FP120-Z1 Power supply kit A (70 W)
Technical Manual
A6V10393194_d_en_
--
2018-11-05 Control Products and Systems
Page 2
Imprint
2 | 32
Building Technologies
A6V10393194_d_en_
--
Fire Safety
2018-11-05
Imprint
Technical specifications and availability subject to change without notice.
Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its contents and communication thereof to others without express authorization are prohibited. Offenders will be held liable for payment of damages. All rights created by patent grant or registration of a utility model or design patent are reserved.
Issued by: Siemens Switzerland Ltd. Building Technologies Division International Headquarters Theilerstrasse 1a CH-6300 Zug Tel. +41 58 724-2424
www.siemens.com/buildingtechnologies
Edition: 2018-11-05 Document ID: A6V10393194_d_en_--
© Siemens Switzerland Ltd, 2014
Page 3
3 | 32
Building Technologies
A6V10393194_d_en_
--
Fire Safety
2018-11-05
Table of contents
1 About this document ............................................................................. 5
1.1 Applicable documents ................................................................................. 6
1.2 Download center ......................................................................................... 7
1.3 Revision history .......................................................................................... 7
2 Safety ................................................................................................. 8
2.1 Safety instructions ...................................................................................... 8
2.2 Safety regulations for the method of operation ............................................ 9
2.3 Standards and directives complied with......................................................11
2.4 Release Notes ...........................................................................................12
3 Structure and function ......................................................................... 13
3.1 'Fault' signal transfer relay .........................................................................14
4 Mounting ........................................................................................... 15
4.1 Mounting the housing.................................................................................15
4.2 Mounting the optional components .............................................................16
4.3 Laying the cables and connecting the batteries ..........................................17
4.3.1 Connecting the signal lines and DC 24 V .....................................19
4.3.2 Connecting the mains cable ........................................................21
4.4 Installing and connecting the batteries .......................................................22
4.5 Mounting the cover cap ..............................................................................22
5 Switching the mains voltage to AC 115 V .............................................. 23
6 Battery capacity.................................................................................. 24
7 Checking functions ............................................................................. 25
8 Maintenance ...................................................................................... 26
9 Faults / Troubleshooting ...................................................................... 27
10 Components / accessories / spare parts ................................................ 28
11 Technical data.................................................................................... 29
12 Disposal ............................................................................................ 31
Page 4
Building Technologies
A6V10393194_d_en_
--
Fire Safety
2018-11-05
4 | 32
Page 5
About this document
Applicable documents
1
5 |
32
Building Technologies
A6V10393194_d_en_
--
Fire Safety
2018-11-05
1 About this document
Goal and purpose
This manual describes the design and functions, as well as the key work steps required for mounting and installation. Information about the function check, maintenance, and troubleshooting makes it possible to use the product as intended.
Scope
The information contained in this document is valid for FP120-Z1 power supply kit A (70 W).
Intended use
This standalone power supply is intended for decentralized supply to external devices. FP120-Z1 has an integrated operating and fault indicator, and makes it possible to forward faults via potential-free contacts.
Target groups
The information in this document is intended for the following target groups:
Target group Activity Qualification
Installation personnel
Assembles and installs the product components at the place of installation.
Carries out a function check following installation.
Has received specialist training in the area of building installation technology or electrical installations.
Maintenance personnel Carries out all maintenance work.
Checks that the products are in perfect working order.
Searches for and corrects malfunctions.
Has obtained suitable specialist training for the function and for the products.
Source language and reference document
The source/original language of this document is German (de).
The reference version of this document is the international version in English.
The international version is not localized.
Document identification
The document ID is structured as follows:
ID code Examples
ID_ModificationIndex_Language_COUNTRY
-- = multilingual or international
A6V10215123_a_de_DE A6V10215123_a_en_-­A6V10315123_a_--_--
Date format
The date format in the document corresponds to the recommendation of international standard ISO 8601 (format YYYY-MM-DD).
Page 6
About this document
Applicable documents
1
6 | 32
Building Technologies
A6V10393194_d_en_
--
Fire Safety
2018-11-05
Conventions for text marking
Markups
Special markups are shown in this document as follows:
Requirement for a behavior instruction
1.
