Siemens BACNET 125-699 User Manual

Siemens BACnet Heat Pump Controller – Multi­Stage Owner’s Manual
125-699 Rev. BA, July 2009
Siemens Building Technologies, Inc. i
Rev. BA, July 2009
The information contained within this document is subject to change without notice and should not be construed as a commitment by Siemens Building Technologies, Inc. Siemens Building Technologies, Inc. assumes no responsibility for any errors that may appear in this document.
All software described in this document is furnished under a license and may be used or copied only in accordance with the terms of such license.
WARNING
This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the instructions manual, may cause interference to radio communications. It has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC rules. These limits are designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference in which case users at their own expense will be required to take whatever measures may be required to correct the interference.
SERVICE STATEMENT
Control devices are combined to make a system. Each control device is mechanical in nature and all mechanical components must be regularly serviced to optimize their operation. All Siemens Building Technologies branch offices and authorized distributors offer Technical Support Programs that will ensure your continuous, trouble-free system performance.
For further information, contact your nearest Siemens Building Technologies, Inc. representative.
Copyright 2009 by Siemens Building Technologies, Inc.
TO THE READER
Your feedback is important to us. If you have comments about this document, please contact your local Siemens Building Technologies representative.
CREDITS
Product or company names mentioned herein may be the trademarks of their respective owners
Pirnted in the U.S.A.
Table of Contents
How to Use This Manual ............................................................................................... III
Manual Organization .................................................................................................. III
Manual Conventions .................................................................................................. III
Manual Symbols ........................................................................................................ IV
Getting Help ............................................................................................................... IV
Product Overview ......................................................................................................... 1
Introduction ................................................................................................................... 1
Ordering Notes........................................................................................................... 1
Hardware Inputs ........................................................................................................ 2
Analog ..................................................................................................................... 2
Digital ...................................................................................................................... 2
Hardware Outputs ...................................................................................................... 2
Analog ..................................................................................................................... 2
Digital ...................................................................................................................... 3
Power Wiring ........................................................................................................... 3
Communication Wiring ............................................................................................ 3
Controller LED Indicators ........................................................................................... 4
Temperature Sensors ................................................................................................ 4
Room Temperature Sensor ..................................................................................... 4
Mixed Air Temperature Sensor ............................................................................... 4
Actuators .................................................................................................................... 4
Related Equipment .................................................................................................. 5
Applications ................................................................................................................... 7
Basic Operation ............................................................................................................. 7
Control Temperature Setpoints.................................................................................. 7
Day/Night Mode ......................................................................................................... 7
Night Mode Override Switch ...................................................................................... 7
Control Loops ............................................................................................................. 7
Mixed Air Control Loop ............................................................................................ 7
Calibration .................................................................................................................. 8
Heating and Cooling Switchover ............................................................................... 9
Electric Reheat ........................................................................................................... 9
Siemens Building Technologies, Inc. I
Siemens BACnet Heat Pump Controller - Multi-Stage Owner’s Manual
Compressor Operation .............................................................................................. 9
Fan Operation ............................................................................................................ 9
Power Failure Recovery ............................................................................................ 10
Centralized Alarm Monitoring .................................................................................... 10
Overriding DOs .......................................................................................................... 10
Fail-safe Operation .................................................................................................... 10
Using Auxiliary Points ................................................................................................ 11
Application 2583: Multiple Compressor Heat Pump with Reversing Valve Control and
Mixed Air Control .......................................................................................................... 12
Compressor Staging .................................................................................................. 12
Reversing Valve Operation ........................................................................................ 12
Application Notes ....................................................................................................... 12
Application 2584: Multiple Heating and Cooling Heat Pump with Mixed Air and Internal
Reversing Valve Control............................................................................................... 14
Compressor/Electric Heat Staging ............................................................................ 14
Application Notes ....................................................................................................... 14
Application 2590: BACnet Heat Pump Slave Mode ................................................... 16
Using the Controller as a Point Extension Device ..................................................... 16
Point Database .............................................................................................................. 18
Overview ........................................................................................................................ 18
Troubleshooting ............................................................................................................ 28
Basic Service Information .......................................................................................... 28
Preventive Maintenance ............................................................................................ 28
Safety Features .......................................................................................................... 29
Controller LEDs.......................................................................................................... 29
Glossary ......................................................................................................................... 30
Overview .................................................................................................................... 30
Index ............................................................................................................................... 34
II Siemens Building Technologies, Inc.
How to Use This Manual
This manual is written for the owner and user of the Siemens Building Technologies, Inc.
Heat Pump Controller—Multi-Stage, often referred to as controller for the remainder of this manual. This manual is designed to help you become familiar with the controller and its
applications.
This chapter covers manual organization, manual symbols and conventions used in the manual, and how to access help.
Manual Organization
This manual contains the following chapters:
Chapter 1 Product Overview, describes the hardware components and accessories
used with the controller.
Chapter 2 Applications, describes the control applications available in the controller.
Chapter 3 Point Database, defines the point database descriptors and includes
addresses and applications.
Chapter 4 Troubleshooting, describes basic corrective measures to take should you
encounter a problem when using this controller. For issues not covered in this chapter, contact your local Siemens Building Technologies representative.
A Glossary describes the terms and acronyms used in this manual.
An Index is provided to assist you in finding information.
Manual Conventions
The following table lists conventions used in this manual.
Convention Example
Actions that you should perform are specified in boldface font.
Error and system messages are displayed in Courier New font.
Type F for Field panels. Click OK to save changes and close the dialog box.
The message Report Definition successfully renamed
appears in the status bar.
New terms appearing for the first time are italicized.
Siemens Building Technologies, Inc. III
The Open Processor continuously executes a user-defined set of
instructions called the control program.
Siemens BACnet Heat Pump Controller - Multi-Stage Owner’s Manual
Manual Symbols
The following table lists symbols that are used to draw your attention to important information.
Notation Symbol Meaning
CAUTION:
WARNING:
Getting Help
For more information about the Siemens BACnet Heat Pump Controller—Multi-Stage, contact your local Siemens Building Technologies representative.
Indicates that equipment damage or loss of data may occur if the user does not follow a procedure as specified.
Indicates that personal injury or loss of life may occur to the user if a procedure is not performed as specified.
IV Siemens Building Technologies, Inc.
1
Product Overview
Introduction
The Siemens BACnet Heat Pump Controller—Multi-Stage is used in multiple compressor heat pump applications. lt provides Direct Digital Control (DDC) for two heat pump applications. The controller can operate as an independent, stand-alone DDC room controller or it can be networked with a field panel.
The controller provides all termination, input/output, system, and local communication connections (Figure 1). The controller hardware consists of the controller with cover and mounting bracket.
Table 1. Siemens BACnet Heat Pump Controller – Multi-Stage Applications.
