Siemens SG8158-00 User Manual

TM
ISGS
Intelligent SwitchGear System Operators Manualfirmware version V3
Manual No. SG8158-00
IMPORTANT
The information contained herein is general in nature and not intended for specific application purposes. It does not relieve the user of responsibility to use sound practices in application, installation, operation, and maintenance of the equipment purchased. Siemens reserves the right to make changes at any time without notice or obligations. Should a conflict arise between the general information contained in this publication and the contents of draw­ings or supplementary material, or both, the latter shall take precedence.
QUALIFIED PERSON
For the purposes of this manual, a qualified person is one who is familiar with the installation, construction, or operation of the equipment and the hazards involved. In addition, this person has the following qualifications:
(a) is trained and authorized to de-energize, clear, ground, and tag cir-
cuits and equipment in accordance with established safety practices.
(b) is trained in the proper care and use of protective equipment such as
rubber gloves, hard hat, safety glasses or face shields, flash clothing, etc. in accordance with established safety procedures.
(c) is trained in rendering first aid.
NOTE
These instructions do not purport to cover all details or variations in equipment, nor to provide for every possible contingency to be met in connection with installation, operation, or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchasers purposes, the matter should be referred to the local sales office.
The contents of the instruction manual shall not become part of or modify any prior or existing agreement, com­mitment or relationship. The sales contract contains the entire obligation of Siemens Energy & Automation, Inc. The warranty contained in the contract between parties is the sole warranty of Siemens Energy & Automation, Inc. Any statements contained herein do not create new warranties or modify the existing warranty.
Introduction
1
Table
of
Contents
Installation
User Interface
Hardware Configuration
Protective Function Configuration
Control & Communications
Data Acquisition
ISGS Wisdom Software
2
3
4
5
6
7
8
Trip Curves & Equations
Metering
Menu Structure
Acceptance Test Procedures
Schematics
Settings Worksheet
Glossary
A
B
C
D
E
S
G
Index
Siemens Energy & Automation, Inc.
I
Table of Contents
1 Introduction ...............................................1
1.1 About this Manual............................................. 1
1.2 Safety................................................................ 1
1.3 Product Description .......................................... 2
1.3.1 Standard Configuration......................... 2
1.3.2 Optional Configurations ........................ 3
1.4 Wisdom Software.............................................. 3
1.5 Technical Specifications ................................... 4
2 Installation .................................................5
2.1 Unpacking......................................................... 5
2.2 Storing............................................................... 5
2.3 Mounting ........................................................... 5
2.4 Wiring................................................................ 6
2.5 Communications............................................... 8
2.5.1 PC Communications (RS-232) ..............8
2.5.2 Network Communications (RS-485) ..... 8
2.6 Cradle Assembly............................................... 8
2.6.1 Removing .............................................. 8
2.6.2 Inserting ................................................ 8
3 User Interface............................................9
3.1 Keypad.............................................................. 9
3.2 Indicators .......................................................... 9
3.2.1 LEDs...................................................... 9
3.2.2 LCD ..................................................... 10
3.3 Password Protection....................................... 10
3.4 Menu ............................................................... 11
3.5 Standard Operating Procedures..................... 11
4 Hardware Configuration.........................15
4.1 Startup ............................................................15
4.1.1 Power On Display................................ 15
4.1.2 Power On Meter Display ..................... 15
4.2 Device Configuration ...................................... 16
4.3 Setting Binary Input Voltages.......................... 16
4.4 CT Configuration............................................. 18
4.5 VT Configuration ............................................. 18
5 Protective Function Configuration ........21
5.1 Overview ......................................................... 21
5.2 Instantaneous Phase Overcurrent (50)............ 21
5.3 High-Set Instantaneous Phase
Overcurrent (50HS) ......................................... 22
5.4 Instantaneous Neutral or Ground
Overcurrent (50N)............................................ 22
5.5 High-Set Instantaneous Neutral or
Ground Overcurrent (50HSN).......................... 22
5 Protective Function Configuration (cont.)
5.6 Phase Time Overcurrent (51)...........................23
5.7 Neutral Time Overcurrent (51N) ......................23
5.8 Blocking Capability for Breaker or
Interrupter Saving............................................ 24
5.9 Directional Phase Time Overcurrent (67).........24
5.10 Directional Neutral or Ground Time
Overcurrent (67N)............................................25
5.11 Overvoltage (59) ..............................................26
5.12 Undervoltage (27)............................................26
5.13 Phase Sequence Voltage (47) .........................27
5.14 Negative Sequence Voltage (47N) ..................27
5.15 Overfrequency (81O) ....................................... 28
5.16 Underfrequency (81U) ..................................... 28
5.17 Breaker Failure (50BF)..................................... 28
5.18 Demand Setpoints ..........................................29
5.19 Power Setpoints.............................................. 30
6 Control & Communications ................... 31
6.1 Matrixing Events to Outputs ...........................31
6.2 Binary Inputs ...................................................33
6.3 Binary Outputs ................................................33
6.4 Trip Contacts ...................................................34
6.5 Comm Events.................................................. 34
6.6 Breaker Monitoring..........................................34
6.7 Logs and Breaker Monitor Reset ....................35
6.8 Breaker Operations Count ..............................36
6.9 Hardware Status (Relay Data) ......................... 36
6.10 Self-Monitoring (Value Supervision) ................ 37
6.11 Parameter Sets ...............................................39
6.11.1 Active Set ............................................40
6.11.2 Default Set........................................... 40
6.11.3 Switching Sets ....................................40
6.11.4 Copying Sets.......................................40
6.12 Communications Port .....................................41
6.13 Passwords.......................................................41
6.14 Date and Time Setting ....................................41
7 Data Acquisition ..................................... 43
7.1 Event Log ........................................................43
7.2 Trip Logs ......................................................... 43
7.3 Min/Max Logs .................................................44
7.3.1 Current Minimum/Maximum Log ........44
7.3.2 Voltage Minimum/Maximum Log ........45
7.3.3 Power Minimum/Maximum Log ..........45
7.3.4 Frequency Minimum/Maximum Log ...45
Siemens Energy & Automation, Inc. i
Table of Contents
7 Data Acquisition (cont.)
7.4 Metered Data ..................................................46
7.4.1 Current Values .....................................46
7.4.2 Voltage Values .....................................46
7.4.3 Power Values....................................... 46
7.4.4 Frequency Values................................46
7.5 Meter Display ..................................................47
7.6 Waveform Capture .......................................... 47
8 ISGS Wisdom Software ..........................49
8.1 Overview .........................................................49
8.2 Setup...............................................................49
8.3 Menus .............................................................49
8.4 Demo Mode ....................................................51
A Trip Curves & Equations.........................53
A.1 Instantaneous Curve ........................................ 53
A.2 Standard Time Overcurrent Equation ..............53
A.3 Definite Inverse Equation .................................55
A.4 I-Squared-T Curve ...........................................56
A.5 Custom Protective Curve................................. 56
A.6 Over/Undervoltage Curves ..............................56
B Metering.................................................. 58
B.1 Accuracy ..........................................................58
B.2 Power Conventions..........................................59
C Menu Structure....................................... 60
D Acceptance Test Procedures ................ 63
E Schematics ............................................. 79
E.1 DC Trip System ................................................79
E.2 AC (Capacitor) Trip Systems............................80
Settings Worksheet
Glossary
Index
Service Request Form
ACCESS, CBPM, ISGS, SEAbus, WinPM, and Wisdom are trademarks of Siemens Energy & Automation, Inc. SIEMENS is a registered trade­mark of Siemens AG. All other brands and product names are trademarks of their respective companies.
ii Siemens Energy & Automation, Inc.
Introduction
1
1
1 Introduction
The Intelligent SwitchGear System (ISGS) from Siemens is a high-speed, numerical, microprocessor-based protective relay designed to be easily incorporated into a computer­monitored medium voltage power system. The relay is designed and manufactured in accordance with the latest provisions of the applicable IEEE, ANSI, and NEMA stan­dards. You must thoroughly read and understand this opera­tors manual before you begin any work with the ISGS relay. Successful application and operation of this equipment depends as much upon proper installation and maintenance by the user as it does upon the careful design and fabrication by Siemens.
1.1 About this Manual
The purpose of this manual is to assist the operator in devel­oping safe and efficient procedures for the installation, main­tenance, and use of the equipment.
This manual provides the necessary information to safely install, operate, configure, maintain, and troubleshoot the ISGS relay. In addition, the manual offers worksheets for parameter settings, acceptance test procedures, and trou­bleshooting. For quick reference, a complete menu structure, metering accuracies, trip curves, equations, and schematics are included in the appendix.
Contact the nearest Siemens representative if any additional information is desired.
1.2 Safety
Qualified Person
For the purpose of this manual and product labels, a Quali­fied Person is one who is familiar with the installation, con-
struction, and operation of this equipment, and the hazards involved. In addition, this person has the following qualifica­tions.
Training and authorization to energize, de-energize,
clear, ground, and tag circuits and equipment in accor­dance with established safety practices
Training in the proper care and use of protective equip-
ment such as rubber gloves, hard hat, safety glasses or face shields, flash clothing, etc., in accordance with established safety procedures
Training in rendering first aid
Siemens Energy & Automation, Inc. 1
1
Introduction
Signal Words
The signal words Danger, Warning, and Caution used in this manual indicate the degree of hazard that the user or operator can encounter. These words are defined as follows:
Danger - indicates an imminently hazardous situation
which, if not avoided, will result in death or serious injury
Warning - indicates a potentially hazardous situation
which, if not avoided, could result in death or serious injury
Caution - indicates a potentially hazardous situation
which, if not avoided, could result in moderate or minor injury
Required Procedures
In addition to normal safety practices, user personnel must adhere to the following procedures:
1. Always work on de-energized equipment. Always de­energize a breaker or contactor, and remove it from the equipment before performing any tests, maintenance, or repair.
2. Always perform maintenance on equipment employing springs after the spring-charged mechanisms are dis­charged.
3. Always let an interlock device or safety mechanism per­form its function without forcing or defeating the device.
Field Service Operation
Siemens can provide competent, well-trained Field Service Representatives to provide technical guidance and advisory assistance for the installation, overhaul, repair, and mainte­nance of Siemens equipment, processes, and systems. Contact regional service centers, sales offices, or the factory for details.
1.3 Product Description
The ISGS relay is a general purpose, multifunction, micropro­cessor-based protective relay. It performs protection, meter­ing, and monitoring for three phase current transformer (CT) inputs and one ground CT input.
The ISGS relay provides two breaker tripping contacts and one relay disabled (alarm) contact. The relay disabled contact is a normally closed contact which opens when the relay is functioning properly.
1.3.1 Standard Configuration
The ISGS relay base unit includes the following standard pro­tection, metering, and monitoring features:
Instantaneous Phase Overcurrent (50) protection
Instantaneous Neutral or Ground Overcurrent (50N)
protection
Phase Time Overcurrent (51) protection
Neutral or Ground Time Overcurrent (51N) protection
ISGS
System Pickup Trip
Direct
Target Reset
Pass
Addr
word
Trip
Target
Log
Reset
F
ISGS
Cat# C552-100V-5D0-000 VPSn120VAC/250VDC IPH 5A IC 5A Ser# Beta05HW15W2.XX
LR
7
4
1
Pass word
Yes No
8
5
2
0
Data Port
9
6
3
-/+
Enter
Figure 1.1 Intelligent SwitchGear System (ISGS) Relay
Nine selectable time overcurrent curves and one custom
curve
Breaker Failure (50BF) protection
Phase and neutral current as well as average current
metering
Minimum/maximum logs for storing metering data
Waveform capture
Trip log for recording information on last eight trip events
Event log for monitoring and recording relay functions
for status changes
2-line by 16-character liquid crystal display (LCD) for
viewing measured data
26-key membrane keypad for local access and selected
manual data entry.
LED indicators for general relay status information
Standard RS-232 communications port for local access
to all parameter settings using a personal computer (PC) and Wisdom software
Password security
The ISGS relay is supplied in an M1-size drawout case with dust tight front cover. The case is compatible with XLA con­necting plugs that are commonly used to test relays.
2 Siemens Energy & Automation, Inc.
Introduction
1
1.3.2 Optional Configurations
The ISGS relay is a dynamic, feature-rich device that can be used in numerous industrial and utility applications. It allows the addition of options or configuration changes at any time without discarding the basic hardware.
There are four optional configurations that can be added to the ISGS relay base unit.
Metering
Adding metering to the ISGS relay provides the relay with three inputs for the connection of VTs. Each input can be set from 100 V to 120 V. These inputs extend metering capabili­ties as follows:
Rms and average rms voltages
Active and apparent power
Kilowatt demand and kilowatt demand hours
Power factor
Frequency
The installation of the voltage input card now also allows the setting of these protective functions:
High-Set Instantaneous Phase Overcurrent (50HS)
High-Set Instantaneous Neutral or Ground Overcurrent
(50HSN)
The metering option is also a prerequisite for the next two options: additional protective functions and remote commu­nications.
Additional Protective Functions
For an ISGS relay with the metering option installed, the fol­lowing additional protective functions offer a powerful exten­sion of its protection capabilities:
Under/Overvoltage (27/59)
Phase Sequence Voltage (47)
Negative Sequence Voltage (47N)
Directional Time Overcurrent (67/67N)
Over/Underfrequency (81U/O)
Communications
Adding communications to the ISGS relay provides the relay with an RS-485 port. Using the SEAbus communications protocol, this port allows remote communications and con­trol via the ACCESS electrical distribution and communica­tion system (ACCESS system).
Communications allows configuration, measurement, and protection functions to be performed or reviewed easily from a remote location using Wisdom software.
1.4 Wisdom Software
While it is possible to completely set up and configure the ISGS relay using the front panel keyboard and display, the free Wisdom software package provided with the relay reduces the complexity of configuring the relay, reading metered values, and retrieving stored data. For more infor­mation on Wisdom software, refer to Chapter 8.
Siemens Energy & Automation, Inc. 3
1
Introduction
1.5 Technical Specifications
Applicable Standards
ANSI / IEEE C37.90-1989 IEEE Standard Relays and Relay
IEC 255-4 Single Input Energizing Quantity
General Technical Data
Operating ambient temperature -20°C to +55°C (-4°F to +131°F)
Storage temperature -40°Cto +75°C (-40°F to +167°F)
Relative humidity The average relative humidity
Altitude < 1500 meters
Frequency 50 Hz or 60 Hz, software select-
Power Supply AC/DC
DC Rated voltages 48 V (19-56 V),
Permissible ripple <10%
AC Rated voltage 120 V rms (102-132 V, 50-60 Hz)
Power consumption <15W
Input Circuit Ratings
Rated current (In) 1 or 5 A, independently for
Maximum input current 4 x In continuous
CT burden <0.1 VA for 1A CT
Rated voltage (Vn) 115 or 120 volts
Maximum input voltage for measurement: 1.25 x Vn
VT burden 150k
Tripping relays 2 or 3
Contact configuration (Trip 1, Trip 2, Trip 3)
Contact rating IEEE/ANSI C37.90-1989, Sec-
Systems Associated With Elec­tric Power Apparatus
Measuring Relays With Depen­dent or Independent Time
may be up to 55% outside of enclosure for temperatures up to 40°C, with excursions up to 95% for a maximum of 96 hours, without condensation.
able
125 V (46-144 V), 250 V (92-288 V)
phase and ground inputs
10 x In for 10 s
100 x In for 1 s
<0.5 VA for 5A CT
MOV protected at: 2.5 x Vn
Trip Circuit
tion 6.7 (Make and carry 30 A for at least 2000 duty cycles, resis­tive load, interrupted by indepen­dent means. Duty cycle: 200 ms on, 15 s off, 250 V)
Trip Circuit (continued)
Binary output contacts (BO1 and BO2)
Maximum switching voltage 300 VDC, 250 VAC
Maximum switching current 8 A
Maximum switching capac­ity (for currents not inter­rupted by independent means)
Trip source monitor 215 mA for 48 VDC supply
Applicable standards ANSI/IEEE C37.90-1989,
Between all circuits (except communications interfaces, ana­log inputs and outputs) and ground, and between these cir­cuits.
Between communications inter­faces, analog inputs and outputs and ground, and between these circuits
Across open contacts rated for tripping
Across open contacts not rated for tripping
Applicable standards IEC 255-4, IEC 255-5
For all circuits (except communi­cations interfaces, analog inputs and outputs), transverse and common mode
RS-485 and local communica­tions interfaces, analog I/Os
Electrostatic Discharge
Applicable standards IEC 801-2 (test without cover)
Contact discharge class 3, 6 kV
Air discharge class 3, 8 kV
Surge Withstand Capability
Applicable standards ANSI/IEEE C37.90-1989,
For all circuits except communi­cations interfaces, analog inputs and outputs
For RS-485 interface, analog inputs and outputs
Electromagnetic Field
Applicable standards ANSI/IEEE C37.90.2
All six faces 10 V/m (+100%, -0%),
2 x N.O. (independent, not rated for tripping)
DC: voltage dependent;
50 W at V 100 W at 48 VDC 270 W at 35 VDC AC: 2000 VA
63 mA for 125 VDC supply 36 mA for 250 VDC supply Source quality checked approxi­mately every 4 minutes
Isolation
IEC 255-4, IEC 255-5
2 kV rms, 50/60 Hz, 1 minute
500 VDC, 1 minute
1500 V rms, 50/60 Hz, 1 minute
1000 V rms, 50/60 Hz, 1 minute
Impulse
class 3, 5 kV, 1.2/50
class 1, 0 kV
IEC 255-4, IEC 255-22-1, IEC 41B (CO) 53
ANSI: Oscillatory and Fast Tran­sient, transverse and common mode IEC: Class 3, 2.5 kV
IEC: Class 1, 0.5 kV
2-1000 MHz
70 VDC
µs, 0.5 J
4 Siemens Energy & Automation, Inc.
Installation
2 Installation
This chapter explains the installation of the ISGS relay and includes procedures for unpacking, storing, mounting, and wiring the relay. Prior to installation, ensure that the system power is off and that you have all required tools and test equipment available.
2.1 Unpacking
Upon receipt of the relay, inspect the carton for signs of dam­age. If the carton has been opened or damaged, carefully inspect and verify the contents against the packing list. If pieces are missing or damaged, contact the shipping agent or your Siemens representative. Refer to Figure 2.1 to iden- tify the different parts of the relay.
Note: To avoid damage to the relay, transport or
store the relay in the original packing mate­rial. Always transport the cradle assembly inside the case.
.
2.3 Mounting
The ISGS relay is typically installed in a switchgear unit or relay panel. The required panel opening and a side view of the relay are shown in Figure 2.2.
5.69
14.63
(371.5)
7.31
(185.7)
(144.5)
2.84
(72.1)
7.13
(181.0)
4X .25 (6.4) DIA
14.25
(362.0)
2
Figure 2.1 Case, Cradle, Paddles, and Cover of ISGS Relay
2.2 Storing
Extended storage of the relay should adhere to the following guidelines:
Store the relay in a clean, dry location in the original
packing material
Storage temperature range is -40°F to +167°F
(-40°C
to +75°C)
Note: This device contains electrolytic capacitors,
which can degrade over time when stored at temperatures over 86°F (30°C). Take care not to store the relay at high temperatures for extended periods.
After extended storage, connect the relay to its auxiliary volt­age source for one or two days prior to taking it into actual service. This serves to regenerate the electrolytic capacitors of the auxiliary supply.
(77.0)
6.06
(154.0)
6.19
(157.2)
(7.9)
7.06
(179.4)
7.06
(179.4)
(7.9)
MOUNTING PANEL
Figure 2.2 Mounting Dimensions
3.03
.31
.31
.63
(16.0)
.63
(16.0)
10-32
SCREWS
10-32
SCREWS
Siemens Energy & Automation, Inc. 5
Installation
2
Mount the relay using the following steps.
1. Install the relay M1-type case in the panel opening on the switchgear equipment.
2. Connect the case ground to the terminal lug on the back of the M1-type case as shown in Figure 2.3.
3. Wire as described in Section 2.4.
Use toothed washers to ensure solid metal contact through paint of cover and panel
Case ground, #12 or braided cable to good cubicle ground, as short as possible
IMPORTANT: Any unused terminals must remain discon­nected. They are for factory use only.
Relay Disabled 2
Relay Disabled 1
Impedance Sense
Impedance Source
Ground Monitor
BI Trip
BI B Switch
Power Input +
Power Input -
Top
BI1A 21 BI1B 22 BI2A 23 BI2B 24 BI3A 25 BI3B 26 BI4A 27 BI4B 28 Trip 3A 29 Trip 3B 30
19
20
17 15 13 11
18 16 14 12
41 VT1+ 42 VT1­43 VT2+ 44 VT2­45 VT3+ 46 VT3­47 NC (unused) 48 SEAbus Signal + 49 SEAbus Signal ­50 SEAbus Ref
Trip 2
Figure 2.3 Case Grounding
2.4 Wiring
Wire the ISGS relay after the case is installed. Connect the wiring to the applicable terminals to support the desired fea­tures. Refer to Figure 2.4 for terminal locations. Figure 2.5 shows the internal connections of the ISGS relay. To avoid injury to personnel or the equipment, perform power connec­tions after all other wiring has been completed.
Assure that all power is off before performing any wiring. Ter­minals 1 through 20 accept ring-tongue or forked spade ter­minals and are suitable for 14 AWG to 10 AWG wire. Terminals 21 through 60 are for directly inserting the appro­priate wire and are suitable for 22 AWG to 14 AWG wire.
Communications connections made to terminals 48 to 50 require shielded twisted pair wire.
CT connections should be made with the polarity end of the CT connected to current terminal marked with an asterisk (*).
BO1A 31 BO1B 32 BO2A 33 BO2B 34 AI1+ 35 AI1- 36 AI2+ 37 AI2- 38 AO1+ 39 AO1- 40
9
10
CTN-2
7531
8642
CTN-1*
CT3-2
CT3-1*
Figure 2.4 Terminal Locations
Case Ground
CT2-2
CT2-1*
CT1-2
CT1-1*
Trip 1
Trip Common
6 Siemens Energy & Automation, Inc.
Current Input
Voltage Input
BI B Switch
CT 1-1 CT 1-2 CT 2-1 CT 2-2
CT 3-1 CT 3-2
CT N-1 CT N-2
VT 1+ VT 1­VT 2+ VT 2-
VT 3+ VT 3-
Installation
2
ISGS
3 4 5 6 7 8 9
10 41
42 43 44 45 46
14
2 Trip 1
Trip Common
1
11
Trip 2
29
Trip 3
30
Relay Disabled 1
19 20
Relay Disabled 2
31
BO 1
32 33
BO 2
34
Binary Outputs
Trip Relays
Relay Disabled Alarm Contact
Breaker and Trip Source Monitor
BI Trip
Impedance Source Impedance Sense
Ground Monitor
1
Binary Input
Power Supply
2
3
4
V
H
Communications In
Data +
RxD
15
17 18 16
+
21
-
22
+
23
-
24
+
25
-
26
+
27
-
28
13 12
48
(3)
DC
DC
RS-485 SEAbus
RS-232
Front Panel
Communications Out
49
Data -
50
Reference
(2)
TxD
(7)
Reference Ground
+
-
Figure 2.5 Internal Connections
Note: The relay disabled contact should be wired to plant-wide distributed control system or external alarm.
Siemens Energy & Automation, Inc. 7
Installation
2
2.5 Communications
The ISGS relay must be connected to a host computer in order for it to communicate with other devices. The relay supports both RS-232 and RS-485 (optional) data inter­faces. The use of either of these data interfaces will allow the same level of access to the system as the front panel key­pad, but configuration through communications does not require a password.
The next section describes the connection to the interfaces. For more information about operating the ISGS relay via the data interfaces, refer to the documentation for the communi­cations software, such as WinPM or Wisdom. Keypad operations are described in Chapter 3.
2.5.1 PC Communications (RS-232)
The RS-232 interface (front port) is intended only for short­term connections to a portable computer. Use this interface to perform initial setup or to read the ISGS relay data logs or waveform buffers using an appropriate software program. To connect your PC to the front port, follow these instructions:
1. Remove the relay case front cover.
2. Locate the RS-232 connector on the front panel of the cradle assembly.
3. Connect the PC to the front panel RS-232 port using a standard DB-9 serial port connection cable (DB-9 male to DB-9 female or DB-25 female depending on the type of port on the computer). This connection does not require the use of special adapters or a null-modem cable.
2.5.2 Network Communications (RS-485)
The optional RS-485 interface (rear port) allows remote com­munication over a shielded twisted pair wire at distances of up to 4000 feet. Use this interface together with an appropri­ate software program for remote monitoring and control of the ISGS relay.
To connect the ISGS relay to your communications system, follow these instructions:
1. Locate the RS-485 connector on the rear of the M1 case.
2.6 Cradle Assembly
Some of the setup and maintenance procedures in this man­ual require removal of the relay cradle assembly from the drawout case. Use the following instructions for the proper removal and insertion of the cradle assembly.
IMPORTANT: The relay module contains CMOS circuits. Electro­static discharges into or around the relay cradle or any of its components must be avoided. Use grounding straps or touch a grounded metal sur­face before handling the relay cradle.
2.6.1 Removing
Use the following procedure to remove the cradle assembly from the case:
1. Remove the relay case front cover.
2. Remove the top and bottom connecting plugs (paddles).
3. Loosen the cradle assembly by pulling the top release lever to the left and the bottom release lever to the right until the assembly ejects from the case.
4. Grasp the cradle assembly by the edges of the front panel and pull it out of the drawout case.
5. Place the cradle assembly on an anti-electrostatic sur­face and perform the desired work.
2.6.2 Inserting
Use the following procedure to insert the cradle assembly into the drawout case:
1. Insert the cradle assembly until the release levers come in contact with the protrusions on the case.
2. Position the top and bottom release levers until the slots on the levers align with the protrusions on the case.
3. Use the release levers to finish inserting the cradle assembly into the case. Apply pressure to the cradle assembly front panel until the assembly fully seats in the case.
2. Use shielded twisted pair wire to connect pins 48, 49, and 50 to your electrical distribution system.
To connect the ISGS relay to your PC via the rear port
directly, use an RS-232 to RS-485 converter.
via modem, use an RS-232 to RS-485 converter and a
null modem.
8 Siemens Energy & Automation, Inc.
4. Insert the top and bottom paddles.
5. Check for proper insertion of the cradle assembly by seeing if the expected measured values are observed on the relay display.
6. Install the front cover.
User Interface
3 User Interface
Operation, parameter selection, and control of the ISGS relay are performed using the front panel controls and indicators. They consist of a 26-key membrane keypad, a 2-line by 16-character liquid crystal display (LCD), three light-emitting diodes (LEDs), and the front port.
3.1 Keypad