2.
Behavior instruction with at least two operation sequences
Version, option, or detailed information for a behavior instruction Intermediate result of a behavior instruction
End result of a behavior instruction
Numbered lists and behavior instructions with an operation
sequence [ X] Reference to a page number 'Text' Quotation, reproduced identically <Key> Identification of keys >
Relation sign and for identification between steps in a sequence,
e.g., 'Menu bar' > 'Help' > 'Help topics' Text Identification of a glossary entry
Supplementary information and tips
The 'i' symbol identifies supplementary information and tips
for an easier way of
working.
1.1 Applicable documents
Document ID Title
A6V10393173 FP120-Z1 power supply kit A (70 W) – Mounting A6V10416448 FP120-Z1 power supply kit A (70 W) – Data sheet A6V10411051 FP2015-A1 power supply (70 W) – Technical manual
Page 7
About this document
Download center
1
7 |
32
Building Technologies
A6V10393194_d_en_
--
Fire Safety
2018-11-05
1.2 Download center
You can download various types of documents, such as data sheets, installation instructions, and license texts via the following Internet address:
http://siemens.com/bt/download
l Enter the document ID in the 'Find by keyword' input box.
You will also find information about search variants and links to mobile
applications (apps) for various systems on the home page.
1.3 Revision history
The reference document's version applies to all languages into which the reference document is translated.
The first edition of a language version or a country variant may, for example, be
version 'd' instead of 'a' if the reference document is already this version.
The table below shows this document's revision history:
Version Edition date Brief description
d 2018-11-05 Technical data revised, row 'Approvals' removed c 2015-06-20 Technical data revised b 2014-11-18 Technical data revised a 2014-02-09 First edition
Page 8
Safety
Safety instructions
2
8 | 32
Building Technologies
A6V10393194_d_en_
--
Fire Safety
2018-11-05
2 Safety
2.1 Safety instructions
The safety notices must be observed in order to protect people and property. The safety notices in this document contain the following elements:
Symbol for danger
Signal word
Nature and origin of the danger
Consequences if the danger occurs
Measures or prohibitions for danger avoidance
Symbol for danger
This is the symbol for danger. It warns of risks of injury. Follow all measures identified by this symbol to avoid injury or death.
Additional danger symbols
These symbols indicate general dangers, the type of danger or possible consequences, measures and prohibitions, examples of which are shown in the following table:
General danger Explosive atmosphere
Voltage/electric shock Laser light
Battery Heat
Signal word
The signal word classifies the danger as defined in the following table:
Signal word Danger level DANGER
'DANGER' identifies a dangerous situation, which will result directly in death or serious injury if you do not avoid this situation.
WARNING
'WARNING' identifies a dangerous situation, which may result in death or serious injury if you do not avoid this situation.
CAUTION
'CAUTION' identifies a dangerous situation, which could result in slight to moderately serious injury if you do not avoid this situation.
NOTICE
'
NOTICE
' identifies a possibly harmful situation or possible damage to property
that may result from non-observance. '
NOTICE
' does not relate to possible bodily injury.
Page 9
Safety
Safety regulations for the method of operation
2
9 |
32
Building Technologies
A6V10393194_d_en_
--
Fire Safety
2018-11-05
How risk of injury is presented
Information about the risk of injury is shown as follows:
WARNING
Nature and origin of the danger
Consequences if the danger occurs
Measures / prohibitions for danger avoidance
How possible damage to property is presented
Information about possible damage to property is shown as follows:
NOTICE
Nature and origin of the danger
Consequences if the danger occurs
Measures / prohibitions for danger avoidance
2.2 Safety regulations for the method of operation
National standards, regulations and legislation
Siemens products are developed and produced in compliance with the relevant European and international safety standards. Should additional national or local safety standards or legislation concerning the planning, mounting, installation, operation or disposal of the product apply at the place of operation, then these must also be taken into account together with the safety regulations in the product documentation.
