Siemens BB-55, BB-55R Installation Instructions Manual

Installation Instructions
SIEMENSINDUSTRY,INC.
MODELBB-55
INSTALLATIONINSTRUCTIONS
P/N315-093298
FLORHAMPARK, NJ 07932
MODELS BB-55 and BB-55R Battery Box (For indoor use only in dry environments)
INTRODUCTION
The Model BB-55 or BB-55R from Siemens Industry, Inc. is used to house BTX-1 (31 AH) and BTX-2 (55 AH) batteries for the MXL/MXLV/MXL-IQ System. The BB-55 is black and the BB-55R is red.
KNOCKOUT FOR WIRING
The backbox can be mounted on a flat surface with four user-supplied bolts that are a maximum of 3/8 inch in diameter.
INSTALLATION
Prior to installation, consider the following:
Weight and size of the enclosure.
Local codes.
1. Select a clean, dry, shock and vibration free surface.
2. Position the backbox directly beneath the MXL enclosure to which it will be wired, lining up the knockouts in the BB-55 with the knockouts in the MXL enclosure.
3. Position the backbox so that it is clear of obstructions and the front door opens freely.
4. Mark the locations of the two upper mounting bolts of the backbox on the wall. (See Figure 2.)
5. Drill the two holes located in the previous step and screw in the top bolts, leaving a small gap between the wall and each top bolt.
6. Place the backbox over the two top bolts and allow it to slide down over the bolts.
7. Mark, drill, and install the two bottom bolts in the backbox.
8. Tighten all four bolts securely against the back wall of the backbox.
9. Place the batteries in the bottom of the BB-55.
BB-55
Figure 1
BB-55 Enclosure
1.38 in
11.00 in
8.00 in
ø0.437 in (2 HOLES)
21.25 in
SIEMENSINDUSTRY,INC.
FLORHAMPARK, NJ 07932
INSTALLATIONINSTRUCTIONS
P/N315-093298
24.00 in
Figure 2
BB-55 Mounting Holes
WIRING
The main AC power line must be turned OFF prior to installation.
Wire in accordance with local codes and NEC 760.
1. Remove the knockouts in the top of the battery box and bottom of MXL enclosure for entry of battery wiring.
2. Connect the Battery Wire Assembly to the batteries in the BB-55. If a longer wire is required, use a minimum of 12 AWG.
SPECIFICATIONS
BB-55: 24"W x 7"D x 11"H
Siemens Industry, Inc. Building Technologies Division Florham Park, NJ
P/N 315-093298-2
Siemens Building Technologies, Ltd. Fire Safety & Security Products 2 Kenview Boulevard Brampton, Ontario L6T 5E4 Canada
P2
P3
TB3
TB5
PIM-1
TB1
MMB
TB2
TB1
TB5
TB4
TBM-1/-2
TB4
M O M
-
4
o r
P8
O M M
-
1
M O M
-
4
o r
P5P5
P8
O M M
-
1
M O M
-
4
o r
P5
P8
O M M
-
1
P/N 315-093298-2
MPS-6
OR
MPS-12
+
__
+
BATTERY BATTERY
BB-55
Figure 3
Typical Battery Connections from MXL to BB-55
Loading...