The relay can be controlled via the keypad, the front port, or the optional rear port. This manual covers only keypad oper­ations. For information about communicating with the ISGS relay via the data ports, refer to the documentation supplied with the communications software (WinPM or Wisdom).
The ISGS relay keypad allows access to any relay informa­tion or function for display or parameter changes where applicable. The keypad consists of 26 keys. Table 3.1 pro- vides a detailed description of each key type.
To access relay information or functions for display or modifi­cation, use the Arrow keys to scroll through relay addresses or use the Direct Addr key and the specific address number to go directly to the information or function.
Use the Double Arrow keys to scroll through the address blocks and use the Single Arrow keys to scroll within an address block.
3.2 Indicators
The indicators on the front panel display consist of three LEDs and a two-line LCD.
.
Key Name Function
Password Accesses the password function,
Direct Addr
l
Trip Log Displays the trip log.
Target Reset Resets the Trip LED.
Double Arrow Scrolls through the address
Single Arrow Scrolls through the addresses
F Saves new settings when followed
Numeric Used to enter an address number
which is required for programming relay settings.
Allows direct entry of addresses.
blocks.
within an address block.
by Enter, enters or exits subad­dress level, or switches to alter­nate parameter set when followed by 1 or 2 and Enter.
after pressing Direct Addr, or to enter a numeric setting.
3
3.2.1 LEDs
The LED indicators are used to provide general status infor­mation, which alerts the operator to an event or problem and prompts the operator to use the LCD to review the logs for more detailed information. The three LEDs and their func­tions are listed below.
LED Color Function
System Green Denotes the relay is operating properly
(always on when relay is in service).
Pickup Red Denotes a protective function is in
pickup.
Trip Red Denotes a protective function or
remote command has initiated a trip.
Both the Pickup and the System LED operate automatically and do not require a reset.
The System LED remains on as long as power is applied
and the relay is functioning properly.
The Pickup LED is illuminated as long as a protective
function is in pickup.
Decimal Point Indicates a decimal point or the
separation between month, day, and year, or between hours, min­utes, and seconds.
Plus/Minus Toggles between positive and
negative values.
Backspace Deletes one character to the left or
selects backwards.
Infinity Programs the setting to the high-
est possible value.
Enter Chooses the setting option, enters
a setting value, or confirms the address entered after pressing
Direct Addr.
Yes Accepts the displayed setting, or
replies yes to the displayed prompt.
No Rejects the displayed setting,
allows entry of a numeric setting, replies No to the displayed prompt, or selects forward.
Table 3.1 Front Panel Keys
Siemens Energy & Automation, Inc. 9
User Interface
3
The Trip LED is illuminated until the Target Reset key is depressed. Reset the Trip LED by momentarily depressing the Target Reset key.
Note: If the Trip LED is on and power is removed, it
will still be set to on when power is restored.
3.2.2 LCD
The two-line by sixteen-character LCD allows the viewing of parameters, measured data, and keypad entries. The LCD also displays messages returned by events such as a relay going into pickup.
Whenever a relay goes into pickup, in addition to lighting the pickup LED, the LCD shows a message that indicates which protection element is in pickup. A pickup message is dis­played as follows:
PICKUP FFF Pxxxx MM/DD hh:mm:ss
In this message
FFF is the two or three character ANSI pro-
tection code number, for example, 50, or 50N.
xxxx is a sequence of the characters 1, 2, 3,
and/or N, indicating which phase or combination of phases and neutral have picked up.
MM/DD hh:mm:ss is the date and time of the event.
Level 3 includes additional access to all matrixing, the
changing of which can cause a device reset.
Password configuration is described in Section 9.4.
To access any password protected information or function, either first enter the password (up to five digits) and then go to the desired address, or first access the address block and then enter the password as described in the following steps:
1. Press the Password key. The password dialog box appears.
Password:
2. Enter a password (00000 to 99999) using the number keys from the keypad. The LCD displays each digit entered as an @ symbol.
Password: @@@@@
3. Press the Enter key after completing the entry.
4. If a correct password has been entered, the dialog box displays a confirmation message that depends on the level password that was entered.
Password: User PW Three OK
These messages are displayed until superseded by another pickup, a trip message, a target reset, or a request by the operator to display other information.
3.3 Password Protection
A password should be used to prevent any accidental or unauthorized parameter changes. While relay information can be accessed for display without a password, all changes to parameter settings require a user password.
Note: The ISGS relay is not password protected
when making parameter changes through Wisdom software.
The ISGS relay offers three password protected access lev­els:
Level 1 consists of simple settings such as all protective
and setpoint settings that do not cause a reset. These simple settings include communications and time and date settings.
Level 2 consists of protective function settings such as
CT and VT ratios, the changing of which can cause a device reset.
For a level 1 or level 2 password, the word Three in the illustration above would be replaced by One and Two, respectively.
If the wrong password has been entered, the dialog box displays the following message:
Password: Rejected
5. When the confirmation message appears, press the Enter key. This action returns the display that was in use before entering the password.
For example, if the address block of the parameter to be changed was displayed prior to entering the password, the display returns to this address block and the device is ready to accept changes.
10 Siemens Energy & Automation, Inc.
User Interface
3.4 Menu
The ISGS relay menu (or memory map) is organized in a hier­archical structure that is made up of address blocks and addresses. The first level consists of address blocks. Each address block represents one complete function or two related functions and is identified by a unique four-digit num­ber ending in two zeros (for example, 1500). Refer to Figure 3.1.
The second level consists of individual addresses confined to an address block. Each address represents a part of a func­tionthe changeable parameteror the measured value of a displayed parameter. The parameter is identified by a unique four-digit number that consists of the first two digits of the address block and two digits indicating the parame­ters number within the address block (for example, 1502). Refer to Figure 3.1.
Block Function Address Parameter
A1500 Instantaneous
Phase Overcurrent (50)
High-Set Instanta­neous Phase Over­current (50HS)
A1900 Directional Phase
Time Overcurrent (67)
A2200 Overvoltage (59) --- ---
Figure 3.1 Example of Menu Structure Displaying Address Blocks with Two Related Functions, an Individual Function, and an Unavailable Function.
A complete ISGS relay menu with parameter listing is pro­vided in Appendix C. The various parameter settings are shown in the respective section describing the complete function.
1501
Function 50
1502
Pickup 50
1504
Delay 50
1510
Freeze Wfm 1 50
1511
Freeze Wfm 2 50
1512
Block 50
1551
Function 50HS
1552
Pickup 50HS
1560
Freeze Wfm 1 HS
1561
Freeze Wfm 2 HS
1901
Function
1902
Curve
1903
Pickup
1905
Time Dial
1906
Filter
1907
Impedance
1908
Direction
1910
Freeze Wfm 1
1911
Freeze Wfm 2
The LCD identifies functions that include parameters config­urable for A and B settings by preceding the functions address block number with the letter A or the letter B, depending on which parameter set is currently displayed. Refer to Figure 3.2.
3
A1500 Instantaneous Phase Overcurrent 50
Figure 3.2 LCD Display of a Function that Includes Parameters Configurable for A and B Settings.
In addition, when scrolling through the individual parameters of an ISGS relay, the LCD identifies each parameter that is configurable for A and B settings by preceding the parame­ters address number with the letter A or the letter B, depending on which parameter set is currently displayed. Refer to Figure 3.3
A1502 Pickup 50 110A
Figure 3.3 LCD Display of a Parameter that is Configurable for A and B Settings
When accessing the ISGS relay menu through the keypad, the Arrow keys allow scrolling through all available functions and parameters. If an option is not installed, the LCD only displays the address block that is reserved for this option. In this case, second level addresses are not available.
3.5 Standard Operating Procedures
Before attempting to display or configure any of the relay data, ensure that the relay has control power which is indi­cated by the system LED (green) being lit.
The steps for displaying data, configuring parameters, saving data, and switching to the alternate parameter set for either display or configuration are described in detail in Table 3.1, Standard Operating Procedures.
Only certain protective function parameters have two set­tings. All A settings are grouped under parameter set A, and all B settings are grouped under parameter set B. Each parameter set automatically includes all the regular parame­ters that can be programmed to only one setting at a time and, therefore, apply to both sets. Examples are protective function enable settings and matrixed output contacts such as waveform buffers and blocking. For more information on parameter sets, refer to Section 6.11.
Siemens Energy & Automation, Inc. 11
3
User Interface
Displaying function names (address blocks), parameter names and their settings or values (addresses), and subpa­rameter settings (subaddress, where applicable), does not require a password (except for viewing the password itself). Data can be displayed by following steps 1 to 3 of the stan­dard operating procedures described in Table 3.1. Viewing passwords requires the entry of an appropriate level user password (refer to Section 3.3 for more information on passwords).
Configuring parameters requires a password. Use steps 1 and 2 or steps 1 to 3 to display the desired parameter or its subparameters. Continue with step 4 to make changes to this parameter or subparameter.
When leaving a function or before scrolling to the waveform parameters of the same function, the relay prompts to indi­cate the end of the password operation and whether the changes made so far shall be saved. When the message End of Password Operation ? appears, press the Ye s key to continue to the next function. Press the No key to scroll back through the parameters of this one function. Pressing the Ye s key returns the message SAVE NEW SETTINGS ?. Press the Yes key again to save the settings, or press the No key to abort any changes made after the last saving proce­dure.
12 Siemens Energy & Automation, Inc.
Table 3.1 Standard Operating Procedures
Step Task Description
Display Data
1 Display data at
Address Block (xx00)
Use Double Arrow keys to scroll forward or backward between address blocks.
OR
Press Direct Addr key; enter address of desired address block using the numeric keypad; press Enter key. To view passwords, carry out step 4 before continuing with the next step.
User Interface
3
2 Display data at
Address (xxxx)
3 Display data at
Subaddress (0xx)
4 Enter Password Press Password key; enter the password; press Enter key twice to return to screen displayed last before
5 Configure at
Address (xxxx)
6 Configure at
Subaddress (0xx)
Use Single Arrow keys to scroll forward or backward between parameter addresses.
Skip step 3 if function has no subaddresses.
OR
Press Direct Addr key; enter address of desired parameter using the numeric keypad; press Enter key.
Skip step 3 if function has no subaddresses.
Press F key once to enter subaddress level; use Single Arrow keys to scroll forward or backward between subaddresses.
Press F key again to return to address level.
Configure Parameters
password entry.
Leaving an address block, leaving a function within an address block, or before scrolling to the waveform parameters within a function prompts for renewed password entry.
For password levels, proper password entry, and display messages, refer to Section 3.3.
Display cursor is blinking (otherwise repeat step 4).
Change displayed value by entering a new value using the keypad. Press Enter key.
Change displayed selection by pressing the No key to scroll forward through options until desired option appears. Press Enter key.
Skip step 6 if function has no subaddresses.
Press F key once to enter subaddress level; use Single Arrow keys to scroll forward or backward between subaddresses.
Change displayed selection by pressing No key to scroll forward through options until desired option appears. Press Enter key.
Press F key again to return to address level.
Save Changes
7 Enter Save
Procedure
Undo Changes To abort any changes made, press No key. After message SAVING PROCEDURE ABORTED appears,
Save Changes To save settings and reset relay to new parameters, press Yes key followed by Enter key. After message
8 Switch
Parameter Set
9 Display/Config-
ure Alternate Parameter Set
Press F key. At the blinking cursor position, the letter F is displayed. Press Enter key. Message SAVE NEW SETTINGS? appears.
press Enter key to return to screen displayed last before aborting settings.
Settings can be undone any time while still in the same function by simply returning to the parameter and assigning a new value.
NEW SETTINGS SAVED appears, press Enter key to return to screen displayed last before saving settings.
Leaving an address block, leaving a function within an address block, or before scrolling to the waveform parameters within a function prompts for the saving of the function settings.
Switch Parameter Set
Press F key followed by either 1 (for normal settings) or 2 (for alternate settings) on the numeric keypad. The message PARAMETER SET COPIED TO EDIT appears. Press Enter key.
Display shows address block (xx00) with either A or B prefix in address (Axx00 or Bxx00). A indicates parameter set 1; B indicates parameter set 2.
Repeat steps 1 to 3 or steps 1 to 7 to display or configure the alternate parameter set.
Siemens Energy & Automation, Inc. 13
3
Notes:
14 Siemens Energy & Automation, Inc.
Hardware Configuration
4 Hardware Configuration
This chapter explains the device startup and how to config­ure the basic ISGS relay parameters. The relay must be con­figured with certain system parameters, such as phase sequence and frequency. In addition, information regarding the manner in which the ISGS relay is connected in the installation must be configured.
All parameter changes require a password. Refer to Section 3.3 for instructions on how to enter your password. Viewing parameter settings does not require a password.
Note: The ISGS relay is not password protected
when making parameter changes through Wisdom software.
Perform parameter changes using steps 1 through 9 of the standard operating procedure described in Section 3.5.
4.1 Startup
Block Function Address Parameter
0000 Power On/
Configuration Display
This section describes the content of address block 0000 represented by the initial Power On display and the initial Power On Meter display.
When the relay is powered on, following a brief hardware ini­tialization check, the green System LED illuminates and the LCD shows the contents of address 0000. First, the Power On display indicates your relay configuration. After approxi­mately five seconds, the Power On display is replaced by the Power On Meter display showing two values. Prior to placing the relay in service, verify that the correct relay configuration was preloaded at the factory. To return to the Power On dis­play, press the Direct Addr key and key in 0000 followed by the Enter key.
4.1.1 Power On Display
The two lines of the Power On display indicate your relay configuration. Line 1 contains the function address 0000 and the relays firmware version. Line 2 identifies the relays cata­log number which depends on the options you ordered with your relay (see Figure 4.2 for catalog numbers).
Reading from left to right in Figure 4.1, line 1 shows the address block 0000 and the ISGS firmware version ISGS-3V3.00. Line 2 displays the catalog number D553100VSDF00000. The first character of this number, D, indicates a 120 VAC power supply, the fourth character, 3, voltage inputs for energy metering, and the eighth through eleventh characters, VSDF, indicate Under/Overvoltage pro- tection, Negative Sequence Voltage protection, Directional Overcurrent protection, and Under/Overfrequency protec­tion, respectively.
--- ---
0000 ISGS-3V3.00 D553100VSDF00000
Figure 4.1 Power On Display
123 4567 891011 121314
-
ISGS
Nominal Supply Voltage
48 VDC 125 VDC 120VAC 250VDC
Phase CT Secondary Rating
1A 5A
Neutral or Ground CT Rating
1A 5A
Voltage Inputs, Power Metering, RS-485 Communications
Without With
Additional I/O
Without With
*
Under/Overvoltage Protection (27/59), Negative Sequence Voltage Protection (47/47N), Directional Overcurrent Protection (67/67N), Under/Overfrequency Protection (81 U/O)
Without With
*
* Voltage Inputs required.
A B D E
1 5
1 5
00 31
0
I
0000
VSDF
---
0 0 00
Figure 4.2 Relay Configuration (Catalog Number)
4.1.2 Power On Meter Display
The Power On Meter display consists of two measured val­ues. The default setting for Line 1 displays average current, and Line 2 shows average current demand. The type of default values displayed can be changed in address block 7000, Operating Parameters, described in Chapter 7.
Iavg = xx A Idmdavg = xx A
Figure 4.3 Power On Meter Display
The Power On Meter display is replaced with other informa­tion anytime an event message is displayed or the LCD is used to set parameters or check logs. To return the LCD to the Power On Meter Display, press the Trip Log key followed by the Target Reset key.
4
Siemens Energy & Automation, Inc. 15
Hardware Configuration
4
4.2 Device Configuration
The Device Configuration function allows you to set up the ISGS relay to match line frequency, phase sequence, and breaker connection settings of your system.
4.3 Setting Binary Input Voltages
Binary inputs are jumpered to correspond to the auxiliary supply voltage of the relay in which they are installed. The inputs will correctly respond to DC or AC depending on the jumpering. The jumpers can be placed to allow the inputs to work with any of the available voltages, independent of the auxiliary supply voltage. Refer to Figure 4.5 and Table 4.1.
13
ISGS Relay
125 VDC Bus
21
BI 1
22
12
Figure 4.4 Binary Inputs Independent of Supply Voltage
Table 4.1 lists the possible jumper positions for setting
binary input voltages. The numbers in this table each refer to a pin from and to which a jumper can be moved.
Table 4.1 Jumper Positions
120 VAC
Aux Relay
120 VAC Source
to be Monitored
1000 Device Configuration
Address Parameter Options
1002 Frequency 50Hz or 60Hz
1003 Phase Sequence 123 (ABC) or 132 (ACB)
1004 Breaker
Connection
1005 Trip Time 0.01-32.00 s (0.01 s steps)
Trip 1, Trip 2, Trip 3, Trip 1 & 2, Trip 1 & 3, Trip 2 & 3, or Trip 1 & 2 & 3
The frequency parameter (1002) must be set to the nominal frequency of your system. Phase sequence (1003) selects the phase sequence of your system as it enters the ISGS relay. The breaker connection parameter (1004) selects the trip contact that your breaker is connected to. Many func­tions use this parameter to determine if the device is attempting to open the breaker. Breaker failure can be initi­ated by either one of the three trips (if the Breaker Failure function is enabled). The default is set to Trip 1.
Voltage Supply
48 V X111-X112 X23-X22 X34-X35 X46-X47
125 V (Default)
120 VAC X110-X111 X24-X23 X35-X36 X47-X48
250 VDC X111-X112 X23-X22 X34-X35 X46-X47
h
BI 1 Te rm in a ls 21/22
X13-X14 X25-X26 X37-X38 X49-X50
X16-X17 X28-X29 X40-X41 X52-X53
X19-X20 X31-X32 X43-X44 X55-X56
X111-X112 X23-X22 X34-X35 X46-X47
X13-X14 X25-X26 X37-X38 X49-X50
X17-X18 X29-X30 X41-X42 X53-X54
X19-X20 X31-X32 X43-X44 X55-X56
X14-X15 X26-X27 X38-X39 X50-X51
X17-X18 X29-X30 X41-X42 X53-X54
X20-X21 X32-X33 X44-X45 X56-X57
X14-X15 X26-X27 X38-X39 X50-X51
X17-X18 X29-X30 X41-X42 X53-X54
X19-X20 X31-X32 X43-X44 X55-X56
BI 2 Terminals 23/22
BI 3 Terminals 25/26
BI 4 Te rm in a ls 27/28
16 Siemens Energy & Automation, Inc.
Hardware Configuration
Figure 4.5 shows option board 2 and its jumpers. The draw­ing indicates the jumpers associated with each binary input. The enlarged set of pins shows an example of pin labeling and a jumper at location X17-X18.
350
350
350
350
Changing Jumper Positions
IMPORTANT:
The relay module contains CAMS circuits. Electro­static discharges into or around the relay cradle or any of its components must be avoided. Use grounding straps or touch a grounded metal sur­face before handling the relay cradle.
1. Remove the cradle assembly from the case as
described in Section 2.6.1.
2. Set the relay on its back.
3. With a small screwdriver, remove the four screws (on the
sides of the relay) that hold the front panel to the relay cradle.
4. Lift the front panel and hang it in the slots provided on
the left side of the casing. Take care not to damage the ribbon cables that connect the electronics in the cradle to the front panel electronics.
5. Disconnect the two ribbon cables from the main board
and the option board 2. The main board is the center board which is screwed to the option board 2 on its right.
6. Withdraw these two attached boards and set them on
the workplace with the jumper side up (see Figure 4.5).
7. Each jumper is pushed over two out of three pins. Each
pin is labeled with numbers identical to those in Tab l e 4 . 1. The numbers of two side-by-side pins repre­sent a possible jumper position.
4
.22 163 .22 163 .22 163 .22 163
Figure 4.5 Option Board 2 with Binary Inputs
8. With a small needle nose pliers, lift the desired jumper
off of its pins and push it down over another two pins of the same set.
Example: In Figure 4.5, the jumper is over pins X17 and X18, a default setting for a 125 V power supply. For a 48 V power supply, set this jumper to X16-X17.
Repeat this step until all desired jumpers are reposi­tioned.
9. Insert the attached boards back into the cradle. The
connectors of each board must snap into the terminals of the casing.
10. Reattach the two ribbon cables to the main board and
the option board 2.
11. Unhook the front panel and carefully place it over the
cradle. Lift the front panel slightly to make sure that the ribbon cables connected to the front panel are posi­tioned in their assigned space to prevent damage.
12. Insert and tighten the four front panel screws.
13. Insert the cradle into the casing as described in
Section 2.6.2.
Siemens Energy & Automation, Inc. 17
4
Hardware Configuration
4.4 CT Configuration
The CT Configuration function allows you to set up the ISGS relay to match the phase CT primary rating, the neutral or ground CT primary rating, and the CT inputs normal power flow setting of your system. For CT connections refer to Figure 4.8.
Main Bus
ISGS
ISGS
Power
Normal Power Flow
(Into CT Polarity Mark)
Figure 4.6 Normal/Reverse Power Flow
(Out of CT Polarity Mark)
Power
Reverse Power Flow
4.5 VT Configuration
Use this address block to configure the ISGS relay to match the VT primary rating and the VT connection setting for your system. These settings are available only if the voltage input option is installed on the relay.
1100 CT Configuration
Address Parameter Options
1101 Phase CT Primary
Rating
1102 Neutral or Ground
CT Primary Rating
1104 Power Flow Normal or Reverse
The phase (1101) and neutral/ground (1102) CT primary rat­ings are independently configurable. However, when a resid­ual sensing method is used for ground fault protection, the primary current ratings for the neutral CT and the phase CT must be equal. The CT secondary ratings (1A or 5A) are set at the factory and are not changeable from the front panel.
Power flow is also referred to as top feed or bottom feed. If the power enters the polarity mark on the CTs, set the Power Flow parameter (1104) to Normal. If power leaves the polarity mark, enter Reverse. Figure 4.6 illustrates examples of nor- mal and reverse power flow.
18 Siemens Energy & Automation, Inc.
5-8000 A (1 A steps)
5-8000 A (1 A steps)
Hardware Configuration
1200 VT Configuration
Address Parameter Options
1201 Primary Rating 120-138,000 V (1 V steps)
1202 VT Connect Line-to-Line or Line-to-Neutral
1203 Sec. VT Rating 100-120 V (1 V steps)
Voltage transformers may be connected in either of two ways:
Two VTs connected open delta-open delta
Three VTs connected wye-wye
For brevity, the open delta connection is referred to as L-L (line-to-line), while the wye connection is referred to as L-N (line-to-neutral). Wye-delta or delta-wye connection of VTs is not allowed. Figure 4.7 shows the correct VT connections and polarities.
Voltage transformers are specified with an input to output voltage ratio (for example, 12000:120). The secondary volt­age rating of the VTs can be set by the Secondary Voltage Rating parameter (1203).
Before leaving the hardware configuration blocks, (only when changing parameters, not when viewing) the ISGS relay dis­plays the message END OF PASSWORD OPERATION?. Press the No button to return to one of the configuration blocks. The message PRESS ANY KEY TO CONTINUE appears. Press any key to return to the screen displayed last before the message prompt appeared. Press the Ye s button if you are finished with the configuration changes. The device prompts you to save the settings.
Press the Yes button to save the settings. The relay
resets and displays the Power On and Power Meter On displays.
123
123
Wye-Wye VT Connection
41
42
43
44
45
46
41
42
ISGS
V1
4
V2
V3
ISGS
V12
Press the No button if you do not want to save the
changes The message SAVING PROCEDURE ABORTED appears. Press Enter to return to the last address block.
Note: For CT configuration, CTs on the neutral
must be the same rating as other CTs for residual ground sensing, directional neutral sensing, or direct ground sensing.
For VT connections, VTs must be either wye-wye or delta-delta. Wye-delta or delta-wye connec­tions are not permissible.
Open Delta-Open Delta VT Connection
Figure 4.7 Voltage Transformer Connections
Siemens Energy & Automation, Inc. 19
43
44
45
46
V23
V31
Hardware Configuration
4
1 2 3
ISGS
1
3
4
2
56
3
7
8
N
910
52 52
Three Phase Current with Residual Ground Sensing
1 2 3
ISGS
1
3
4
2
56
3
7
8
1 2 3
3
ISGS
1
4
N
2
56
3
7
8
N
910
Three Phase Current with Direct Neutral Sensing
1 2 3
3
ISGS
1
4
G
2
56
3
78
52
N
910
52
N
910
Three Phase Current with Zero Sequence CT Three Phase Current with Direct Ground Sensing
52 = Power Circuit Breaker
= ISGS Internal CT
Figure 4.8 Current Transformer Configuration
20 Siemens Energy & Automation, Inc.
Protective Function Configuration
5 Protective Function Configuration
5.1 Overview
This chapter explains how to set the parameters for the protective functions of the ISGS relay.
Password
All parameter changes require a password. Refer to Section 3.3 on how to enter your password. Viewing parameter settings does not require a password.
Note: The ISGS relay is not password protected
when making parameter changes through Wisdom software.
Configuration Steps
Perform parameter changes using steps 1 through 9 of the standard operating procedures described in Section 3.5.
Parameter Sets
Many protective functions can be set to two different param­eter setsset A and set B. These functions are indicated by the letter A or B preceding the address block number. Alter­nate sets are useful for seasonal settings or for special oper­ating periods. Either set can be selected (in address block
7100) to be the active set that controls the relay operation. The parameters for both sets are entered in the relevant address blocks. Waveform capture buffer settings apply to both parameter sets. Unless you do not desire an alternate set, configure both sets when configuring the relay.
Note: The settings for parameter sets A and B are
entered in the address block. However, the parameter set which the ISGS relay is actively using is selected at address block
7100. Refer to Section 6.11 for discussion of parameter sets.
Actions on Pickup or Trip
Protective functions can be set to have actions occur on pickup or on trip. Binary outputs can be set to be actuated on pickup of a protective function. A protective function is set to trip a breaker by assigning the trip contact that is con­nected to the breaker (default is Trip 1). Binary outputs can also be assigned to trip a breaker. It is possible, however to have a protective function enabled and not assigned to any output. Events and their sequences are entered in the trip log as usual, but the breaker will not be affected. This setting is useful for monitoring and alarming without tripping, and for waveform capture. For more information on the control of inputs and outputs, refer to Chapter 6.
Pickup
When testing induction disk relays, an established practice is to set the pickup value to 1.0 A of secondary CT output. The time overcurrent curves will show a pickup, but the relay will not trip in a predefined repeatable manner until it reaches 1.3 to 1.5 A. With numerical relays like the ISGS, however, a sus­tained pickup indication means definite operation. To account for measurement inaccuracies, and to guarantee that the relay will never trip at 100% of pickup or below, the pickup point is set at 106% of the pickup setting to avoid any unintended nuisance trips.
