Siemens ILP-1, ILPT-1 Installation Instructions Manual

Installation Instructions
Models ILP-1/ILPT-1
Fire Safety
These instructions are written in accordance with the installation guidelines of NFPA 72, National Fire Alarm Code, and CAN/ULC-S524, The Installation of Fire Alarm Systems.
CAUTION: Detector Device Storage
DO NOT install this detection device until all construction is completed.
DO NOT store this detection device where it can be contaminated by dirt, dust, or humidity.
DETECTOR PLACEMENT
Although no specific spacings are set for the detectors used for a clean air application, use 30 foot center spacing (900 sq ft) from NFPA Standard 72 Chapter 5 and CAN/ULC-S524, if practical, as a guide or starting point for a detector installation layout. This spacing, however, is based on ideal conditions - smooth ceiling, no air movement, and no physical obstructions. In some applications, therefore, considerably less area is protected adequately by each smoke detector. This is why it is mandatory to closely follow the installation drawings. In all installations place the detector on the ceiling, a minimum of 6 inches from a side wall, or on a wall, 6 inches from the ceiling.
If you have any questions regarding detector placement, follow the drawings provided or approved by Siemens Building Technologies, Inc. or by its
authorized distributors. This is extremely important! The detector placements shown on these drawings were chosen after a careful evaluation of the area that is protected. Factors such as air currents, temperature, humidity, pressure, and the nature of the load were carefully considered. Especially noted were the room or area configuration and the type of ceiling (sloped or flat, smooth or beamed). Siemens Building Technologies, Inc.'s extensive experience in the design of the system assures the best detector placement by following these drawings. Sound engineering judgement by qualified personnel must be followed.
To avoid nuisance alarms:
Do not locate the detector next to an oil burner, electric heaters, kitchens, or garages where exhaust fumes can trigger an alarm. Other causes of false alarms are dust accumulation, heavy concentrations of steam, heavy pipe or cigar smoking, high relative humidity
or other humid areas where condensation may occur, and concentrated aerosol sprays.
AIR CURRENTS
Before a detector can sense a fire, the products of combustion or smoke must travel from the fire to the detector. This travel is especially influenced by air currents; therefore, consider air movement when designing the system. While combustion products tend to rise, drafts from hallways, air diffusers, fans, etc., may help or hinder the travel of combustion products
Siemens Building Technologies, Inc. 8 Fernwood Road Florham Park, New Jersey 07932
P/N 315-092594-8
Figure 1
Installation and Wiring Diagram
Siemens Building Technologies, Ltd. 2 Kenview Boulevard Brampton, Ontario L6T 5E4 CN
to the detector. When positioning a detector at a particular location, give consideration to windows and doors, both open and closed, to ventilating systems, both in and out of operation, and to other factors influencing air movement. Do not install a detector in the air stream of a room air supply diffuser. It is better to position a detector closer to an air return.
The distance that products of combustion or smoke travel from a fire to the detector is not usually the shortest linear route. Combustion products or smoke usually rise to the ceiling, then spread out. Average ceiling heights of 8 to 10 feet do not abnormally affect detector response. High ceilings, located in churches, warehouses, auditoriums, etc., do affect detector response and should be considered.
SPECIAL CEILING CONSTRUCTION FACTORS
Ceiling obstructions can change the natural movement of air and combustion products. Depending on the direction of smoke travel, joists and beams can slow the movement of heated air and smoke, while pockets between them can contain a reduced level of smoke.Take obstructions created by girders, joists, beams, air conditioning ducts, or architectural design into consideration when determining area protection. Refer to the Initiating Devices chapter of NFPA Standard 72 for Location and Spacing requirements for specific types of construction; e.g. beam, suspended, level, sloped and peaked ceilings.
The ILP-1 detector is UL listed for use only with Air Duct Cover P/N 305-093076. When installing the ILP-1 in older existing installations, order a new ILP-1 Air Duct Cover Kit DA-303, P/N 500-093078 and use it in that installation. This kit includes the required cover.
DETECTOR MOUNTING
To ensure proper installation of the detector head into the base, be sure the wires are property dressed at installations:
1. Position all wires flat against the base.
2. Take up all slack in the outlet box
3. Route wires away from connector terminals.
4. When mounting the detector base and routing wires through the cutouts in the air shield, make sure the shield is sealed against air leaks. Open the cutouts only as much as required.
INSTALLATION OF DETECTOR HEAD
1. Align notch in detector cover to raised surface on outer ring of base; refer to Figure 2.
TEMPERATURE  HUMIDITY  PRESSURE  AIR VELOCITY
The temperature range for the ILP-1/ILPT-1 detector is from 32°F (0°C) to 100°F (38°C). Use the detector in environments where the humidity does not exceed 93% (non-condensating). Normal changes of atmospheric pressure do not affect detector sensitivity. The air velocity range is 0-4000 ft/min for open areas applications.
ILP-1 Air Duct Applications
In Air Duct applications, the Model ILP-1 requires Air Duct Cover P/N 305-093076. Do not use the Model ILP-1 with any other air duct covers. The air duct cover part numbers are located on the air duct cover flange near the sensitivity test jack trap door.
Figure 2
Mounting The Base
2. Push detector head into base and rotate clockwise to make electrical connections. The detector automatically stops and locks into place.
3. To remove, push detector head up into the base while rotating the detector head counterclockwise. Continue to rotate counterclockwise until stop is reached; then pull downward to disengage from base.
2
Loading...
+ 2 hidden pages