineering personnel in the sense of this manual are people
who can demonstrate technical qualifications as electrical technicians. These persons may commission,
isolate, ground and label devices, systems and circuits according to the standards of safety engineering.
Proper Use
The equipment (device, module) may be used only for such applications as set out in the catalogs and the
technical description, and only in combination with third-party equipment recommended and approved by
Siemens.
Problem-free and safe operation of the product depends on the following:
• Proper transport
• Proper storage, setup and installation
• Proper operation and maintenance
When electrical equipment is operated, hazardous voltages are inevitably present in certain parts. If proper
action is not taken, death, severe injury or property damage can result:
• The equipment must be grounded at the grounding terminal before any connections are made.
• All circuit components connected to the power supply may be subject to dangerous voltage.
• Hazardous voltages may be present in equipment even after the supply voltage has been disconnected
(capacitors can still be charged).
• Operation of equipment with exposed current-transformer circuits is prohibited. Before disconnecting the
equipment, ensure that the current-transformer circuits are short-circuited.
• The limiting values stated in the document must not be exceeded. This must also be considered during
testing and commissioning.
■
4
SICAM P35 P36, 3-phase Multi-Function Power Meter, User Manual
SICAM P35 P36, 3-phase Multi-Function Power Meter, User Manual
E50417-H8940-C562-4, Release Date 06.2018
5
Contents
6
SICAM P35 P36, 3-phase Multi-Function Power Meter, User Manual
E50417-H8940-C562-4, Release Date 06.2018
Overview1
1.1Introduction8
1.2Features8
SICAM P35 P36, 3-phase Multi-Function Power Meter, User Manual
E50417-H8940-C562-4, Release Date 06.2018
7
Overview
1.1 Introduction
1.1Introduction
SICAM P35 and SICAM P36 3-phase electronic multi-function power meters integrate measurement, power
metering, remote communication and control, large screen LCD and communication functions. It is designed
for measuring power grid parameters such as voltage, current, power, power factor and frequency and metering
active and reactive power. RS485 communication support MODBUS-RTU communication protocol. Binary
input and output functions are optional.
This product is extensively applicable to power substation and distribution automation system, industrial control
and industrial automation system, energy management system and community power monitoring, etc.
This 3-phase electronic multi-function power meter meets following standards:
• IEC 62052-11:2003 (Electricity metering equipment (a.c.) General requirements, tests and test conditionsPart 11: Metering equipment) standard
• IEC 62053-22:2003 static meters for active energy (classes 0.2 S and 0.5 S)
• IEC 62053-23:2003 static meters for reactive energy (classes 2 and 3)
• Modbus-RTU
1.2Features
This project uses high-precision sampling and metering unit and high-speed MCU data processing unit, supporting high-precision, wide-range and accurate measurement and quick data analysis; segmented multi-line
WVA LCD, realizing various and abundant display; white backlight for LCD, satisfying the need for viewing data
in dark environment; NVRAM, supporting long-time data storage without data loss even in the event of power
failure; RS485 communication port and industrial standard communication protocols, realizing flexible and reliable communication.
■
8
SICAM P35 P36, 3-phase Multi-Function Power Meter, User Manual
E50417-H8940-C562-4, Release Date 06.2018
Technical Data2
2.1Technical Data10
SICAM P35 P36, 3-phase Multi-Function Power Meter, User Manual
E50417-H8940-C562-4, Release Date 06.2018
9
Technical Data
2.1 Technical Data
2.1Technical Data
ItemTechnical Data
Product standardIEC61557-12:2007
Input connection3-phase-3-wire, 3-phase-4-wire, single phase
Voltage
Measurement
Metering
Digital signal
CommunicationRS-485 port
Environment
Current
Power
(active, reactive, apparent)
Power grid frequency
Active power
Reactive power
Power pulse output
Binary output (optional)
Binary input (optional)
Operating temp.-25 ℃ ... +60 ℃
Operating temp. limit-35 ℃ ... +70 ℃
Relative humidity≤ 95% (condensation free)
Reference voltage U
AC57.7 V
: AC380 V, AC220 V, AC100 V,
n
Measuring range: 10 V ... 276 V phase voltage
Maximum measuring range: 400 V phase voltage
Power consumption: < 0.1 VA (single phase @220VAC)
Accuracy: RMS 0.2%
Resolution: 0.01 V
Rated current I
: 1 A, 5 A
n
Measuring range: 0.015 A ... 6 A
Maximum measuring range: 9 A
Power consumption: < 0.3 VA (single phase @5A)
Accuracy: RMS 0.2%
Resolution: 0.001 A
Accuracy: 0.5%
Resolution: 0.001 kW/kVar/kVA
Measuring range: 45 Hz ... 65 Hz
Accuracy: 0.2%
Resolution: 0.01 Hz
Accuracy level: 0.5 S, Acc. To IEC 62053-22
Resolution: 0.01 kWh, 5000 imp/kWh
Accuracy: Class 2, Acc. To IEC 62053-23
Resolution: 0.01 kvarh, 5000 imp/kvarh
2 electric energy (active and reactive) pulse outputs
SICAM P35 P36, 3-phase Multi-Function Power Meter, User Manual
E50417-H8940-C562-4, Release Date 06.2018
■
Others
ItemTechnical Data
AC or DC power supply
Operating power
supply
Max. input range: 40 V ... 420 V
Power consumption: ≤2 W, 4 VA
Overall dimension (mm): 96×96×95
Dimension
Panel cut out size (mm): 92×92
IP53
WeightApprox. 450 g
Technical Data
2.1 Technical Data
SICAM P35 P36, 3-phase Multi-Function Power Meter, User Manual
E50417-H8940-C562-4, Release Date 06.2018
11
Technical Data
2.1 Technical Data
12
SICAM P35 P36, 3-phase Multi-Function Power Meter, User Manual
E50417-H8940-C562-4, Release Date 06.2018
Functions3
3.1Measurement14
3.2Energy Metering14
3.3Limit violation Alarm15
3.4Display and Buttons16
3.5Communication16
3.6Permission and Security Management16
3.7Digital Input and Output Interface17