Neutral or Ground
The availability of protective functions for neutral or ground depends on how the external CTs are connected. If a ground or zero-sequence CT is used and connected to the fourth internal CT, the ground or neutral protective function is a ground function. If the fourth CT is connected in the common return of the other three internal CTs (residual), the function is indicated as being neutral. There does not need to be an explicit selection of neutral or ground.
Custom Curve
The custom curve is one user-defined curve that can be used by one or more protective functions that have the cus­tom curve option in the curve list.
Wisdom Software
While the ISGS relay protective functions can be completely configured manually using the LCD and the keypad, Wisdom software allows faster and easier configuration when it is used on a PC connected to either data port. For data port connections refer to Section 2.5.
5.2 Instantaneous Phase Overcurrent (50)
The Instantaneous Phase Overcurrent function consists of a phase instantaneous overcurrent function and an adjustable delay. This function begins timing when any individual phase current exceeds the pickup at 100% of set pickup point and drops out at 95% of the pickup point.
A1500 Instantaneous Phase Overcurrent (50)
Address Parameter Option
1501 Function Enabled or Disabled
1502 Pickup 5 A CTs: 1-120 A
1 A CTs: 0.2-24 A (0.1 A steps)
1504 Time Delay 0-60 s (0.01 s steps)
1510 Freeze Wfm1 on Pickup, on Trip, or None
1511 Freeze Wfm2 on Pickup, on Trip, or None
1512 Blocked by None, 50HS & 50HSN, 50 HSN,
or 50HS
The function can be enabled or disabled (1501).
The range of the pickup value (1502) depends on the sec­ondary phase CT rating (1 A or 5 A), and the value is in sec­ondary amperes.
The time delay (1504) represents the time between pickup and trip and can be adjusted from 0 to 60 seconds in steps of 0.1 second. If the function remains in pickup for longer than the time delay, the function causes a trip. The delay can also be set to infinity so that the function never times out.
Each of the two waveform capture buffers (1510 and 1511) can be independently programmed to freeze snapshots on pickup or trip.
The function is able to actuate any binary output contact on pickup, and any trip or binary output contact on trip.
5
Siemens Energy & Automation, Inc. 21
Protective Function Configuration
5
5.3 High-Set Instantaneous Phase Overcurrent (50HS)
The High-Set Instantaneous Phase Overcurrent function causes an undelayed trip when any individual measured phase current exceeds the preprogrammed threshold (pickup value). The relay will trip at 100% of the set pickup point.
A1500 High-SetInstantaneous Phase Overcurrent (50HS)
Address Parameter Option
1551 Function Enabled or Disabled
1552 Pickup 5A CTs: 5-120 A or
1A CTs: 0.2-24 A (0.1 A steps)
1560 Freeze Wfm1 on Trip, or None
1561 Freeze Wfm2 on Trip, or None
The function can be enabled or disabled (1551). The range of the pickup value (1552) depends on the secondary phase CT rating (1 A or 5 A) and the value is in secondary amperes.
Each of the two waveform capture buffers (1560 and 1561) can be independently programmed to freeze snapshots on trip.
The function is able to actuate any binary output contact on pickup, and any trip or binary output contact on trip.
The Instantaneous Neutral or Ground Overcurrent function can be enabled or disabled (1601). The form of protection provided depends on the manner in which the external CTs are connected to the ISGS relay. Figure 4.5 in Chapter 4 shows correct CT connections and polarities.
The range of the pickup value (1602) depends on the sec­ondary neutral CT rating (1 A or 5 A) and the value is in sec­ondary amperes.
The time delay (1604) represents the time between pickup and trip and can be adjusted from 0 to 60 seconds in steps of 0.1 second. If the function remains in pickup for longer than the time delay, this parameter causes a trip. The delay can also be set to infinity so that the function never times out.
Each of the two waveform capture buffers (1610 and 1611) can be independently programmed to freeze snapshots on pickup or trip.
The function is able to actuate any binary output contact on pickup, and any trip or binary output contact on trip.
5.5 High-Set Instantaneous Neutral or Ground Overcurrent (50HSN)
The High-Set Instantaneous Neutral or Ground Overcurrent function causes an undelayed trip when any individual mea­sured phase current exceeds the preprogrammed threshold (pickup value). The relay will trip at 100% of the set pickup point.
5.4 Instantaneous Neutral or Ground Overcurrent (50N)
The Instantaneous Neutral or Ground Overcurrent function has an adjustable delay whose input is the current measured by the neutral CT. It begins timing when the neutral or ground current exceeds the pickup value. The ISGS relay will pickup at 100% of set pickup point and drop out at 95% of the pickup point.
A1600 Instantaneous Neutral or Ground Overcurrent
(50N)
Address Parameter Option
1601 Function Enabled or Disabled
1602 Pickup 5 A CTs: 1-120 A or
1 A CTs: 0.2-24 A (0.1 A steps)
1604 Time Delay 0-60 s (0.01 s steps)
1610 Freeze Wfm1 on Pickup, on Trip, or None
1611 Freeze Wfm2 on Pickup, on Trip, or None
1612 Blocked by None, 50HS & 50HSN, 50HSN,
or 50HS
A1600 High-Set Instantaneous Neutral or Ground
Overcurrent (50HSN)
Address Parameter Option
1651 Function Enabled or Disabled
1652 Pickup 5 A CTs: 5-120 A or
1 A CTs: 0.2-24 A (0.1 A steps)
1660 Freeze Wfm1 on Trip, or None
1661 Freeze Wfm2 on Trip, or None
The High-Set Instantaneous Neutral or Ground Overcurrent function can be enabled or disabled (1651).
The range of the pickup value (1652) depends on the sec­ondary phase CT rating (1 A or 5 A) and the value is in sec­ondary amperes.
Each of the two waveform capture buffers (1660 and 1661) can be independently programmed to freeze snapshots on trip.
The function is able to actuate any binary output contact on pickup, and any trip or binary output contact on trip.
22 Siemens Energy & Automation, Inc.
Protective Function Configuration
5.6 Phase Time Overcurrent (51)
The Phase Time Overcurrent function uses a selected time overcurrent characteristic curve to determine the trip time for the applied phase currents. The defined characteristic curves are valid over a range of multiple of pickup values. The func­tion also includes the ability to select a customer defined curve. This function is always enabled. Refer to Appendix A for detailed trip curve information.
A1700 Phase Time Overvurrent (51)
Address Parameter Option
1702 Curve Inverse
1703 Pickup 5 A CTs: 0.5-20 A or
1705 Time Dial 0.1-9.9 (0.1 steps)
1706 Filter rms or fundamental
1709 Reset Instantaneous or Disk Emulation
1710 Freeze Wfm1 on Pickup, on Trip, or None
1711 Freeze Wfm2 on Pickup, on Trip, or None
1712 Blocked by None, 50HS, 50HSN, or
The Curve parameter (1702) allows the selection of the pre­programmed characteristic curve used by this function. The ISGS relay comes with nine standard and one custom over­current characteristic curves that can be adjusted with the Time Dial parameter. The custom curve is a user-definable protective curve that integrates with instantaneous reset. The lower limit of the custom curve is 1.10. The maximum time to trip is the time at 1.10.
The range of the pickup value (1703) depends on the sec­ondary phase CT rating (1 A or 5 A) and the value is in sec­ondary amperes. The function begins timing when any individual phase current exceeds the pickup current setting.
Note: The pickup point is 1.06 of the pickup set-
ting. Refer also to paragraph on Pickup in Section 5.1.
Short Inverse Long Inverse Moderately Inverse Custom Very Inverse Extremely Inverse Definite Inverse Slightly Inverse
2
T Without Limit
I
1 A CTs: 0.1-4 A (0.1 A steps)
50HS & 50 HSN
The Reset parameter (1709) offers instantaneous or disk emulation settings. Selecting Instantaneous causes the relay to clear the timer when the current drops below the pickup threshold. Selecting Disk Emulation causes the relay to simu­late the integrating disk characteristics of electromechanical relays, where the delay time decays over time. With disk emulation, a relay that continuously picks up and drops out will eventually trip. Set this parameter to Instantaneous when using a custom curve.
Each of the two waveform capture buffers (1710 and 1711) can be independently programmed to freeze snapshots on pickup or trip.
The function is able to actuate any binary output contact on pickup, and any trip or binary output contact on trip.
5.7 Neutral Time Overcurrent (51N)
The Neutral Time Overcurrent function uses a selected time overcurrent characteristic curve to determine the trip time for the applied current at the fourth current input. The defined characteristic curves are valid over a range of multiple of pickup values. The function also includes a customer defined curve. Refer to Appendix A for detailed trip curve informa­tion.
A1800 Neutral Time Overcurrent (51N)
Address Parameter Option
1801 Function Enabled or Disabled
1802 Curve Inverse
1803 Pickup 5 A CTs: 0.5-20 A or
1805 Time Dial 0.1-9.9 (0.1 steps)
1806 Filter rms or fundamental
1809 Reset Instantaneous or Disk Emulation
1810 Freeze Wfm1 on Pickup, on Trip, or None
1811 Freeze Wfm2 on Pickup, on Trip, or None
1812 Blocked by None, 50HS, 50HSN, or
Short Inverse Long Inverse Moderately Inverse Custom Very Inverse Extremely Inverse Definite Inverse Slightly Inverse
2
T Without Limit
I
1 A CTs: 0.1-4 A (0.1 A steps)
50HS & 50 HSN
5
The Time Dial parameter (1705) used for the selected curve allows the time-to-trip of the curve to be raised or lowered The dial can be adjusted from 0.1 to 9.9 in steps of 0.1.
The Filter parameter (1706) sets the sensing method used by the function in its pickup calculations. The rms filter uses fun­damental current plus harmonics, while the fundamental filter ignores harmonics.
The Neutral or Ground Time Overcurrent function can be enabled and disabled (1801).
The Curve parameter (1702) allows the selection of the pre­programmed characteristic curve used by this function. The ISGS relay comes with nine standard and one custom over­current characteristic curves that can be adjusted with the Time Dial parameter. The custom curve is a user-definable
Siemens Energy & Automation, Inc. 23
5
Protective Function Configuration
protective curve that integrates with instantaneous reset. The lower limit of the custom curve is 1.10. The maximum time to trip is the time at 1.10.
The range of the pickup value (1803) depends on the sec­ondary phase CT rating (1 A or 5 A) and the value is in sec­ondary amperes.
The Time Dial parameter (1805) used for the selected curve allows the time-to-trip of the curve to be raised or lowered. The dial can be adjusted from 0.1 to 9.9 in steps of 0.1.
The Filter parameter (1806) sets the sensing method used by the function in its pickup calculations. The rms filter uses fun­damental current plus harmonics, while the fundamental filter ignores harmonics.
The Reset parameter (1709) offers instantaneous or disk emulation settings. Selecting Instantaneous causes the relay to clear the timer when the current drops below the pickup threshold. Selecting Disk Emulation causes the relay to simu­late the integrating disk characteristics of electromechanical relays, where the delay time decays over time. With disk emulation, a relay that continuously picks up and drops out will eventually trip. Set this parameter to Instantaneous when using a custom curve.
Figure 5.1 Blocking Capability Diagram
Each of the two waveform capture buffers (1810 and 1811) can be independently programmed to freeze snapshots on pickup or trip.
The function is able to actuate any binary output contact on pickup, and any trip or binary output contact on trip.
5.8 Blocking Capability for Breaker or Interrupter Saving
High-set instantaneous phase overcurrent (50HS) and high­set instantaneous neutral or ground overcurrent (50HSN) functions have the capability to block 50, 51, 50N, and 51N selectively to prevent opening an interrupting device should the fault current exceed the rating of the device.
This function is used to keep an electrically-operated load break switch, recloser, or aging circuit breaker from attempt­ing to interrupt current beyond its capability or rating. It must be used in conjunction with a slight delay (25 ms) in 50 so that 50HS can pickup or trip before 50 times out and trips. Should these parameters be set, a fault large enough to cause 50HS to pickup or trip before 50 has timed out will prevent 50 and/or 51, 50N, and 51N from tripping.
50HS/N can also be matrixed to an output contact to block differential tripping of a transformer differential relay when a fault is between the interrupter and the high side (bushings) of the transformer.
5.9 Directional Phase Time Overcurrent (67)
The Directional Phase Time Overcurrent function uses a selected time overcurrent characteristic curve to determine the trip time for the applied phase currents, utilizing the volt­ages present on the VTs to determine current direction. The defined characteristic curves are valid over a range of multi- ple of pickup values. The function also includes a customer defined curve. Refer to Appendix A for detailed trip curve information. This function is only available if the voltage input option is installed.
A1900 Directional Phase Time Overcurrent (67)
Address Parameter Option
1901 Function Enabled or Disabled
1902 Curve Inverse
1903 Pickup 5 A CTs: 0.5-20 A or
1905 Time Dial 0.1-9.9 (0.1 steps)
1906 Filter rms or fundamental
1907 Impedance 0-90°
1908 Direction Forward or Reverse
1910 Freeze Wfm 1 on Pickup, on Trip, or None
1911 Freeze Wfm 2 on Pickup, on Trip, or None
Short Inverse Long Inverse Moderately Inverse Custom Very Inverse Extremely Inverse Slightly Inverse Definite Inverse
2
T Without Limit
I
1 A CTs: 0.1-4 A (0.1 A steps)
24 Siemens Energy & Automation, Inc.
Protective Function Configuration
The Directional Phase Time Overcurrent function can be enabled or disabled (1901).
The Curve parameter (1902) allows the selection of the pre­programmed characteristic curve used by this function. The ISGS relay comes with nine standard overcurrent character­istic curves that can be adjusted with the Time Dial parame­ter. The custom curve is a user-definable protective curve that integrates with instantaneous reset. The lower limit of the custom curve is 1.10. The maximum time to trip is the time at 1.10.
The range of the pickup value (1903) depends on the sec­ondary phase CT rating (1 A or 5 A) and the value is in sec­ondary amperes. The function begins timing when any individual phase current exceeds the pickup current setting.
The Time Dial parameter (1905) used for the selected curve allows the time-to-trip of the curve to be raised or lowered The dial can be adjusted from 0.1 to 9.9 in steps of 0.1.
The Filter parameter (1906) sets the sensing method used by the function in its pickup calculations. The rms filter uses fun­damental current plus harmonics, while the fundamental filter ignores harmonics.
Impedance (1907) sets the angle used by this function. Impedance determines the direction of current flow being measured and can be set from 0 to 90 degrees. The direc­tional characteristic (line) in the complex impedance plane is shown in Figure 5.2. The directional characteristic is always perpendicular to the line impedance vector.
The sensing direction (1908) can be set to forward or reverse. The forward setting allows the directional protection element to pickup on fault current only in the direction oppo­site to normal power flow.
Each of the two waveform capture buffers (1910 and 1911) can be independently programmed to freeze snapshots on pickup or trip.
The function is able to actuate any binary output contact on pickup, and any trip or binary output contact on trip.
5.10 Directional Neutral or Ground Time Overcurrent (67N)
The Directional Neutral or Ground Time Overcurrent function uses a selected time overcurrent characteristic curve to determine the trip time for the applied current at the fourth current input, utilizing the voltages present on the VTs to determine current direction. The defined characteristic curves are valid over a range of multiple of pickup values. The function also includes a customer defined curve. Refer to Appendix A for detailed trip curve information. This func- tion is only available if the voltage input option is installed.
A2000 Directional Neutral or Ground Time Overcurrent
Address Parameter Option
(67N)
2001 Function Enabled or Disabled
2002 Curve Inverse
2003 Pickup 5 A CTs: 0.5-20 A or
2005 Time Dial 0.1-9.9 (0.1 steps)
2006 Filter rms or fundamental
2007 Impedance 0-90°
2008 Direction Forward or Reverse
2010 Freeze Wfm1 on Pickup, on Trip, or None
2011 Freeze Wfm2 on Pickup, on Trip, or None
Short Inverse Long Inverse Moderately Inverse Custom Very Inverse Extremely Inverse Definite Inverse Slightly Inverse
2
T Without Limit
I
1 A CTs: 0.1-4 A (0.1 A steps)
5
The Directional Neutral or Ground Time Overcurrent function can be enabled or disabled (2001).
The Curve parameter (2002) allows the selection of the pre­programmed characteristic curve used by this function. The ISGS relay comes with nine standard overcurrent character­istic curves that can be adjusted with the time dial parameter (see below). The custom curve is a user-definable protective curve that integrates with instantaneous reset. The lower limit of the custom curve is 1.10. The maximum time to trip is the time at 1.10.
Figure 5.2 Directional Characteristic
Siemens Energy & Automation, Inc. 25
Protective Function Configuration
5
The range of the pickup value (2003) depends on the sec­ondary phase neutral CT rating (1 A or 5 A) and the value is in secondary amperes. The function begins timing when any individual neutral current exceeds the pickup current setting.
Note: The pickup point is 1.06 of the pickup set-
ting. Refer also to paragraph on Pickup in Section 5.1.
The Time Dial (2005) used for the selected curve allows the time-to-trip of the curve to be raised or lowered The dial can be adjusted from 0.1 to 9.9 in steps of 0.1.
The Filter (2006) sets the sensing method used by the func­tion in its pickup calculations. The rms filter uses fundamen­tal current plus harmonics, while the fundamental filter ignores harmonics.
Impedance (2007) sets the angle used by this function. It determines the direction of current flow being measured and can be set from 0 to 90 degrees. The directional characteris­tic (line) in the complex impedance plane is shown in Figure 5.2. The directional characteristic is always perpen­dicular to the line impedance vector.
The sensing direction (2008) can be set to forward or reverse. The forward setting allows the directional protection element to pickup on fault current only in the direction of nor­mal power flow.
Each of the two waveform capture buffers (2010 and 2011) can be independently programmed to freeze snapshots on pickup or trip.
The Directional Neutral or Ground Time Overcurrent function is able to actuate any binary output contact on pickup, and any trip or binary output contact on trip.
The Overvoltage function can be enabled or disabled (2201).
The Curve parameter (2202) allows the selection of a definite time delay or a characteristic curve. When the definite time characteristic is selected, the time delay begins as soon as the device goes into pickup. The inverse time characteristic utilizes a moderate inverse curve using the time dial.
The Pickup Source Voltage parameter (2203) indicates the VT connection. If the VTs are connected line-to-ground, the device can pickup on line-to-line or line-to-ground voltages. If the VTs are connected line-to-line, the VTs can only pickup on line-to-line voltages. The maximum continuous voltage across a VT input is 150 VAC.
The pickup value (2204) is in secondary volts ranging from 60 to 250 V. The function begins timing when any individual phase voltage exceeds the pickup voltage setting.
The time delay (2205) represents the time between pickup and trip and can be set when definite time is selected. The delay can be adjusted from 0.1 to 60.0 seconds in steps of
0.01 second. If the function remains in pickup for longer than the time delay, the function causes a trip. The delay can also be set to infinity so that the function never times out.
The Time Dial parameter (2206) is used for the characteristic curve. The dial allows the time-to-trip of the curve to be raised or lowered. It can be adjusted from 0.1 to 9.9 in steps of 0.1.
Each of the two waveform capture buffers (2210 and 2211) can be independently programmed to freeze snapshots on pickup or trip.
The function is able to actuate any binary output contact on pickup, and any trip or binary output contact on trip.
5.11 Overvoltage (59)
The Overvoltage function causes a trip if the rms value of any of the line voltages exceeds a set level. This function is only available if the voltage input option is installed.
A2200 Overvoltage (59)
Address Parameter Option
2201 Function Enabled or Disabled
2202 Curve Definite
Inverse Moderately Inverse Very Inverse
2203 Pickup Source V Line-to-ground
Line-to-line
2204 Pickup 60-250 V (0.1 V steps)
2205 Time Delay (Def.) 0.1-60 s (0.01 s steps),
or infinity
2205 Time Dial (Inverse) 0.1-9.9 (0.1 steps)
2210 Freeze Wfm2 on Pickup, on Trip, or None
2211 Freeze Wfm2 on Pickup, on Trip, or None
5.12 Undervoltage (27)
The Undervoltage function causes a trip if the rms value of any of the line voltages falls below a set level and can be use­ful for capturing power quality disturbances. This function is only available if the voltage input option is installed.
2300 Undervoltage 27
Address Parameter Option
2301 Function Enabled or Disabled
2302 Curve Definite
Inverse Moderately Inverse Very Inverse
2303 Pickup Source V Line-to-Neutral or Line-to-Line
2304 Pickup 40-230 V (0.1 V steps)
2305 Time Delay (Def.) 0.1-60 s (0.01 s steps),
or infinity
2305 Time Dial (Inverse) 0.1-9.9 (0.1 steps)
2310 Freeze Wfm 2 on Pickup, on Trip, or None
2311 Freeze Wfm 2 on Pickup, on Trip, or None
26 Siemens Energy & Automation, Inc.
Protective Function Configuration
The Undervoltage function can be enabled or disabled (2301).
The Curve parameter (2302) allows the selection of a definite time delay or a characteristic curve. When the definite time characteristic is selected, the time delay begins as soon as the device goes into pickup. The inverse time characteristic utilizes a moderate inverse curve using the time dial.
The Pickup Source Voltage parameter (2303) indicates the VT connection. If the VTs are connected line-to-ground, the device can pickup on line-to-line or line-to-ground voltages. If the VTs are connected line-to-line, the VTs can only pickup on line-to-line voltages. The maximum continuous voltage across a VT input is 150 VAC.
The pickup value (2304) is in secondary volts ranging from 60 to 250 V. The function begins timing when any individual phase voltage exceeds the pickup voltage setting.
The time delay (2305) represents the time between pickup and trip and can be set when definite time is selected. The delay can be adjusted from 0.1 to 60.0 seconds in steps of
0.01 second. If the function remains in pickup for longer than the time delay, the function causes a trip. The delay can also be set to infinity so that the function never times out.
The Time Dial parameter (2306) is used for the characteristic curve. The dial allows the time-to-trip of the curve to be raised or lowered. It can be adjusted from 0.1 to 9.9 in steps of 0.1.
Each of the two waveform capture buffers (2310 and 2311) can be independently programmed to freeze snapshots on pickup or trip.
The function is able to actuate any binary output contact on pickup, and any trip or binary output contact on trip.
5.13 Phase Sequence Voltage (47)
The Phase Sequence Voltage function operates instanta­neously if the correct system voltage phase sequence defined in the hardware configuration is not present at the device voltage inputs. This function will not respond if the input to the device is less than 40 V line-to-line or 23.1 V line­to-neutral. The function operates without delay or inverse time characteristic. It responds in 100 ms or less.
The Phase Sequence Voltage function can be used to pre­vent closure of a breaker. The assigned output contact would be wired to open a contact in the breaker-close circuit and remain activated until the line rotation is normal.
A2400 Phase Sequence Protection (47)
Address Parameter Option
2401 Function Enabled or Disabled
2410 Freeze Wfm 1 on Trip, or None
2411 Freeze Wfm 2 on Trip, or None
The 47 Phase Sequence Voltage function can be enabled or disabled (2401).
Each of the two waveform capture buffers (2410 and 2411) can be independently programmed to freeze snapshots on trip.
The function is able to actuate any binary output contact on pickup, and any trip or binary output contact on trip.
5.14 Negative Sequence Voltage (47N)
The Negative Sequence Voltage function operates when the percent negative sequence voltage exceeds the preset value for a specified time. This function resets instantaneously when the negative sequence voltage drops below pickup.
A2400 Negative Sequence Voltage (47N)
Address Parameter Option
2451 Function Enabled or Disabled
2452 Curve Definite or Inverse
2453 Pickup 4-40% negative sequence
(1% steps)
2454 Time Delay (Def.) 0-100 s (0.01 s steps),
or infinity
2455 Time Dial (Inverse) 0.1-9.9 (0.1 steps)
2456 Max Time (Inverse) 1-250 s (1 s steps)
2457 Blocked at 40-120 V (1 V steps)
2460 Freeze Wfm 2 on Pickup, on Trip, or None
2461 Freeze Wfm 2 on Pickup, on Trip, or None
The Negative Sequence Voltage function can be enabled or disabled (2451).
The Curve parameter (2452) allows the selection of a definite time delay or an inverse curve. The inverse time characteris­tic utilizes a moderate inverse curve using the time dial.
The pickup value (2453) ranges from 4% to 40% of negative sequence voltage. The function begins timing when the per­cent of negative sequence voltage exceeds the preset value for a specified time.
The time delay (2454) represents the time between pickup and trip and can be set when definite time is selected. The delay can be adjusted from 0 to 100 seconds in steps of
0.01 second. The delay can also be set to infinity so that the
function never times out.
The Time Dial parameter (2455) is used for the characteristic curve. The dial allows the time-to-trip of the curve to be raised or lowered. It can be adjusted from 0.1 to 9.9 in steps of 0.1.
5
Siemens Energy & Automation, Inc. 27
Protective Function Configuration
5
When the curve is set to inverse, the Max Time parameter (2456) sets an absolute maximum amount of time that the function will remain in pickup regardless of the inverse curve. The value ranges from 1 to 250 seconds and can be set in steps of 1 second.
Blocking (2457) can be set from 40 to 120 V. Regardless of the setting, the function is automatically blocked if the volt­age drops below 40 V. An event will be generated when this function is blocked due to an undervoltage condition.
Each of the two waveform capture buffers (2460 and 2461) can be independently programmed to freeze snapshots on pickup or trip.
The function is able to actuate any binary output contact on pickup, and any trip or binary output contact on trip.
5.15 Overfrequency (81O)
The Overfrequency function has only a definite time charac­teristic and causes a time-delayed trip if the system line fre­quency rises above a set level.
A2500 Overfrequency (81O)
Address Parameter Option
2501 Function Enabled or Disabled
2502 Pickup Nominal frequency
60.1-65.0 Hz (0.1 Hz steps)
2504 Time Delay 0-100 s (0.01 s steps),
or infinity
2505 Blocked at 40-120 V (at VT input)
(1 V steps)
2510 Freeze Wfm1 on Pickup, on Trip, or None
2511 Freeze Wfm2 on Pickup, on Trip, or None
5.16 Underfrequency (81U)
The Underfrequency (81U) function has only a definite time characteristic and causes a time-delayed trip if the system line frequency drops below a set level. This function can be useful for load shedding applications.
A2500 81U Underfrequency
Address Parameter Option
2551 Function Enabled or Disabled
2553 Pickup Nominal frequency
55.0-59.9 Hz (0.1 Hz steps)
2554 Time Delay 0-100 s (0.01 s steps),
or infinity
2556 Blocked at 40-120 V (at VT input)
(1 V steps)
2560 Freeze Wfm1 on Pickup, on Trip, or None
2561 Freeze Wfm2 on Pickup, on Trip, or None
The Underfrequency function can be enabled or disabled (2551).
The function begins timing when the frequency drops below the pickup frequency setting (2553).
The time delay (2554) represents the time between pickup and trip. The delay can be adjusted from 0 to 100 seconds in steps of 0.1 second. The delay can also be set to infinity so that the function never times out.
Blocking (2556) can be set from 40 to 120 V. Regardless of the setting, the function is automatically blocked if the volt­age drops below 40 V. An event will be generated when this function is blocked due to an undervoltage condition.
The Overfrequency function can be enabled or disabled (2501).
The function begins timing when the frequency exceeds the pickup frequency setting (2503).
The time delay (2504) represents the time between pickup and trip. The delay can be adjusted from 0 to 100 seconds in steps of 0.1 second. The delay can also be set to infinity so that the function never times out.
Blocking (2506) can be set from 40 to 120 V. Regardless of the setting, the function is automatically blocked if the volt­age drops below 40 V. An event will be generated when this function is blocked due to an undervoltage condition.