Application
Number
2583 Multiple Compressor with Reversing Valve and Mixed Air Control
2584 Multiple Heating and Cooling with Internal Reversing Valve
and Mixed Air Control
2590 Slave Mode
Application Description
Ordering Notes
Siemens BACnet Heat Pump Controller – Multi-Stage 550-490
Siemens Building Technologies, Inc. 1
Siemens BACnet Heat Pump Controller - Multi-Stage Owner’s Manual
COVER
DO 2
DO 1
DO 3
DO 4
DO 5
24 V-AC
C H GND
RX
TX
BST
FLN TRUNK
+-
-
+
NO C
NO C
NO C
NO C
NO C
DO 7
DO 6
NO C
NO C
0
NO C
AI 3
AI 4 + -
+ -
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 161 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4
+ -
1 2 1 2 3 4 5 6 7 8 9 101 2 3 4 5 6 7 8 9 1 11 12 13 14 15 16
AO 3AO 2AO 1DI 6DI 2AI 5DO 8 + -+ -+ -
RTS
CONTROLLER
BOARD
MOUNTING
HOLE
(2)
MOUNTING
RAIL
POWER TRUNK
TERMINATIONS
TEC04XXR1
FLN TRUNK
TERMINATIONS
RECEIVE LED, TRANSMIT LED, AND BST LED
Hardware Inputs
Analog
Mixed air temperature sensor (optional)
Room Temperature Sensor (RTS)
Room temperature setpoint dial (optional)
Digital
Heat pump alarm (optional)
DO LEDS
INPUT / OUTPUT TERMINATIONS
Figure 1. Siemens BACnet Heat Pump ControlIer—Multi-Stage.
ROOM TEMPERATURE
SENSOR / HMI PORT
Night mode override (optional)
Wall switch (optional)
Hardware Outputs
Analog
Damper actuator (spring return) (optional)
2 Siemens Building Technologies, Inc.
Product Overview
Digital
Power Wiring
Compressor 1
Compressor 2 (optional); or stage 3 electric heat (optional)
Compressor 3 (optional); or stage 2 electric heat (optional)
Stage 1 electric heat (optional)
Reversing valve
Damper actuator (floating control) (optional)
Fan
Stage 1 cooling compressor (optional)
Stage 2 cooling compressor (optional)
Stage 1 heating compressor (optional)
Stage 2 heating compressor (optional)
Application
2583
2583
2583
2583, 2584
2583
2583, 2584
2583, 2584
2584
2584
2584
2584
The controller is powered by 24 Vac. Power wiring connects to terminals on the controller labeled “C” (Common) and “H” (Hot). An earth ground termination is also present. See Figure
3.
Communication Wiring
The controller connects to the field panel by means of a Field Level Network (FLN) trunk. See Figure 4.
POWER TRUNK
C H EGRND WHEN THIRD TER-
MINA TION IS PRESENT
24 V COMMON
24 V HOT
TEC0471R2
Figure 3. Power Wiring. Figure 4. Communication Wiring.
E GRND
3-WIRE FLN TRUNK
TWISTED PAIR
SHIELD
TEC0528R1
WIRENUT
REFERENCE (EQUIPOTENTIAL)
GROUNDED AT SINGLE LOCATION
TYPICALLY AT FIELD PANEL
REFERENCE CONNECTION ABSENT
IF 2-WIRE CABLE MUST BE USED
REFERENCE
IS NOT SHIELD
Siemens Building Technologies, Inc. 3
Siemens BACnet Heat Pump Controller - Multi-Stage Owner’s Manual
Controller LED Indicators
The controller has several Light Emitting Diode (LED) indicators. (Figure 1). Table 2 lists the LED types and what they indicate.
Table 2. Controller LEDs.
LED Type Label
(if present)*
DO LED 1–LED 8 Indicates the ON/OFF status of the DO associated with it. A
Receive RX Indicates , when flashing, that the controller is receiving
Transmit TX Indicates, when flashing, that the controller is transmitting
Basic Sanity
Test
* Some LED labels may be hidden by the controller cover.
BST Indicates, when flashing ON and OFF once per second, that
Temperature Sensors
An electronic Room Temperature Sensor (RTS) or an optional auxiliary temperature sensor may be used with the Siemens BACnet Heat Pump Controller—Multi-Stage.
Room Temperature Sensor
The controller room temperature sensor connects to the controller by means of a cable preterminated at both ends with a 6-conductor RJ-11 plug-in connector. See Figure 1 for the location of the RTS/Human-Machine lnterface (HMl) port.
Indication
glowing LED indicates that the DO is energized.
information from the field panel.
information to the field panel.
the controller is functioning properly.
Mixed Air Temperature Sensor
The mixed air temperature sensor is a 10K Ω thermistor that connects to the controller at Al
5.
For more information about Siemens temperature sensors, contact your local Siemens Building Technologies representative.
Actuators
The actuator used with the Siemens BACnet Heat Pump Controller—Multi-Stage may be an optional floating control or 0 to 10V spring return electronic damper motor that is powered through the controller to position an outside air damper.
For more information about Siemens actuators, contact your local Siemens Building Technologies representative.
4 Siemens Building Technologies, Inc.
Related Equipment
Relay Module
Damper Actuator(s)
Mixed Air Temperature Sensor (optional)
Room Temperature Sensor
Contact your local Siemens Building Technologies, Inc. representative for product numbers and more information.
Product Overview
Siemens Building Technologies, Inc. 5
Siemens BACnet Heat Pump Controller - Multi-Stage Owner’s Manual
6 Siemens Building Technologies, Inc.
2
Applications
Basic Operation
The Siemens BACnet Heat Pump Controller—Multi-Stage provides Direct Digital Control (DDC) technology for multiple compressor heat pump applications. Temperature control varies with the application. If present, mixed air temperature control and up to three stages of electric heat or staged heating and cooling can be provided.
Control Temperature Setpoints
The controller maintains a specified temperature setpoint based on Day/Night mode, the heating/cooling mode, and the setpoint dial (if used).
Day/Night Mode
The controller maintains the specified day setpoint temperature during daytime hours and the specified night setpoint at night.
Night Mode Override Switch
If the RTS has an override switch, it can be used to command the controller into day mode for an adjustable period of time. This only affects a controller in night mode.
Control Loops
Heating Loop – maintains room temperature setpoint by turning compressors and electric
heat stages on and off.
Cooling Loop – maintains room temperature setpoint by turning compressors on and off and
using free cooling (mixed air control) when available.
Mixed Air Control Loop
The heat pump is controlled by three Proportional, Integral, and Derivative (PID) control loops; a cooling loop and a heating loop. This section describes the mixed air control loop.
Siemens Building Technologies, Inc. 7
Siemens BACnet Heat Pump Controller - Multi-Stage Owner’s Manual
The mixed air loop controls only the mixed air portion of the application.
The mixed air damper motor can be either a spring return or floating control damper motor.
For a spring return damper, the mixed air loop will control the damper through its 0 to 10 volt analog output and the digital outputs will be spare.
For a floating control damper the mixed air loop will control the damper through DO 1 and DO 2, and the analog output will be a spare.
CAUTION:
This application does not have built in low temperature detection for the mixed air dampers. The low temperature detection is handled differently depending on what type of damper is used (spring return or floating control).
Stand-alone low temperature detection is not possible with floating control dampers. A program can be written in the field panel to close the damper when a low temperature situation occurs. Contact your local Siemens Building Technologies representative for more information.
Day Mode – When heating is required and the fan is on, the damper is set to minimum
position. If the fan is off, the damper is closed.
When cooling is required the damper will be modulated by the mixed air temperature control loop. Damper position will not be set below minimum position to make sure that the ventilation requirements are being met.
Night Mode – The damper is closed (0%) during night mode when cooling is not required
and/or mixed air control is not used at night.
Mixed Air Control - When cooling is required the damper will be modulated by the mixed air
temperature control loop.
If the cooling loop is between the limits for free cooling and all other conditions have been met for enabling the mixed air loop, control depends on the following:
NOTE: This can happen in day or night mode.
Calibration
If the cooling loop was previously higher than free cooling, the mixed air loop will remain enabled.
If the cooling loop was previously lower than free cooling, the mixed air loop will remain disabled.