Electrical installations
WARNING
Electrical voltage
Electric shock
Work on electrical installations may only be carried out by qualified electricians or by instructed persons working under the guidance and supervision of a qualified electrician, in accordance with the electrotechnical regulations.
Wherever possible disconnect products from the power supply when carrying out commissioning, maintenance or repair work on them.
Lock volt-free areas to prevent them being switched back on again by mistake.
Label the connection terminals with external voltage using a
'DANGER External voltage' sign.
Route mains connections to products separately and fuse them with their own, clearly marked fuse.
Fit an easily accessible disconnecting device in accordance with IEC 60950-1 outside the installation.
Produce earthing as stated in local safety regulations.
Page 10
Safety
Safety regulations for the method of operation
2
10 | 32
Building Technologies
A6V10393194_d_en_
--
Fire Safety
2018-11-05
CAUTION
Noncompliance with the following safety regulations
Risk of injury to persons and damage to property
Compliance with the following regulations is required.
Specialist electrical engineering knowledge is required for installation.
Only an expert is permitted to carry out installation work.
Incorrect installation can take safety devices out of operation unbeknown to a layperson.
Mounting, installation, commissioning and maintenance
If you require tools such as a ladder, these must be safe and must be intended for the work in hand.
When starting the fire control panel ensure that unstable conditions cannot arise.
Ensure that all points listed in the 'Testing the product operability' section below are observed.
You may only set controls to normal function when the product operability has been completely tested and the system has been handed over to the customer.
Testing the product operability
Prevent the remote transmission from triggering erroneously.
If testing building installations or activating devices from third-party companies,
you must collaborate with the people appointed.
The activation of fire control installations for test purposes must not cause injury to anyone or damage to the building installations. The following instructions must be observed:
Use the correct potential for activation; this is generally the potential of the
building installation. – Only check controls up to the interface (relay with blocking option). – Make sure that only the controls to be tested are activated.
Inform people before testing the alarm devices and allow for possible panic responses.
Inform people about any noise or mist which may be produced.
Before testing the remote transmission, inform the corresponding alarm and
fault signal receiving stations.
Modifications to the system design and the products
Modifications to the system and to individual products may lead to faults, malfunctioning and safety risks. Written confirmation must be obtained from Siemens and the corresponding safety bodies for modifications or additions.
Page 11
Safety
Standards and directives complied with
2
11 |
32
Building Technologies
A6V10393194_d_en_
--
Fire Safety
2018-11-05
Modules and spare parts
Components and spare parts must comply with the technical specifications defined by Siemens. Only use products specified or recommended by Siemens.
Only use fuses with the specified fuse characteristics.
Wrong battery types and improper battery changing lead to a risk of explosion.
Only use the same battery type or an equivalent battery type recommended by Siemens.
Batteries must be disposed of in an environmentally friendly manner. Observe national guidelines and regulations.
Disregard of the safety regulations
Before they are delivered, Siemens products are tested to ensure they function correctly when used properly. Siemens disclaims all liability for damage or injuries caused by the incorrect application of the instructions or the disregard of danger warnings contained in the documentation. This applies in particular to the following damage:
Personal injuries or damage to property caused by improper use and incorrect application
Personal injuries or damage to property caused by disregarding safety instructions in the documentation or on the product
Personal injury or damage to property caused by poor maintenance or lack of maintenance
2.3 Standards and directives complied with
A list of the standards and directives complied with is available from your Siemens contact.
Page 12
Safety
Release Notes
2
12 | 32
Building Technologies
A6V10393194_d_en_
--
Fire Safety
2018-11-05
2.4 Release Notes
Limitations to the configuration or use of devices in a fire detection installation with a particular firmware version are possible.
WARNING
Limited or non
-
existent fire detection
Personal injury and damage to property in the event of a fire.
Read the 'Release Notes' before you plan and/or configure a fire detection installation.
Read the 'Release Notes' before you carry out a firmware update to a fire
detection installation.
NOTICE
Incorrect planning and/or configuration
Important standards and specifications are not satisfied. Fire detection installation is not accepted for commissioning. Additional expense resulting from necessary new planning and/or configuration.