Each of the two waveform capture buffers (2510 and 2511) can be independently programmed to freeze snapshots on pickup or trip.
The function is able to actuate any binary output contact on pickup, and any trip or binary output contact on trip.
28 Siemens Energy & Automation, Inc.
Each of the two waveform capture buffers (2560 and 2561) can be independently programmed to freeze snapshots on pickup or trip.
The function is able to actuate any binary output contact on pickup, and any trip or binary output contact on trip.
5.17 Breaker Failure (50BF)
The Breaker Failure function responds to a fault condition where any phase current being measured by the CTs does not drop below a programmable level. Whenever another protective function activates the contact identified by the breaker parameter, (usually Trip 1), this function will wait until the set amount of time has expired. Then it checks the phase currents. If they are not equal to or less than the set pickup value, the function executes its defined actions.
Protective Function Configuration
2800 50BF Breaker Failure
Address Parameter Option
2801 Function Enabled or Disabled
2802 Pickup 5 A CTs: 0.25-5 A
1 A CTs: 0.05-1 A (0.01 A steps)
2804 Delay 8-254 cycles
2805 Check current, breaker opened,
current or breaker opened
The 50BF Breaker Failure function can be enabled and dis­abled (2801). When enabled, the protective function begins monitoring the current flow in the circuit following a trip com­mand by the relay. Simultaneously, the protective function starts a timer. If the current flow does not drop below the pickup value specified (2802) and before the set time delay (2804) has elapsed, a breaker failure is assumed. At this point, another trip command can be issued to a different breaker (via a different output ocntact if available).
The condition of a breaker failure trip depend on the method chosen, the value of the current after the time has run out, and the position of the a and b switches.
The range of the pickup value (2802) is based on the sec­ondary phase CT rating and is in secondary amperes.
The time delay (2804) represents the time between pickup and trip. The delay can be adjusted from 8 to 254 line cycles of delay. The function operates if it remains in pickup for longer than the time delay.
Breaker failure protection monitors the current flow only fol­lowing a trip by the contact identified at address 1004 (see Section 4.2). This is the contact matrixed to the overcurrent protection.
Exceptions to the normal operating conditions include the presence of push-to-test switches across either the a-switch, b-switch, or both. A push-to-test switch across the b-switch will produce a false indication of a breaker mecha­nism error when the breaker is actually closed. A push-to test switch across the a-switch (and hence across the trip solenoid) will produce a false indication of a breaker mecha­nism error when the breaker is actually closed.
The Breaker Mechanism function (8305), when enabled, senses an error in the mechanism that controls the position of one or both switches (breaker mechanism error), causes an action to be taken, and an event to be logged if the switches are ever both closed for more than 100 ms. No other time delay is implemented. When this function detects an error, it is considered to be in pickup until the condition is no longer present.
The ISGS relay considers the b-switch to be more reliable. If it senses the switches both open at the same time, the breaker is considered to have a trip coil continuity error or to be withdrawn. The 52a switch closed and the 52b switch open are interpreted as a closed breaker. If the relay senses the 52a switch open and the 52b switch closed, the breaker is considered to be open. Refer also to Table 5.3.
5.18 Demand Setpoints
The ISGS relay is capable of activating outputs and sending events when predefined demand calculations exceed the set thresholds. These setpoints can be enabled or disabled and are capable of activating any output. Measurement and set­point parameters in address block 3100 set the alarm report­ing threshold for the ISGS relay.
The Demand Parameters function selects the time periods for demand calculations performed by the relay and allows the user to enable overcurrent demand and kilowatt demand protection.
5
Breaker position is sensed through dedicated binary inputs that monitor the 52a and 52b switches on the breaker mech­anism (breaker mounted). The 52a and 52b switches have a total of four possible position combinations which can be decoded as illustrated in Table 5.3. The 52a and 52b switches referred to are those which traditionally provide indi­cation of circuit breaker position (52b) and trip coil continuity (52a). All error reporting can be enabled and disabled, and the actions to be taken are configurable. Refer to
Section 6.6.
Table 5.3 52a and 52b Switches Decoding
52a Switch Position
Open Open Trip Coil Continuity Error, or
Open Closed Circuit Breaker Open
Closed Open Breaker Closed
Closed Closed Circuit Breaker Mechanism Error
52b Switch Position
Condition Registered
Breaker Withdrawn
3100 Demand Parameters
Address Parameter Option
3101 Demand Interval 15, 30, 60 minutes
3102 Sync Time 0, 15, 30, or 45 after hour
3103 Subperiods 60 1, 2, 3, 4, 6, or 12
3104 Subperiods 30 1, 2, 3, or 6
3105 Subperiods 15 1 or 3
3106 I Av Dmd Function Enabled or Disabled
3107 I Av Dmd Pickup 0-9999 A (1 A steps)
3108 KW Dmd Function Enabled or Disabled
3109 KW Dmd Pickup 0-999,999 kW (1 kW steps)
Demand intervals (periods) are set to 15, 30, or 60 minutes (3101). Demand calculations are updated at the end of every demand period.
Demand period calculations can begin on the hour or at any quarter hour afterwards. The intervals are indicated as 0, 15, 30, or 45 minutes and are set in the Sync Time parameter (3102).
Siemens Energy & Automation, Inc. 29
Protective Function Configuration
5
Demand calculations are made every subperiod (3103, 3104, or 3105). The number of subperiods depends on the length of the demand interval and is based on 10, the mini­mum number of monitoring intervals in a subperiod. For example, a 15 minute interval can have one or three subperi­ods, a 30 minute interval can have 1, 2, 3, or 6 subperiods. The length of a subperiod is your demand period divided by the number of subperiods.
The Average Current Demand function can be enabled or disabled (3106) in this Demand Setpoints function. When enabled, the Overcurrent Demand function causes an alarm if the average current demand value exceeds the setpoint.
The pickup value for the Average Current Demand function (3107) ranges from 0 to 9999 A.
The Kilowatt Demand function (3108) can be enabled or dis­abled. When enabled, the Kilowatt Demand function causes an alarm if the kilowatt demand value exceeds the setpoint.
The pickup value for the Kilowatt Demand function (3109) ranges from 0 to 999,999 kW.
5.19 Power Setpoints
The ISGS relay is capable of activating outputs and sending events when predefined power measurements exceed the set thresholds. These setpoints can be enabled or disabled and are capable of activating any output. Measurement and setpoint parameters in address block 3200 set the alarm reporting threshold for the ISGS relay.
The kVAR and the kVA functions (3201 and 3203) can be enabled or disabled. If enabled, the functions cause an alarm if the kVAR or the kVA value exceeds the setpoint for the pre­set time delay.
The kVAR and the kVA function pickup value (3202 and
3204) ranges from 0 to 999,999 kVAR or kVA.
The time delay for kVAR and kVA can be adjusted from 0 to 3600 seconds in steps of 1 second.
The leading or lagging power factor function can be enabled or disabled (3207 and 3211). If one of the functions is enabled, it causes an alarm if the power factor value leads or lags the setpoint.
The threshold for both leading and lagging power factors (3208 and 3212) ranges from 0.2 to 1.0 in steps of 0.1.
The sign for the leading or lagging power factor (3209 and
3213) can be set to lead or lag.
The time delay for both leading and lagging power factors can be adjusted from 0 to 3600 seconds in steps of 1 sec­ond.
The leading setpoint will react if the measured power factor leads the setpoint for the set delay time. The lagging setpoint will react if the measured power factor lags the setpoint for the set delay time.
The Power Setpoints function allows the setting of all power setpoints.
3200 Power Setpoints
Address Parameter Selection
3201 KVAR Function Enabled or Disabled
3202 KVAR Pickup 0-999,999 kVAR (1 kVAR steps)
3203 KVAR Time Delay 0-3600 s (1 s steps)
3204 KVA Function Enabled or Disabled
3205 KVA Pickup 0-999,999 kVA (1 kVA steps)
3206 KVA Time Delay 0-3600 s (1 s steps)
3207 PF Lead Function Enabled or Disabled
3208 PF Lead Pickup 0.2-1.0 (0.1 steps)
3209 PF Lead Sign lag or lead
3210 PF Lead Delay 0-3600 s (1 s steps)
3211 PF Lag Function Enabled or Disabled
3212 PF Lag Pickup 0.2-1.0 (0.1 steps)
3213 PF Lag Sign lag or lead
3214 PF Lag Delay 0-3600 s (1 s steps)
(default is 100000)
(default is 1800)
(default is 1800)
(default is 0.8)
(default is 1800)
(default is 0.8)
(default is 1800)
30 Siemens Energy & Automation, Inc.
6 Control & Communications
6.1 Matrixing Events to Outputs
One of the powerful functions of the ISGS relay is its ability to send control outputs based on inputs from the real world. This process of assigning various outputs to various inputs is called matrixing. Utilities in Europe call this marshalling. Since most customers in America are not familiar with this term and because the word configuring is used in too many other con­texts, we use the more specific word matrixing. The inputs that can be used to control outputs can be binary (on/off) inputs and communication events. The binary inputs deter­mine if a certain type of protection is being violated and can close a trip contact or binary output based on the intelligence of the relay. The outputs can be trip contacts or binary out­puts. Figure 6.1 shows in general form how the outputs can be controlled by various inputs. The outputs can also be controlled by a command from an external communication device on the network; this input is called a Communication Event. The ISGS relay offers four binary inputs (BI 1, BI 2, BI 3, and BI 4), two binary outputs (BO 1, BO 2), and three trip contacts (Trip 1, Trip 2, and Trip 3). Matrixing is used for blocking and event-driven functions as well as for binary input and setpoint functions.
A physical input is a hardware connection to the relay such as binary input 1 (BI 1). A logical input is an input to a func­tion internal to the relay such as the blocking input for under­voltage (protective function, 27) (see Section 5.12). The logical input can only be activated if it is matrixed to the physical input. Connecting the physical input BI 1 to the logi­cal input for function number 27 allows BI 1 to block PF27 when active. Up to 10 logical inputs can be matrixed to each output contact.
Control & Communications
Events
Event 1
50HS
Event 2
27
Event 3
50N
Comm Event
Figure 6.1 Matrixing Inputs to Outputs
Outputs
Output Contact
Trip Contact
Binary Output
Output 1
Output 2
Output 3
or or
6
A physical output is a trip contact or binary output (BO). A logical output is the output of a function internal to the relay such us Pickup, which is active when function 27 is in pickup. Connecting a logical output to a physical output allows function 27 to trip (actuate a contact). Up to 20 logical outputs can be matrixed to each output contact.
Note: Matrixing includes defining which protective
functions actuate an output contact, and which output contact they actuate. Matching the output connections of the relay with the wiring connections of the protective circuit, including the connections to the circuit breaker, is extremely important. If the matrix­ing of the ISGS relay is changed, double­check the wiring of the protective circuit, and always test that the operation of a protective function results in the circuit breaker tripping.
Without matrixing, an event will cause an entry in the Event Log, but nothing will happen with the outputs and no control activity will occur. With matrixing, an event can cause the relay to trip a breaker (for example) as well as causing an entry in the Event Log.
Siemens Energy & Automation, Inc. 31
6
Control & Communications
Matrixing Procedure
The following steps provide a detailed description on how to matrix the ISGS relay manually using the front panel LCD and keypad. Before matrixing the relay, ensure that power is applied to the relay which is indicated by the lit system LED (green).
Table 6.1 Matrixing Procedure
How to Matrix Inputs to Outputs
Step Description
Press Direct Addr key; enter block address of one of the matrix functions (6100, 6200, or 6400) using the numeric keypad; press Enter key.
OR
Press Direct Addr key; enter the address of the desired
1
parameter using the numeric keypad; press Enter key. Skip to step 4.
A complete list of ISGS relay parameters is provided in Appendix C.
Use Single Arrow keys to scroll to the desired address.
2
Press F key once; use Single Arrow keys to scroll to the
3
desired matrix position (001-020)
Press Password key; enter your level 3 password fol­lowed by Enter key. The message PW THREE ACCEPTED appears. Press Enter key again to return to
4
the screen displayed last before password entry.
For password levels, proper password entry, and display messages, refer to Section 3.3.
The display cursor located next to the address is blinking (otherwise repeat step 4). Press No key until the desired parameter option appears on display. Press Enter key to set the displayed option.
Your settings can be undone any time while still in the
5
same address block by simply returning to the parameter and assigning a new value.
Use Single Arrow keys to move to the next matrix posi­tion to change additional parameters, or proceed to the next step.
Press F key. At the blinking cursor position, the letter F is displayed. Press Enter key. Message SAVE NEW SET-
6
TINGS? appears.
Press Yes key followed by Enter key to save settings and reset relay to new parameters. Message NEW SET­TINGS SAVED appears.
7
Press No key to abort any changes made. Message SAVING PROCEDURE ABORTED appears.
Press Enter key to return to screen displayed last before
8
starting saving procedure.
Wisdom Software
While the ISGS relay can be matrixed manually using the keypad and LCD, Wisdom configuring and analysis software allows faster and easier configuration by connecting a PC installed to either data port. For data port connections refer to Section 2.5.1. All binary inputs, binary outputs, and the trip contacts can be simply checked off inside the configura­tion window of protective and other functions. Refer to Chapter 8 for more description of how this can be done with Wisdom software.
32 Siemens Energy & Automation, Inc.
Control & Communications
6.2 Binary Inputs
Binary inputs are optically-isolated voltage level sensors with a fixed threshold. The input is considered activated if voltage above the threshold is applied and de-activated if no voltage or voltage below the threshold is applied.
The status of the binary inputs is monitored whether they are configured or not. As a result, the relay logs events when any binary input changes state (from active to de-active or vice versa).
Actions matrixed to binary inputs have the choice of being performed when the binary input is activated (Hi) or de­activated (Lo). For example, BI1 >blk 50 Hi means that 50 is blocked when BI1 is activated. And BI1 >blk 50 Lo means that 50 is blocked when BI1 is de-activated.
The ISGS relay displays the options at each matrix position in the sequence listed in the table below.
6100 Binary Inputs
Address
Para­meter
6101 Input 1 001
6102 Input 2 001-010 (same as Input 1 above)
6103 Input 3 001-010 (same as Input 1 above)
6104 Input 4 001-010 (same as Input 1 above)
Matrix Position
to 010
(Options apply to each matrix position)
Option Option (cont.)
not matrixed Frz.Buff1 Hi Frz.Buff1 Lo Frz.Buff2 Hi Frz.Buff2 Lo blk 47N Hi blk 47N Lo blk 47 Hi blk 47 Lo blk 81U Hi blk 81U Lo blk 81O Hi blk 81O Lo blk 50 Hi blk 50 Lo blk 50N Hi blk 50N Lo blk 50HS Hi blk 50HS Lo blk 50HSN Hi blk 50HSN Lo blk 51N Hi blk 51N Lo
blk 59 Hi blk 59 Lo blk 27 Hi blk 27 Lo blk 67 Hi blk 67 Lo blk 67N Hi blk 67N Lo blk 50BF Hi blk 50BF Lo blk ComEvt Hi blkComEvt Lo SwitchPara Hi SwitchPara Lo BI1 Hi BI1 Lo BI2 Hi BI2 Lo BI3 Hi BI3 Lo BI4 Hi BI4 Lo
6.3 Binary Outputs
The ISGS relay offers two binary outputs. The options at each matrix position are displayed in the sequence listed in the table below.
6200 Binary Outputs
Address
6201 Output 1
6202 Output 2
Para­meter
(BO 1)
(BO 2)
Matrix Position
001 to 020
(Options apply to each matrix position)
001-020 (same as Output 1 above)
Option Option (cont.)
not matrixed BI1 BI2 BI3 BI4 Error Sum I Error Sym I Error Sym V OC Pickup OC Trip Non OC PU Non OC Trip Relay Pickup Relay Tripped no f f <> 50HS Trip 50HSN Trip 81O Pickup 81O Trip UV blks 81O 81U Pickup 81U Trip UV blks 81U 47N Pickup 47N Trip UV blks 47N 50HS blks 50 50HSN blks 50 50 Pickup 50 Trip 50HS blks 50N 50HSN blks
50N 50N Pickup 50N Trip 50HS blks 51 50HSN blks 51
51 Pickup 51 Trip 50HS blks 51N 50HSN blks
51N Pickup 51N Trip 67 Pickup 67 Trip 67N Pickup 67N Trip 27 Pickup 27 Trip 59 Pickup 59 Trip 47 Trip OvrBrOps PU OvrBrAmps PU OvrAmpsDmd
PU OvrkWDmd PU OvrkVAR PU OvrkVA Pickup PFLag Pickup PFLead Pickup 50BF Pickup 50BF Trip TrScMon PU TrCoilCont PU BrMech PU CommEvent 1 CommEvent 2 CommEvent 3 CommEvent 4 CommEvent 5
51N
6
On power-on or reset, the relay creates an internal state change of all binary inputs to determine whether they are active or inactive, and it performs all actions corresponding to their condition and matrixing accordingly.
Binary inputs can be matrixed to disable the acceptance of communication events.
Siemens Energy & Automation, Inc. 33
Control & Communications
6
6.4 Trip Contacts
The ISGS relay offers up to three trip contacts which are monitored by the microprocessor. Trip contacts may be con­figured by the user to trip the relay based on any of a number of functions. Trip contact reaction time is about 4.5 ms.
The relay displays the options at each matrix position in the sequence listed in the table below.
6400 Trip Contacts
Address
Para­meter
6401 Contact 1 001
6402 Contact 2 001-020 (same as Contact 1 above)
6403 Contact 3 001-020 (same as Contact 1 above)
Matrix Position
to 020
(Options apply to each matrix position)
Option Option (cont.)
not matrixed BI1 BI2 BI3 BI4 OC Trip NonOC Trip Relay Tripped 50HS Trip 50HSN Trip 81O Trip 81U Trip 47N Trip 50 Trip 50N Trip 51 Trip 51N Trip 67 Trip 67N Trip 27 Trip
59 Trip 47 Trip OvrBrOps PU OBrAmps PU OvrAmps-
Dmd PU OkWDmd PU OvrkVAR PU OvrkVA PU PFLag PU PFLead PU 50BF Trip TrScMon PU TrCoilCont PU BrMech PU CommEvent 1 CommEvent 2 CommEvent 3 CommEvent 4 CommEvent 5
6.5 Comm Events
Protective functions are internally generated events that can trip a relay. For the protection to function properly, the pro­cessor interprets these events (inputs) and makes a decision. Communication (Comm) events are externally generated messages that can trip a relay without any interpretation. This remote communication allows Comm events to control outputs (contacts), such as opening a breaker; or switch parameter sets if matrixed to a binary input. Comm events are sent from a PC or other devices on the RS-232 or RS-485 networks.
Comm events can be blocked (disabled) with binary inputs to prevent remote parameterization during service periods or as a general safety measure. Refer to the list of binary inputs in
Section 6.2.
6.6 Breaker Monitoring
To increase the security of the protective system, it is helpful to monitor several parameters directly from the switchgear. The ISGS relay can monitor the components such as the 52a and the 52b switches, the traditional circuit breaker position lamps, and the tripping voltage supply.
The 52a and 52b switches have a total of four possible posi­tion combinations which can be decoded as illustrated in Tab l e 6 .1. The 52a and 52b switches referred to are those which traditionally provide indication of circuit breaker posi­tion (52b) and trip coil continuity (52a). All error reporting can be enabled and disabled, and the actions to be taken are configurable.
Table 6.1 52a and 52b Switches Decoding
52a Switch Position
Open Open Trip Coil Continuity Error, or
Open Closed Circuit Breaker Open
Closed Open Breaker Closed
Closed Closed Circuit Breaker Mechanism Error
The ISGS relay monitors:
breaker position
trip coil continuity
trip source impedance.
Breaker position is sensed through dedicated binary inputs that monitor the 52a and 52b switches on the breaker mech­anism (breaker mounted). Trip coil continuity is monitored by continually sensing a current that flows through the trip coil. Trip source impedance is checked using a switchable elec­tronic load across the trip voltage supply.
8300 Breaker Monitoring
Address Function/
8301 TripSrcImp Enabled or Disabled
8302 TripSrcFail Yes or No
8303 TrpCoil Cont Enabled or Disabled
8304 TrpCoilFail Yes or No
8305 BrkrMech Enabled or Disabled
Exceptions to the normal operating conditions include the presence of push-to-test switches across either the a-switch, b-switch, or both. A push-to-test switch across the b-switch will produce a false indication of a breaker mecha­nism error when the breaker is actually closed. A push-to test switch across the a-switch (and hence across the trip solenoid) will produce a false indication of a breaker mecha­nism error when the breaker is actually closed.
52b Switch Position
Parameter
Condition Registered
Breaker Withdrawn
Options
34 Siemens Energy & Automation, Inc.
Control & Communications
The Trip Source Impedance parameter (8301) can be enabled or disabled. When enabled, the circuit periodically monitors the trip supply voltage (auxiliary voltage, station bat­tery) and will perform an action (for example, close a binary output) should the voltage drop below ANSI minimum val­ues. Monitoring the trip source (auxiliary power) to detect bad connections and weak batteries is done by periodically drawing a small current from the trip supply and monitoring the subsequent sag in the voltage. Using averaging tech­niques, the trip source impedance can be estimated. Based on this estimate, an error message is given if the source volt­age drops below ANSI minimum values during a trip event. When the function is enabled, it can cause the actuation of any of the output contacts. This circuit can function only in true DC trip systems. It should be disabled and the inputs left disconnected when the device is used in AC trip systems.
The Trip Source Fail parameter of the Trip Source Impedance function (8302), when set to yes, allows the relay fail contact to be asserted when the monitoring function detects an error. When set to no, the relay fail contact is not affected.
The Trip Coil Continuity function (8303), when enabled, senses a trip coil continuity error, causes an action to be taken, and logs the event if the 52a and 52b switches are ever both open at the same time for more than 100 ms. No other time delay is implemented. When the function detects the error, the function is considered to be in pickup until the condition is no longer present.
The Trip Coil Fail parameter of the Trip Coil Continuity func­tion (8304), when set to yes, allows the relay fail contact to be asserted when the monitoring function detects an error. When set to no, the relay fail contact is not affected.
6.7 Logs and Breaker Monitor Reset
With the Reset function, the user can independently reset logs and breaker monitoring functions. Performing the reset operation for an individual category will reset all values within that category to zero, but new values are tracked immedi­ately. The Resets address block also includes functions to set the number of breaker operations and the sum of inter­rupted current on each phase.
8200 Resets
Address Function Option/Display
8201 Trip Log yes, in progress, successful
8202 Min/Max Values yes, successful
8203 Energy yes, successful
8204 Breaker Ops yes, successful
8205 Sum I interrupted yes, in progress, successful
8211 Breaker Ops
(Counter)
8212 Sum IL1 0-99999 kA (0.01 kA steps)
8213 Sum IL2 0-99999 kA (0.01 kA steps)
8214 Sum IL3 0-99999 kA (0.01 kA steps)
The Trip Log reset function (8201) can be set to yes to reset the values in all trip logs. This function requires a password. When the parameter is activated by setting it to yes, the LCD displays the message IN PROGRESS followed by the mes­sage SUCCESSFUL.
0-65535
6
Because the 52b switch does not need to interrupt the cur­rent through the trip coil, it provides a reliable indication of breaker position: when it is open, the breaker is considered closed. The practice (in DC trip systems) of placing a red sta­tus indicator lamp in series with the trip coil allows a conve­nient method for monitoring the continuity of the trip coil. When the circuit breaker is closed, the 52a switch is closed and the voltage across them and the trip coil is small because most of the voltage drop occurs across the indicat­ing lamp circuit. If the trip coil is open or the a-switch is defective, an error condition exists and an alarm can be gen­erated. An exception is a breaker withdrawn for servicing.
The Breaker Mechanism function (8305), when enabled, senses an error in the mechanism that controls the position of one or both switches (breaker mechanism error), causes an action to be taken, and an event to be logged if the switches are ever both closed for more than 100 ms. No other time delay is implemented. When this function detects an error, it is considered to be in pickup until the condition is no longer present.
The ISGS relay considers the b-switch to be more reliable. If it senses the switches both open at the same time, the breaker is considered to have a trip coil continuity error or to be withdrawn. The 52a switch closed and the 52b switch open are interpreted as a closed breaker. If the relay senses the 52a switch open and the 52b switch closed, the breaker is considered to be open. Refer also to Table 6.1.
Resetting the minimum and maximum logs with the Min/Max Values reset function (8202) discards all current values, but new minimum and maximum values are tracked immediately.
The Energy reset function (8203) resets all demand values.
The Breaker Operations reset function (8204) resets the breaker operations counter.
The sum of interrupted current reset function resets the sum of interrupted current for each phase (8205).
The Breaker Operations (Counter) reset function (8211) sets the number of breaker operations, for example, when mov­ing the breaker to a cubicle protected by an ISGS relay where the previous breaker had a different operations count.
The Sum of Interrupted Current for phases A, B, and C reset functions (8212, 8213, 8214) can be set from 0 to 99999 kA.
Siemens Energy & Automation, Inc. 35
Control & Communications
6
6.8 Breaker Operations Count
Breaker Operations refers to the number of times the device has opened the breaker. The Breaker Operation function allows the setting of the breaker monitoring parameters.
The Sum of Interrupted Current is the total sum of the cur- rents that were interrupted by these breaker openings. The setpoint is triggered when any phase exceeds the set limit.
3500 Breaker Operation
Address Parameter Selection
3501 Int. I Function Enabled or Disabled
3502 Int. I Pickup 0-9999.90 kA
(0.01 kA steps)
3503 Brks Ops Function Disabled or Enabled
3504 Brks Ops Counter 0-65535
The Interrupted I (current) Function (3501) can be enabled or disabled. When enabled, the function generates an event (which can be matrixed to an output contact) when the inter­rupted current exceeds the pickup value. The interrupted current pickup value (3502) can be set to any value from 0 to
9999.90 kA in steps of 0.01 kA.
The Circuit Name (7401) identifies a relay, breaker, bus, or feeder which your ISGS relay is protecting. This string (up to 16 characters) is user-definable with Wisdom software. Accessing this parameter through the keypad allows only the display of this string.
All circuit boards installed in your ISGS relay are provided with a serial number and a special identification number. These numbers can be displayed by accessing addresses 7403 to 7407.
Similar to the firmware version identification number of your ISGS relay described in Section 4.1, the serial and identifi­cation numbers of your main board and optional board(s) help Siemens track the versions and options available on your boards.
Binary Inputs (7408) displays the status of the binary inputs as illustrated in Figure 6.2. The status updates automatically as they change.
The Breaker Operations Function (3503) can be enabled or disabled. When enabled, the function counts the breaker operations since the last reset.
The Breaker Operations Counter (3504) can be set from 0 to
65535.
6.9 Hardware Status (Relay Data)
The Relay Data function provides additional hardware infor­mation on the ISGS relay, shows all set binary inputs and outputs, and displays a relay identification string.
7400 Relay Data
Address Data Description
7401 Circuit Name String of up to 16 characters
7402 MainBd S/N Serial number of main board
7403 MainBd ID ID number of main board
7404 OptBd1 S/N Serial number of option board 1
7405 OptBd1 ID ID number of option board 1
7406 OptBd2 S/N Serial number of option board 2
7407 OptBd2 ID ID number of option board 2
7408 Bin. Inputs Binary input status
7409 Bin. Outputs Output contact status
Figure 6.2 Binary Input Status
36 Siemens Energy & Automation, Inc.
Binary Outputs (7409) displays the output contact status as illustrated in Figure 6.3. The status updates automatically as they change.
Control & Communications