Floating Control Damper – The damper is briefly commanded closed to get an accurate
damper position during calibration.
8 Siemens Building Technologies, Inc.
Heating and Cooling Switchover
The heating/cooling switchover determines whether the controller is in heating or cooling mode by monitoring the room temperature and the demand for heating and cooling (as determined by the temperature control loops).
Electric Reheat
CAUTION:
Verify that the equipment is supplied with safeties by others to ensure that there is airflow across the heating coils when they are to be energized.
The heating loop controls up to three stages of electric reheat (Application 2583) or one stage (Application 2584) to warm up the room. The electric reheat is cycled on and off based on heating demand that is determined by the room temperature heating loop. When the controller is in cooling mode, the electric heat is OFF at all times.
Applications
Compressor Operation
When in cooling mode, the output of the cooling loop controls the staging of the compressors and enabling/disabling the mixed air control (used as a source of cooling when the outside air temperature is cool enough.
When in heating mode, the output of the heating loop controls the staging of the compressors or electric heat.
NOTE: Application 2583 only. When cooling or heating mode is opposite the reversing
valve control, the compressors are turned off.
Fan Operation
Day Mode – The fan can be set to run all the time or the same as night mode.
Night Mode – The fan is controlled as follows:
The fan will turn ON when at least one of the following two conditions has been met:
Free cooling is provided by the mixed air control loop.
At least one compressor or stage of electric heat is ON.
The fan will turn OFF only after the following two conditions have been met:
Free cooling is not provided by the mixed air control loop.
All compressors and stages of electric heat have been OFF for at least 30 seconds.
Siemens Building Technologies, Inc. 9
Siemens BACnet Heat Pump Controller - Multi-Stage Owner’s Manual
Power Failure Recovery
Upon return from a power failure, the heating and cooling compressors are kept off, the electric heat (if used) is kept off and the fan is kept off. In addition to the equipment being OFF, both cooling and heating loops are set to 0. This situation will remain in effect until the power failure recovery period for this controller is over.
The controller returns to normal control when its power failure recovery period is over. The power failure recovery time for a heat pump is based on the following formula:
RETURN DELAY + (CTLR ADDRESS × 10 seconds)
This lessens the demand of having all the electrical equipment starting at once.
Centralized Alarm Monitoring
DI 6 can be used to monitor an input that changes state when the heat pump is in alarm.
DI 6 can be unbundled to send alarm information to the field panel for centralized alarm monitoring.
Overriding DOs
Heat Pump applications allow spare DOs, damper (DO1 and DO2) and electric heat stages (DO3, DO6 and DO7 when applicable) to be commanded.
Physical points DO1 and DO2 can never be overridden when configured for motor control. However, the position of the attached motor is always commandable via the DMPR COMD point.
To prevent damage to the mechanical equipment, the fan, reversing valve, and compressor(s) DOs cannot be directly commanded ON or OFF unless the point HP DO OVRD is set to ENABLE. When HP DO OVRD is set to DISABL (default), commands to the fan, reversing valve and compressor DO points are ignored regardless of BACnet command priority.
CAUTION:
HP DO OVRD should be set to ENABLE only when there is a complete understanding of the consequences. Since the direct control will override the application minimum on/off time safeties, improper use of DO commands can cause permanent equipment damage. Also, during normal daily operation the override of critical DOs should only be done via a BACnet command.
Fail-safe Operation
If the RTS or the setpoint dial fails, the controller operates using the last known temperature value.
10 Siemens Building Technologies, Inc.
Using Auxiliary Points
lt is possible to have extra points available on a Heat Pump Controller—Multi-Stage in addition to the ones used by the current application that is running in the controller. If these extra points will be controlled by a field panel, they must be unbundled at the field panel.
Applications
Siemens Building Technologies, Inc. 11
Siemens BACnet Heat Pump Controller - Multi-Stage Owner’s Manual
Application 2583: Multiple Compressor Heat Pump with Reversing Valve Control and Mixed Air Control
In Application 2583 (Figure 5), the controller controls a multi-stage heat pump with a reversing valve controlled by the heat pump controller. In addition to compressors, this heat pump may also be equipped with electric heat for auxiliary heat and mixed air control for free cooling. The mixed air control can use either a spring return or a floating control damper motor.
Compressor Staging
Three compressors or electric heat stages are available for use. Each compressor has a time delay (at least 30 seconds) to lessen the demand of having more than one compressor stage start at once.
Reversing Valve Operation
The reversing valve determines the operation of the heat pump's compressors (heating or cooling) depending on the demand.
Application Notes
1. If the heat pump cycles excessively, temperature swings in the room are excessive, or there is trouble maintaining the setpoint, the cooling loop, the heating loop, or both need to be tuned. Contact your local Siemens Building Technologies representative for more information.
2. The Heat Pump Controller—Multi-Stage, as shipped from the factory, keeps all associated equipment OFF. The controller and its equipment are released to application control at start-up.
3. Running the mixed air loop during night mode can increase energy savings by taking advantage of free cooling at night to pre-cool the building for day mode, and, thereby, reduce the need for mechanical cooling during day mode. This method for pre-cooling the building can also improve indoor air quality because it is accomplished with fresh air.
A field panel program can be written to pre-cool the building with this application. Contact your local Siemens Building Technologies representative for more information.
12 Siemens Building Technologies, Inc.
4. In this application, the maximum configurations are as follows:
The maximum of CMP TOTL = 3.
The maximum of EHTG STG CNT = 3.
The maximum of CMP TOTL plus EHTG STG CNT = 4.
If these limits are exceeded, CMP TOTL will be set to 0 and EHTG STG CNT will be set to 0. These points will remain at 0 until they are set correctly. This prevents the application from trying to use the same DO as both a compressor and a stage of electric heat.
COMPRESSOR 1
REVERSING
VALVE
WATER
SOURCE
* THE O.A. AND R.A. DAMPERS MUST BE MECHANICALLY LINKED.
TEC2573CDR1
COIL
COMPRESSOR 2
REVERSING
VALVE
COIL
COMPRESSOR 2; OR 3RD STAGE ELECTRIC HEAT (OPTIONAL) COMPRESSOR 3; OR 2ND STAGE ELECTRIC HEAT (OPTIONAL)
SPARE AI (10K THERMISTOR) OR SPARE DI (DRY CONTACT)
MIXED AIR TEMPERATURE SENSOR 10K THERMISTOR (OPTIONAL)
ON BOARD, AO1 IS GROUPED PYSICALLY WITH AO2 AND AO3
*
COMPRESSOR 3
REVERSING
VALVE
COIL
1ST STAGE ELECTRIC HEAT (OPTIONAL)
SPARE AI (0-10V or 4-20mA) OR SPARE DI (DRY CONTACT)
N.O.
WALL
SWITCH
(OPTIONAL)
HEAT PUMP ALARM (OPTIONAL)
SUPPLY AIR
ELECTRIC
HEAT
(OPTIONAL)
HEATING /
COOLING
COIL COIL COIL
REVERSING VALVE
COMPRESSOR 1
FAN
FAN
N.O.
MIXED AIR
TEMPERATURE
SENSOR
(OPTIONAL)
RTS
Applications
O.A. N.C.
O.A.
DAMPER*
(OPTIONAL)
R.A.
R.A.
DAMPER*
(OPTIONAL)
24 V-AC FLN TRUNK AO1 (0-10V) DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8 DI3/AI3 DI4/AI4 DI5/AI5 DI2 DI6 AO2 (0-10V) AO3 (0-10V) RTS
CONTROLLER -
MULTI-STAGE
*
HEAT PUMP
Figure 5. Application 2583 Control Drawing.
