Siemens REV100 User Manual

CE1N2211en
16.05.2000
6LHPHQV%XLOGLQJ7HFKQRORJLHV
/DQGLV6WDHID'LYLVLRQ

5RRP7HPSHUDWXUH &RQWUROOHU
5(9
with touch screen
0DLQVLQGHSHQGHQWURRPWHPSHUDWXUHFRQWUROOHU
6HOIH[SODQDWRU\WRXFKVFUHHQ
6HOIOHDUQLQJWZRSRVLWLRQFRQWUROOHUZLWK3,'FRQWUROSDWHQWHG
&KRLFHRIWZRGLIIHUHQWKRXURSHUDWLQJPRGHV
8VH
For the control of the room temperature in
apartments, single-family or holiday houses
offices, individual rooms and consulting rooms or commercially used spaces
For the control of the following pieces of equipment:
Solenoid valves of instantaneous water heaters
Solenoid valves of atmospheric gas burners
Heating circulating pumps, zone valves (normally closed)
Electric direct heating systems or fans of electric storage heaters
)XQFWLRQV
PID control with self-learning or selectable switching cycle
Two different 24-hour operating modes
Remote control and override button
Sensor balancing and reset function
Locking of display to facilitate cleaning or to prevent tampering
Frost protection function and minimum limitation of the setpoint
2/8 Siemens Building Technologies Room temperature controller REV100 CE1N2211en
Landis & Staefa Division 16.05.2000
7\SHVXPPDU\
Room temperature controller with 24-hour time switch 5(9 When ordering, please give type reference according to "Type summary".
The unit is supplied complete with batteries.
0HFKDQLFDOGHVLJQ
Plastic casing with a large display which also serves as a touch screen. A hinged bat­tery compartment cover facilitates the straightforward exchange of the two 1.5 V alka­line batteries type AA. The base can be removed and fitted to all commercially available recessed conduit boxes or directly on the wall, to be wired before the control- ler is fitted. The casing accommodates the electronics with a ',3switch and a relay with a potential-free N.O. contact. The connection terminals are integrated in the base.
2211D11
5 1
2
6
3
4
7
Temperature values and symbols Normal temperature
Economy temperature Standby with frost protection Time of day or switching time
Change batteries Bumer in operation Remote control active Locking of display active Holiday program active Increasing ,decreasing values
24-hour operation with one heating period 24-hour operation with two heating periods Continuously normal temperature Continuously economy temperature Standby with frost protection For the switching times 1 to 4 For switching manually from normal to economy temperature, or vice
versa Opening for locking the display or for the reset
2UGHULQJDQG GHOLYHU\
'LVSOD\DQGRSHUDWLQJ HOHPHQWV
1 Display buttons
2 Symbols
3 Arrow buttons 4 Operating mode buttons
5 Switching time buttons 6 Level button
7 Locking ,reset
3/8
Siemens Building Technologies Room temperature controller REV100 CE1N2211en Landis & Staefa Division 16.05.2000
Not highlighted and no symbol: function cannot be selected.
Highlighted ,symbol visible: function can be selected but is not yet acti-
vated.
Highlighted ,symbol /angle bar visible at top left: function is activated.
When an adjustable display button is pressed, the displayed value will automatically be stored 5 seconds later and the previous operating mode will be resumed or reactivated.
Pressing one ofthese buttons forless than one second produces a step ofone minute (time settings) or of0.2 °C(temperature settings). Pressing formore that one second means quick adjustment which can be cancelled again by pressing the button repeatedly.
Standard value Setting range Setting range with setpoint limitation
20 °C 3…29 °C 16…29 °C 16 °C 3…29 °C 16…29 °C
5 °C 3...16 °C 3...16 °C
The setpoints of and are identical in both 24-hour operating modes.
Press the temperature button and then the required operating mode button.
. Press to adjust the setpoint temperature of each operating
mode.
Press the temperature button and then to readjust the displayed tem­perature in increments of 0.2 °C (max. ±4 °C) to the room temperature temporarily re­quired. The warmer ,colder function can be applied to all three temperature setpoints, but the values thus changed will be reset again when the next switching point is reached.
Press the time button and then to set the correct time of day.
The two switching points forthe 24-hour operation with one heating period and the four switching points forthe 24-hour operation with two heating periods can be entered individually and independently.
Operating mode
Switching point
1
Switching point2
Switching point3
Switching point4
06:00 09:00 17:00 22:00 07:00 23:00
Press or and select the individual switching points by pressing the respe ctiv e
switching time button . Then, change the displayed switching time by pressing
.
If two switching times coincide on the same switching time button, the display alter-
nates between the two switching points when pressing the button repeatedly
Manual changeover from the normal to the economy temperature, or vice versa. The selection will automatically be reset when the next switching point is reached or when changing the operating mode.
Manual changeover to the normal temperature is active
Manual changeover to the economy temperature is active
When absent fora longer period oftime, it is possible to switch manually to the econ­omy temperature and to enter the period ofabsence.
'LVSOD\EXWWRQ IXQFWLRQ
Automatic storage
Adjusting the values
6HWSRLQWV
$GMXVWLQJWKH VHWSRLQWV
:DUPHU/ FROGHU
6HWWLQJWKHWLPHRIGD\
6ZLWFKLQJSRLQWV
Standard values
Changing the switching points
2YHUULGHEXWWRQ
+ROLGD\SURJUDP
Loading...
+ 5 hidden pages