V125 V>

AND V
0.33 V
<
2
 
1
Figure 6.3 Output Contact Status
6.10 Self-Monitoring (Value Supervision)
Value supervision refers to the relays ability to monitor its own input and measurement functions for problems. The complete chain, from input transformers up to and including the A/D converter internal to the ISGS, is monitored by a plausibility check on the measured values. These checks consist of voltage balance checks, current balance checks, and current summation checks.
Voltage or current balance checks can be performed to detect open or short circuits in the external transformers and their connections. Current summation checks are performed on the instantaneous samples of the A/D converter.
A useful application of the current and voltage balance and monitoring functions is the detection of blown VT fuses. A blown fuse condition can be said to exist when the following conditions are present:
Voltage is present but unbalanced,
AND
current is present but NOT unbalanced.

AND I20.167 I
where V1 = positive sequence voltage
Therefore, a voltage balance alarm in the absence of a cur­rent unbalance alarm is a good indication that a fuse is blown. If a current unbalance alarm were also active, it would indicate the presence of negative sequence current and therefore a fault rather than a blown VT fuse.
3400 Value Supervision
Address Parameter Selection
3401 Function V Bal Enabled or Disabled
3402 Pickup V Bal 40-120 V (0.1 V steps)
3404 Factor V Bal 0.58-0.95 (0.01 steps)
3411 Function I Sum Enabled or Disabled
3412 Pickup I Sum 5 A CTs: 0.5-5 A
3414 Factor I Sum 0.10-0.95 (0.01 steps)
3421 Function I Bal Enabled or Disabled
3422 Pickup I Bal 5 A CTs: 0.5-5 A
3424 Factor I Bal 0.10-0.95 (0.01 steps)
Voltage Balance
The Voltage Balance function can be enabled or disabled (3401). When enabled, the function monitors the phase volt­ages to see if they are approximately balanced (of equal magnitude). Balance is defined as the ratio of minimum to maximum voltage, where the maximum voltage is the largest and the minimum voltage the smallest of the three voltages determined by the way the relay is connected (line-to-line or line-to-neutral).
<

I2 = negative sequence current
I1 = positive sequence current
IN = nominal current (1 or 5 A)
1

OR I10.1 I
(default is 100)
(default is 0.8)
1 A CTs: 0.1-1 A (0.1 A steps)
(default is 0.1)
1 A CTs: 0.1-1 A (0.1 A steps)
(default is 0.8)
<

N
6
Siemens Energy & Automation, Inc. 37
Control & Communications
6
Figure 6.4 Voltage Balance Threshold
Monitoring is done when the maximum voltage is larger than the voltage balance pickup value. The voltage is considered balanced and will not cause an alarm if the voltage min/max ratio is larger than the voltage balance factor. The voltage is unbalanced and will cause an alarm if the min/max ratio is smaller than the voltage balance factor.
Failure of this check will cause an event Voltage Balance Error. This event can activate an output contact.
The voltage balance pickup value (3402) can be set from 40 to 120 V in steps of 1 V. If one of the three phase voltages is above the preset threshold, the function checks for balance.
The voltage balance factor indicates the amount of unbal­ance tolerated before the function generates an alarm (3404). It ranges from 0.58 to 0.95 and can be set in steps of
0.01.
Current Summation
The Current Summation function can be enabled or disabled (3411). When enabled, it monitors the instantaneous sam­ples of the A/D converter using the currents flowing into all four relay CTs regardless of whether there are four primary CTs connected or not. The calculation is therefore valid for systems with both residual connections or explicit neutral/ ground/zero sequence CTs.
Figure 6.5 Current Sum Threshold
Failure of this check will cause an event Current Summation Error. This event can activate an output contact.
The pickup value (3412) for the current summation check depends on the secondary phase CT rating and the value is in secondary amperes. The value for 5 A CTs ranges from
0.5 A to 5.0 A; and the value for 1 A CTs ranges from 0.1 to
1.0 A. Both values can be set in steps of 0.1 A. If one of the three phase currents is above the preset threshold, the mon­itoring function is activated.
The current summation factor indicates allowable compen­sation for differences between primary CTs (3414). It ranges from 0.1 to 0.95 and can be set in steps of 0.01. This factor is important under high fault currents or when CTs are oper­ated closely to their rated current.
Current Balance
The Current Balance function can be enabled or disabled (3421). When enabled, the function monitors the phase cur­rents to see if they are approximately balanced (of equal magnitude). Balance is defined as the ratio of minimum to maximum current, where the maximum current is the largest and the minimum current the smallest of the three phase cur­rents.
Current balance monitoring is done when the maximum cur­rent is larger than the current balance pickup value. The cur­rent is considered balanced and will not cause an alarm if the current min/max ratio is larger than the current balance fac­tor. The current is unbalanced and will cause an alarm if the min/max ratio is smaller than the current balance factor.
38 Siemens Energy & Automation, Inc.
Figure 6.6 Current Balance Threshold
Failure of this check will cause an event Current Balance Error. This event can activate an output contact.
Control & Communications
6.11 Parameter Sets
The ISGS relay can be programmed to operate with either of two parameter setsset A or set B. Separate parameter sets are programmed to satisfy separate user defined condi­tions, such as seasonal considerations or special operating periods. For example, set A may be used for protective set­tings used in the summertime, whereas set B might com­prise the settings appropriate to winter, when lower ambient temperatures could allow higher loading than in the summer. Alternatively, set A might be configured for normal production periods, with set B reserved for construction or periodic shutdown periods. The choice of two separate parameter sets prevents the need to reconfigure the relay when condi­tions change and different parameter settings are desired.
Figure 6.2 shows the use of these parameter sets. The val­ues in set A or B may be chosen as the active set, and are thus put in the relays memory for easy access. The default set includes all the factory default values and these values are stored in long-term memory.
Default
Set
Copy
6
The pickup value (3422) for the current balance check depends on the secondary phase CT rating and the value is in secondary amperes. For 5 A CTs, the value ranges from
0.5 to 5.0 A; and the value for 1 A CTs ranges from 0.1 to
1.0 A. Both values can be set in steps of 0.1 A. If one of the three phase currents is above the preset threshold, the mon­itoring function is activated.
The current balance factor indicates the amount of unbal­ance tolerated before the function generates an alarm (3424). This factor is provided to compensate for differences between primary CTs. It ranges from 0.1 to 0.95 and can be set in steps of 0.01.
Set B
Save
Save
Set A
Activate
Active
Set
Figure 6.2 Parameter Set Actions
7101 Parameter Set
Address Parameter Description
7101 Active Set Displays active parameter set
7103 Activation Activate set A or set B
7104 Copy Default to A Copy default set to set A
7105 Copy Default to B Copy default set to set B
7106 Copy A to B Copy set A to set B
7107 Copy B to A Copy set B to set A
Only certain protective function parameters have two set­tings. All A settings are grouped under parameter set A, and all B settings are grouped under parameter set B. Each parameter set automatically includes all the regular parame­ters that can be programmed to only one setting at a time
(A or B)
Siemens Energy & Automation, Inc. 39
Control & Communications
6
and, therefore, apply to both sets. Examples are protective function enable settings and matrixed output contacts such as waveform buffers and blocking. All parameter set func­tions require a password.
6.11.1 Active Set
The active parameter set refers to the parameter set that is currently used by the ISGS relayset A or set B. The Active Set parameter (7101) indicates which set is currently active on the LCD using the letter A or B.
Refer to Section 6.11.3 on how to make a parameter set the active set.
6.11.2 Default Set
The default set refers to factory default parameter settings. These are stored in read-only memory (ROM) and cannot be overwritten. The default set cannot become an active set in itself, it has to be copied to either set A or set B (7104 and
7105).
6.11.3 Switching Sets
A parameter set can be made active by selecting the desired set in the Activation parameter (7103). Switching between sets requires 4.5 seconds.
Note: Switching the parameter sets could cause a
trip if the pickups are set lower than in the previous set. View the settings before acti­vating the new set.
Switching between parameter sets for viewing and configur­ing parameter settings is possible regardless of address or address level currently displayed by the LCD, or whether the parameter can be configured to an alternate setting.
2. Press Enter. The parameter set has switched to the
alternate set. The LCD displays the same address and function as before the switch, but the address prefix has changed to the letter representing the displayed param­eter set. The alternate parameter may or may not con­tain a value depending on whether the alternate parameter had been configured before.
B1502 Pickup 50
If the parameter was not configurable to an alternate set (had no prefix), the display will not have changed.
Note: Switching the parameter sets for viewing
and configuration does not make the alter­nate set active.
For detailed descriptions on how to display, configure, save, and switch parameters, and when to use a password, refer to the standard operating procedures in Section 3.5.
Exceptions to the switching of sets are binary inputs, binary outputs, and the trip contacts in the 6000 address blocks. For these parameter settings, the relay retains these values regardless of the parameter set. For example, if the output contact is set while set A is active, switching to set B will not change the output contact setting.
6.11.4 Copying Sets
Parameter settings for set A can be copied to set B and vice versa (7106 and 7107). Factory default settings can also be copied to either set A or set B (7104 and 7105), but no parameter set can override the default settings.
A1502 Pickup 50
110 A
1. At any address, press the F key
A1502FPickup 50
110 A
followed by either 1 (set A) or 2 (set B).
The LCD displays the following message:
PARAMETER SET
COPIED TO EDIT
40 Siemens Energy & Automation, Inc.
Control & Communications
6.12 Communications Port
The Configure Communications Port function lets the user change the communications parameters for the ISGS relay.
7200 Configure Communications Port
Address Parameter Options
7201 Local Port (front) 2400, 4800, 9600, 19,200 baud
7202 System Port (rear) 2400, 4800, 9600, 19,200 baud
7203 Parameter Change Enabled or Disabled
7204 Comm Events Enabled or Disabled
7207 Local Address 1-254
The ISGS relay can connect at 2400, 4800, 9600, and 19,200 baud at both ports (7201 and 7202). Higher baud rates will improve response and update rate, but slower PCs may lose characters due to the high rate. Both ports can be operated at different baud rates and simultaneously.
The Parameter Change function can be enabled or disabled. When enabled, this function allows the remote change of the parameter sets (A or B).
The Comm Events function can be enabled or disabled (7204). When enabled, this function allows remote activation of the breaker and binary outputs. The function can be dis­abled to prevent remote access during service periods or as a general security measure. For more information on Comm Events, refer to Section 6.5.
The Local Address parameter (7207) can be changed by entering a value from 1 to 254 to assign the local SEAbus address. Make sure that the new address does not represent a duplicate address of another device connected to the communications loop.
6.13 Passwords
The Configure Passwords function allows the change or dis­play of the three passwords. This function requires your old password before you can access the individual parameters. All passwords can consist of one to five digits.
7300 Configure Passwords
Address Parameter Range
7301 CW-Level 1 1 to 5 digits
7302 CW-Level 2 1 to 5 digits
7303 CW-Level 3 1 to 5 digits
A lower level password does not allow you to scroll to a higher level password parameter. But the higher level pass­word always lets you move to the lower level(s). For example, entering the level 2 password allows you to view and change the passwords for level 2 and level 1, but the same password does not provide access to view or change the level 3 pass­word.
6.14 Date and Time Setting
The Date and Time Setting function sets the date and time of the ISGS relay to match it with other connected devices and to provide an accurate setting for event and trip information.
8100 Date and Time Setting
Address Data Range
8101 Current Date 01/01/1970 00:00:00
8102 Set Date mm.dd.yyyy
8103 Set Time hh.mm.ss
The Current Date parameter (8101) displays the present date and time on the clock in the ISGS relay. The date and time is used to stamp the event and trip logs.
The date can be changed with the Set Date parameter (8102). To enter the date, separate the month, day, and year with a decimal point. Each field must contain two digits with the exception of the year field which must contain four digits (mm.dd.yyyy).
The time can be changed with the Set Time parameter (8103). To enter the time, separate hours, minutes, and sec­onds with a decimal point. Each field must contain two digits (hh.mm.ss).
Note: The clock in an ISGS relay is not a real-time
clock. It has no battery backup and will drift over time.
If the relay is connected to an ACCESS system, the supervi­sory software used for this system, for example, WinPM, reads all relays and synchronizes their clocks. If the relay is not connected to an ACCESS system, date and time should be set periodically, at least once a day, for accurate event and trip information. Date and time must always be reset after a loss of control power.
When reading events, the time can be off as much as 10 ms because events (inputs) are not interrupt driven; they are polled about every 10 ms. Binary inputs are also slower than protective functions; events can be reported later even if they occurred earlier.
6
Only the level 3 password (7303) can set all passwords. Use this level if you intend to change all passwords. Level 1 and level 2 passwords (7301 and 7302) can be displayed and changed by entering the respective level password.
Siemens Energy & Automation, Inc. 41
6
Notes:
42 Siemens Energy & Automation, Inc.
7 Data Acquisition
The ISGS relay provides several forms of data acquisition and display to give the user the most comprehensive picture of the power system. This data includes:
event log for monitoring functions and status changes
trip logs, including date and time of trip
minimum/maximum logs for storing metering data
individual metering data
waveform captures
7.1 Event Log
The event log is a chronological record of the last 127 signifi­cant events that occur during operation of the relay and is stored in nonvolatile memory. These events include opera­tional events, such as enabling or disabling protective ele­ments; and fault events, such as pickup and trip. Each entry in the log provides a description of the event and its time (to nearest millisecond) and date of occurrence.
Data Acquisition
Figure 7.2 Sample Trip Log Data Display (from Wisdom)
The event log cannot be viewed through the ISGS relay oper­ator panel. It can only be viewed after being retrieved through one of the relay communication ports using either Wisdom or WinPM software.
Figure 7.1 Sample Event Log (viewed with Wisdom)
Events that require special attention appear in the event log in red when displayed on a PC. The entire event log can be saved to a file (for later viewing or printing) using Wisdom software. For information on Wisdom software, refer to Chapter 8.
Whenever the ISGS relay resets, such as when changing parameter sets or output control actions, the event log is considered invalid and all events are re-read by communica­tions.
7.2 Trip Logs
The Trip Logs function stores times and measured data present at the time of pickup and trip for the last eight trip events. The information for each trip is stored in its own log. These eight logs are located at address blocks 5100 through
5800. The most recent trip event is stored under address 5100 and the oldest of the eight trip events is stored in address 5800. Pressing the Trip Log key takes you directly to the trip log address block. The first trip to be sensed is the trip to be logged
5100 to
Address Data Description
* If VTs are connected line-to-line (see address 1202,
Section 4.5), the line-to-line voltage is displayed.
Trip Logs
5800
001 Trip Number Date and event record number
002 Pickup Time Time of the event to the nearest
millisecond
003 Pickup The function that picked up
004 Phase The phase that picked up
005 I1 Current at pickup for phase 1
006 I2 Current at pickup for phase 2
007 I3 Current at pickup for phase 3
008 IN Ground current at pickup
009 V1 Voltage at pickup phase 1 (1-2*)
010 V2 Voltage at pickup phase 2 (2-3*)
011 V3 Voltage at pickup phase 3 (3-1*)
012 Trip The function that caused the trip
013 Phase The phase that caused the trip
014 I1 Secondary current at trip for phase 1
015 I2 Secondary current at trip for phase 2
016 I3 Secondary current at trip for phase 3
017 IN Secondary Ground current at trip
018 V1 Secondary voltage at trip phase 1
(1-2*)
019 V2 Secondary voltage at trip phase 2
(2-3*)
020 V3 Secondary voltage at trip phase 3
(3-1*)
021 TinPU Total time in pickup
022 End of Table Last entry in this log
7
Siemens Energy & Automation, Inc. 43
Data Acquisition
7
For each log the following applies:
The ISGS relay keeps a lifetime count of protective func-
tion trips. The trip number (address 001) is the count at the time of the trip. The trip number cannot be reset unless the relay is returned to the factory.
The pickup time (002) consists of the date and time of
the event to the nearest millisecond.
The pickup parameter (003) refers to the protective
function that caused the trip. Only protective function trips are stored in the log (no breaker monitoring, set­points, or communications trips are logged).
The phase parameter (004) stores the current or voltage
phase(s) that violated protective function settings.
I1, I2, I3, and IN parameters (005 to 008) give the cur-
rents at pickup for phases A, B, C, and the ground cur­rent.
V1, V2, and V3 (009 to 011) indicate the voltage at
pickup for phases A, B, and C. If VTs are connected line­to-line (refer to address 1202, Section 4.5, the line-to- line voltage is displayed for phases A-B, B-C, and C-A.
Trip (012) displays the function that caused the trip.
Phase (013) indicates the phase that caused the trip.
I1, I2, I3, and IN (014 to 017) give the secondary cur-
rents at trip for phases A, B, C, and the ground current.
V1, V2, and V3 (018 to 020) indicate the voltage at
pickup for phases A, B, and C. If VTs are connected line­to-line (refer to address 1202, Section 4.5, the line-to- line voltage is displayed for phases A-B, B-C, and C-A.
Total time in pickup (021) is the total time that the relay
read the voltage above the pickup value, not the time the breaker is told to open or actually opens. The timer is only reset when no function is in pickup.
Events that require special attention appear in the event log in red when displayed on a PC. For information on Wisdom software, refer to Chapter 8.
7.3 Min/Max Logs
7.3.1 Current Minimum/Maximum Log
The Current Minimum/Maximum Log function allows the dis­play of minimum and maximum values measured by the relay. The collected information is compared against previ­ously stored values and the log is updated. All logged values are time stamped and resetting the log (see Section 6.7) will reset all log values.
4600 Current Minimum/Maximum Log
Address Data Description
4601 I1 min Phase A minimum current
4602 I1 max Phase A maximum current
4603 I2 min Phase B minimum current
4604 I2 max Phase B maximum current
4605 I3 min Phase C minimum current
4606 I3 max Phase C maximum current
4607 IN min Ground minimum current
4608 IN max Ground maximum current
4609 IAv min Average minimum current
4610 IAv max Average maximum current
4611 I1 dmin Phase A minimum demand
current
4612 I1 dmax Phase A maximum demand
current
4613 I2 dmin Phase B minimum demand
current
4614 I2 dmax Phase B maximum demand
current
4615 I3 dmin Phase C minimum demand
current
4616 I3 max Phase C maximum demand
current
4617 IAv dmin Average minimum demand
current calculated
4618 IAv dmax Average maximum demand
current calculated
4619 MinTHD Minimum value of estimated
total harmonic distortion
4620 MaxTHD Maximum value of estimated
total harmonic distortion
The MinTHD and MaxTHD parameters (4619 and 4620) dis­play the minimum or maximum total harmonic distortion cal­culation for the average current. The calculation is an estimate of the harmonics on the system rather than an exact measurement.
44 Siemens Energy & Automation, Inc.
Data Acquisition
7.3.2 Voltage Minimum/Maximum Log
The Voltage Minimum/Maximum Log function allows the dis­play of minimum and maximum values measured by the relay. The collected information is compared against previ­ously stored values and the log is updated. All logged values are time stamped and resetting the log (see Section 6.7) will reset all log values. No voltages are metered unless the VT option is installed.
4700 Voltage Minimum/Maximum Log
Address Data Description
4701 V12 min Minimum phase voltage
between phases A and B
4702 V12 max Maximum phase voltage
between phases A and B
4703 V23 min Minimum phase voltage
between phases B and C
4704 V23 max Maximum phase voltage
between phases B and C
4705 V31 min Minimum phase voltage
between phases C and A
4706 V31 max Maximum phase voltage
between phases C and A
4713 VAv min Minimum average voltage
4714 VAv max Maximum average voltage
4717 MinTHD Minimum value of estimated
total harmonic distortion
4718 MaxTHD Maximum value of estimated
total harmonic distortion
The MinTHD and MaxTHD parameters (4717 and 4718) dis­play the minimum or maximum total harmonic distortion cal­culation for the average current. The calculation is an estimate of the harmonics on the system rather than an exact measurement.
4800 Power Minimum/Maximum Log
Address Data Description
4801 kW min Minimum power value
4802 kW max Maximum power value
4803 kW dem min Minimum active power demand
value
4804 kW dem max Maximum active power demand
value
4805 kVA min Minimum kilovolt-ampere value
4806 kVA max Maximum kilovolt-ampere value
4807 kVAR min Minimum kilovolt-ampere
reactive value
4808 kVAR max Maximum kilovolt-ampere
reactive value
4809 PF max Maximum power factor value
4810 PF min Minimum power factor value
7.3.4 Frequency Minimum/Maximum Log
The Frequency Minimum/Maximum Log function allows the display of minimum and maximum values measured by the relay. The collected information is compared against previ­ously stored values and the log is updated. All logged values are time stamped, and resetting the log (see Section 6.7) will reset all log values.
4900 Frequency Metering
Address Data Description
4901 Fmin Minimum frequency value
4902 Fmax Maximum frequency value
7
7.3.3 Power Minimum/Maximum Log
The Power Minimum/Maximum Log function allows the dis­play of minimum and maximum values measured by the relay. The collected information is compared against previ­ously stored values and the log is updated. All logged values are time stamped, and resetting the log (see Section 6.6) will reset all log values. No voltages are metered unless the VT option is installed.
Siemens Energy & Automation, Inc. 45
Data Acquisition
7
7.4 Metered Data
Metered data is stored by the ISGS relay and can be dis­played by accessing address blocks 4100 to 4900. The dis­play of this data does not require a password. You can display the same data more conveniently by using Wisdom software described in Chapter 8.
7.4.1 Current Values
The Current Metering function stores the metered current and current demand values for the ISGS relay. The relay will measure and display the rms values of the current for the three phases and ground or neutral. The ISGS relay also shows total harmonic distortion as a percentage of the fun­damental for the three phase current inputs. This function displays undefined when the measured components are below the total harmonic distortion threshold.
4100 Current Metering
Address Data Range
4101 I Phase A 0-250% I
4102 I Phase B 0-250% I
4103 I Phase C 0-250% I
4104 I Neutral 0-250% I
4105 I Average 0-250% I
4106 I Demand Phase A 0-250% I
4107 I Demand Phase B 0-250% I
4108 I Demand Phase C 0-250% I
4109 I Demand Average 0-250% I
4110 THD Current 0-250% I
1
ICT = primary CT rating
7.4.2 Voltage Values
The Voltage Metering function allows the display of metered voltage data for the ISGS relay. The rms voltage measure­ments for this function depend on the selected VT connec­tion method, either line-to-ground or line-to-line. The relay also shows total harmonic distortion as a percentage of the fundamental for the three phase voltage inputs. It displays undefined when the measured components are below the total harmonic distortion threshold. This function is only avail­able if the voltage input option is installed.
1
CT
CT
CT
CT
CT
CT
CT
CT
CT
CT
4200 Voltage Metering
Address Data Range
4201 V Phases A-B 10-125% V
4202 V Phases B-C 10-125% V
4203 V Phases C-A 10-125% V
4204 V L-L Average 10-125% V
4209 THD Volts 10-125% V
1
IVT = primary VT rating
1
n
n
n
n
n
7.4.3 Power Values
The Power Metering function stores the metered voltage data for the ISGS relay. This function is only available if the voltage input option is installed.
4300 Power Metering
Address Data Range
4301 kW 3-Phase 0-999,999.99 kW
4302 kW Hours 0-999,999.99 kWHR
4303 kW Demand 0-999,999.99 kWD
4304 kVA 3-Phase 0-999,999.99 kVA
4305 kVAR 3-Phase 0-999,999.99 kVAR
4306 kVAR Hours 0-999,999.99 kVARH
4307 PF -1  0  +1
7.4.4 Frequency Values
The Frequency Metering function allows the display of the system frequency. This function is only available if the voltage input option is installed.
4400 Frequency Metering
Address Data Range
4401 Frequency 45-65 Hz
46 Siemens Energy & Automation, Inc.
7.5 Meter Display
The Operating Parameters function allows the user to deter­mine what appears in Line 1 and Line 2 of the Power On Meter display described in Chapter 4.
7000 Operating Parameters
Address Parameter Options
7005 LCD Line 1 I avg, Idmd1, Idmd2, Idmd3,
Idmdavg, V1-2, V2-3, V3-1, VLLavg, V1-N, V2-N, V3-N, VLNavg, W, WH, Wdmd, VA, VAR, VARH, PF, f, I1, I2, I3, IN
7006 LCD Line 2 I avg, Idmd1, Idmd2, Idmd3,
Idmdavg, V1-2, V2-3, V3-1, VLLavg, V1-N, V2-N, V3-N, VLNavg, W, WH, Wdmd, VA, VAR, VARH, PF, f, I1, I2, I3, IN
The operating parameters can be set to provide you with a quick and constantly updated overview of your most impor­tant data.
Data Acquisition
7
7.6 Waveform Capture
The Waveform Capture function sets the pre-trigger time of the two waveform buffers. You can configure the ISGS relay to capture waveforms on a variety of events. For example, waveforms can be captured for protective functions on pickup or trip, or for communication events.
8400 Configure Waveform Capture
Address Parameter Range
8401 Wfm1Pretrp 100-900 ms, default is 800 ms,
8402 Wfm2Pretrp 100-900 ms, default is 800 ms,
Each buffer stores one full second of data for each wave. This second always includes the event that caused the trip. The pre-trip parameter of each buffer (8401 and 8402) lets you specify where in the buffer the event appears. By setting a time in milliseconds, you indicate how much data of this one second wave data you want included in the buffer prior to the trip.
For example, if buffer 1 is configured to be captured on trip (see also Chapter 5 and its protective functions with wave- form capture), and the activity that led up to the trip is of great interest, buffer 1 can be configured to contain 900 ms of pre-trigger data. These first 900 ms of pre-trigger data represent the signal before the actual trip. The remaining 100 ms show the signal after the trip.
(1 ms steps)
(1 ms steps)
A waveform stored in a buffer will be lost after a loss of con­trol power. Exporting an important waveform immediately to a file will prevent unexpected data loss.
Siemens Energy & Automation, Inc. 47
7
Notes:
48 Siemens Energy & Automation, Inc.
8 ISGS Wisdom Software
8 ISGS Wisdom Software
8.1 Overview
The ISGS relay is an extremely advanced protective relay for medium voltage switchgear applications. In order to reduce the complexity of configuring the relay, reading the metered values, and retrieving stored data, Siemens developed ISGS Wisdom software. Wisdom software is a Windows-based tool that monitors and controls an ISGS relay. Wisdom soft­ware provides a flexible, easy to use interface allowing the performance of a wide variety of tasks such as
remote configuration via network, local port, or modem
offline configuration in DEMO mode
configuration file storage
custom curve creation
display and retrieval of captured waveforms
event log retrieval
real-time data and status display
8.2 Setup
Using Wisdom software requires Microsoft® Windows®. To make full use of the Waveform Capture display, a color moni­tor is highly recommended. Setting up Wisdom software requires two basic operations:
1. Installing the program on a PC
Wisdom software is provided on a floppy diskette. The setup program on this diskette will install Wisdom soft­ware on your hard drive and will create a Windows pro­gram group icon.
2. Connecting the relay to the PC
For local connection of the PC, install an RS-232 inter­face cable between the serial communications port on the PC and the front port on the relay.
For remote connection of the PC, use an RS-232 to RS-485 converter for direct connection and null-modem connectors for modem use.
Wisdom software offers five main menus from which to select the various tasks or operations to be performed and one help menu.
8.3 Menus
In the main window, you can choose from the following main menus: Relay, Breaker, Configure, View, Logs, and Help. The Main Window also displays the Event Log which is automati­cally updated (refer to Figure 8.1). The Event Log can be saved or re-read. These commands can be found in the Logs menu.
8
Figure 8.1 Wisdom Main Window
Note: For a free copy of Wisdom software, fax a
request to 919-365-2552. Please include your name, company, phone number, fax number, mail­ing address, and e-mail address (if applicable). The software can also be downloaded from the World Wide Web at http://www.sea.siemens.com. Search for Wisdom Software using the Search function.
Relay Menu
From the Relay menu, you can connect or disconnect the ISGS relay, save or load device data, select parameter sets, and synchronize the internal time of your device with the time of your computer.
Breaker Menu
From the Breaker menu, you can control breakers and reset targets.
The Control submenu opens or closes the breaker and asserts or releases the communication events. Refer to
Figure 8.2.
Figure 8.2 Breaker Control
Siemens Energy & Automation, Inc. 49
8 ISGS Wisdom Software
8
Configure Menu
The Configure menu provides an easy way to set the param­eters for the following areas:
Communications
Protection Functions
Breaker Monitoring
ISGS Hardware
Demand
Alarms
Value Supervision
I/O Setup
Passwords
Each function or task offers an individual window with an overview of the complete set of parameters available and their default or user-defined settings. A simple click with the mouse selects your choices from check boxes, option but­tons, or list boxes. A slider lets you adjust ranges in pre­defined steps within minimum and maximum values. Refer to Figure 8.3.
The Realtime Data submenu allows a complete data display at one glance (refer to Figure 8.4).
Figure 8.4 Real-Time Data Display
The Waveform Capture submenu opens a color display that allows you to freeze and then retrieve all waveform data, selectively or together from either of the two buffers. The curves are color coded for easy identification. From the same window, you can configure your waveform settings, view your trip logs and display a buffer summary. Refer to
Figure 8.5.
Figure 8.3 Configuring a Protection Function
View Menu
The View menu offers functions for processing and display­ing various forms of data stored in the relay.
The Info submenu displays device data such as CT and VT ratings.
50 Siemens Energy & Automation, Inc.
Figure 8.5 Waveform Capture
The Marshalling display provides an overview of all trip and binary input settings. Refer to Figure 8.6.
Figure 8.6 Marshalling Display
Logs Menu
The Logs menu allows a complete data display of the Trip Logs and the Min/Max Log at one glance (see Figure 8.7 and Figure 8.8. This menu also contains the commands for saving or re-reading the Event Log.
8 ISGS Wisdom Software
Figure 8.8 Min/Max Log Data Display
Help Menu
The Help menu provides detailed information on how to use Wisdom software. The menu allows searching for and print­ing of specific help topics. The Help menu contains an ISGS relay settings worksheets that can be printed and used for manual configuration of the device if desired.
8.4 Demo Mode
To evaluate the software offline, a demonstration mode is provided that allows all of the program functions to be exer­cised without actual connection to an ISGS relay. Information on the methods and equipment required to connect the per­sonal computer to the relay are included in the Help function.
8
Figure 8.7 Trip Log Data Display
In addition to allowing experimentation, the demo mode per­mits the user to create relay configuration files that can be saved and used at a later time to configure an actual relay.
Siemens Energy & Automation, Inc. 51
Notes:
8
52 Siemens Energy & Automation, Inc.
Appendix A: Trip Curves & Equations
A Trip Curves & Equations
This section provides equations and curve characteristics for current and voltage to show the relationship between trip time and threshold levels. Determine which curve closely fol­lows the requirements of your system and select this curve in the applicable protective functions.
A.1 Instantaneous Curve
The Instantaneous response characteristics can be used with protection functions 50, 50N, 50HS, and 50HSN.
1
0.1
Time to Trip (Seconds)
0.01 11050
Multiples of Pickup
Trip Characteristic
For
i
---- -
1 : T
ip
AD
------------------------BD0.028++=>
N
i
---­i
p
1