Read the 'Release Notes' before you plan and/or configure a fire detection installation.
Read the 'Release Notes' before you carry out a firmware update to a fire
detection installation.
Page 13
Structure and function
Release Notes
3
13 |
32
Building Technologies
A6V10393194_d_en_
--
Fire Safety
2018-11-05
3 Structure and function
Figure 1: Installation situation FP120-Z1
1 LED function display 6 Connection card FP120-Z1 mainboard 2 Battery 7 U-rail TS35, 122 mm long 3 Housing 8
Installation positions for input/output
modules and relay modules 4 Power supply (70 W) 9 Front panel 5 Mains connection terminals 10 Cover cap
Symbol LED function display Status LED Description
System: Green ON System operational
OFF System not operational
Fault: Yellow OFF No fault
ON Mains or battery fault
5
1
4
7
839
10
6
2
Page 14
Structure and fun
ction
'Fault' signal transfer relay
3
14 | 32
Building Technologies
A6V10393194_d_en_
--
Fire Safety
2018-11-05
3.1 'Fault' signal transfer relay
The power supply has two relays with changeover contact for the 'Fault' signal transfer.
Contact Normal operation Fault
MAINS Relay is activated.
NC contact is open. NO contact is closed.
Relay is deactivated.
NC contact is closed.
NO contact is open.
BATT Relay is activated.
NC contact is open. NO contact is closed.
Relay is deactivated.
NC contact is closed.
NO contact is open.
Page 15
Mounting
Mounting the housing
4
15 |
32
Building Technologies
A6V10393194_d_en_
--
Fire Safety
2018-11-05
4 Mounting
Scope of delivery
The power supply kit (70 W) is supplied mounted with housing, a left-hand installation frame with integrated power supply (70 W) FP2015 and FP120-Z1 mainboard, a right-hand installation frame for optional components, and a pre­wired connection for the battery, as well as mounting instructions for wall mounting and optional components: Document ID A6V10393173.
NOTICE
Electrostatic discharge
Damage to electronics
Take protective measures against electrostatic discharges (ESD).
Observe the following order for mounting the FP120-Z1:
1. Mount the housing
2. Mount the optional components
3. Connect the signal lines
4. Disconnect the mains voltage, disconnect the mains cable, and connect the mains cable
5. Install and connect the batteries
6. Mount the cover cap
7. Switch on the mains voltage
4.1 Mounting the housing
Use the mounting instructions, document ID A6V10393173, from the scope of delivery.
Page 16
Mounting
Mounting the optional components
4
16 | 32
Building Technologies
A6V10393194_d_en_
--
Fire Safety
2018-11-05
4.2 Mounting the optional components
A component can be mounted on the rear panel of the housing without a U-rail. Up to seven components can be mounted on a U-rail, depending on the size of the component.
Installation on rear panel of the housing Installation on U-rail
1 Input/output module 3 Large component, e.g., FDCIO223 2 U-rail 4 Small component, e.g., FDCIO221
1
243
Page 17
Mounting
Laying the cables and connecting the batteries
4
17 |
32
Building Technologies
A6V10393194_d_en_
--
Fire Safety
2018-11-05
4.3 Laying the cables and connecting the batteries
Primary wiring
WARNING
Electrical voltage
Electric shock
Before connecting the mains cable, make sure that the cable is current-free.
Ensure that the mains is secured against inadvertently being switched on.
Secondary wiring
NOTICE
Short
-
circuit
Damage to hardware
Before removing or fitting the power supply, remove the jumper wire between the two batteries.
a This ensures that the secondary side is current-free and that no components
can be damaged due to a short circuit.
1 Mains cable 2 Boundary of mains zone: White 3 Current-limited area: Gray 4 Signal lines
}
1
2 3
4
Page 18
Mounting
Laying the cables and connecting the batteries
4
18 | 32
Building Technologies
A6V10393194_d_en_
--
Fire Safety
2018-11-05
The following instructions must be observed.
The cable cross section for each of the three lines of the mains cable is
1.5…2.5 mm2.
