Siemens Free Energy Band TH 193 HC, Powers Controls Free Energy Band TH 193 HC Technical Instructions

Page 1
Powers® Controls
Free Energy Band® TH 193 HC Heating/Cooling Room Thermostat
Technical Instructions
Document No. 155-068P25
TH 193-4
6050 70 80
70
60
TH0356R1
POWERS
80
Description
Features
The TH 193 HC thermostats are proportional dual output, dual setpoint, two-pipe (dual one-pipe, low air capacity) or three-pipe (dual two-pipe, high air capacity) sensor controllers. Each thermostat includes a wall mounting plate for installation in a variety of rough-in terminal boxes. Sensitive bimetals respond to temperature changes to modulate control air through a flapper nozzle. As the heating load decrea ses due to internal heat gains, a dead band of control minimizes energy consumption while the setpoint changes from 72°F (22°C) heating mode to 78°F (26°C) cooling mod e. Two setpoint dials allow adjustment of the dead band 4°F (2°C) minimum. Air connections are made with 5/32-inch (4 mm) O.D. plastic tubing, directly to the thermostat chassis for retrofit applications or with plug-in adapters (provided with the TH 192 rough-in terminal box or optional accessories), which slide into the wall mounting plate.
Direct and reverse acting for heating and cooling modes.
Two separate adjustable temperature setpoint indicating dials.
Two highly sensitive bimetal thermostatic elements.
Fahrenheit or Celsius models.
Individual field adjustable sensitivity with graduated scale.
Integral field adjustable limit stops.
Control pressure test port accessible without removing cover.
Easily replaceable thermometer, setpoint dials, filters and restrictor plate.
Covers available for concealed or exposed thermometers, and for concealed
adjustment and setpoint indication.
Standard plastic thermostat covers provide Desert Beige or white finish.
Siemens Industry, Inc.
Page 2
Technical Instructions Free Energy Band TH 193 HC Heating/Cooling Room Thermostat Document Number 155-068P25 October 26, 2010
Optional Design Features
Fixed temperature limit stops meet government specifications.
Metal covers available in standard configurations with Desert Beige or white finish.
Competitor adapter mounting kits available
Application
TH 193 HC thermostats control space temperature and take advantage of the dead band to "float" room temperature between heating and cooling modes while maintaining energy management (maximum economy) and occupancy comfort. TH 193 HC thermostats control valve and damper actuators in building applications that require early morning heat and afternoon cooling.
Use TH 193 HC two-pipe (dual one-pipe) thermostats with external restrictors (20 scim,
5.4 ml/sec) where a limited air capacity operates a single valve and/or actuator. Use TH 193 HC three-pipe (dual two-pipe) thermostats where multiple valves an d actuators, used with or without high/low limiting controls, require higher air capacities. The thermostats are available with covers that conceal or expose the setpoint adjustment dials.
Piping
Figure 2. TH 193 HC Thermostat
Dual One-Pipe Connections.
Page 2 Siemens Industry, Inc.
Figure 1. Typical TH 193 HC Thermostat Application.
Figure 3. TH 193 HC Thermostat
Dual Two-Pipe Connections.
Page 3
Free Energy Band TH 193 HC Heating/Cooling Room Thermostat Technical Instructions Document Number 155-068P25 October 26, 2010
Product Numbers and Ordering Information
Chassis
See Table 1 for product number and ordering information on TH 193 HC thermo stat chassis.
1. Does application require one-pipe or two-pipe connection? a. One-pipe thermostats are low air capacity devices and have only one port
connection (R1). This application requires an external restrictor.
b. Two-pipe thermostats are high air capacity devices for controlling two or more
terminal devices such as damper actuators or valves. This application req uires two port connections: supply (S) and return (R1).
2. Is a Fahrenheit or Celsius scale required?
3. Is the heating control direct or reverse acting?
4. Is the cooling control direct or reverse acting?
Table 1. TH 193 HC Thermostat Chassis Part Numbers.
