Siemens GLB132.1P, GLB131.1P, GLB136.1P, GDE131.1P/B, GLB161.1P Installation Instructions Manual

...
Installation Instructions
Document No. 129-367
September 1, 2003
OpenAir™ Electronic Damper Actuator GDE/GLB Rotary Non-spring Return
9
0
5
4
90
EA0678R3
a
b
Figure 1. Parts of the GDE/GLB Rotary Actuator.
Product Description
Steps for direct-coupled mounting of the OpenAir GDE/GLB Series non-spring return rotary electronic damper actuator.
Product Numbers
GDE131.1U GLB131.1P GDE131.1U/B (24 pk) GLB132.1P GDE131.1P GLB136.1P GDE131.1P/B (24 pk) GLB161.1P GDE131.1Q/B 6-ft cable (12 pk) GLB163.1P GDE132.1P GLB164.1P GDE136.1P GLB166.1P GDE161.1P GDE161.1P/B (24 pk) GDE163.1P GDE164.1P GDE166.1P
Required Tools
4 mm hex wrench
4 mm (5/32-inch) drill bit and drill
Small flat-blade screwdriver
Marker or pencil
Estimated Installation Time
30 minutes
Warning/Caution Notations
WARNING :
CAUTION:
Personal injury/loss of life may occur if you do not follow a procedure as specified.
Equipment damage or loss of data may occur if you do not follow a procedure as specified.
d
Instructions
NOTE: Place the actuator on the damper shaft so
1. Determine whether the damper blades will rotate clockwise or counterclockwise to open. See Figure 2.
2. If the blades will rotate counterclockwise, slide the manual override switch to manual, and move the adjustment lever to the right. Return the switch to automatic. See Figure 9.
To mount a (modulating) GDE/GLB16x, set the Dual In-line Package (DIP) switches to the required positions.
1. To access the DIP switches, raise the tab on the lower left side of the actuator. See Figure 2. The factory setting is clockwise (middle switch), with a direct-acting feedback signal (right switch).
2. Close the tab over the DIPswitches.
To mount a (3-positon) GDE/GLB13x for counter­clockwise rotation, follow the Counterclockwise
Damper Rotation instructions located in the Wiring Diagrams section when wiring the actuator to the
controller.
a. Actuator b. Position indicator
c
c. Mounting bracket d. Mounting screws e. 4 mm hex key f. Shaft insert for use with
f
3/8-inch (8-10 mm) shafts
WARNING:
Do not open the actuator.
that the front of the actuator is accessible. The label is on the front side.
Item Number: 129-367, Rev. 010 Page 1 of 6
Document No. 129-367 Installation Instructions September 1, 2003
1
CLOCKWISE
TO OPEN
only for: GDE16...1P
GLB16...1P
EA0680R2
MODULATING
self adapt
0
"0"
90
5
4
2
90
self adapt
0
3
COUNTER
CLOCKWISE
TO OPEN
only for: GDE16...1P
GLB16...1P MODULATING
self adapt
0
2’
3’
90
45
9
0
self adapt
0
Figure 2. Setting the Direction of Rotation.
NOTE: For DIP switch setting options, see the
Technical Instructions EA GDE/GLB-1 (155-187P25).
Mounting and Installation
NOTE: The GDE/GLB actuator comes with a factory
installed 1/2-inch shaft guide. If shaft size is 1/2-inch, proceed with Figure 6.
1. A 3/8-inch shaft adapter is provided in actuator package.
2. Hold the shaft insert so that the raised tabs are inserted last when placing the insert into the back of the actuator.
3. Proceed to Figure 6.
When using a 5/8-inch shaft:
90
45
90
EA01001R2
Figure 5. 5/8 Ø inch shaft.
1. Remove factory installed 1/2-inch guide. See Figure 3.
2. Mount actuator to shaft per Figure 6.
When using a 3/8-inch shaft: Remove factory installed 1/2-inch guide. See Figure 3.
EA0999R1
Figure 3. Removing 1/2-inch Ø shaft
guide for 3/8-in or 5/8-in shaft.
90
45
90
EA0679R3
Figure 4. 3/8 Ø inch shaft, see Figure 1 Item f.
f
Mounting GDE/GLB on
~
3/8-inch
~
8...10 mm shafts
2
90
45
90
EA0532R2
3
Figure 6. Mounting Actuator to Damper Shaft.
4 mm
60-90 lb-in
(7-10 Nm)
Torque
b
EA0533R3
5
90
45
90
4
1
Page 2 of 6 Siemens Building Technologies, Inc.
Figure 7. Installing the Position Indicator (b).
Loading...