Siemens Building Technologies, Inc. 13
Siemens BACnet Heat Pump Controller - Multi-Stage Owner’s Manual
Application 2584: Multiple Heating and Cooling Heat Pump with Mixed Air and Internal Reversing Valve Control
ln Application 2584, (Figure 6) the controller controls one or two heating compressors for heating and one or two cooling compressors for cooling. The reversing valve is controlled internally by the heat pump. ln addition to compressors, this heat pump may also be equipped with electric heat for auxiliary heat and mixed air control for free cooling. This application also controls small air handling units with two position heating and cooling control. The mixed air control can use either a spring return or a floating control damper motor.
Compressor/Electric Heat Staging
This application can support up to two cooling compressors and up to two heating compressors. Each compressor heat has a time delay (at least 30 seconds) to lessen the demand of having more than one compressor start at once.
Application Notes
1. lf the heat pump cycles excessively, temperature swings in the room are excessive, or there is trouble maintaining the setpoint, the cooling loop, the heating loop or both need to be tuned. Contact your local Siemens Building Technologies representative for more information.
2. The Heat Pump Controller—Multi-Stage, as shipped from the factory, keeps all associated equipment OFF. The controller and its equipment are released to application control at start-up.
3. Running the mixed air loop during night mode can increase energy savings by taking advantage of free cooling at night to pre-cool the building for day mode, and thereby, reduce the need for mechanical cooling during day mode. This method for pre-cooling the building can also improve indoor air quality because it is accomplished with fresh air.
A field panel program can be written to pre-cool the building with this application. Contact your local Siemens Building Technologies representative for more information.
4. ln this application the maximum configurations are as follows:
The maximum of HTG CMP TOTL (Point 75) = 2.
The maximum of CLG CMP TOTL (Point 77) = 2.
The maximum of EHTG STG CNT (Point 76) = 1.
lf these limits are exceeded, HTG CMP TOTL, CLG CMP TOTL, and EHTG STG CNT will all be set to 0. These points will remain at 0 until they are set correctly. This prevents the application from trying to control equipment that it does not have.
14 Siemens Building Technologies, Inc.
SUPPLY AIR
Applications
COMPRESSOR 1
REVERSING
VALVE*
WATER
SOURCE
* CONTROLLED INTERNALLY BY THE HEAT PUMP
** THE O.A. AND R.A. DAMPERS MUST BE MECHANICALLY LINKED.
TEC2574CDR1
COIL
MIXED AIR TEMPERATURE SENSOR 10K THERMISTOR (OPTIONAL)
ON BOARD, AO1 IS GROUPED PYSICALLY WITH AO2 AND AO3
*
COMPRESSOR 2
SPARE AI (0-10V or 4-20mA) OR SPARE DI (DRY CONTACT)
SPARE AI (10K THERMISTOR) OR SPARE DI (DRY CONTACT)
REVERSING
VALVE*
COIL
N.O.
WALL
SWITCH
(OPTIONAL)
ELECTRIC
HEAT
(OPTIONAL)
HEATING /
COOLING
COIL COIL
FAN
TEMPERATURE
ELECTRIC HEAT (OPTIONAL)
1ST HEATING COMPRESSOR 2ND HEATING COMPRESSOR 1ST COOLING COMPRESSOR
2ND COOLING COMPRESSOR
HEAT PUMP ALARM (OPTIONAL)
FAN
MIXED AIR
SENSOR
(OPTIONAL)
RTS
DAMPER**
(OPTIONAL)
N.O.
DAMPER**
(OPTIONAL)
24 V-AC
FLN TRUNK AO1 (0-10V) DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8 DI3/AI3 DI4/AI4 DI5/AI5 DI2 DI6 AO2 (0-10V) AO3 (0-10V) RTS
HEAT PUMP
CONTROLLER -
MULTI-STAGE
O.A. N.C.
O.A.
R.A.
R.A.
*
Figure 6. AppIication 2584 Control Drawing.
Siemens Building Technologies, Inc. 15
Siemens BACnet Heat Pump Controller - Multi-Stage Owner’s Manual
Application 2590: BACnet Heat Pump Slave Mode
Application 2590 is the default slave mode application that comes up when power is first applied to the controller. Slave mode provides no control. lts purpose is to allow the operator to perform equipment checkout before a control application is put into effect and to set some basic controller parameters (CTLR ADDRESS, APPLlCATlON, etc.).
Using the Controller as a Point Extension Device
lf the controller is used only as a point extension device with no control application in effect, the application must be set to slave mode and the points must be unbundled at the field panel. All of these points must be controlled from the field panel in order to be used.
16 Siemens Building Technologies, Inc.
Applications
Siemens Building Technologies, Inc. 17
3
Point Database
Overview
This chapter presents a description of the Siemens BACnet Heat Pump Controller—Multi­Stage point database including point descriptors, point addresses, and a listing of applications in which each point is found.
Description Address Application Description
CTLR ADDRESS 01 2583, 2584, 2590 ldentifies the controller on the FLN trunk.
APPLICATION 02 2583, 2584, 2590 Identification number of the program running in the
controller.
Valid input: 2583, 2584, 2590
RETURN DELAY 03 2583, 2584 Amount of time the heat pump will remain off after a return
from power failure.
ROOM TEMP {04} 2583, 2584, 2590 Actual reading from the room temperature sensor.
HEAT.COOL {05} 2583, 2584 Current mode of operation for applications that can be either
a heating mode or a cooling mode.
DAY CLG STPT 06 2583, 2584 Temperature setpoint in degrees that the controller
maintains during day periods in cooling mode if a room temperature sensor setpoint dial is not present or is not
used. See STPT DIAL. Valid entry range: 48° to 95°F (9°to 35°C)
DAY HTG STPT 07 2583, 2584 Temperature setpoint in degrees that the controller
maintains during day periods in heating mode if a room temperature sensor setpoint dial is not present or is not
used. See STPT DIAL. Valid entry range: 48° to 95°F (9° to 35°C)
NGT CLG STPT 08 2583, 2584 Temperature setpoint in degrees that the controller
maintains during night periods in cooling mode.
Valid entry range: 48° to 95°F (9° to 35°C)
NGT HTG STPT 09 2583, 2584 Temperature setpoint in degrees that the controller
maintains during night periods in heating mode.
Valid entry range: 48° to 95°F (9° to 35°C)
DMPR MlN POS 10 2583, 2584 Minimum position the damper will be commanded to during
day mode.
Siemens Building Technologies, Inc. 18
Point Database
Description Address Application Description
RM STPT MlN 11 2583, 2584 Minimum temperature setpoint in degrees that the controller
can use from the setpoint dial. This overrides any temperature setpoint from the setpoint dial that falls below this minimum.
Valid entry range: 48° to 95°F (9° to 35°C)
RM STPT MAX 12 2583, 2584 Maximum temperature setpoint in degrees that the controller
can use from the setpoint dial. This overrides any temperature setpoint from the setpoint dial that raises above this maximum.
Valid entry range: 48° to 95°F (9° to 35°C)
RM STPT DIAL {13} 2583, 2584, 2590 Temperature setpoint in degrees from the room temperature
sensor (not available on all temperature sensor models). This setpoint will be used for control in day mode (heating or cooling) when enabled by STPT DIAL (Point 14).