Reset Characteristic
i
---- -
For
1 : T
<
ip
T = time to trip, in seconds

i
---- -
= multiple of pickup setting

i

p
D = time dial setting, 0.1 to 9.9 in steps of 0.1
=
------------------------
t
D
r
N
i
----

i
p
A, B, N, tr = constants
1
Figure A.1 Instantaneous Curve
A.2 Standard Time Overcurrent Equation
The ISGS comes with nine standard overcurrent characteris­tic curves that can be adjusted with a time dial parameter. Seven of the nine curves are based on suggested IEEE stan­dards for approximation of electromechanical relays. Table A.1 describes the first seven curves (SEA1 to SEA7) listed below.
Standard Overcurrent Coefficients
Curve Type Des.
Inverse SEA 1 8.9341 0.17966 2.0938 8.8
Short Inverse SEA 2 0.2663 0.03393 1.2969 0.831
Long Inverse SEA 3 5.6143 2.18592 1.0000 12.9
Moderately Inverse
Very Inverse SEA 5 5.4678 0.10814 2.0469 5.741
Extremely Inverse
Slightly Inverse
1
The A, B, and N coefficients are for the standard relay formula
SEA 4 0.3022 0.12840 0.5000 1.07
SEA 6 7.7624 0.02758 2.0938 7.432
SEA 7 0.4797 0.21359 1.5625 1.5625
1
A
1
B
1
N
t
r
Equation A.1 Standard Inverse Curves Equation
1000
100
10
1
Time to Trip (Seconds)
0.1
0.01 11050
Multiples of Pickup
Time Dial
9.9
7.0
5.0
3.0
1.5
0.5
0.1
A
Table A.1 Standard Overcurrent Coefficients
Figure A.2 Inverse Curve (SEA1)
Siemens Energy & Automation, Inc. 53
Appendix A: Trip Curves & Equations
100
10
100
10
Time Dial
1
Time to Trip (Seconds)
0.1
0.01 11050
9.9
7.0
5.0
3.0
1.5
0.5
0.1
1
Time to Trip (Seconds)
0.1
0.01 11050
Multiples of Pickup
Time Dial
9.9
7.0
5.0
3.0
1.5
0.5
0.1
Multiples of Pickup
A
Figure A.3 Short Inverse Curve (SEA2)
1000
100
10
Time to Trip (Seconds)
1
0.1 11050
Multiples of Pickup
Time Dial
9.9
7.0
5.0
3.0
1.5
0.5
0.1
Figure A.5 Moderately Inverse Curve (SEA4)
1000
100
10
1
Time to Trip (Seconds)
0.1
0.01 11050
Multiples of Pickup
9.9
7.0
5.0
3.0
1.5
0.5
0.1
Time Dial
Figure A.4 Long Inverse Curve (SEA3)
Figure A.6 Very Inverse Curve (SEA5)
54 Siemens Energy & Automation, Inc.
Appendix A: Trip Curves & Equations
1000
100
10
1
Time to Trip (Seconds)
0.1
0.01 11050
Multiples of Pickup
Time Dial
9.9
7.0
5.0
3.0
1.5
0.5
0.1
Equation A.2 The ISGS provides an emulation of the popular CO-6 Definite Inverse characteristic. This curve is defined by the equations shown in Equation A.3.
For
A.3 Definite Inverse Equation
i
---- -
1.5
>
ip
T 785
For1.0
T 785
=
Trip Characteristic
671
+
-------------------------------
N
i
----

i
p
i
---- -
1.5:
<<
ip
671
+
-------------------------------
N
i
----

i
p
6.33D 0.37+
-------------------------------
×=
24000
1.19
6.33D 0.37+
--------------------------------- -
×
24000
1.19
Figure A.7 Extremely Inverse Curve (SEA6)
100
10
1
Time to Trip (Seconds)
0.1
0.01 11050
Multiples of Pickup
Time Dial
9.9
7.0
5.0
3.0
1.5
0.5
0.1
Reset Characteristic
i
---- -
For
1 : T
<
=
ip
T = time to trip, in seconds

i
---- -
= multiple of pickup setting

i

p
D = time dial setting, 0.1 to 9.9 in steps of 0.1
tr = reset constant = 1.0394
N = inverse constant = 2.54096
D
t
r
------------------------
N
i
----

i
p
1
Equation A.3 Definite Inverse Equation
In Equation A.3, the time dial term 6.33D + 0.37 is neces- sary to convert the time dial range defined by Westinghouse and the range that Siemens is using.
Equation (1) is valid for values of I/Ip greater than 1.5 and equation (2) is valid for values of I/Ip between 1.0 and 1.5 (note that the equation is undefined at I/Ip = 1.0).
A
Figure A.8 Slightly Inverse Curve (SEA7)
Siemens Energy & Automation, Inc. 55
Appendix A: Trip Curves & Equations
100
10
1
Time to Trip (Seconds)
0.1
0.01 11050
Multiples of Pickup
Figure A.9 Definite Inverse Curve (SEA8)
Time Dial
9.9
7.0
5.0
3.0
1.5
0.5
0.1
1000
100
10
Time to Trip (Seconds)
1
0.1
0.01 1
Multiples of Pickup
Figure A.10 I-Squared-T Curve
Time Dial
9.9
7.0
5.0
3.0
1.5
0.5
0.1
10
50
A
A.4 I-Squared-T Curve
The ISGS provides an I-Squared-T characteristic in addition to the standard inverse curves.
Trip Characteristic
50.7D 10.14+
T
-------------------------------------=
Reset Characteristic
i
---- -
For
1 : T
<
ip
T = time to trip, in seconds

i
---- -
= multiple of pickup setting

i

p
D = time dial setting, 0.1 to 9.9 in steps of 0.1
t
= reset constant = 7.4
r
i

--- -

i
p
2
=
-----------------------
t
D
r
2
i
----
1

i
p
A.5 Custom Protective Curve
The custom curve consists of up to 60 current-time pairs corresponding to points on the time-current characteristic curve. Current refers to multiple-of-pickup value (I/Ip) on the horizontal axis, and time refers to time-to-trip values on the vertical axis. Each point consists of two values (I/Ip and t), loaded in order from lowest to highest value of I/Ip via the SEAbus or local ports. Siemens Wisdom software is required in order to load a custom curve. Time-to-trip has a range of
0.00 to 655.35 seconds in steps of 0.01 seconds. I/Ip has a range of 1.1 to 20.00 in steps of 0.01. The first point in the data set must be I/Ip=1.1, the last point must be I/Ip=20. Points in between these two limits can be for any values of I/ Ip and t as long as the slope ( described by the points is between 0 (horizontal) and -
t/(I/Ip)) of the curve
(ver-
tical). For input current in excess of 20 x Ip, the relay will enter a definite time mode and the curve will be considered to be flat (constant time) at the time value associated with I/ Ip=20. Once loaded, a custom curve is not adjustable, that is there is no time dial adjustment.
A.6 Over/Undervoltage Curves
The ISGS provides a moderately inverse overvoltage and a moderately inverse undervoltage protection defined by the equation in Equation A.5 and Equation A.6. Their charac­teristics are provided in Figure A.11 and Figure A.12.
Equation A.4 I-Squared-T Equation
56 Siemens Energy & Automation, Inc.
Appendix A: Trip Curves & Equations
Over/Undervoltage Coefficients
Curve Type Des.
1
A
1
B
1
N
Inverse 0.51 -1.75 0.50 ---
Mod. Inverse 0.51 -0.45 0.50 ---
Very Inverse 0.51 1.75 0.50 ---
1
The A, B, and N coefficients are for the standard relay formula
Table A.2 Under/Overvoltage Coefficients
v
For1.01
For
-----
1.5: T
v
p

v
-----
1.5: T

v
p

T = time to trip, in seconds v = measured input voltage
= pickup value (tap setting)
v
p

v
------
= multiple of pickup setting

v

p
D = time dial setting, 0.1 to 9.9 in steps of 0.1
= constants for inverse curves
A, B, N
AD
-------------------------BD+=≤≤
N
v
-----
v
AD
--------------------------BD+=>
)(
1.5
1
p
N
1
t
r
1000
100
10
Time to Trip (Seconds)
1
0.1 1 1.1 1.2 1.3 1.4 1.5 1.6
Multiples of Pickup
Time Dial
9.9
5.0
2.0
1.0
0.5
0.2
0.1
Figure A.11 Moderately Inverse Overvoltage Curve
A
1000
Equation A.5 Overvoltage Equation
v
For 0.5
For
-----
1.5: T
v
p

v
-----
0.5:

v
p

T
--------------------------BD+=
1.5
T = time to trip, in seconds v = measured input voltage
= pickup value (tap setting)
v
p

v
------
= multiple of pickup setting

v

p
D = time dial setting, 0.1 to 9.9 in steps of 0.1
= constants for inverse curves
A, B, N
Equation A.6 Undervoltage Equation
-------------------------BD+=≤≤
 