SICAM P35 P36, 3-phase Multi-Function Power Meter, User Manual
E50417-H8940-C562-4, Release Date 06.2018
13
Functions
3.1 Measurement
3.1Measurement
This meter is provided with various measuring functions. Power grid parameters and index measurable are as
follows:
• voltage of each phase and mean voltage
• voltage of each line and mean voltage
• current of each phase, average current and neutral current
• overall and separate active power, reactive power and apparent power of each phase
• phase angle of voltage and current of each phase
• overall and separate power factor of each phase
• power grid frequency and measuring range 45Hz to 65 Hz
3.2Energy Metering
This meter can meter various energy data:
• combined active and supply and demand active energy
• combined reactive and four-quadrant reactive energy
• supply and demand active energy of each phase and combined reactive energy of each phase
14
SICAM P35 P36, 3-phase Multi-Function Power Meter, User Manual
E50417-H8940-C562-4, Release Date 06.2018
3.3Limit violation Alarm
1. This product is provided with limit violation alarm function. User may select from voltage, current, power,
power factor and frequency parameters at most 6 data groups at the same time as detection object and set
upper and lower limits and judgment condition for them. Alarm will be activated when measured value is over
the set limit. This product is provided with 2 relay outputs. When alarm parameters are configured that output
is made from certain relay which is at automatic mode (not manual), limit violation alarm signal can be output
through such relay (relay closing).
2. At most 6 limit violation alarm parameters can be set at the same time within the product. Configuration flow
of each limit violation alarm parameter: select type of detected data-set threshold of detected data-set
judgment condition-select output relay for alarm signal.
• Code of various detected data: (hexadecimal number for Modbus-RTU code)
MODBUS codeContent of dataMODBUS codeContent of data
00Phase A power factor14Phase A active power
01Phase B power factor15Phase B active power
02Phase C power factor16Phase C active power
03Total power factor17Total active power
06Frequency18Phase A reactive power
07Phase A voltage 19Phase B reactive power
08Phase B voltage 1APhase C reactive power
09Phase C voltage 1BTotal reactive power
0BUab line voltage 1CPhase A apparent power
0CUbc line voltage 1DPhase B apparent power
0DUca line voltage 1EPhase C apparent power
0FPhase A current1FTotal phase apparent power
10Phase B current
11Phase C current
12Neutral current
Functions
3.3 Limit violation Alarm
When code of detected data is FF, limit violation alarm function of such group is off.
• Threshold of detected data: threshold judging whether detected value is out of limit; Different units for
different data types: such as voltage-V, current-A, active-KW, reactive power-KVAR, apparent-KVA,
frequency-Hz.
• Judging condition: 0 means alarm activated when exceeding limit; 1 means alarm activated when falling
below limit.
• Alarm signal output relay: 0 means no alarm signal output; 1 means alarm signal outputted from relay1;2
means alarm signal outputted from relay 2; 3 means alarm signal outputted from relay 1 and relay 2 at the
same time. .
3. Example of alarm parameter setting. Set one limit violation alarm parameter to automatic detection and alarm
for "Phase A voltage", assuming that alarm threshold is 240 V, judging criterion is "over limit” and signal is
outputted from relay 2.
Use MODBUS RTU protocol to set alarm parameter: set 0110 address to "07", 0111 to "0000", 0112 to
"5DC0" (multiply "240" by 100 to generate "24,000" and convert it into "00005DC0"), 0113 to "00" and 0114
to "02".
SICAM P35 P36, 3-phase Multi-Function Power Meter, User Manual
E50417-H8940-C562-4, Release Date 06.2018
15
Functions
3.4 Display and Buttons
3.4Display and Buttons
This product uses large-screen WVA multi-line LCD to provide visual and various display. The screen is
provided with white backlight, enabling clear display in dark environment. Specific data information can be
obtained through display with button operation. For details, see Chapter Operation and Display.
3.5Communication
RS485 port is provided for parameter setting and reading of various data. For specific description, see Chapter
Communication.
3.6Permission and Security Management
1. This product is provided with programming permission management function.
• L0 password: used for meter reset, setting all parameters and modifying L0, L2 and L4 passwords;
• L2 password: used for meter reset, setting all parameters and modifying L2 and L4 passwords;
• L4 password: used for parameter setting and modifying L4 password, not for meter reset, clearing extreme
values and PT/CT ratio setting.
• All level default PASSWORD is "000000"
2. Parameter setting is available only when this product is in programmable state. Steps for entering
programming state: press " " and "" at the same time to enter "PASS" screen; input correct
password and press "" to enter "SET" screen and enable programmable state. After entering
programmable state, programmable state prompt appears on the bottom right corner of LCD. Programmable
state will remain valid in 10 minutes after program button is pressed and become invalid after power down.
3. If incorrect password is used to set this product continuously (including communication setting and button
programming) up to specific number of times (factory default 5 times), parameter setting function will be
locked (factory default 60 minutes). Error count will be reset after setting once using correct password if such
count is less than specific limit. Error count of password and lock time can be set (available in factory state).
16
SICAM P35 P36, 3-phase Multi-Function Power Meter, User Manual
E50417-H8940-C562-4, Release Date 06.2018
Loading...
+ 36 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.