Valid entry range: 48° to 95°F (9° to 35°C)
STPT DIAL 14 2583, 2584 YES indicates that there is a room setpoint dial on the room
temperature sensor and must be used as the temperature setpoint for control in day/occupied mode. NO indicates that the appropriate preset setpoint will be used as the temperature setpoint for control in day/occupied heating or cooling mode.
Valid input: YES or NO
AUX TEMP {15} 2590 Actual reading from a 10K thermistor connected to the
controller's AI 5 input. When a thermistor is connected at
Al 5, DI 5 is not available. See DI 5. The physical input can
not be used for both analog and digital input at the same time.
MA TEMP {15} 2583, 2584 Actual reading from a 10K thermistor connected to the
controller's Al 5 input. When a thermistor is connected at
Al 5, DI 5 is not available. See DI 5. The physical input can
not be used for both analog and digital input at the same time.
CMP2 ON 16 2583 Value, in percent, that the active temperature control loop
output must exceed for compressor 2 to turn ON. Actual turn on is subject to the CMP2 MlN OFF time being expired.
HTG CMP2 ON 16 2584 Value, in percent, that the heating control loop output must
exceed for compressor 2 to turn ON. Actual turn on is subject to the CMP2 MlN OFF time being expired.
CMP2 OFF 17 2583 Value, in percent, that the active temperature control loop
output must go below for compressor 2 to turn OFF. Actual turn off is subject to the CMP2 MlN ON time being expired.
HTG CMP2 OFF 17 2584 Value, in percent, that the heating control loop output must
go below for compressor 2 to turn OFF. Actual turn off is subject to the CMP2 MlN ON time being expired.
WALL SWITCH 18 2583, 2584, 2590 YES indicates that the controller is to monitor the status of a
wall switch that is connected to Dl 2. NO indicates that the controller will not monitor the status of a wall switch, even if one is connected.
Valid input: YES or NO
Siemens Building Technologies, Inc. 19
Siemens BACnet Heat Pump Controller - Multi-Stage Owner’s Manual
Description Address Application Description
Dl OVRD SW {19} 2583, 2584, 2590 Actual indication of the status of the override switch (not
physically available on all temperature sensor models) at the room temperature sensor. ON indicates that the switch is being pressed. OFF indicates that the switch is released.
Valid input: ON or OFF
OVRD TIME 20 2583, 2584 Amount of time in hours that the controller will operate in
day/occupied mode when the override switch is pressed while the controller is in night/ unoccupied mode.
NGT OVRD {21} 2583, 2584 Indicates the mode that the controller is operating in with
respect to the override switch. NIGHT indicates that the switch has not been pressed and the override timer is not active. DAY indicates that the switch has been pressed and the override timer is active. The controller then uses a day mode temperature setpoint. This point is only in effect when DAY.NGT indicates night mode.
RMTMP OFFSET 22 All
FREE CLG {23} 2583, 2584 Point commanded by the field panel PPCL to enable or
DI 2 {24} 2583, 2584, 2590 Actual status of a contact connected to the controller at Dl 2.
DI 5 {25} 2583, 2584, 2590 Actual status of a contact connected to the controller at
DI 6 {26} 2583, 2584, 2590 Actual status of a contact connected to the controller. ON
CMP2 MlN OFF 27 2583 Minimum time, in minutes, that compressor 2 will remain
HTG2 MlN OFF 27 2584 Minimum time, in minutes, that heating compressor 2 will
Compensates for deviations between the value of ROOM TEMP and the actual room temperature. This corrected value is displayed in CTL TEMP. RMTMP OFFSET + ROOM TEMP = CTL TEMP
disable mixed air control (free cooling).
ON indicates that the contact is closed; OFF indicates that the contact is open. If a wall switch is used, it is connected
to DI 2. See WALL SWITCH.
Al 5/Dl 5. ON indicates that the contact is closed; OFF indicates that the contact is open. When a contact is connected at Dl 5, Al 5 is not available. See Point number
15. The physical input can not be used for both analog and
digital input at the same time.
indicates that the contact is closed; OFF indicates that the contact is open. Application 2583/2584: DI 6 can be used to monitor an input that changes state when the heat pump is in alarm. DI 6 can be unbundled to send alarm information to the field panel for centralized alarm monitoring.
OFF before turning ON.
remain OFF before turning ON.
CMP2 MlN ON 28 2583 Minimum time, in minutes, that compressor 2 will remain ON
before turning OFF.
HTG2 MlN ON 28 2584 Minimum time, in minutes, that heating compressor 2 will
remain ON before turning OFF.
20 Siemens Building Technologies, Inc.
Point Database
Description Address Application Description
DAY.NGT {29} 2583, 2584, 2590 Indicates the mode in which the controller is operating.
Day temperature setpoints are used in day mode. Night temperature setpoints are used in night mode. This point is normally set by the field panel.
CLG CMP1 ON 30 2584 Value, in percent, that the cooling temperature control loop
output must exceed for cooling compressor 1 to turn ON. Actual turn on is subject to the CLG1 MlN OFF time being expired.
CLG CMP1 OFF 31 2584 Value, in percent, that the cooling temperature control loop
output must go below for cooling compressor 1 to turn OFF. Actual turn off is subject to the CLG1 MlN ON time being expired.
CLG1 MlN OFF 32 2584 Minimum time, in minutes, that cooling compressor 1 will
remain OFF before turning ON.
CLG1 MlN ON 33 2584 Minimum time, in minutes, that cooling compressor 1 will
remain ON before turning OFF.
CLG CMP2 ON 34 2584 Value, in percent, that the cooling temperature control loop
output must exceed for cooling compressor 2 to turn ON. Actual turn on is subject to the CLG 2 MIN OFF time being expired.
CMP3 ON 34 2583 Value, in percent, that the active temperature control loop
output must exceed for compressor 3 to turn ON. Actual turn on is subject to the CMP3 MlN OFF time being expired.
CLG CMP2 OFF 35 2584 Value, in percent, that the cooling temperature control loop
output must exceed for cooling compressor 2 to turn OFF. Actual turn off is subject to the CLG2 MIN ON time being expired.
CMP3 OFF 35 2583 Value, in percent, that the active temperature control loop
output must go below for compressor 3 to turn OFF. Actual turn off is subject to the CMP3 MlN ON time being expired.
CLG2 MIN OFF 36 2584 Minimum time, in minutes, that cooling compressor 2 will
remain OFF before turning ON.
CMP3 MlN OFF 36 2583 Minimum time, in minutes, that compressor 3 will remain
OFF before turning ON.
CLG2 MlN ON 37 2584 Minimum time, in minutes, that cooling compressor 2 will
remain ON before turning OFF.
CMP3 MlN ON 37 2583 Minimum time, in minutes, that compressor 3 will remain ON
before turning OFF.
DAMPER TYPE 38 2583, 2584 FLOAT indicates that a floating control damper is used.
SPRING indicates that a spring return damper is used.
Valid input: FLOAT or SPRING.
AO DIR.REV 39 2583, 2584 Configuration setup code for AO. Allows the AO to be direct
(normally closed) or reverse acting (normally open).
AOV1 {40} 2583, 2584, 2590 Analog output 1 controls a 0 to 10V signal.
Siemens Building Technologies, Inc. 21
Siemens BACnet Heat Pump Controller - Multi-Stage Owner’s Manual
Description Address Application Description
DO 1 {41} 2583, 2584, 2590 Digital output 1 controls a 24 Vac load with an ON or OFF
status. If Motor 1 is enabled, DO 1 is coupled with DO 2 to control an actuator.