v
----­v
AD
)(
AD
N
1
p
N
1
Time Dial
9.9
5.0
2.0
1.0
0.5
0.2
0.1
0.4 0.5 0.6 0.7 0.8 0.9 1.0
Multiples of Pickup
100
10
Time to Trip (Seconds)
1
0.1
Figure A.12 Moderately Inverse Undervoltage Curve
Siemens Energy & Automation, Inc. 57
B
Appendix B: Metering
B Metering
B.1 Accuracy
Table B.1 Metering Accuracies
Parameter Range Accuracy
rms Current (L & G) 0-250% I
Average rms Current 0-250% In Displayed in Amperes ±1% of measurement from 50-125% of I
Ampere Demand per Phase 0.. 250% In Displayed in Amperes ±1% of measurement from 50-125% of In
Average Ampere Demand 0-250% In Displayed in Amperes ±1% of measurement from 50-125% of In
rmsVoltage (L-L and L-N) 10-125% Vn Displayed in kV ±1% of measurement from 50-125% of Vn
Average rms Voltage 10-125% Vn Displayed in kV ±1% of measurement from 50-125% of Vn
Active Power (kW) 0-999,999.99 kW ±2% of measurement from 50-125% of Pn
kW Demand 0-999,999.99 kWD ±2% of measurement from 50-125% of Pn
kW Hours 0-999,999.99 kWHR ±2% of measurement from 50-125% of Pn
Apparent Power (kVA) 0-999,999.99 kVA ±2% of measurement from 50-125% of Pn
Volt-Amperes Reactive (kVAR) 0-999,999.99 kVAR ±2% of measurement from 50-125% of Pn
kVAR Hours 0-999,999.99 kVARH ±2% of measurement from 50-125% of Pn
Power Factor -1- 0-+1
Frequency 45-65 Hz ±0.1% of reading providing voltage is 50% VT primary rating
Displayed in Amperes ±1% of measurement from 50-125% of In
n
±0.5% of I
from 10- 50% of I
n
±0.5% of In from 10-50% of I
±0.5% of I
±0.5% of I
±0.5% of V
±0.5% of V
±0.1% of V
±0.1% of V
±0.1% of V
±0.1% of V
±0.1% of V
±0.1% of V
±0.04
from 10-50% of I
n
from 10-50% of I
n
from 10-50% of V
n
from 10-50% of V
n
from 10-50% of P
n
from 10-50% of P
n
from 10-50% of P
n
from 10-50% of P
n
from 10-50% of P
n
from 10-50% of P
n
4
n
n
n
n
n
n
n
n
n
n
n
n
1, 5
1, 5
1, 3, 5
1, 5
1, 2, 5
1, 2, 3, 5
n
1
Measured at PF=1. For |PF|<1, ±2% + angle error (±2% for |PF|0.7)
2
Measured at PF=0. For |PF|>0, ±2% + angle error (±2% for |PF|0.7)
3
Energy is accumulated in either kHR or MHR, selectable (parameter).
4
For power factor, 1 is considered perfect, negative is leading and positive is lagging.
5
Pn = Vn x In, where Vn = VT rating (120 V) and In = CT rating (5A).
Note for all values: Stated accuracy applies only when the device is not in pickup. These measurements are valid over a frequency range of 45- 65Hz and include fundamental, second harmonic, and all odd harmonics up to the 13th harmonic of the fundamental line frequency.
58 Siemens Energy & Automation, Inc.
B.2 Power Conventions
Line Load
Appendix B: Metering
Export
Reverse
Negative
(kW/kVAR supplied
by the load)
Ø=90 to 180° Power Factor Lead
Ø=180°, -kW, kWh Exported, Power Factor = 1
Ø=90°, +kVAR, kVARh Imported, Power Factor = 0
Phase Angle Ø
Import Forward Positive
(kW/kVAR consumed
by the load)
Ø=0 to 90° Power Factor Lag
Ø=0°, +kW, kWh Imported, Power Factor = 1
B
Ø=180 to 270° Power Factor Lag
Ø=270°, -kVAR, kVARh Exported, Power Factor = 0
Figure B.1 Complex Power Plane
Siemens Energy & Automation, Inc. 59
Ø=270 to 360° Power Factor Lead
Appendix C: Menu Structure
C
C Menu Structure
The following table provides a complete list of addresses and parameters available to the ISGS in its standard and optional configuration.
Functions that set the device, the CTs, or the VTs, or func­tions that require a change in the matrix are indicated by and asterisk (*) next to the address. Observe the warning label below when changing the settings of these functions.
Block Function Address Parameter
0000 Power On/Configu-
ration Display
1000 * Device
Configuration
1100 * CT Configuration 1101
1200 * VT Configuration 1201
--- ---
1002
Frequency
1003
Phase Seq.
1004
Brkr Conn.
1005
Trip Time
Ph Pri Rtg
1102
Neu Pri Rtg
1104
Norm Pwr Flo
Pri Rating
1202
VT Mode
1203
Secondary Rating
Block Function Address Parameter
A1500 Instantaneous
Phase Overcurrent (50)
High-Set Instanta­neous Phase Over­current (50HS)
A1600 Instantaneous Neu-
tral or Ground Overcurrent (50N)
High-Set Instanta­neous Neutral or Ground Overcur­rent (50HSN)
A1700 Phase Time Over-
current (51)
A1800 Neutral Time Over-
current (51N)
A1900 Directional Phase
Time Overcurrent (67)
A2000 Directional Neutral
Time Overcurrent (67N)
A2200 Overvoltage (59) 2201
1501
Function 50
1502
Pickup 50
1504
Delay 50
1510
Freeze Wfm 1 50
1511
Freeze Wfm 2 50
1512
Block 50
1551
Function 50HS
1552
Pickup 50HS
1560
Freeze Wfm 1 HS
1561
Freeze Wfm 2 HS
1601
Function 50N
1602
Pickup 50N
1604
Time Delay 50N
1610
Freeze Wfm 1 50N
1611
Freeze Wfm 2 50N
1612
Block 50N
1651
Function HSN
1652
Pickup HSN
1660
Freeze Wfm 1HSN
1661
Freeze Wfm 2HSN
1702
Curve
1703
Pickup
1705
Time Dial
1706
Filter
1709
Reset
1710
Freeze Wfm 1
1711
Freeze Wfm 2
1712
Block 51
1801
Function
1802
Curve
1803
Pickup
1805
Time Dial
1806
Filter
1809
Reset
1810
Freeze Wfm 1
1811
Freeze Wfm 2
1812
Block 51N
1901
Function
1902
Curve
1903
Pickup
1905
Time Dial
1906
Filter
1907
Impedance
1908
Direction
1910
Freeze Wfm 1
1911
Freeze Wfm 2
2001
Function
2002
Curve
2003
Pickup
2005
Time Dial
2006
Filter
2007
Impedance
2008
Direction
2010
Freeze Wfm 1
2011
Freeze Wfm 2
Function
2202
Curve
2204
Pickup
2205
Delay (Definite)
2206
Dial (Inverse)
2210
Freeze Wfm 1
2211
Freeze Wfm 2
60 Siemens Energy & Automation, Inc.
Appendix C: Menu Structure
Block Function Address Parameter
A2300 Undervoltage (27) 2301
A2400 Phase Sequence
Voltage (47)
Negative Sequence Voltage (47N)
A2500 Overfrequency
(810)
Underfrequency (81U)
2800 Breaker Failure
(50B)F
3000 Alarm Setpoints --- ---
3100 Demand Setpoints 3101
3200 Power Setpoints 3201
Function
2302
Curve
2304
Pickup
2305
Delay (Definite)
2306
Dial (Inverse)
2310
Freeze Wfm 1
2311
Freeze Wfm 2
2401
Function 47
2410
Freeze Wfm1 47
2411
Freeze Wfm2 47
2451
Function 47N
2452
Curve 47N
2453
Pickup 47N
2454
Delay 47N
2455
Time Dial 47N
2456
Max Time 47N
2457
Block 47N
2460
Freeze Wfm1 47N
2461
Freeze Wfm2 47N
2501
Function 810
2503
Pickup 81O
2504
Time Delay 81O
2506
Block 81O
2510
Freeze Wfm1 81O
2511
Freeze Wfm2 81O
2551
Function 81U
2553
Pickup 81U
2554
Time Delay 81U
2556
Block 81U
2560
Freeze Wfm1 81U
2561
Freeze Wfm2 81U
2801
Function
2802
Pickup
2804
Time Delay
2805
Check
Demand Interval
3102
Sync Time
3103
Subperiods 60
3104
Subperiods 30
3105
Subperiods 15
3106
ADmd Function
3107
ADmd Pickup
3108
KWDmdFunction
3109
KWDmdPickup
KVAR Enable
3202
KVAR Pickup
3203
KVARTime Delay
3203
KVA Enable
3204
KVA Pickup
3206
KVA Delay
3207
PF Lead Enable
3208
PF Lead Pickup
3209
PF Lead Sign
3210
PF Lead Delay
3211
PF Lag Enable
3212
PF Lag Pickup
3213
PF Lag Sign
3214
PF Lag Delay
Block Function Address Parameter
3400 Analog Monitoring
(Value Supervision)
3500 Breaker Operation 3501
4000 Metering --- ---
4100 Current Metering 4101
4200 Voltages 4201
4300 Power Metering 4301
4400 Frequency
Metering
4600 Current Minimum/
Maximum Log
3401
Function V Bal
3402
Pickup V Bal
3404
Factor V Bal
3411
Function I Sum
3412
Pickup I Sum
3414
Factor I Sum
3421
Function I Bal
3422
Pickup I Bal
3424
Factor I Bal
Int. I Enable
3502
Int. I Pickup
3503
Brkr Ops Enable
3504
Brkr Ops Pickup
I Phase A
4102
I Phase B
4103
I Phase C
4104
I Neutral
4105
I Average
4106
I Demand, Phase A
4107
I Demand, Phase B
4108
I Demand, Phase C
4109
I Demand, Average
4110
I THD
V 1-2
4202
V 2-2
4203
V 3-1
4204
V L-L Average
4209
V THD
KW 3-Phase
4302
KW Hours
4303
KW Demand
4304
KVA 3-Phase
4305
KVAR 3-Phase
4306
KVAR Hours
4307
Power Factor
4401 Frequency
4601
I1 min
4602
I1 max
4603
I2 min
4604
I2 max
4605
I3 min
4606
I3 max
4607
IN min
4608
IN max
4609
IAv min
4610
IAv max
4611
I1 dem min
4612
I1 dem max
4613
I2 dem min
4614
I2 dem max
4615
I3 dem min
4616
I3 dem max
4617
IAv dem min
4618
IAv dem max
4619
MinTHD?
4620
MaxTHD
C
Siemens Energy & Automation, Inc. 61
Appendix C: Menu Structure
C
Block Function Address Parameter
4700 Voltage Minimum/
Maximum Log
4800 Power Minimum/
Maximum Log
4900 Frequency Mini-
mum/Maximum Log
5000 Trip Logs --- ---
5100
Trip Log
(most
thru
5800
Information
Note: Access address block first, then scroll to desired 3-digit address
recent)
(oldest)
6000 * Matrixing --- ---
6100 * Binary Inputs 6101
6200 * Binary Outputs 6201
6400 * Trip Contacts 6401
4701
V1-2 min
4702
V1-2 max
4703
V2--3 min
4704
V2-3 max
4705
V3-1 min
4706
V3-1 max
4713
VAv min
4714
VAv max
4717
Min THD
4718
Max THD
4801
kW min
4802
kW max
4803
kW dem min
4804
kW dem max
4805
kVA min
4806
kVA max
4807
kVAR min
4808
kVAR max
4809
PF max
4810
PF min
4901
Frequency min
4902
Frequency max
(001)
Trip #
(002)
Time in Pickup
(003)
Pickup Function
(004)
Phase (at Pickup)
(005)
I1 (at Pickup)
(006)
I2 (at Pickup)
(007)
I3 (at Pickup)
(008)
IN (at Pickup)
(009)
V1 (at Pickup)
(010)
V2 (at Pickup)
(011)
V3 (at Pickup)
(012)
Trip Function
(013)
Phase (at Trip)
(014)
I1 (at Trip)
(015)
I2 (at Trip)
(016)
I3 (at Trip)
(017)
IN (at Trip)
(019)
V1 (at Trip)
(020)
V2 (at Trip)
(021)
V3 (at Trip)
(022)
TinPU
(023)
Trip Log full
Input 1
6102
Input 2
6103
Input 3
6104
Input 4
Output 1
6202
Output 2
Contact 1
6402
Contact 2
6403
Contact 3
Block Function Address Parameter
7000 Operating
Parameters
7100 Parameter Set 7101
7200 Configure Comm
Port SEAbus
7300 Configure
Passwords
7400 Relay Data 7401
8000 Other Settings --- ---
8100 Date and Time
Setting
8200 Reset 8201
8300 Breaker Monitoring 8301
8400 Waveform Capture 8401
7005
LCD Line 1
7006
LCD Line 2
Active Set
7103
Activation
7104
Copy? Defaults to A
7105
Copy? Defaults to B
7106
Copy? A to B
7107
Copy? B to A
7201
Local Port
7202
System Port
7203
ParaChange
7204
Com Events
7207
Local Address
7301
CW Level 1
7302
CW Level 2
7303
CW Level 3
Circuit Name
7402
MainBd S/N
7403
MainBd ID
7404
OptBd 1 S/N
7405
OptBd 1 ID
7406
OptBd 2 S/N
7407
OptBd 2 ID
7408
Bin. Inputs
7409
Bin. Outputs
8101
Current Date
8102
Date
8103
Time
Trip Log
8202
Min/Max Values?
8203
Energy
8204
Breaker Ops
8205
SumCurrInter
8211
Breaker Ops
8212
Sum IL1
8213
Sum IL2
8214
Sum IL3
TripSrcImp
8302
TripSrcFail
8303
TrpCoil Cont
8304
TrpCoilFail
8305
BrkrMech
Wfm1 Pre-Trip
8402
Wfm2 Pre-Trip
62 Siemens Energy & Automation, Inc.
Appendix D: Acceptance Test Procedures
D Acceptance Test Procedures
When performing the acceptance tests, follow the sequence listed here; first test protective function 51, then 50, etc.)
Note: The following procedures should be performed using accurately calibrated test equipment connected to a source free of harmonics. Refer to Figure D.1 for connection diagram.
ISGS Acceptance Test
Set the ISGS as follows:
Parameter Set A 7103 5000:5 Current Transformer (CT) 1101 Curve SEA 5, Very Inverse 1702 1 A Nominal Pickup 1703 Time Dial per Chart 1705 Trip Matrixed to Trip 1 Contact 6401 Disable Other Conflicting Functions 1501, 1551, 1601, 1651, 1801, 1901, 2001, 2301
Phase
A B C Connections
1. Connect the appropriate source of control voltage to terminals 13 (+) and 12 (-).
Relay Disabled contact on terminals 19 and 20 opens.
2. Connect suitable variable source current to phase A, terminals 3 and 4,
to phase B, terminals 5 and 6,
to phase C, terminals 7 and 8,
Phase Time Overcurrent (51) Function
to neutral, terminals 9 and 10.
3. Connect timer to Trip 1 contacts, terminals 1 and 2.
Pickup
4. Increase current until relay picks up (this should occur at 1.06 x pickup.
Pickup LED illuminates.
Wisdom software records pickup in event log.
Return current to zero and reset timer.
Timing
5.
Apply appropriate value of current for the test. The results match Table D.1.
Pickup LED illuminates.
Display shows PICKUP 51 P1 (2, 3).
Wisdom software records pickup in event log.
Siemens Energy & Automation, Inc. 63
D
E
Appendix D: Acceptance Test Procedures
ISGS Acceptance Test (continued)
Phase
ABC
6.
Relay times out per Table D.1
Trip LED illuminates.
Timer stops as Trip 1 contacts close.
Trip log indicates trip current value and time in pickup.
Wisdom software records trip on overcurrent.
Return current to zero and reset timer.
7. Remove control power from relay for five seconds, then restore it.
Trip LED re-illuminates after relay is powered up again.
8. Reset relay target.
Trip LED resets.
.
Phase Time Overcurrent (51) Function
D
Repeat above steps for phase B and phase C; repeat the same steps also for Parameter Set B. Testing may also be done for each phase at the user settings following the same procedure.
Table D.1 Test Points for Very Inverse Curve Characteristics
Multiple of Pickup Time Band 2 (seconds) Time Band 5 (seconds) Time Band 9.9 (seconds)
2X 3.73 9.30 18.38
4X 0.92 2.27 4.46
8X 0.40 0.96 1.87
Accuracy of the time curve for 2 I/Ip 20 is 5% from the defined value, or 30 ms, whichever is greater.
64 Siemens Energy & Automation, Inc.
Appendix D: Acceptance Test Procedures
ISGS Acceptance Test
Set the ISGS as follows:
Parameter Set A 7103 5000:5 Current Transformer (CT) 1102 Curve SEA 5, Very Inverse 1802 1 A Nominal Pickup 1803 Time Dial per Chart 1805 Trip Matrixed to Trip 1 Contact 6401 Enable 51N 1801 Disable Other Conflicting Functions 1501, 1551, 1601, 1651, 1901, 2001, 2301 Raise 51 Pickup to Maximum 1703
Phase N Connections
1. Connect the appropriate source of control voltage to terminals 13 (+) and 12 (-).
Relay Disabled contact on terminals 19 and 20 opens.
2. Connect suitable variable source current to neutral, terminals 9 and 10.
3. Connect timer to Trip 1 contacts, terminals 1 and 2.
Neutral Time Overcurrent (51N) Function
Pickup
4. Increase current until relay picks up (this should occur at 1.06 A x pickup).
Pickup LED illuminates.
Wisdom software records pickup in event log.
Return current to zero and reset timer.
Timing
5. Apply appropriate value of current for the test. The results match Table D.2.
Pickup LED illuminates.
Display shows PICKUP 51N PN.
Wisdom software records pickup in event log.
D
Siemens Energy & Automation, Inc. 65
Appendix D: Acceptance Test Procedures
ISGS Acceptance Test (continued)
Phase N
6. Relay times out per Table D.2
Trip LED illuminates.
Timer stops as Trip 1 contacts close.
Trip log indicates trip current value and time in pickup.
Wisdom software records trip on overcurrent.
Return current to zero and reset timer.
7. Remove control power from relay for five seconds, then restore it.
Trip LED re-illuminates after relay is powered up again.
8. Reset relay target.
Trip LED resets.
Repeat the same steps also for Parameter Set B. Testing may also be done for the user settings following the same procedure.
.
Neutral Time Overcurrent (51N) Function
D
Table D.2 Test Points for Very Inverse Curve Characteristics
Multiple of Pickup Time Band 2 (seconds) Time Band 5 (seconds) Time Band 9.9 (seconds)
2X 3.73 9.30 18.38
4X 0.92 2.27 4.46
8X 0.40 0.96 1.87
Accuracy of the time curve for 2 I/Ip 20 is 5% from the defined value, or 30 ms, whichever is greater.
66 Siemens Energy & Automation, Inc.
Appendix D: Acceptance Test Procedures
ISGS Acceptance Test
Set the ISGS as follows:
Parameter Set A 7103 5000:5 Current Transformer (CT) 1102 Curve SEA 5, Very Inverse 1702 20 A Nominal Pickup 1703 Time Dial 9.9 1705 Instantaneous Pickup 1 A 1501, 1502, 1503 Instantaneous Time Delay 0.0 1504 Trip Matrixed to Trip 1 Contact 6401
Phase
A B C Connections
1. Connect the appropriate source of control voltage to terminals 13 (+) and 12 (-).
2. Connect suitable variable source current
to phase A on terminals 3 and 4,
to phase B on terminals 5 and 6,
to phase C on terminals 7 and 8.
Instantaneous Phase Overcurrent (50) Function
3. Connect a timer to the trip contacts on terminals 1 and 2.
Pickup
4. Apply a current approximately 75% of the instantaneous pickup.
5. Raise the current and note the value of current at which the relay trips.
Trip LED illuminates.
Timer stops on trip.
Display shows TRIP 50 P1 (2, 3).
Trip log shows TRIP 50 P1 (2, 3) and the correct date and time.
Trip log shows value of current at trip.
Wisdom software records trip in event log.
Return current to zero and reset timer.
6. Set value of current slightly above Instantaneous Overcurrent pickup and record time required to trip.
Repeat above steps for phase B and phase C; repeat the same steps also for Parameter Set B. Tests may be repeated at required settings.
CAUTION: Extended testing at high current levels may damage the relay. Note rat­ings (Maximum Input Current) in Chapter 1, Section 1.5, Test Specifications.
D
Siemens Energy & Automation, Inc. 67
Appendix D: Acceptance Test Procedures
ISGS Acceptance Test
Set the ISGS as follows:
Parameter Set A 7103 Voltage Primary Rating 120 V 1201 Connection Line to Neutral 1202 Enable Function 2301 Time Characteristic: Inverse Time 2302 Trip on Line to Neutral 2303 Pickup Level 100 V 2304 Time Dial 5.0 2306 Trip Matrixed to Trip 1 Contact 6401
Phase
A B C Connections
1. Connect the appropriate source of control voltage to terminals 13 (+) and 12 (-).
Relay Disabled contact on terminals 19 and 20 opens.
With 27 enabled, pickup LED is illuminated; relay may trip on Undervoltage before VT source is applied.
2. Connect suitable variable voltage source to terminals 41, 43, and 45 with
Undervoltage (27) Function
D
neutral connected to 42, 44, and 46.
3. Connect timer to Trip 1 contacts on terminals 1 and 2.
Pickup
4. Apply nominal to neutral system voltage.
Pickup LED extinguishes.
Trip LED may be reset.
5. Slowly reduce voltage until relay picks up.
Pickup LED illuminates.
Display shows PICKUP 27 P1 (2, 3).
Wisdom software records pickup in event log.
6. Return voltage to nominal value.
Pickup LED extinguishes.
Wisdom software records end of pickup.
68 Siemens Energy & Automation, Inc.
Appendix D: Acceptance Test Procedures
ISGS Acceptance Test (continued)
Phase
A B C Timing
7.
Set voltage per Table D.3.
Pickup LED illuminates.
Display shows PICKUP 27 P1 (2, 3).
Wisdom software records pickup in event log.
8.
Relay times out per Table D.3.
Trip LED illuminates.
Timer stops as Trip 1 contacts close.
Trip log indicates trip voltage value and time in pickup.
Wisdom software records relay trip on Undervoltage.
Return voltage to nominal and reset timer.
9. Remove control power from relay for five seconds; then restore it.
Undervoltage (27) Function
Trip LED re-illuminates after relay is powered up again.
10. Reset the relay target.
Trip LED resets.
Repeat above steps for phase B and phase C; repeat the same steps also for Parameter Set B. Testing may also be done at the user settings following the same procedure.
Table D.3 Test Points for Inverse Undervoltage Curve Characteristics
Percent of Pickup Time Band 2 (seconds) Time Band 5 (seconds) Time Band 9.9 (seconds)
90 20.00 50.00 99.00
75 7.74 19.35 38.32
50 3.64 9.10 18.01
0 1.56 3.91 7.73
Accuracy of the time curve for 2 I/Ip 20 is 5% from the defined value, or 30 ms, whichever is greater.
D
Siemens Energy & Automation, Inc. 69
Appendix D: Acceptance Test Procedures
ISGS Acceptance Test
Set the ISGS as follows:
Parameter Set A 7103 Voltage Primary Rating 120 V 1201 Connection Line to Neutral 1202 Enable Function 2201 Time Characteristic: Inverse Time 2202 Trip on Line to Neutral 2203 Pickup Level 100 V 2204 Time Dial per Table 2206 Trip Matrixed to Trip 1 Contact 6401
Phase
A B C Connections
1. Connect the appropriate source of control voltage to terminals 13 (+) and 12 (-).
Relay Disabled contact on terminals 19 and 20 opens.
2. Connect suitable variable voltage source to terminals 41, 43, and 45 with
Overvoltage (59) Function
D
neutral connected to 42, 44, and 46.
3. Connect a timer to the Trip 1 contacts on terminals 1 and 2.
Pickup
4. Apply nominal to neutral system voltage.
Pickup LED extinguishes.
Trip LED may be reset.
5. Slowly increase voltage until relay picks up.
Pickup LED illuminates.
Display shows PICKUP 59 P1 (2, 3).
Wisdom software records pickup in event log.
6. Return voltage to nominal value.
Pickup LED extinguishes.
Wisdom software records end of pickup.
70 Siemens Energy & Automation, Inc.
Appendix D: Acceptance Test Procedures
ISGS Acceptance Test (continued)
Phase
A B C Timing
7.
Set voltage per Table D.4.
Pickup LED illuminates.
Display shows PICKUP 59 P1 (2, 3).
Wisdom software records pickup in event log.
8.
Relay times out per Table D.4.
Trip LED illuminates.
Timer stops as Trip 1 contacts close.
Trip log indicates trip voltage value and time in pickup.
Wisdom software records relay trip on Overvoltage.
Return voltage to nominal and reset timer.
9. Remove control power from relay for five seconds; then restore it.
Overvoltage (59) Function
Trip LED re-illuminates after relay is powered up again.
10. Reset relay target.
Trip LED resets.
Repeat above steps for phase B and phase C; repeat the same steps also for Parameter Set B. Testing may also be done at the user settings following the same procedure.
Table D.4 Test Points for Inverse Overvoltage Curve Characteristics
Percent of Pickup Time Band 2 (seconds) Time Band 5 (seconds) Time Band 9.9 (seconds)
110 20.00 50.00 99.00
125 7.74 19.35 38.32
150 3.64 9.10 18.01
>150 1.56 3.91 7.73
Accuracy of the time curve for 2 I/Ip 20 is 5% from the defined value, or 30 ms, whichever is greater.
D
Siemens Energy & Automation, Inc. 71
Appendix D: Acceptance Test Procedures
ISGS Acceptance Test
Directional Phase Time Overcurrent (67) Function
(Phase-Neutral Connected VTs)
Set the ISGS as follows:
Parameter Set A 7103 5000:5 Current Transformer (CT) 1101 Curve SEA 5, Very Inverse 1902 1 A Nominal Pickup 1903 Time Dial per Chart 1905 Impedance to 45° 1907 Direction to Reverse 1908 Trip Matrixed to Trip 1 Contact 6401 Enable 67 1901 Disable Other Conflicting Functions 1501, 1551, 1601, 1651, 1801, 1901, 2001, 2301 Raise 51 Pickup to Maximum 1703
Phase
A B C Connections
1. Connect the appropriate source of control voltage to terminals 13 (+) and 12 (-).
Relay Disabled contact on terminals 19 and 20 opens.
2. Connect suitable variable source current to phase A, terminals 3 and 4,
D
to phase B, terminals 5 and 6,
to phase C, terminals 7 and 8,
3. Connect suitable AC voltage to phase A, terminals 41 and 42,
to phase B, terminals 43 and 44,
to phase C, terminals 45 and 46,
Connect timer to Trip 1 contacts, terminals 1 and 2.
Pickup
4. Apply nominal voltage to the relays voltage inputs, for example, 69 V
Apply 2x pickup current to phase A and B in forward direction, for example, 2.0 A
-relay should not go into pickup,
-reset test current to zero A,
0 to phase A, 240 to phase B,
69 V 69 V
120 to phase C.
30 to phase A and 2.0 A ∠ 210 to phase B, or 270 to phase B and 2.0 A 90 to phase C, or
2.0 A
150 to phase C and 2.0 A 330 to phase A.
2.0 A
-increase phase A and phase B current in reverse direction until relay picks up (at 1.06 x pickup) for example, 1.06 A
72 Siemens Energy & Automation, Inc.
210 to phase A and 1.06 A 30 to phase B, or 90 to phase B and 1.06 A ∠ 270 to phase C, or
1.06 A
1.06 A
330 to phase C and 1.06 A ∠ 150 to phase A.
Appendix D: Acceptance Test Procedures
ISGS Acceptance Test
(continued)
Phase
ABC
Pickup LED illuminates.
Wisdom software records pickup in event log.
Return current to zero and reset timer.
Timing
5.
Apply appropriate value of current in reverse direction for the test. The results match Table D.5.
Pickup LED illuminates.
Display shows PICKUP 67 P12 (23, 31).
Wisdom software records pickup in event log.
6.
Relay times out per Table D.5
Trip LED illuminates.
Timer stops as Trip 1 contacts close.
Directional Phase Time Overcurrent (67) Function
(Phase-Neutral Connected VTs)
.
Trip log indicates trip current value and time in pickup.
Wisdom software records trip on directional overcurrent.
Return current to zero and reset timer.
7. Remove control power from relay for five seconds, then restore it.
Trip LED re-illuminates after relay is powered up again.
8. Reset relay target.
Trip LED resets.
Repeat above steps for phase B-C and phase C-A; repeat the same steps also for Parameter Set B. Testing may also be done for each phase at the user settings following the same procedure.
Table D.5 Test Points for Very Inverse Curve Characteristics
Multiple of Pickup Time Band 2 (seconds) Time Band 5 (seconds) Time Band 9.9 (seconds)
2X 3.73 9.30 18.38
4X 0.92 2.27 4.46
8X 0.40 0.96 1.87
Accuracy of the time curve for 2 I/Ip 20 is 5% from the defined value, or 30 ms, whichever is greater.
D
Siemens Energy & Automation, Inc. 73
Appendix D: Acceptance Test Procedures
ISGS Acceptance Test
Directional Phase Time Overcurrent (67) Function
(Phase-Phase Connected VTs)
Set the ISGS as follows:
Parameter Set A 7103 5000:5 Current Transformer (CT) 1101 Curve SEA 5, Very Inverse 1902 1 A Nominal Pickup 1903 Time Dial per Chart 1905 Impedance to 45° 1907 Direction to Reverse 1908 Trip Matrixed to Trip 1 Contact 6401 Enable 67 1901 Disable Other Conflicting Functions 1501, 1551, 1601, 1651, 1801, 1901, 2001, 2301 Raise 51 Pickup To Maximum 1703
Phase
A B C Connections
1. Connect the appropriate source of control voltage to terminals 13 (+) and 12 (-).
Relay Disabled contact on terminals 19 and 20 opens.
2. Connect suitable variable source current to phase A, terminals 3 and 4,
D
to phase B, terminals 5 and 6,
to phase C, terminals 7 and 8,
to neutral, terminals 9 and 10,
3. Connect suitable AC voltage to phase A-B, terminals 41 and 42,
to phase B-C, terminals 43 and 44,
to phase C-A, terminals 45 and 46,
Connect timer to Trip 1 contacts, terminals 1 and 2.