The mains cable must be inserted from above on the left of the housing and must not be laid outside the boundary of the mains zone.
The lines of the mains cable must be secured with a cable tie.
Signal lines must only be fed into the housing on the right from above or from
the rear.
Signal lines must be secured with a cable tie.
Cable entries must be closed completely.
No cable entries should be made in the back box.
Batteries must be installed so that they cannot leak.
Page 19
Mounting
Laying the cables and c
onnecting the batteries
4
19 |
32
Building Technologies
A6V10393194_d_en_
--
Fire Safety
2018-11-05
4.3.1 Connecting the signal lines and DC 24 V
Figure 2: x = cable tie
The figure above shows the cable ties (x), which are also required for the mains
lines, even though these are only connected after the signal lines.
Figure 3: Stripping the cables
Max. current for AUX
1orAUX
2 is 2
A.
Max. current for AUX 1and AUX 2total is 2 A.
Figure 4: Terminal block
x
x
x
x
x
x
5 mm
Page 20
Mounting
Laying the cables and connecting the batteries
4
20 | 32
Building Technologies
A6V10393194_d_en_
--
Fire Safety
2018-11-05
1. Strip the signal cables and lay these in the housing as shown above.
2. Connect the lines to the terminal block in accordance with the following wiring
diagram.
3. Strip the DC 24 V lines and lay these in the housing as shown above.
4. Connect the DC 24 V lines to the terminal block.
5. Secure the lines with cable ties (x).
'Fault' signal transfer via input/output module
The line for the 'Fault' signal transfer of the power supply is wired to an input/output module, such as an FDCIO221, for example.
'Fault' signal transfer to a fire control panel
The line for the 'Fault' signal transfer of the power supply is wired to a fire control panel, such as an FC120, for example.
This connection is only permitted if the housings are mounted side by side.
Otherwise, the connection must be monitored.
3.3 k
Ω
FCnet /
C-Net
FDCIO221
Input
LINE
OUT A
+
-
-
FC120
AUX. 24V INPUT
+
-
1
FP120-Z1
Page 21
Mounting
Laying the cables and connecting the batteries
4
21 |
32
Building Technologies
A6V10393194_d_en_
--
Fire Safety
2018-11-05
4.3.2 Connecting the mains cable
1 Outer insulation of the mains cable 2 Cable tie
w The mains cable is de-energized and the network is secured against
inadvertently being switched on.
1. Feed the mains cable into the housing with the length required.
2. Remove the outer insulation (1) of the mains cable up to max. 5 mm before the
cable gland.
3. Connect the lines.
4. Insert the cable tie (2) through the opening and secure the lines of the mains
cable.
5 mm
1
2
Page 22
Mounting
Installing and connecting the batteries
4
22 | 32
Building Technologies
A6V10393194_d_en_
--
Fire Safety
2018-11-05
4.4 Installing and connecting the batteries
1 Cable bridge B Cables, black (–) R Cables, red (+)
Connect suitable1 batteries, as shown, and connect the cable bridge (1).
1
You will find suitable batteries in the 'Components / accessories / spare parts
[ 28]' chapter.
4.5 Mounting the cover cap
Use the mounting instructions, document ID A6V10393173, from the scope of delivery.
1
R
B
Page 23
Switching the mains voltage to AC 115 V
5
23 |
32
Building Technologies
A6V10393194_d_en_
--
Fire Safety
2018-11-05
5 Switching the mains voltage to AC 115 V
The mains voltage set in the factory is AC
230
V.
Observe the safety instructions in the 'Laying the cables and connecting the batteries [ 17]' chapter.
w The mains cable is de-energized and the network is secured against
inadvertently being switched on.
w The wire jumper between both batteries is removed.
l Remove the power supply.
1. Open the power supply housing.
2. Switch the jumper from position X12 = AC 230 V to position X11 = AC 115 V.
Mark the change from AC 230 V to AC 115 V on the product label as shown below.
Jumper X12
= AC 230 V
Jumper X11
= AC 115 V
s
Power supply (70 W) Typ FP2015-A1
:
P.Nr.