DO 2 {42} 2583, 2584, 2590 Digital output 2 controls a 24 Vac load with an ON or OFF
status. lf Motor 1 is enabled, DO 2 is coupled with DO 1 to control an actuator.
DO 3 {43} 2590 Digital output 3 controls a 24 Vac load with an ON or OFF
status. lf Motor 2 is enabled, DO 3 is coupled with DO 4 to control an actuator.
ELEC HEAT {43} 2584 This output controls the contact for the first stage of electric
heat and has a status of ON or OFF.
ELEC HEAT 1 {43} 2583 This output controls the contact for the first stage of electric
heat and has a status of ON or OFF.
DO 4 {44} 2590 Digital output 4 controls a 24 Vac load with an ON or OFF
status. lf Motor 2 is enabled, DO 4 is coupled with DO 3 to control an actuator.
HTG CMP 1 {44} 2584 Digital output used to control the heating compressor 1.
REV VALVE {44} 2583 Digital output used to control the reversing valve.
COOL and HEAT status is indicated for the 24 Vac valve or relay. The default configuration is energized for HEAT. The configuration may be reversed in DO DIR.REV.
DO 5 {45} 2590 Digital output 5 controls a 24 Vac load with an ON or OFF
status. lf Motor 3 is enabled, DO 5 is coupled with DO 6 to control an actuator.
COMPRESSOR 1 {45} 2583 Digital output used to control the compressor. ON or OFF
status is indicated for the 24 Vac relay.
HTG CMP 2 {45} 2584 Digital output used to control heating compressor 2. ON or
OFF status is indicated for the 24 Vac relay.
CLG CMP 1 {46} 2584 Digital output used to control cooling compressor 1.
DO 6 {46} 2590 Digital output 6 controls a 24 Vac load with an ON or OFF
status. lf Motor 3 is enabled, DO 6 is coupled with DO 5 to control an actuator.
EHEAT3.CMP2 {46} 2583 Digital output used to control either compressor 2 or the
third stage of electric heat.
CLG CMP 2 {47} 2584 Digital output used to control cooling compressor 2.
DO 7 {47} 2590 Digital output 7 controls a 24 Vac load with an ON or OFF
status.
EHEAT2.CMP3 {47} 2583 Digital output used to control either compressor 3 or 2nd
stage of electric heat.
DMPR COMD {48} 2583, 2584 Value to which the damper motor is commanded in percent
of full travel.
MTR1 COMD {48} 2590 Value to which the Motor 1 actuator is commanded in
percent of full travel.
22 Siemens Building Technologies, Inc.
Point Database
Description Address Application Description
DMPR POS {49} 2583, 2584 Current position of the damper motor in percent of full travel.
This value is calculated based on motor run time.
MTR1 POS {49} 2590 Current position of the damper motor in percent of full travel.
This value is calculated based on motor run time. See
MTR1 TIMING.
DO 8 {50} 2590 Digital output 8 controls a 24 Vac load with an ON or OFF
status.
FAN {50} 2583, 2584 Digital output used to control the fan. ON indicates the DO is
energized; OFF indicates the DO is de-energized.
MTR TIMING 51 2583, 2584 Time required for the damper actuator to travel from full
closed to the full open position.
MTR1 TIMING 51 2590 Time required for the Motor 1 actuator to travel from full
closed to the full open position.
AI 3 {52} 2583, 2584, 2590 Spare analog input, switch selectable to be 0-10V or 4-
20mA (consult your Siemens Building Technologies
representative). Or, spare DI dry contact, see DI 3. The
physical input can not be used for both analog and digital input at the same time.
AI 4 {53} 2583, 2584, 2590 Spare anolog input, 10K thermistor. Or, spare DI dry
contact, see DI 4. The physical input can not be used for
both analog and digital input at the same time.
AOV 2 {54} 2583, 2584, 2590 Analog output 2 controls a 0 to 10V signal.
DI 3 {55} 2583, 2584, 2590 Actual status of a contact connected to the controller at
Dl 3. ON indicates that the contact is closed; OFF indicates that the contact is open. When a contact is connected at Dl
3, Al 3 is not available. See AI 3. The physical input can not
be used for both analog and digital input at the same time.
DMPR ROT ANG 56 2583, 2584 Number of degrees the damper is free to travel.
DPR1 ROT ANG 56 2590 Number of degrees the damper is free to travel.
DI 4 {57} 2583, 2584, 2590 Actual status of a contact connected to the controller at
Dl 4. ON indicates that the contact is closed; OFF indicates that the contact is open. When a contact is connected at Dl
4, Al 4 is not available. See AI 4. The physical input can not
be used for both analog and digital input at the same time.
MTR SETUP 58 2583, 2584, 2590 Configuration setup code for Motors 1 and 2. This enables
the motors individually and sets each motor to be either direct or reverse acting.
NOTE: When a motor is enabled, its associated DOs are
enabled.
DO DIR.REV 59 2583, 2584, 2590 Configuration setup code for DOs. Allows the DOs to be
direct or reverse acting (enabled equals energized or disabled equals de-energized).
Siemens Building Technologies, Inc. 23
Siemens BACnet Heat Pump Controller - Multi-Stage Owner’s Manual
Description Address Application Description
CYCLE FAN 60 2583, 2584 YES indicates that the fan should cycle ON and OFF with
the compressor during day mode. NO indicates that the fan should remain ON constantly in day mode.
Valid input: YES or NO NOTE: In either case, the fan will cycle during night mode.
FREE CLG ON 61 2583, 2584 Value, in percent, that the cooling loopout must exceed for
free cooling to turn ON.
FREE CLG OFF 62 2583, 2584 Value, in percent, that the cooling loopout must exceed for
free cooling to turn OFF.
CLG P GAIN 63 2583, 2584 Proportional gain value for the cooling temperature control
loop.
CLG I GAIN 64 2583, 2584 Integral gain value for the cooling temperature control loop.
STPT SPAN 65 2583, 2584 Used to configure the allowable temperature range when
using the optional Relative Setpoint Adjustment feature.
STAT TYPE 66 2583, 2584 Default = NORMAL. Can be set to OFFSET for optional
Relative Setpoint Adjustment feature when room sensor part number SB1-0916 or SB1-1072 is used.
Valid input: NORMAL or OFFSET
HTG P GAIN 67 2583, 2584 Proportional gain value for the heating temperature control
loop.
HTG I GAIN 68 2583, 2584 Integral gain value for the heating temperature control loop.
HP DO OVRD 69 2583, 2584 For the commanding of critical digital outputs. CAUTION:
IMPROPER USE CAN CAUSE PERMANENT EQUIPMENT DAMAGE.
STPT OFFSET {70} 2583, 2584 For use with optional Relative Setpoint Adjustment feature.
MA P GAIN {71} 2583, 2584 Proportional gain value for the mixed air control loop.
MA I GAIN {72} 2583, 2584 Integral gain value for the mixed air control loop.
MA D GAIN {73} 2583, 2584 Derivative gain value for the mixed air control loop.
MA BIAS {74} 2583, 2584 Biasing of the mixed air control loop.
CMP TOTL 75 2583 Number of compressors used by the application.
Valid values: 0, 1, 2, 3
HTG CMP TOTL 75 2584 Number of heating compressors used by the application.
Valid values: 0, 1, 2
EHTG STG CNT 76 2583, 2584 Number of electric heating stages used by the application.
Valid values: 0, 1, 2, 3
CLG CMP TOTL 77 2584 Number of cooling compressors used by the application.
