Siemens FPT-11, FP-11 Installation Instructions Manual

These instructions are written in accordance with the installation guidelines of NFPA 72, National Fire Alarm Code, and CAN/ULC-S524, The Installation of Fire Alarm Systems.
CAUTION: Detector Device Storage
DO NOT install this detection device until all construction is completed.
NOTE:
When using this detector with a protective detector guard such as the DGH-11 from Siemens Industry, Inc., or the STI 8100IS, be sure to install per the instructions supplied with the guard and set the ASD setting to duct detector per the detector programming instructions located on pages 2-3 of this document.
DETECTOR PLACEMENT FOR FP-11
Although no specific spacings are set for the detectors used for a clean air application, use 30 foot center spacing (900 sq ft) from NFPA Standard 72 Chapter 5 and CAN/ULC-S524, if practical, as a guide or starting point for a detector installation layout. This spacing, however, is based on ideal conditions–smooth ceiling, no air movement, and no physical obstructions. In some applications, therefore, considerably less area is protected adequately by each smoke detector. This is why it is mandatory to closely follow the installation drawings. In all installations place the detector on the ceiling, a minimum of 6 inches from a side wall, or on a wall, 4 to 6 inches from the ceiling.
If you have any questions regarding detector placement, follow the drawings provided or approved by Siemens Industry, Inc., or by its authorized distributors. This is
extremely important! The detector placements shown on these drawings were chosen after a careful evaluation of the area that is protected. Such factors as air currents, temperature, humidity, pressure, and the nature of the load were carefully considered. Especially noted were the room or area configuration and the type of ceiling (sloped or flat, smooth or beamed). Siemens Industry, Inc.'s extensive experience in the design of the system assures the best detector placement by following these drawings. Sound engineering judgement by qualified personnel must be followed.
Fire Print detectors and nuisance alarms:
The neural network within each Model FP-11 FirePrint detector is optimized to reject the most common nuisance alarms for its selected FirePrint Application; e.g. Parking Garage or Health Care. If the detector is exposed to an excess level of smoke or aerosol for an extended period of time, the detector is programmed to make the "safe decision" and signal an alarm condition. Because the amplitude and duration of deceptive phenomena are unbounded, the rule of thumb is to keep detectors as far as practical from sources that can produce an unusually large quantity of smoke for about a minute. This effort during placement of detectors within a FirePrint Application enhances the ability of FirePrint's deceptive phenomena rejection. Avoid close proximity of detectors to smoke sources such as oil burners, electric heaters, kitchens, garages, and areas of high relative humidity
where condensation may occur.
Air Currents
Before a detector can sense a fire, the products of com­bustion or smoke must travel from the fire to the detector. This travel is especially influenced by air currents; therefore, consider air movement when designing the system. While combustion products tend to rise, drafts from hallways, air diffusers, fans, etc., may help or hinder the travel of combustion products to the detector. When positioning a detector at a particular location, give
To initiating circuit of Siemens Industry, Inc. compatible control unit (See
below)
Compatible Control Equip­ment
Optional Remote Alarm Indicator Models RLI-1/RLI-2
To Next Base
To Next Base
Do Not Use an End of Line Device
Do Not Use an End of Line Device
Detector Base: Model DB-11 or Model DB-3 with DB-ADPT
5
6
61a1a
1b
561a
1b
Relay* Contacts 3A, 120 VAC 3A, 30 VDC
Remote Relay Base: Model DB-X11RS or Model DB-3XRS with DB-ADPT
*The relaycontacts are shown after System reset,which represents the non-alarm condition.
5+
NO
C
NC
6–
5+
NO
C
NC
6–
++ ++
+
+
+
––
Models FP-11/FPT-11
Figure 1
Installation and Wiring Diagram
Installation Instructions
P/N 315-095921-13
Siemens Industry, Inc. Building Technologies Division Florham Park, NJ
Siemens Canada Limited Building Technologies Division 2 Kenview Boulevard Brampton, Ontario L6T 5E4 Canada
2
consideration to windows and doors, both open and closed, to ventilating systems, both in and out of operation, and to other factors influencing air movement. Do not install a detector in the air stream of a room air supply diffuser. It is better to position a detector closer to an air return.
The distance that products of combustion or smoke travel from a fire to the detector is not usually the shortest linear route. Combustion products or smoke usually rise to the ceiling, then spread out. Average ceiling heights of 8 to 10 feet do not abnormally affect detector response. High ceilings, located in churches, warehouses, auditoriums, etc., do affect detector response and should be considered.