Chassis with Wall Plate
Fahrenheit Celsius Connection
Type
Setpoint
Adjustment
Heating DA Heating RA Heating DA Heating RA
One-Pipe
Relay
Two-Pipe
Relay
Exposed
at bottom
of cover
Cooling DA
193-211
Cooling RA
193-212
Cooling DA
193-215
Cooling RA
193-216
Cooling DA
193-213
Cooling RA
193-214
Cooling DA
193-217
Cooling RA
193-218
Cooling DA
193-231
Cooling RA
193-232
Cooling DA
193-235
Cooling RA
193-236
Cooling DA
193-233
Cooling RA
193-234
Cooling DA
193-237
Cooling RA
193-238
Siemens Industry, Inc. Page 3
Page 4
Technical Instructions Free Energy Band TH 193 HC Heating/Cooling Room Thermostat Document Number 155-068P25 October 26, 2010
Covers
See Table 2 for product number and ordering information on TH 193 HC thermostat covers.
1. Is the setpoint adjustment exposed for customer adjustment or concealed to prevent alteration of setting?
2. Is the thermometer exposed or concealed?
3. Is the setpoint indication exposed or concealed behind cover?
4. Is a plastic or zinc cast metal cover required? a. Plastic covers order 192-2XX. b. Metal covers order 192-3XX.
5. Is finish of cover standard or optional? The standard finish color for plastic and metal covers is Desert Beige.
2. For white plastic cover option, add “W” suffix code to cover part number
(for example: 192-256W). See Table 2.
3. For white metal cover option, add "H" suffix code to cover part
(for example: 192-356H). See Table 2.
Table 2. TH 193 HC Thermostat Cover Part Numbers.
Setpoint
Adjustment
1
Key
Cover Configuration
Thermometer
Concealed 192-256 192-356 Concealed
Setpoint
Indicator
Concealed
Exposed
Concealed 192-267 192-367
Exposed
Cover Part Number
Standard
Plastic Cover
Desert Beige
Metal Cover
Desert Beige
192-254 192-354
Exposed 192-268 192-368
Concealed 192-258 192-358 Exposed
Exposed
192-260 192-360
1. Key setpoint adjustment cover is required for all thermostat chassis with optional 1/2-inch setpoint adjustment knobs (for replacement only).
2. To order a plastic cover with white finish, add the "W" suffix code. To order a metal cover with a white finish, add the "H" suffix code.
2
Optional
Page 4 Siemens Industry, Inc.
Page 5
Free Energy Band TH 193 HC Heating/Cooling Room Thermostat Technical Instructions Document Number 155-068P25 October 26, 2010
Specifications
Control action See Table 1 Operating ranges 45°F to 85°F (7°C to 30°C) Supply air pressure, maximum 30 psi (207 kPa) Normal air supply pressure 18 to 25 psi (124 to 172 kPa) Sensitivity adjustment 1 to 4 psi/°F (12 to 50 kPa/°C) Nominal air consumption One-pipe 25 scim (6.8 ml/sec) per side
Two-pipe 230 scim (63 ml/sec) per side Temperature response 0.1°F (0.06°C) Temperature Storage temperature -10°C to 140°F (-23°C to 60°C)
Ambient operating temperature 40°F to 140°F (4°C to 60°C) Dial graduations 2°F (1°C) Factory settings Calibration @ 72°F (22°C) 7.5 psi (52 kPa)
Sensitivity 2.5 psi/°F (31 kPa/°C) Limit stop adjustment 45°F and 85°F (7°C and 30°C)
Standard cover Cycolac, Desert Beige Shipping weight 0.7 lbs. (0.3 kg) Dimensions See Figure 10
Accessories
Operation
See the following Technical Bulletins for information on accessories:
Technical Bulletin
TB 237 Terminal Kits
TB 214 Adapter Kits
TB 193 Guard Kit
TB 241 Test Head Kit
TB 167 Restrictors
The TH 193 HC thermostat is a two-temperature thermostat with two separate outputs. In direct acting control, an increase in temperature increases the control air pressure and a decrease in temperature decreases the control pressure. In reverse acting control, an increase in temperature decreases the control air pressure and a decrease in temperature increases the control pressure.