Valid values: 0, 1, 2
CTL TEMP {78} 2583, 2584, 2590 Temperature used as input for the temperature
control loops. This value will be the same as the value in ROOM TEMP + RMTMP OFFSET unless it is overridden.
CLG LOOPOUT {79} 2583, 2584 Cooling temperature control loop output value in percent.
24 Siemens Building Technologies, Inc.
Point Database
Description Address Application Description
HTG LOOPOUT {80} 2583, 2584 Heating temperature control loop output value in percent.
ELEC HEAT ON 81 2584 Value, in percent, that the heating Ioopout must exceed for
the electric heat to turn ON.
EHEAT 1 ON 81 2583 Value, in percent, that the heating loopout must exceed for
the first stage of electric heat to turn ON.
CMP1 ON 82 2583 Value, in percent, that the active temperature control
loop output must exceed for compressor 1 to turn ON. Actual turn on is subject to the CMP MlN OFF time being expired. lt is also the value, in percent, which HTG LOOPOUT must go below for the electric heat (ELEC HEAT
1) to turn OFF when only one compressor is used.
HTG CMP1 ON 82 2584 Value, in percent, that the heating temperature control loop
output must exceed for heating compressor 1 to turn ON. Actual turn on is subject to the HTG1 MlN OFF time being expired.
CMP1 OFF 83 2583 Value, in percent, that the active temperature control loop
output must go below for compressor 1 to turn OFF. Actual turn off is subject to the CMP1 MlN ON time being expired.
HTG CMP1 OFF 83 2584 Value, in percent, that the heating temperature control loop
output must go below for heating compressor 1 to turn OFF. Actual turn off is subject to the HTG1 MlN ON time being expired.
RVAL SWITCH 84 2583 Value, in percent, that the active temperature control loop
output must go above for the reversing valve to switch. Actual switchover is subject to the status of HEAT.COOL, RVAL SW TIME, and HTG LOOPOUT or CLG LOOPOUT.
SWITCH LIMIT 85 2583, 2584 Active temperature control loop output must be less than
this value to switch between cooling mode and heating mode. Actual switchover depends on SWITCH DBAND being exceeded and is subject to SWITCH TIME being expired.
SWITCH TIME 86 2583, 2584 Time, in minutes, that must expire to switch between cooling
mode and heating mode. Actual switchover depends on the active temperature control loop being below the value of SWITCH LIMIT and exceeding the value of SWITCH DBAND.
CMP1 MlN OFF 87 2583 Minimum time, in minutes, that compressor 1 will remain
OFF before turning ON.
HTG1 MlN OFF 87 2584 Minimum time, in minutes, that heating compressor 1 will
remain OFF before turning ON.
CMP1 MlN ON 88 2583 Minimum time, in minutes, that compressor 1 will remain ON
before turning OFF.
HTG1 MlN ON 88 2584 Minimum time, in minutes, that heating compressor 1 will
remain ON before turning OFF.
RVAL SW TIME 89 2583 Length of time the compressor must be OFF before the
reversing valve can switch modes.
Siemens Building Technologies, Inc. 25
Siemens BACnet Heat Pump Controller - Multi-Stage Owner’s Manual
Description Address Application Description
SWITCH DBAND 90 2583, 2584 Temperature range in degrees that is compared to the
difference between CTL TEMP and CTL STPT. The difference must exceed this value for temperature control mode to change over. Changeover is also subject to the active temperature control loop output being below SWITCH LIMIT and SWITCH TIME being expired.
NGT MA CTL {91} 2583, 2584 YES indicates that mixed air control should occur during
night mode. NO indicates that mixed air control will not occur during night mode.
Valid input: YES or NO.
CTL STPT {92} 2583, 2584 Actual setpoint value being used as input for the active
temperature control loop.
MA STPT {93} 2583, 2584 Setpoint of the mixed air control loop.
EHEAT 2 ON 94 2583 Value, in percent, that the heating loopout must exceed for
the second stage of electric heat to turn ON.
EHEAT 3 ON 95 2583 Value, in percent, that the heating loopout must exceed for
the third stage of electric heat to turn ON.
CAL TIMER 96 2583, 2584, 2590 Time interval, in hours, between the calibration sequence.
AOV 3 {97} 2583, 2584, 2590 Analog output 3 controls a 0 to 10V signal.
LOOP TIME 98 2583, 2584 Time, in seconds, between control loop calculations.
ERROR STATUS {99} 2583, 2584, 2590 Status code indicating any errors detected during controller
power up. A status of 0 indicates there are no problems.
CLG D GAIN 102 2583, 2584 Derivative gain value for the cooling temperature control
loop.
CLG BIAS 103 2583, 2584 Biasing of the cooling temperature control loop.
See CLG LOOPOUT.
HTG D GAIN 104 2583, 2584 Derivative gain value for the heating temperature control
loop.
HTG BIAS 105 2583, 2584 Biasing of the heating temperature control loop.
See HTG LOOPOUT.
1. Points not listed are not used in this application.
2. Point numbers that appear in brackets { } may be unbundled at the field panel.
26 Siemens Building Technologies, Inc.
Point Database
Siemens Building Technologies, Inc. 27
4
Troubleshooting
This chapter describes corrective measures you can take should you encounter a problem when using a Siemens BACnet Heat Pump Controller—Multi-Stage.
You are not required to do any controller troubleshooting. You may want to contact your local Siemens Building Technologies representative if a problem occurs or you have any questions about the controller.
NOTE: When troubleshooting, record what the problem is and what actions were
performed immediately before the problem occurred. Being able to describe the problem in detail is important, should you need assistance from your local Siemens Building Technologies representative.
Basic Service Information
Always remove power to the controller when installing or replacing it. Since the controller does not have a power switch, the recommended method of removing power to a locally powered controller is to turn OFF the power to the 24 Vac transformer. The recommended method of removing power to a controller on a power cable (even to service a single controller) is to turn OFF the power at the transformer.
NOTE: When removing power to a controller to perform maintenance or service, make
sure that the person in charge of the facility is aware of this and that appropriate steps are taken to keep the building in control.
Never remove the cover from the controller. There are no serviceable parts inside. If a problem is found with a controller, contact your local Siemens Building Technologies representative for replacement. An anti-static wrist strap is recommended when installing or replacing controllers.
Preventive Maintenance
Most controller components are designed so that, under normal circumstances, they do not require preventive maintenance. Periodic inspections, voltage checks, and point checks are normally not required. The controller's rugged design makes most preventive maintenance unnecessary. However, devices that are exposed to dusty or dirty environments may require periodic cleaning to function properly.
Siemens Building Technologies, Inc. 28
Safety Features
The controller board stores the controller's address, applications, and point values. In the event of a power failure or a reset, these values are retrieved from the controller's permanent memory and are used by the controller unless overridden by a field panel. If one of the following conditions occurs, the controller will activate safety features present in its fail-safe mode.
Sensor failure.
Loss of power. Upon controller power loss, communication with the controller is also
lost. The controller will appear as failed (
Controller LEDs
To determine if the controller is powered up and working, verify that the Basic Sanity Test (BST) Light Emitting Diode (LED) is flashing ON/OFF once per second. The controller
contains eleven LEDs located on the circuit board. See the Controller LED lndicators section of Chapter 1, Product Overview for more information about LEDs.
Troubleshooting
*F*) at the field panel.
NOTE: The TX and RX LEDs indicate communication over the FLN.