Pickup
4. Apply nominal voltage to the relays voltage inputs, for example, 69 V
Apply 2x pickup current to phase A and B in forward direction, for example, 2.0 A
-relay should not go into pickup,
30 to phase A-B,
69 V
270 to phase B-C, 150 to phase C-A.
69 V
30 to phase A and 2.0 A ∠ 210 to phase B, or 270 to phase B and 2.0 A 90 to phase C, or
2.0 A
2.0 A
150 to phase C and 2.0 A 330 to phase A.
-reset test current to zero A,
74 Siemens Energy & Automation, Inc.
Appendix D: Acceptance Test Procedures
ISGS Acceptance Test
(continued)
Phase
ABC
-increase phase A current in the reverse direction until relay picks up. This should occur at 1.06 x pickup, for example, 1.06 A
1.06 A
1.06 A
Pickup LED illuminates.
Wisdom software records pickup in event log.
Return current to zero and reset timer.
Timing
5.
Apply appropriate value of current in reverse direction for the test. The results match Table D.6.
Pickup LED illuminates.
Display shows PICKUP 67 P12 (23, 31).
Wisdom software records pickup in event log.
Directional Phase Time Overcurrent (67) Function
(Phase-Phase Connected VTs)
210 to phase A and 1.06 A 30 to phase B, or 90 to phase B and 1.06 A 270 to phase C, or 330 to phase C and 1.06 A 150 to phase A.
6.
Relay times out per Table D.6
Trip LED illuminates.
Timer stops as Trip 1 contacts close.
Trip log indicates trip current value and time in pickup.
Wisdom software records trip on directional overcurrent.
Return current to zero and reset timer.
7. Remove control power from relay for five seconds, then restore it.
Trip LED re-illuminates after relay is powered up again.
8. Reset relay target.
Trip LED resets.
Repeat above steps for phase B-C and phase C-A; repeat the same steps also for Parameter Set B. Testing may also be done for each phase at the user settings following the same procedure.
Table D.6 Test Points for Very Inverse Curve Characteristics
Multiple of Pickup Time Band 2 (seconds) Time Band 5 (seconds) Time Band 9.9 (seconds)
2X 3.73 9.30 18.38
4X 0.92 2.27 4.46
8X 0.40 0.96 1.87
Accuracy of the time curve for 2 I/Ip 20 is 5% from the defined value, or 30 ms, whichever is greater.
.
D
Siemens Energy & Automation, Inc. 75
Appendix D: Acceptance Test Procedures
ISGS Acceptance Test
Set the ISGS as follows:
Parameter Set A 7103 5000:5 Current Transformer (CT) 1102 Curve SEA 5, Very Inverse 2002 1 A Nominal Pickup 2003 Time Dial per Chart 2005 Impedance to 45° 1907 Direction to Reverse 1908 Trip Matrixed to Trip 1 Contact 6401 Enable 67 2001 Disable Other Conflicting Functions 1501, 1551, 1601, 1651, 1801, 1901, 2001, 2301 Raise 51 Pickup to Maximum 1703
Phase N Connections
1. Connect the appropriate source of control voltage to terminals 13 (+) and 12 (-).
2. Relay Disabled contact on terminals 19 and 20 opens.
3. Connect suitable variable source current to phase A, terminal 3,
Directional Neutral Time Overcurrent (67N)
(Only Available with Phase-Neutral Connected VTs)
Function
D
to phase B, terminal 5,
to phase C, terminal 7,
Connect terminals 4, 6, and 8 to terminal 9.
Connect terminal 10 to the common of the current sources.
4. Connect suitable AC voltage to phase A, terminals 41 and 42,
to phase B, terminals 43 and 44,
to phase C, terminals 45 and 46,
Connect timer to Trip 1 contacts, terminals 1 and 2.
Pickup
5. Apply nominal voltage to the relays voltage inputs, for example, for example, 69 V
Apply 2x pickup current to phase A in forward direction, for example, for example, 2.0 A
-relay should not go into pickup,
0 to phase A,
69 V
240 to phase B, 120 to phase C.
69 V
0 to phase A, 240 to phase B,
2.0 A
2.0 A
120 to phase C.
-reset test current to zero A,
76 Siemens Energy & Automation, Inc.
Appendix D: Acceptance Test Procedures
ISGS Acceptance Test
(continued)
Phase N
-increase phase A current in the reverse direction until relay picks up. This should occur at 1.06 x pickup, for example, 1.06 A
Pickup LED illuminates.
Wisdom software records pickup in event log.
Return current to zero and reset timer.
Timing
6.
Apply appropriate value of current in reverse direction for the test. The results match Table D.7.
Pickup LED illuminates.
Display shows PICKUP 67N PN.
Wisdom software records pickup in event log.
180 to phase A,
60 to phase B,
1.06 A
1.06 A
300 to phase C.
Directional Neutral Time Overcurrent (67N)
Function
(Only Available with Phase-Neutral Connected VTs)
7.
Relay times out per Table D.7
Trip LED illuminates.
Timer stops as Trip 1 contacts close.
Trip log indicates trip current value and time in pickup.
Wisdom software records trip on directional overcurrent.
Return current to zero and reset timer.
8. Remove control power from relay for five seconds, then restore it.
Trip LED re-illuminates after relay is powered up again.
9. Reset relay target.
Trip LED resets.
Repeat above steps for phase B and phase C; repeat the same steps also for Parameter Set B. Testing may also be done for each phase at the user settings following the same procedure.
Table D.7 Test Points for Very Inverse Curve Characteristics
Multiple of Pickup Time Band 2 (seconds) Time Band 5 (seconds) Time Band 9.9 (seconds)
2X 3.73 9.30 18.38
4X 0.92 2.27 4.46
8X 0.40 0.96 1.87
Accuracy of the time curve for 2 I/Ip 20 is 5% from the defined value, or 30 ms, whichever is greater.
.
D
Siemens Energy & Automation, Inc. 77
Appendix D: Acceptance Test Procedures
50/
50/51
51N
ISGS Relay
D
I
TS
V
TS
Test Equipment
CT 1-1 CT 1-2
CT 2-1 CT 2-2 CT 3-1 CT 3-2 CT N-1 CT N-2
VT 1+
VT 1­VT 2+
VT 2­VT 3+
VT 3-
3 4 5 6 7 8 9 10
41
42 43
44 45
46
21
22 23
24 25
26 27
28
I
A
I
B
I
C
I
N
V
A
V
B
V
C
Binary Input 1
Binary Input 2
Binary Input 3
Binary Input 4
Trip 1
Trip Common
Trip 2
Trip 3
Binary Output 1
Binary Output 2
2 1 11
29 30
31 32
33 34
ISGS Relay
Figure D.1 Terminal Connections for Test Procedures
78 Siemens Energy & Automation, Inc.
E Schematics
E.1 DC Trip System
The following diagram illustrates a typical connection scheme for the ISGS relay when using a DC trip system.
+
-
Appendix E: Schematics
48
13
11718
49
(see below)
Optional
RS-485
Communications
PS
IN1
Impedance
Sense
Impedance
Source
Trip
Common
Trip 1 Trip 2
19
Case
Ground
Power
Supply
(DC-DC)
Impedance
Trip Source
Sense Circuit
BI BSW
Monitors
b-contacts
Relay
14
20
Disabled*
PS
IN2
Ground
Monitor
211
BI
Trip
15 16 12
closed when
relay is out of service
ISGS Relay
*Contact is
95C
Monitors
a-contacts
and trip coil
Optional
Remote
Closing
Incoming
RS-485
Shield
Data +
Bus
Data -
Outgoing
RS-485
Bus
Shield
Data + Data +
Data - Data -
49
48
Optional
RS-485
Communications
52a
52
52T
88
SRC
LS
52b
52a
4
15 2 14
3
Breaker
Fuse
4
Fuse
3
Aux Switch (open when breaker is open)
Aux Switch (closed when breaker is open)
Opening Solenoid (Trip)
Spring Release Solenoid
Spring Charging Motor
Control Switch/Close
Control Switch/TripRRed Lamp (breaker open)
Green Lamp (breaker open)
Interposing Relay
???
N
Key
52a
52b
52T
52SRC
88
CS/C
CS/T
G
95C
LS
RES
RES
RES
RG
RES
2
2
Fuse
1
P
Fuse
1
3
CS
1
CS
C
4
95C
T
2
(Station
Battery)
313 161 4
DC Supply
Figure E.1 Wiring for DC Trip Systems
Siemens Energy & Automation, Inc. 79
E
Appendix E: Schematics
E.2 AC (Capacitor) Trip Systems
The following diagram illustrates a typical connection scheme for the ISGS relay when using an AC trip system.
Key
52a
52b
52T
52SRC
88
CS/C
CS/T
G
95C
CTD
LS
AC0
(120 VAC
Only)
AC Supply
AC1
Spring Charging Motor
Control Switch/Close
Control Switch/TripRRed Lamp (breaker open)
Green Lamp (breaker open)
Interposing Relay
Capacitor Trip Device
???
Optional
RS-485
Communications
3
Aux Switch (open when breaker is open)
Aux Switch (closed when breaker is open)
Opening Solenoid (Trip)
Spring Release Solenoid
ground monitor (16), and impedance
sense (18) to AC0.
3
Slug
4
*Not used with AC configuration.
Tie impedance source (terminal 17),
Slug
4
15 214
Breaker
Closing
LS
SRC
88
CTD
52a
52T
Optional
Remote
52
52a
95C
52
313 16 1114
95C
4
CS
C
2
3
RG
2
T
CS
Trip 1 Trip 2
1-Fuse
RES
RES
1
1
1
1-Fuse
2
1
Trip
Common
17 18
Sense Circuit*
Trip Source
Impedance
E
494848
PS
Data - Data -
Shield
RS-485
Bus
Data + Data +
Outgoing
Data +
Data -
RS-485
Bus
Shield
Incoming
52b52a
RES
RES
IN2
BI
Trip
1516 12
BI
BSW
14211
*Contact is
relay is out of service
ISGS Relay
closed when
Disabled*
20
Relay
19
(AC-DC)
Supply
Power
Case
Ground
PS
IN1
13
Optional
RS-485
Communications
(see below)
49
+
-
Figure E.2 Wiring for AC (Capacitor) Trip System
80 Siemens Energy & Automation, Inc.
ISGS Settings Worksheet for Date: Set A
This ISGS settings worksheet allows easy recording of the desired ISGS parameter settings when configuring the device manually with the keypad controls.
Functions and parameters are listed in numerical sequence of their address blocks and addresses just as they appear on the LCD. Where applicable, value ranges and resolution are provided for easy reference. Only configurable functions and parameters are listed. For a complete list refer to the ISGS relay menu in Appendix C.
Before configuring the device, copy this form and enter the desired configuration data. Include the device identification number (device version number and its catalog number on front panel label; or line 1 and line 2 of Power On display) and the date of configuration. Then simply circle the desired set-
0000 Power On Display (enter display)
----
Line 1
----
Line 2
tings and enter numerical values in the blank spaces pro­vided. Boldfaced settings indicate factory defaults. For indicating matrix settings, draw a line from the matrix position number to the desired setting and circle the setting.
Take special care in copying lines 1 and 2 of the relays Power On display (refer to Section 4.1). The information dis­played in these two lines provides Siemens with detailed information about the device in the event you encounter a problem and have to contact Siemens customer service.
After entering all data on this configuration form, take it to the device and enter the information into the relay. This form allows for the recording of both parameter sets. After com­pleting this form, file it for future reference.
1000 Device Configuration
1002
Frequency
1003
Phase Sequence
1004
Breaker Connection
1005
Trip T im e
1100 Current Transformer Configuration
1101 Phase CT Primary Rating 1200 A
1102 Neutral CT Primary Rating 1200 A
1104 Power Flow Normal Reverse
1200 Voltage Transformer Configuration
1201 Primary Rating 12000 V
1202 VT Mode Line-to-Line Line-to-Neutral
60 Hz 50 Hz
123 (ABC) 132 (ACB)
Trip1 Trip2 Trip3 Trips 1&2 Trips1&3 Trips 123
0.1 s
Range: 0.01-32 s (0.01 s steps)
Range: 5-8000 A (1 A steps)
Range: 5-8000 A (1 A steps)
Range: 120-138000 V (1 V steps)
s
A
A
V
S
1203 Secondary VT Rating 120 V Range: 100-120 V (1 V steps) V
Siemens Energy & Automation, Inc. S-1
ISGS Settings Worksheet for Date: Set A
A1500
A1501 Function 50 Enabled Disabled
A1502
A1504 Time Delay 50 0.00 s Range: 0-60 s (0.01 s steps) s
A1512 Block 50 by None 50HS & 50HSN 50HS 50HSN
A1551 Function 50HS Enabled Disabled
A1552
Instantaneous Phase Overcurrent (50) High-Set Instantaneous Phase Overcurrent (50HS)
Pickup 50 5 A CT 1.0 A Range: 1-120 A (0.1 A steps) A
1 A CT 0.2 A Range: 0.2-24 A (0.1 A steps) A
1510 Freeze Waveform 1 50 on pickup on Trip None
1511 Freeze Waveform 2 50 on pickup on Trip None
Pickup 50HS 5 A CT 5.0 A Range: 5-120 A (0.1 A steps) A
1 A CT 0.2 A Range: 0.2-24 A (0.1 A steps) A
1560 Freeze Waveform 1 50HS --- on Trip None
S
1561 Freeze Waveform 2 50HS --- on Trip None
A1600
A1601 Function 50N Enabled Disabled
A1602
A1604 Time Delay 50N 0.00 s Range: 0-60 s (0.01 s steps) s
A1612 Block 50N by None 50HS & 50HSN 50HS 50HSN
A1651 Function 50HSN Enabled Disabled
A1652
Instantaneous Neutral or Ground Overcurrent (50N) High-Set Instantaneous Neutral or Ground Overcurrent (50HSN)
Pickup 50N 5 A CT 1.0 A Range: 1-120 A (0.1 A steps) A
1 A CT 0.2 A Range: 0.2-24 A (0.1 A steps) A
1610 Freeze Waveform 1 50N on Pickup on Trip None
1611 Freeze Waveform 2 50N on Pickup on Trip None
Pickup 50HSN 5 A CT 5.0 A Range: 5-120 A (0.1 A steps) A
1 A CT 0.2 A Range: 0.2-24 A (0.1 A steps) A
1660 Freeze Waveform 1 50HSN --- on Trip None
1661 Freeze Waveform 2 50HSN --- on Trip None
S-2 Siemens Energy & Automation, Inc.
ISGS Settings Worksheet for Date: Set A
A1700 Phase Time Overcurrent (51)
A1702
A1703
A1705 Time Dial 51 0.1 Range: 0.1-9.9 (0.1 steps)
A1706 Filter 51 rms fundamental
A1709 Reset 51 Disk Emulation Instantaneous
A1712 Block 51 by None 50HS & 50HSN 50HS 50HSN
A1800 Neutral Time Overcurrent (51N)
Curve 51 Inverse Short Inverse Long Inverse
Custom Very Inverse Extremely Inverse Definite Inverse
Slightly Inverse
Pickup 51 5 A CT 0.5 A Range: 0.5-20 A (0.1 A steps) A
(PU point is 1.06 1 A CT of PU setting).
1710 Freeze Waveform 1 51 on Pickup on Trip None
1711 Freeze Waveform 2 51 on Pickup on Trip None
0.1 A Range: 0.1-4 A (0.1 A steps) A
2
T without Limit
I
Moderately Inverse
A1801 Function 51N Enabled Disabled
A1802
A1803
A1805 Time Dial 51N 0.1 Range: 0.1-9.9 (0.1 steps)
A1806 Filter 51N rms fundamental
A1809 Reset 51N Disk Emulation Instantaneous
A1812 Block 51N by None 50HS & 50HSN 50HS 50HSN
Curve 51N Inverse Short Inverse Long Inverse
Custom Very Inverse Extremely Inverse Definite Inverse
Slightly Inverse
Pickup 51N 5 A CT 0.5 A Range: 0.5-20 A (0.1 A steps) A
1 A CT 0.1 A Range: 0.1-4 A (0.1 A steps) A
1810 Freeze Waveform 1 51N on Pickup on Trip None
1811 Freeze Waveform 2 51N on Pickup on Trip None
2
T without Limit
I
Moderately Inverse
S
Siemens Energy & Automation, Inc. S-3
ISGS Settings Worksheet for Date: Set A
A1900 Directional Phase Time Overcurrent (67)
A1901 Function 67 Enabled Disabled
A1902 Curve 67 Inverse Short Inverse Long Inverse
Custom Very Inverse Extremely Inverse Definite Inverse
Slightly Inverse
A1903
A1905 Time Dial 67 0.10 Range: 0.1-9.9 (0.1 steps)
A1906 Filter 67 rms fundamental
A1907 Impedance 67 45° Range: 0-90° (1° steps) °
A1908 Direction 67 Normal Reverse
A2000 Directional Neutral Time Overcurrent (67N)
Pickup 67 5 A CT 0.5 A Range: 0.5-20 A (0.1 A steps) A
1 A CT 0.1 A Range: 0.1-4 A (0.1 A steps) A
1910 Freeze Waveform 1 67 on Pickup on Trip None
1911 Freeze Waveform 2 67 on Pickup on Trip None
2
T without Limit
I
Moderately Inverse
S
A2001 Function 67N Enabled Disabled
A2002 Curve 67N Inverse Short Inverse Long Inverse
Custom Very Inverse Extremely Inverse Definite Inverse
Slightly Inverse
A2003
A2005 Time Dial 67N 0.10 Range: 0.1-9.9 (0.1 steps)
A2006 Filter 67N rms fundamental
A2007 Impedance 67N 45° Range: 0-90° (1 ° steps) °
A2008 Direction 67N Normal Reverse
Pickup 67N 5 A CT 0.5 A Range: 0.5-20 A (0.1 A steps) A
(PU point is 1.06 1 A CT of PU setting).
2010 Freeze Waveform 1 67N on Pickup on Trip None
2011 Freeze Waveform 2 67N on Pickup on Trip None
0.1 A Range: 0.1-4 A (0.1 A steps) A
2
T without Limit
I
Moderately Inverse
S-4 Siemens Energy & Automation, Inc.
ISGS Settings Worksheet for Date: Set A
A2200 Overvoltage (59)
A2201 Function 59 Enabled Disabled
A2202 Curve 59 Inverse
A2203
A2204 Pickup 59 130 V Range: 60-250 V (0.1 V steps) V
A2205 Time Delay 59 (Definite) 0.10 s
A2206 Time Dial 59 (Inverse) 0.1 Range: 0.1-9.9 (0.1 steps)
A2300 Undervoltage (27)
A2301 Function 27 Enabled Disabled
A2302 Curve 27 Inverse
A2303
A2304 Pickup 27 50 V Range: 40-230 V (0.1 V steps) V
Pickup Source Voltage 59 (if VT mode is (L-N)
2210 Freeze Waveform 1 59 on Pickup on Trip None
2211 Freeze Waveform 2 59 on Pickup on Trip None
PU Source V 27 (if VT mode is (L-N)
Line-to-Line Line-to-Neutral
Line-to-Line Line-to-Neutral
Moderately Inverse
Range: 0-60 s (0.01 s steps),
or
Moderately Inverse
Very Inverse Definite Inverse
Very Inverse Definite Inverse
s
A2305 Time Delay 27 (Definite) 0.10 s
A2306 Time Dial 27 (Inverse) 0.1 Range: 0.1-9.9 (0.1 steps)
2310 Freeze Waveform 1 27 on Pickup on Trip None
2311 Freeze Waveform 2 27 on Pickup on Trip None
Range: 0-60 s (0.01 s steps),
or
s
S
Siemens Energy & Automation, Inc. S-5
ISGS Settings Worksheet for Date: Set A
A2400
A2401 Function 47 Enabled Disabled
A2451 Function 47N Enabled Disabled
A2452 Curve 47N Inverse Definite Inverse
A2453 Pickup 47N 10% Range: 4-40% (1% steps) %
A2454 Time Delay 47N(Defin.) 0.00 s
A2455 Time Dial 47N (Inverse) 0.10 Range: 0.1-9.9 (0.1 steps)
A2456 Maximum Time (Inverse) 120 s Range: 1-250 s (1 s steps) s
A2457 Block 47N by 40 V Range: 40-120 V (1 V steps) V
Phase Sequence Voltage (47) Negative Sequence Voltage (47N)
2410 Freeze Waveform 1 47 --- on Trip None
2411 Freeze Waveform 2 47 --- on Trip None
Range: 0-100 s (0.01 s steps),
or
2460 Freeze Waveform 1 47N on pickup on Trip None
s
S
2461 Freeze Waveform 2 47N on pickup on Trip None
S-6 Siemens Energy & Automation, Inc.
ISGS Settings Worksheet for Date: Set A
A2500
A2501 Function 81O Enabled Disabled
A2502 Pickup 81O 62.0 Hz
A2504 Time Delay 81O 0.10 s
A2551 Function 81U Enabled Disabled
A2553 Pickup 81U 58.0 Hz
A2554 Delay 81U 0.10 s
A2556 Block 81U 40 V Range: 40-120 V (1 V steps) V
Overfrequency (81O) Underfrequency (81U)
Range: 60.1-65.0 Hz (0.1 Hz steps)
Range: 0-100 s (0.01 s steps), or
2506 Block 81O 40 V Range: 40-120 V (1 V steps) V
2510 Frz. Wfm1 81O on Pickup on Trip None
2511 Frz. Wfm2 81O on Pickup on Trip None
Range: 55.0-59.9 Hz (0.1 Hz steps)
Range: 0-100 s (0.01 s steps),
or
2560 Freeze Waveform 1 81U on pickup on Trip None
Hz
Hz
s
s
2561 Freeze Waveform 2 81U on pickup on Trip None
2800 Breaker Failure (50BF)
2801 Function 50BF Enabled Disabled
2803 Pickup 50BF 5 A CT 0.25 A
1 A CT 0.1 A
2804 Delay 50BF 10 cycles Range: 8-254 cycles cycles
2805 Monitor 50BF current breaker both
Range: 0.25-5.0 A (0.01 A steps)
Range: 0.02-1.0 A (0.01 A steps)
A
A
S
Siemens Energy & Automation, Inc. S-7
ISGS Settings Worksheet for Date: Set A
3000 Alarm Setpoints
3100 Demand Setpoints
3101 Demand Interval 15 30 60 minutes
3102 Sync time 0 15 30 45 minutes after hour
3103 Subperiods 60 1 234612
3104 Subperiods 30 1 236
3105 Subperiods 15 1 3
3106 Current Average Demand Enabled Disabled
3107 Current Average Demand Pickup 3000 A Range: 0-9999 A (1 A steps) A
3108 KW Demand Enabled Disabled
3109 KW Demand Pickup 100000 kW
3200 Power Setpoints
3201 KVAR Function Enabled Disabled
3202 KVAR Pickup 100000 kVAR
3203 KVAR Time Delay 1800 s Range: 0-3600 s (1 s steps) s
3204 KVA Function Enabled Disabled
3205 KVA Pickup 100000 kVA
3206 KVA Time Delay 1800 s Range: 0-3600 s (1 s steps) s
3207 PF Lead Function Enabled Disabled
3208 PF Lead Pickup 0.8 Range: 0.2-1.0 (0.1 steps)
3209 PF Lead Sign Lag Lead
3210 PF Lead Delay 1800 s Range: 0-3600 s (1 s steps) s
Range: 0-999,999 kW (1 kW steps)
Range: 0-999,999 kVAR (1 kVAR steps)
Range: 0-999,999 kVA (1 kVA steps)
kW
kVAR
kVA
S
3211 PF Lag Function Enabled Disabled
3212 PF Lag Pickup 0.8 Range: 0.2-1.0 (0.1 steps)
3213 PF Lag Sign Lag Lead
3214 PF Lag Delay 1800 s Range: 0-3600 s (1 s steps) s
S-8 Siemens Energy & Automation, Inc.
ISGS Settings Worksheet for Date: Set A
3400 Value Supervision
3401 Voltage Balance Function Enabled Disabled
3402 Voltage Balance Pickup 100 V Range: 40-120 V (0.1 V steps) V
3404 Voltage Balance Factor 0.80
3411 Current Sum Function Enabled Disabled
3412 Current Sum Pickup 5 A CT 0.5 A Range: 0.5-5 A (0.1 A steps) A
1 A CT 0.1 A Range: 0.1-1 A (0.1 A steps) A
3414 Current Sum Factor 0.10
3411 Current Balance Function Enabled Disabled
3412 Current Balance Pickup 5 A CT 2.5 A Range: 0.5-5 A (0.1 A steps) A
1 A CT 0.1 A Range: 0.1-1 A (0.1 A steps) A
3414 Current Balance Factor 0.80
3500 Breaker Operation
3501 Interrupted Current Function Enabled Disabled
3502 Interrupted Current Pickup 1000.00 kA
Range: 0.58-0.95 (0.01 teps)
Range: 0.10-0.95 (0.01 steps)
Range: 0.10-0.95 (0.01 steps)
Range: 0-9999.9 kA (1 kA steps)
kA
3503 Breaker Operations Functions Enabled Disabled
3504 Breaker Operations Counter 100 Range: 0-65535
Siemens Energy & Automation, Inc. S-9
S
ISGS Settings Worksheet for Date: Set A
6000 Matrixing
6100 Binary Inputs
001
6101
Input 1
Frz.Buff1 Hi Frz.Buff1 Lo Frz.Buff2 Hi Frz.Buff2 Lo
blk 47N Hi blk 47N Lo blk 47 Hi blk 47 Lo
002
blk 81U Hi blk 81U Lo blk 81O Hi blk 81O Lo
003
blk 50 Hi blk 50 Lo blk 50N Hi blk 50N Lo
004
blk 50HS blk 50HS Lo blk 50HSN Hi blk 50HSN Lo
005
blk 51N Hi blk 51N Lo blk 59 Lo blk 59 Hi
blk 27 Hi blk 27 Lo blk 67 Hi blk 67 Lo
006
blk 67N Hi blk 67N Lo blk 50BF Hi blk 50BF Lo
007
blk ComEvt Hi blkComEvt Lo SwitchPara Hi SwitchPara Lo
008
BI1 Hi (001) BI1 Lo BI2 Hi BI2 Lo
S
6102
Input 2
009
BI3 Hi BI3 Lo BI4 Hi BI4 Lo
not matrixed
010
001
Frz.Buff1 Hi Frz.Buff1 Lo Frz.Buff2 Hi Frz.Buff2 Lo
blk 47N Hi blk 47N Lo blk 47 Hi blk 47 Lo
002
blk 81U Hi blk 81U Lo blk 81O Hi blk 81O Lo
003
blk 50 Hi blk 50 Lo blk 50N Hi blk 50N Lo
004
blk 50HS blk 50HS Lo blk 50HSN Hi blk 50HSN Lo
005
blk 51N Hi blk 51N Lo blk 59 Lo blk 59 Hi
blk 27 Hi blk 27 Lo blk 67 Hi blk 67 Lo
006
blk 67N Hi blk 67N Lo blk 50BF Hi blk 50BF Lo
007
blk ComEvt Hi blkComEvt Lo SwitchPara Hi SwitchPara Lo
008
BI1 Hi BI1 Lo BI2 Hi (001) BI2 Lo
009
BI3 Hi BI3 Lo BI4 Hi BI4 Lo
not matrixed
010
S-10 Siemens Energy & Automation, Inc.
ISGS Settings Worksheet for Date: Set A
6100 Binary Inputs (continued)
001
6103
Input 3
Frz.Buff1 Hi Frz.Buff1 Lo Frz.Buff2 Hi Frz.Buff2 Lo
blk 47N Hi blk 47N Lo blk 47 Hi blk 47 Lo
002
blk 81U Hi blk 81U Lo blk 81O Hi blk 81O Lo
003
blk 50 Hi blk 50 Lo blk 50N Hi blk 50N Lo
004
blk 50HS blk 50HS Lo blk 50HSN Hi blk 50HSN Lo
005
blk 51N Hi blk 51N Lo blk 59 Lo blk 59 Hi
blk 27 Hi blk 27 Lo blk 67 Hi blk 67 Lo
006
blk 67N Hi blk 67N Lo blk 50BF Hi blk 50BF Lo
007
blk ComEvt Hi blkComEvt Lo SwitchPara Hi SwitchPara Lo
008
BI1 Hi BI1 Lo BI2 Hi BI2 Lo
6104
Input 4
009
BI3 Hi (001) BI3 Lo BI4 Hi BI4 Lo
not matrixed
010
001
Frz.Buff1 Hi Frz.Buff1 Lo Frz.Buff2 Hi Frz.Buff2 Lo
blk 47N Hi blk 47N Lo blk 47 Hi blk 47 Lo
002
blk 81U Hi blk 81U Lo blk 81O Hi blk 81O Lo
003
blk 50 Hi blk 50 Lo blk 50N Hi blk 50N Lo
004
blk 50HS blk 50HS Lo blk 50HSN Hi blk 50HSN Lo
005
blk 51N Hi blk 51N Lo blk 59 Lo blk 59 Hi
blk 27 Hi blk 27 Lo blk 67 Hi blk 67 Lo
006
blk 67N Hi blk 67N Lo blk 50BF Hi blk 50BF Lo
007
blk ComEvt Hi blkComEvt Lo SwitchPara Hi SwitchPara Lo
008
BI1 Hi BI1 Lo BI2 Hi BI2 Lo
S
009
BI3 Hi BI3 Lo BI4 Hi (001) BI4 Lo
not matrixed
010
Siemens Energy & Automation, Inc. S-11
ISGS Settings Worksheet for Date: Set A
6200 Binary Outputs
001
6201
Output 1
BI1 BI2 BI3 BI4
002
Error Sum I Error Sym I Error Sym V OC Pickup
003
OC Trip Non OC PU Non OC Trip Relay Pickup
004
Relay Tripped no f f <> 50HS Trip
005
50HSN Trip 81O Pickup 81O Trip UV blks 81O
006
81U Pickup 81U Trip UV blks 81U 47N Pickup
007
47N Trip UV blks 47N 50HS blks 50 50HSN blks 50
008
50 Pickup 50 Trip 50HS blks 50N 50HSN blks 50N
009
50N Pickup 50N Trip 50HS blks 51 50HSN blks 51
010
011
51 Pickup 51 Trip 50HS blks 51N 50HSN bl. 51N
012
51N Pickup 51N Trip 67 Pickup 67 Trip
013
67N Pickup 67N Trip 27 Pickup 27 Trip
014
59 Pickup 59 Trip 47 Trip OvrBrOps PU
015
OvrbrAmpsPU
016
OvrkVA Pickup PFLag Pickup PFLead Pickup 50BF Pickup
017
50BF Trip TrScMon PU TrCoilCont PU BrMech PU
018
CommEvent 1 CommEvent 2 CommEvent 3 CommEvent 4
019
CommEvent 5 not matrixed
020
OvrAmpsDmd PU
OvrkWDmdPU OvrkVAR PU
S
S-12 Siemens Energy & Automation, Inc.
ISGS Settings Worksheet for Date: Set A
6200 Binary Outputs (continued)
001
6202
Output 2
BI1 BI2 BI3 BI4
002
Error Sum I Error Sym I Error Sym V OC Pickup
003
OC Trip Non OC PU Non OC Trip Relay Pickup
004
Relay Tripped no f f <> 50HS Trip
005
50HSN Trip 81O Pickup 81O Trip UV blks 81O
006
81U Pickup 81U Trip UV blks 81U 47N Pickup
007
47N Trip UV blks 47N 50HS blks 50 50HSN blks 50
008
50 Pickup 50 Trip 50HS blks 50N 50HSN blks 50N
009
50N Pickup 50N Trip 50HS blks 51 50HSN blks 51
010
011
51 Pickup 51 Trip 50HS blks 51N 50HSN bl. 51N
012
51N Pickup 51N Trip 67 Pickup 67 Trip
013
67N Pickup 67N Trip 27 Pickup 27 Trip
014
59 Pickup 59 Trip 47 Trip OvrBrOps PU
015
OvrbrAmpsPU
016
OvrkVA Pickup PFLag Pickup PFLead Pickup 50BF Pickup
017
50BF Trip TrScMon PU TrCoilCont PU BrMech PU
018
CommEvent 1 CommEvent 2 CommEvent 3 CommEvent 4
019
CommEvent 5 not matrixed
020
OvrAmpsDmd PU
OvrkWDmdPU OvrkVAR PU
Siemens Energy & Automation, Inc. S-13
S
ISGS Settings Worksheet for Date: Set A
6400 Trip Contacts
001
6401
Contact 1
BI1 BI2 BI3 BI4
002 003
OC Trip Non OC Trip Relay Tripped 50HS Trip
004 005
50HSN Trip 81O Trip 81U Trip 47N Trip
006
(005)
007
50 Trip
008 009
67 Trip 67N Trip 27 Trip 59 Trip
010 011
47Trip OvrBrOps PU OvrbrAmpsPU OvrAmpsDmd PU
012 013
OvrkWDmdPU OvrkVAR PU OvrkVA Pickup PFLag Pickup
014 015
PFLead Pickup 50BF Pickup TrScMon PU TrCoilCont PU
016 017
BrMech PU
018 019
CommEvent 4 CommEvent 5 not matrixed
020
(002)
50N Trip
(001) CommEvent 1
(003)
51 Trip
CommEvent 2 CommEvent 3
(004) 51N Trip
S
6402
Contact 2
001
BI1 BI2 BI3 BI4
002 003
OC Trip Non OC Trip Relay Tripped 50HS Trip
004 005
50HSN Trip 81O Trip 81U Trip 47N Trip
006 007
50 Trip 50N Trip 51 Trip 51N Trip
008 009
67 Trip 67N Trip 27 Trip 59 Trip
010 011
47Trip OvrBrOps PU OvrbrAmpsPU OvrAmpsDmd PU
012 013
OvrkWDmdPU OvrkVAR PU OvrkVA Pickup PFLag Pickup
014 015
PFLead Pickup 50BF Pickup TrScMon PU TrCoilCont PU
016 017
BrMech PU CommEvent 1
018 019
CommEvent 4 CommEvent 5 not matrixed
020
(001)
CommEvent 2
CommEvent 3
S-14 Siemens Energy & Automation, Inc.
Loading...