Rated voltage 115/230 V
:
Frequency: 50~60 Hz I in 1/0.5 A
:
Output 70 W
:
ES
:
DO NOT OPEN COVER
Siemens Switzerland Ltd Country of Origin: China
X2
X1
Akku
- + - +
Usys
M a
i
n
N o t
U s e
d
B a t
t
e
r
y
N
L
!
N o t
U s
e
d
Selected voltage
230 V
115 V
X
:
S54400-B121-A1
Control Code
:
XXYZWWW
EN54-4 VdS: G
213083
0786-CPR-21302
Selected volt age
230 V
115 V
X
X
Page 24
Battery capacity
6
24 | 32
Building Technologies
A6V10393194_d_en_
--
Fire Safety
2018-11-05
6 Battery capacity
The required battery capacity depends on the required standby and alarm time, the aging factor, and the total current in the relevant mode.
Observe the country-specific or EN regulations. The required battery capacity can be identified using the following table and the
calculation formula.
Consumer Standby [mA] Alarm [mA]
Internal use by PSU 24 24 AUX 1 (e.g., sounders) AUX 2(e.g., sounders)
Total current [mA]
Total current [mA] = standby [mA] + alarm [mA] =
max. 2000
mA
[(Standby time * standby current) + (alarm time * sum alarm current)] * aging factor = capacity
Standby time [h] 24, 30 or 72 Alarm time [h] 0.5 Aging factor 1.25 Standby current [A] Total current in standby mode Alarm current [A] Total current in alarm mode Capacity [Ah]
Max. 17 Ah depending on type, see the 'Components / accessories / spare parts [ 28]' chapter
l Choose the appropriate battery based on calculated capacity.
See also
2 Components / accessories / spare parts [ 28]
Page 25
Check
ing functions
7
25 |
32
Building Technologies
A6V10393194_d_en_
--
Fire Safety
2018-11-05
7 Checking functions
The functions must be checked after installation and in accordance with the maintenance regulations.
NOTICE
Open line of the power supply for external devices
Unwanted automatic service provider notification.
For both function checks, ensure that the alternative power supply is active
respectively.
l Check the following functions:
1. Display and transmission of a mains fault
2. Display and transmission of a battery fault
Mains fault
1. Disconnect the mains voltage.
2. Check the LED function display on the housing.
3. Check the 'Fault' signal transfer on the fire control panel.
a The 'Fault' LED function display lights up. a The event 'Fault' is displayed on the fire control panel.
Battery fault
1. Disconnect the batteries.
2. Check the LED function display on the housing.
3. Check the 'Fault' signal transfer on the fire control panel.
a The 'Fault' LED function display lights up. a The event 'Fault' is displayed on the fire control panel.
Page 26
Maintenance
8
26 | 32
Building Technologies
A6V10393194_d_en_
--
Fire Safety
2018-11-05
8 Maintenance
Comply with all local maintenance regulations and use the following maintenance recommendation.
Depending on national regulations, the maintenance intervals can be set
differently from the following maintenance recommendation.
Maintenance recommendation Interval/year
Check the display and transmission of a mains fault and a battery fault in the overall connected system.
1x
Perform a visual of the batteries 1x Check the ground conductor 1x Remove dust 1x
Page 27
Faults / Troubleshooting
9
27 |
32
Building Technologies
A6V10393194_d_en_
--
Fire Safety
2018-11-05
9 Faults / Troubleshooting
If a fault cannot be eliminated with the help of the
following information, please
contact the service engineer.
Symbol Status LED Description Possible cause Measures
OFF System not operational
With a voltage <DC 20.5 V, batteries are switched off automatically
Check the mains voltage.
Check fuse F1, see
document A6V10411051.
ON Mains or battery fault
Mains voltage disconnected
Battery voltage too low
Batteries disconnected
Check the mains voltage.
Check the battery voltage.
Check the cabling.
Check fuse F3, see
document A6V10411051.
Status Possible cause Measures
No voltage at AUX 1 or AUX 2
The electronic fuse for overload and short-circuit has switched.
Check the installation and cabling.