Siemens Building Technologies, Inc. 29
Glossary
Overview
The glossary contains terms and acronyms that are used in this manual. For definitions of
point database descriptors, see Chapter 3, Point Database.
Al
Analog Input. Point that receives a signal that represents a condition which has more than two states. For example, flow rate sensors (water or air), temperature sensors (room or duct), pressure sensors (static or velocity), and humidity sensors (room, duct, or outdoor).
airflow
Rate at which a volume of air moves through a duct. Usually expressed in cubic feet per minute (cfm).
algorithm
Mathematical formula that uses varying inputs to calculate an output value.
AO
Analog Output. Physical point that generates a continuous variable signal.
BACnet
A data communication protocol for Building Automation and Control networks.
centralized control
Type of control offered by a controller that is connected by means of a Field Level Network (FLN).
cfm
Cubic Feet per Minute.
Siemens Building Technologies, Inc. 30
control loop
PID algorithm that is used to control an output based on a setpoint and an input reading from a sensor.
DDC
Direct Digital Control.
DI
Digital Input. Physical input point that receives a two-state signal (ON/OFF, OPEN/CLOSED, YES/NO).
DO
Digital Output. Physical output point that sends a two-state signal (ON/OFF, OPEN/CLOSED, YES/NO).
Glossary
English units
The foot-pound-second system of units for weights and measurements.
equipment controller
FLN device that provides additional point capacity to a field panel or provides individual room or mechanical equipment control.
field panel
A device containing a microprocessor for centralized control of system components and equipment controllers.
FLN
Field Level Network. Network consisting of equipment controllers, FLN end devices, fume hoods, etc.
HMI
Human Machine Interface. Terminal and its interface program that allows you to communicate with a field panel or equipment controller.
Siemens Building Technologies, Inc. 31
Siemens BACnet Heat Pump Controller - Multi-Stage Owner’s Manual
lps
Liters per Second.
loopout
The output of the control loop expressed as a percentage.
override switch
Button on a room temperature sensor that an occupant can press to change the status of a room from unoccupied to occupied (or from night to day) for a predetermined time.
pressure independent
Variable Air Volume (VAV) room temperature control system in which the temperature drives an airflow setpoint.
PID
Proportional, Integral, Derivative.
pressure dependent
Variable Air Volume (VAV) room temperature control system in which the temperature directly drives the damper.
RTS
Room Temperature Sensor.
setpoint
Virtual point that stores a point value such as a temperature setting. Points that monitor inputs, such as temperature, report actual values.
SI units
Systeme International d'Unites. The international metric system.
slave mode
Default application that displays when power is first applied to a Terminal Equipment Controller. No control action is initiated in the slave mode.
32 Siemens Building Technologies, Inc.
stand-alone control
Type of control offered by a controller that is providing independent DDC control to a space.
Equipment Controller
Siemens Building Technologies, Inc. product family of equipment controllers (one is the BACnet Heat Pump Controller — Electronic Output) that house the applications software used to control terminal units, such as heat pumps, VAV terminal boxes, fan coil units, unit ventilators, etc.
unbundle
Term used to describe the entering of a point that resides in a controllers database into the field panel's database so that it can be monitored and controlled from the field panel.
Glossary
Siemens Building Technologies, Inc. 33
Index
A
actuator .............................................................. 4
address descriptions ........................................ 18
AI (see analog input) ........................................ 30
airflow ............................................................... 30
algorithm .......................................................... 30
analog input ........................................................ 2
analog input (Glossary) .................................... 30
analog output ............................................... 2, 30
AO ........................................ (see analog output)
application
notes ....................................................... 12, 14
slave mode ................................................... 16
Application 2583 ............................................... 12
compressor operation and staging ................. 9
control drawing ............................................. 13
fan operation ................................................... 9
maximum configurations .............................. 13
notes ............................................................. 12
reversing valve operation ............................. 12
Application 2584 ............................................... 14
compressor/electric heat staging ................. 14
control drawing ....................................... 14, 15
maximum configurations .............................. 14
notes ............................................................. 14
Application 2590 ............................................... 16
applications
calibration ....................................................... 8
control loops ................................................... 7
control temperature setpoints ......................... 7
day/night mode ............................................... 7
electric reheat
stage 1 ........................................................ 9
stage 2 ........................................................ 9
stage 3 ........................................................ 9
heating and cooling switchover ...................... 9
night mode override switch ............................. 7
auxiliary points, using ....................................... 11
B
Basic Sanity Test (BST) ................................... 29
basic service information ................................. 28
BST LED ...................................................... 4, 29
C
centralized alarm monitoring ........................... 10
centralized control ............................................ 30
communication wiring ........................................ 3
compressor
operation ........................................................ 9
control drawing
Application 2583 ........................................... 13
Application 2584 ........................................... 15
control loop ...................................................... 31
mixed air ......................................................... 7
controller
hardware ........................................................ 1
LEDs/LED indicators ................................ 4, 29
D
damper motor
floating control ................................................ 8
spring return ................................................... 8
database ............................. (see point database)
DDC (see Direct Digital Control) ...................... 31
DI (see digital inputs) ....................................... 31
digital input ......................................................... 2
digital output ....................................................... 3
overriding ...................................................... 10
Direct Digital Control .......................................... 1
DO (see digital outputs) ................................... 31
E
English units ..................................................... 31
equipment controller ........................................ 31
F
fail-safe operation ............................................ 10
fan operation ...................................................... 9
field panel ................................................... 31, 33
FLN .................................................................. 31
Floor Level Network (FLN)................................. 3
H
hardware
power wiring ................................................... 3
Siemens Building Technologies, Inc. 34
Index
relay module ................................................... 5
hardware, inputs and outputs ............................. 2
heat pump controller—multi-stage ..................... 1
I
inputs and outputs
analog ............................................................. 2
digital .......................................................... 2, 3
hardware ......................................................... 2
L
Light Emitting Diodes (LEDs) ....................... 4, 29
BST ............................................................... 29
RX and TX .................................................... 29
loopout.............................................................. 32
M
mixed air control loop
day mode ........................................................ 8
night mode ...................................................... 8
MMI (see Man-Machine Interface) ................... 31
MMI port ............................................................. 4
mounting bracket ................................................ 1
O
override switch ................................................. 32
overriding DOs ................................................. 10
P
PID ................................................................... 32
point database .................................................. 18
point addresses ............................................ 18
point descriptors ........................................... 18
point extension device
using controller as ........................................ 16
power failure recovery ...................................... 10
power wiring ....................................................... 3
pressure dependent ......................................... 32
preventive maintenance ................................... 28
R
related equipment .............................................. 5
relay module ...................................................... 5
reversing valve operation ................................. 12
Room Temperature Sensor ......................... 4, 18
RTS .................................................................. 32
RX LED ........................................................ 4, 29
S
safety features ................................................. 29
service information, basic ................................ 28
setpoint ............................................................ 32
dial ................................................................ 10
SI units ............................................................. 32
slave mode ................................................. 16, 32
stand-alone ...................................................... 32
stand-alone control .......................................... 32
static discharge ................................................ 28
T
temperature sensors .......................................... 4
mixed air ......................................................... 4
room ............................................................... 4
Terminal Equipment Controller ........................ 33
troubleshooting ................................................ 28
basic service information.............................. 28
TX LED ........................................................ 4, 29
U
unbundle .................................................... 16, 33
V
valve
2-position heating ........................................... 8
valve, reversing ................................................ 12
W
wiring
communication wiring ..................................... 3
power wiring ................................................... 3
Siemens Building Technologies, Inc. 35
Loading...