Installation Instructions
Model FP2011-U1
6.5 Amp Power Supply Module
INTRODUCTION
The Model FP2011-U1 is a modular power supply that
provides primary regulated 26VDC power for normal
operation. The FP2011-U1 is rated at 6.5A and is filtered
and regulated. Regulation is +/- 0.25V under all load/
line cases.
The module incorporates a 4.0A non-resettable slowblow fuse on the primary input and includes a built-in
AC line filter for surge and noise suppression. The
FP2011-U1 mounts in a standard enclosure.
There are no serviceable parts to be maintained.
INSTALLATION
Remove all system power before installation, first battery then AC. (To power up,
connect the AC first, then the battery.)
The installation kit for the FP2011-U1 includes the
following:
One FP2011-U1 module
Four #10 lock nuts
One 4-wire cable
For 240VAC installation, reference the
Jumper Removal section on page 2
before installing the FP2011-U1 module.
3. Using the lock nuts provided, secure the FP2011U1 to the mounting studs of the enclosure.
Typical Enclosure
FP2011-U1
FP2011-U1 Mounting
Studs (4 places)
Figure 1
FP2011-U1 Mounting in Typical Enclosure
Wiring
The FP2011-U1 is designed to operate from a 120 or
240 VAC, 50/60 Hz power source. Use a separate or
dedicated circuit breaker. Wire in accordance with the
authority having jurisdiction and Article 760 of the NEC
NFPA 70 latest edition.
Mounting
Mount the enclosure to the wall before mounting the
FP2011-U1 power supply to the enclosure.
1. Make sure that the dedicated circuit breaker for
the FP2011-U1 is turned off at the mains.
2. Place the FP2011-U1 housing over the four studs
provided in the enclosure indicated in the system
installation manual. (Refer to Figure 1 for a typical
example.)
Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ
P/N 315-050222-2
Run the earth ground from a suitable source to the
FP2011-U1. Check local requirements. Conduit is not
an acceptable earth ground conductor.
1. Connect the AC mains to the 3-position terminal
block on the FP2011-U1 as shown in Figure 2.
Black (L - Live)
White (N - Neutral)
Green (G - Earth Ground)
Siemens Canada, Ltd.
1577 North Service Road East
Oakville, Ontario
L6H 0H6 Canada

2. Connect the 4-wire cable included in the installation
kit to the 4-position header on the FP2011-U1. The
cable is keyed and will connect in only one way.
Connect the other end of the cable to the terminal
block (TB) indicated in the system installation
manual. This cable is also keyed and will connect
in only one way. (Refer to Figure 3.)
If the AC input is 240VAC, you will need to remove
the cover of the FP2011-U1 housing and remove the
jumper on J1. Follow the steps listed below.
1. On the side of the housing with 5 screws, remove
all 5 screws and place them to one side.
2. On the side of the housing with 8 screws, remove
the 5 screws indicated in Figure 4 and place them to
one side.
AC
Mains
Black (L)
White (N)
Green (G)
SUPERVISED
NON-POWER
LIMITED
18 AWG MIN.
Blue
Black
Black
Red
FP2011-U1
DISCONNECT POWER
BLOCK PROTECTION
REMOVING
TERMINAL
PRIOR TO
WARNING
DESACTIVEZ L'UNITE
AVANTENTRETIEN
LNG
Figure 2
Wiring the FP2011-U1
MATES WITH CONNECTOR
ON PCB BOARD
MATES WITH
POWER SUPLY
Figure 3
FP2011-U1 Power Supply Cable
FP2011-U1
4-POSITION
HEADER
FERRITE
CORE
DO NOT REMOVE THE REMAINING 3 SCREWS.
Figure 4
Removing 5 Screws from the Side of the
FP2011-U1 that has 8 Screws
3. Take off the top cover.
4. Locate jumper J1. Refer to Figure 5 to find the
location.
FP2011-U1 PCB
ELECTRICAL RATINGS
Primary Power:
Input: 120VAC or 240VAC,
50/60Hz @ 2.0A Max.
Output: 26VDC @ 6.5A Max.
Max Current: 6.5A (2 Hours Max.)
Filtered and Regulated
JUMPER REMOVAL FOR 240VAC ONLY
Remove all system power before installation, first battery then AC. (To power up,
connect the AC first, then the battery.)
P/N 315-050222-2
For 240VAC, Remove Jumper
Figure 5
Location of Jumper J1 for 120VAC on the FP2011-U1
Power Supply (For 240VAC, Remove Jumper)
5. Remove J1 by hand or by using a tool.
6. Replace the top cover on the FP2011-U1 and
secure in place by installing the 10 screws that
were removed.
2