The TH 193 HC provides two separate bimetal elements; one for heating mode and the other for cooling mode. The setpoint of the two elements determines the window of the dead band. A 4°F (2°C) minimum dead band is standard, where the heating mode setpoint is 72°F (22°C) and the cooling mode setpoint is 78°F (26°C). Figure 4 shows a typical application with setpoints adjusted for a 6°F (4°C) dead band.
Figure 5 shows direct acting TH 193 HC output characteristics. As heating increases, the output pressure increases from 0 to 15 psi (0 to 103 kPa). A field adjustable dead band occurs. When the dead band elapses, cooling occurs from 0 to 15 psi (0 to 103 kPa).
Document Number
155-244P25 155-231P25 155-222P25 155-255P25
155-213
Siemens Industry, Inc. Page 5
Page 6
Technical Instructions Free Energy Band TH 193 HC Heating/Cooling Room Thermostat Document Number 155-068P25 October 26, 2010
Operation, Continued
TH 193 HC Thermostat Details
Figure 4. TH 193 HC Operating
Characteristics.
Figure 5. TH 193 HC Input/Output
Characteristics.
Figure 6. TH 193 HC Thermostat Details.
Thermometer Calibration
Page 6 Siemens Industry, Inc.
1. Use a test thermometer to read the current room temperature.
2. Place a screwdriver in the center of the thermometer assembly (Figure 6). Carefully rotate thermometer assembly until pointer tip indicates the correct room temperature.
NOTE: Avoid breathing on or touching the bimetal spiral since this influences the
temperature reading.
Page 7
Free Energy Band TH 193 HC Heating/Cooling Room Thermostat Technical Instructions Document Number 155-068P25 October 26, 2010
Limit Stop Adjustment
Sensitivity Adjustment
Thermostat limit stops define the minimum and maximum thermostat setpoints. The limit stops engage in the setpoint cam gear teeth and cause interference between the setpoint cam gear and the adjustment knob gear.
To change limit stop settings, use needle nose pliers to pull limit stop between the setpoint cam gear teeth. Rotate limit stop to its new position. Do not pull limit stop any more than necessary to clear the gear teeth. Changing the limit stop position one gear tooth changes the limit stop setting by 1-1/3°F (0.7°C).
To change thermostat sensitivity, use a flat-blade screwdriver to carefully move the sensitivity slide to the desired position as follows:
Graduation
closest to the
rigid end of the bimetal
element
4 psi/°F
(50 kPa/°C)
NOTE: If the thermostat sensitivity is adjusted,
the thermostat must be recalibrated.
Graduation
closest to the
minimum
(MIN) end of
the bimetal
element
1 psi/°F
(12 kPa/°C)
Figure 7. TH 193 HC
Limit Stop Adjustments.
Figure 8. TH 193 HC
Sensitivity Adjustment.
Thermostat Calibration
Siemens Industry, Inc. Page 7
The thermostat is factory-calibrated to a control pressure of 7.5 psi (52 kPa) when the setpoint and the ambient temperature are both at 72°F (22°C). The factory sensitivity setting is approximately 2.5 psi/°F (31 kPa/°C). No adjustments are required if these settings are appropriate for the application. If the thermostat has been tampered with, the sensitivity changed, or is out of adjustment, use the following steps to recalibrate the instrument.
Page 8
Technical Instructions Free Energy Band TH 193 HC Heating/Cooling Room Thermostat Document Number 155-068P25 October 26, 2010
Cooling Calibration
Step 1
Remove cover using P/N 192-632 calibration tool. Verify room temperature is between 70°F and 80°F (2°C and 27°C).