The electronic fuse resets automatically after the cause of the switch has been
eliminated.
Page 28
Components / accessories / spare parts
10
28 | 32
Building Technologies
A6V10393194_d_en_
--
Fire Safety
2018-11-05
10 Components / accessories / spare parts
Component
Type Designation Order no. Weight
FP120-Z1 Power supply kit (70 W) S54400-S122-A1 3,920 kg
Scope of delivery
The power supply kit (70 W) is supplied mounted with housing, a left-hand installation frame with integrated power supply (70 W) FP2015 and FP120-Z1 mainboard, a right-hand installation frame for optional components, and a pre­wired connection for the battery, as well as mounting instructions for wall mounting and optional components: Document ID A6V10393173.
Accessories
The following accessories are not included in the scope of delivery and must be ordered separately.
Type Designation Order no. Weight
TS35/122 U-rail TS35/7.5/122 BPZ:5644780001 0.041 kg FA2003-A1 Battery (12 V, 7 Ah, VDS) A5Q00019353 2.450 kg FA2004-A1 Battery (12 V, 12 Ah, VDS) A5Q00019354 3.930 kg FA2005-A1 Battery (12 V, 17 Ah, VDS) A5Q00019677 5.640 kg
Spare part
Type Designation Order no. Weight
FP2015-A1 Power supply (70 W) S54400-B121-A1 0.576 kg
Page 29
Technical data
11
29 |
32
Building Technologies
A6V10393194_d_en_
--
Fire Safety
2018-11-05
11 Technical data
Mains supply Voltage
AC 97…127 V, AC 196…253 V,
50 / 60 Hz Current 0.5…1 A Power consumption Max. 90 VA
System supply output Designation 'AUX 1', 'AUX 2'
Voltage
2x DC 20.2…28.6 V, depending on charge
and temperature Current (sum of both outputs)
Maximum output current with
battery charge (I
max a
)
0.9 A
Maximum output current without
battery charge (I
max b
)
2.0 A
Minimum output current (I
min
) 0.05 A Output power 70 W Ripple Max. 5 %
Battery supply output Designation 'Accu'
Voltage
DC 20.5…28.6 V, depending on charge and temperature
Charging current
Max. 1.6 A, the charging current is reduced at full load
Connectable batteries 2x 12 V / 7…17 Ah
Battery types recommended by Siemens in accordance with 'Components / accessories / spare parts' chapter
Battery internal resistance (R
imax
) Max. 1 Ω, batteries incl. line
Batteries are monitored for Short-circuit
Open line
Presence
Low discharge protection Battery voltage DC 20.5…21.0 V
Mains fault monitoring signal
Designation 'MAINS' Active in event of No mains voltage, signaling within 10 s Design
Potential-free changeover contact DC 30 V/1 A
Battery fault monitoring signal
Designation 'BATT' Active in event of Battery fault
Battery voltage <DC 21.0 V
Design
Potential-free changeover contact DC 30 V/1 A
Connections
Mains supply, battery supply and monitoring signals
Plug-type connection and terminals
0.2…2.5 mm
2
Page 30
Technical data
11
30 | 32
Building Technologies
A6V10393194_d_en_
--
Fire Safety
2018-11-05
Mechanical data Dimensions (W x H x D) 430 x 399 x 124 mm
Weight 3,920 kg, without batteries Housing color RAL 9010 pure white Protection category (IEC 60529) IP 30
Page 31
Disposal
12
31 |
32
Building Technologies
A6V10393194_d_en_
--
Fire Safety
2018-11-05
12 Disposal
This equipment is manufactured using materials and procedures which comply with current environmental protection standards as best as possible. More specifically, the following measures have been undertaken:
Use of reusable materials
Use of halogen-free plastics
Electronic parts and synthetic materials can be separated
Larger plastic parts are labeled according to ISO 11469 and ISO 1043. The plastics can be separated and recycled on this basis.
Electronic parts and batteries must not be disposed of with domestic waste.
Take electronic parts and batteries to local collection points or recycling centers.
Contact local authorities for more information.
Observe national requirements for disposing of electronic parts
and batteries.