Special Ceiling Construction Factors
Ceiling obstructions can change the natural movement of air and combustion products. Depending on the direction of smoke travel, joists and beams can slow the movement of heated air and smoke, while pockets between them can contain a reduced level of smoke.Take obstructions created by girders, joists, beams, air conditioning ducts, or architectural design into consideration when determining area protection. Refer to the Initiating Devices chapter of NFPA Standard 72 for Location and Spacing requirements for specific types of construction; e.g. beam, suspended, level, sloped and peaked ceilings.
DETECTOR PLACEMENT FOR FPT-11
Locate the FPT-11 on the ceiling, at least 4 inches from the side walls. For an ideal, smooth ceiling condition, place the detectors at a maximum center spacing of 50 feet (2500 square feet), 25 feet from side walls or room partitions. For FM Approved installations this device is rate compensated and has an RTI rating of QUICK. Use a maximum center spacing of 20 feet (400 square feet), 10 feet from sidewalls or room partitions.
Actual job conditions and sound engineering judgment must determine detector spacing. Consider environmental factors including ambient temperature fluctuation, and the nature of the fire hazard. Room or area configuration and ceiling type (sloped or flat, smooth or beamed) also dictates placement.
Should questions arise regarding detector placement, follow the drawings provided and/or approved by Siemens Industry, Inc., or by its authorized distributors. This is extremely important! The detector placements shown on these drawings were chosen after a careful evaluation of the area being protected. Siemens Industry, Inc.'s extensive experience in design of the system assures the best detector placement by following these drawings.
TEMPERATURE – HUMIDITY – PRESSURE – AIR VELOCITY
The operating temperature range for the FP-11 and FPT-11 detectors is from 32°F (0°C) to 100°F (38°C). The thermal alarm temperature is rate compensated at 135°F (57°C). Use these detectors in environments where the humidity does not exceed 93% (non-condensing). Normal changes of atmospheric pressure do not affect detector sensitivity. For FP-11 open area 0-1200 ft/min
applications, use the appropriate application from the FirePrint ASD application list. Use the ASD duct application for 300-4000 ft/min applications a) in above­ceiling and under-floor plenums, b) inside an air duct, and c) in an air duct housing using sampling tubes. Follow detector spacing and location requirements in NFPA 72 Chapter 5 for High Air Movement Areas and Control of
Smoke Spread.
When installing Model FP-11 in existing installations with an existing duct detector housing, order an AD-11UK Air Duct Upgrade Kit DA-304, P/N 500-695967 and use it in that installation. This kit includes the required housing cover, P/N 305-095676. Do not use Model FP-11 with any other air duct cover.
NOTE For air duct and open area applications, the FP-11 smoke sensitivity range is indicated on its nameplate. For application/sensitivity settings, refer to the MXL/MXLV OPERATION, INSTALLATION, AND MAINTENANCE MANUAL, P/N 315-092036, the MXL-IQ OPERATION, INSTALLATION, AND MAINTENANCE MANUAL, P/N 315-093624, or the FireFinder-XLS INSTALLATION, OPERATION AND MAINTENANCE MANUAL, P/N 315-033744, as applicable.
DETECTOR MOUNTING
To ensure proper installation of the detector head into the base, be sure the wires are properly dressed at installations:
1. Position all wires flat against the base.
2. Take up all slack in the outlet box
3. Route wires away from connector terminals.
INSTALLATION / REMOVAL OF DETECTOR HEAD
To Install:
Align LED in detector with LED symbol on base and insert detector into base.
Rotate detector counterclockwise while gently pressing on it until the detector drops fully into base.
Then rotate the detector clockwise until it stops and locks in place. Insert optional locking screw (Order Model LK-11).
To Remove:
Loosen locking screw, if installed. Then rotate the detector counter clockwise until stop is reached.
Pull detector out of base.
PROGRAMMING
Each detector on a loop must be programmed to respond to a unique system address.
1. To program the detector address, use: a) Model
FPI-32 Programmer/Tester firmware version 3.0 or greater (refer to the FPI-32 OPERATIONS MANUAL, P/N 315-090077), or b) Model DPU Device Programming Unit (refer to the DPU Manual, P/N 315-033260).
Loading...
+ 2 hidden pages