Step 2 — Verify that supply pressure is 18 to 25 psi (124 to 172 kPa). Set cooling dial to room temperature by turning the exposed adjustment knob or using a hex key as shown. Allow thermostat to stand for about five minutes to adjust to the new setting.
Step 3 — Moisten needle and insert P/N 192-633 test gauge and needle adapter in the test port. Read control pressure.
Step 4 — If control pressure does not read 7 to 8 psi (48 to 55 kPa), turn calibration screw using P/N 192-632 calibration tool or 1/8-inch (3.2 mm) wrench until pressure is 7 to 8 psi (48 to 55 kPa). The sensing element is now in calibration and the setpoint can be changed to the desired room temperature.
Page 8 Siemens Industry, Inc.
Page 9
Free Energy Band TH 193 HC Heating/Cooling Room Thermostat Technical Instructions Document Number 155-068P25 October 26, 2010
Heating Calibration
Step 1
If not already done, remove cover using P/N 192-632 calibration tool. Verify room temperature is between 70°F and 80°F (21°C and 27°C).
Step 2 — Verify that supply pressure is 25 psi (172 kPa). Set heating dial to room temperature by turning the exposed adjustment knob or using a hex key as shown. Allow thermostat to stand for about five minutes to adjust to the new setting.
Step 3 — Moisten needle and insert P/N 192-633 test gauge and needle adapter in the test port. Read control pressure.
Step 4 — If control pressure does not read 7 to 8 psi (48 to 55 kPa), turn calibration screw using P/N 192-632 calibration tool or 1/8-inch (3.2 mm) wrench until pressure is 7 to 8 psi (48 to 55 kPa). The sensing element is now in calibration and the setpoint can be changed to the desired room temperature.
Siemens Industry, Inc. Page 9
Page 10
Technical Instructions Free Energy Band TH 193 HC Heating/Cooling Room Thermostat Document Number 155-068P25 October 26, 2010
Troubleshooting
Before troubleshooting thermostat (see Table 4), make certain there is clean, dry supply air at 18 psi (124 kPa) minimum. Use test probe gauge and needle adapter to measure control pressure at thermostat test port.
The output pressure test port is accessible without removing the thermostat cover through the 8th opening from the top. For one-pipe thermostats, the port is on the right side. For two-pipe thermostats, the port is on the left side.
Figure 9. Accessing Output Pressure Test Port.
CAUTION:
If you use the wrong test port, thermostat damage can occur and result in replacement of the device.
Table 3. Troubleshooting Guide.
Problem Check Cause Action
Control pressure stays at approximately zero
Air supply Low supply pressure As required Nozzle or flapper
Dirt on nozzle or
flapper Restrictor Clogged restrictor Replace restrictor Calibration Out of calibration Recalibrate
Control pressure
Nozzle Clogged nozzle
stays at approximately supply pressure
Excessive air leakage from exhaust port on left side of thermostat
Calibration
Supply and return line connection
Dirt on either supply or
exhaust valve seat
Connections are
interchanged or
connection to port is
incorrect
Clean nozzle or replace thermostat
Clean nozzle or replace thermostat
Alternately close and open nozzle by gently pushing down the bimetal
As required
Page 10 Siemens Industry, Inc.
Page 11
Free Energy Band TH 193 HC Heating/Cooling Room Thermostat Technical Instructions Document Number 155-068P25 October 26, 2010
Chassis Tube Connector and Restrictor Plate
1. Remove thermostat chassis from wall. Terminal does not have a ball check valve. NOTE: You must close off the supply air. For example, use a connector with the
supply air terminal plugged.
Replacement
2. Remove two Phillips head screws from connector on back of thermostat chassis. Pull connector out of recess. If necessary, pry connector loose with a screwdriver, but be careful not to damage restrictor plate and gasket.
3. Remove gasket from under connector. Remove restrictor. Remove second gasket from under restrictor.
4. Use restrictor replacement kit P/N 192-321 to replace gasket, restrictor, and second gasket.
NOTE: The restrictor plate is keyed to ensure proper orientation during installation.
5. Remove filters from existing connector and insert in new connector. Or, if filters are dirty, use restrictor replacement kit P/N 192-321 to replace filters.
6. Use chassis tube connector replacement kit P/N 192-525 to replace connector and mounting screws.
Siemens Industry, Inc. Page 11
Page 12
Technical Instructions Free Energy Band TH 193 HC Heating/Cooling Room Thermostat Document Number 155-068P25 October 26, 2010
Service Parts
The following chart lists accessory parts and tools available for thermostat service.
Description Part Number
Dial thermometer (-40°F to 140°F, -40°C to 60°C) with pocket
141-0573
case Basic pneumatic calibration kit with thermometer, gauge, squeeze
832-177
bulb, fittings, and case Test head kit 832-179 Calibration tools 832-178 Test probe to check pressure with cover on
Needle probe with 1-1/2" diameter gauge 0-30 psig
192-633
(0-200 kPa) and calibration/cover wrench Needle probe, no gauge (package of five) 192-759 1-1/2" diameter gauge, 0-200 kPa,
142-0344
back connected 1/8" NPT male 1-1/2" diameter compound gauge, 0-30 psig/0-200 kPa,
142-0373
back connected 1/8" NPT male 1-1/2" diameter compound gauge, 0-30 psig/0-200 kPa,
142-0426 bottom connected 1/8" NPT male. Replacement for use with 192-633
Chassis tube connector replacement kit with mounting screws
192-525
(material for 10 thermostats included) Restrictor plate replacement kit with filters and gasket
192-321
(material for 10 thermostats included) Plug-in adapters for quick thermostat removal
Straight, blue (package of 20) 192-485 Straight, white (package of 20) 192-486 Air link connects adapters for pressure tests (package of 20) 192-501 Compression ring (package of 100) 141-388 Elbow (provides quick return for wall surface mounting), blue
192-487
(package of 20) Elbow (provides quick return for wall surface mounting), white
192-488
(package of 20)
20 scim (5.4 ml/sec) restrictors for one-pipe systems (package of 5). (1/4", 6.4 mm, O.D. plastic barb unless noted.)
Brass coupling, 1/8" NPT (one only). 184-040 Coupling 184-116 Tee 184-113 Pre-piped dual tee for dual one-pipe systems 184-130
Page 12 Siemens Industry, Inc.
Page 13
Technical Instructions Free Energy Band TH 193 HC Heating/Cooling Room Thermostat Document No. 155-068P25 October 26, 2010
Description Part Number
Replacement thermometer kits, brown (packages of 5)
Scale Range Thermostat Model
45°F to 85°F
192-775
10°C to 30°C
TH0443R1
192-776
Model 3 and Up
45°F to 85°F
192-786
10°C to 30°C
TH0442R1
192-785
Models 1 and 2
Replacement setpoint dials (packages of 10)
°F, Direct Acting 192-779
Right Side
°F, Reverse Acting 192-780
°C, Direct Acting 192-783
°C, Reverse Acting
°F, Direct Acting 192-777
Left Side
192-784
°F, Reverse Acting 192-778
°C, Direct Acting 192-781
°C, Reverse Acting
192-782
Dimensions
Figure 10. TH 193 HC Dimensions in Inches (Millimeters).
Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. Powers and Free Energy Band are registered trademarks of Siemens Industry, Inc. Other product or company names mentioned herein may be the trademarks of their respective owners. © 2010 Siemens Industry, Inc.
Siemens Industry, Inc.
Building Technologies Division 1000 Deerfield Parkway Buffalo Grove, IL 60089 USA
Your feedback is important to us. If you have
comments about this document, please send them to
SBT_technical.editor.us.sbt@siemens.com
Document No. 155-068P25
Printed in the USA
Page 13
Loading...