Siemens 24 V nonstop User Manual

Page 1
© Siemens 2020 1
24 V nonstop – even upon power failure
The right UPS system for every application – summary of advantages and disadvantages
A reliable power supply is essential for guaranteeing the productivity of automated
plants and machines. PLCs, sensors and actuators are usually provided with
24 V DC from a switched-mode power supply. Modern power supply units such as
SITOP offer a maximum degree of security for the supply. However, they are not
invulnerable to longer power supply failures. Critical applications therefore require
one, and what must be considered when dimensioning?
Page 2
Application Note | 24 V nonstop – even upon power failure
© Siemens 2020 2
AC or DC UPS?
In order to provide protection against power failure, an un­interruptible power supply can be used on the AC or DC side. The advantage of an AC UPS is that it provides buffer­ing of all electrical consumers, e.g. also of AC drives. How­ever, an AC UPS is more expensive than a DC UPS. If it is per­missible with the application to only buffer the 24 V side in the event of a power failure, a DC UPS is quite definitely the more economical solution. On the one hand, the powers re­quired are usually smaller, resulting in smaller dimensioning of the DC UPS, and on the other hand an AC UPS is always more expensive because of its increasingly complex design. Furthermore, the total efficiency is significantly better with a DC UPS. This is because conversion of the battery voltage into an AC voltage and the repeated transformation into the required 24 V DC voltage are unnecessary.
With the DC UPS, the energy is provided where it is re­quired, namely directly on the consumer without "loss-mak­ing detours".
The right solution for every application
No other manufacturer of power supplies provides such a comprehensive range of units for safeguarding a 24 V DC supply like Siemens does. The range extends from a simple buffer module up to the multi-function DC UPS.
24V DC power supply from SITOP can be combined with
A 3 different solutions for 24V buffering:
Additionally to the above 3 solutions, the PSU8600 offers its own solution for buffering ranging from millisecond to hours.
Figure 1: Buffering the 24V control circuit with the SITOP PSU100S power supply, SITOP DC-UPS UPS1600 and 2 battery modules SITOP UPS1100. The DC-UPS is fully integrated via PROFITNET in the automation system.
Note: The SITOP PSU8600 system power supply and its buffering technologies merit its own application note. For more in­formation, please see www.siemens.com/sitop-psu8600 for more information.
Page 3
Application Note | 24 V nonstop – even upon power failure
© Siemens 2020 3
Bridging brief power failures
When power supply conditions are unstable, for example in low-meshed network infrastructures, brief power fail­ures may occur occasionally or even frequently as a result load transfers in the network, for example. Problems fol­lowing such interruptions with non-buffered power sup­plies are the long ramp-up times and initialization of the automation system or involved drives. It is already possible to significantly increase the plant availability by using a buffer module for bridging such brief interruptions of up to 10 seconds. The buffer module is simply connected in parallel with a 24 V SITOP power supply. The electrolytic capacitors supply up to 40 A which supports the power supply even in the event of an overload.
Protection of plant status upon power failure
In applications where a plant is to be switched off in the event of a power failure with retention of the last plant status, extended bridging of the power failure is required. Such requirements are typical for PC-based automation, visualization, or archiving of operating data. Recording of the failure, saving of the plant status, as well as controlled shutdown of the PC require bridging in the minute range. Comparatively high buffer reserves are required in such a scenario by powerful industrial PCs, especially when a large panel has to continue to operate during the shut­down. High buffer capacities are also required by actuators which have to be driven into an end position or processes in which plant components must continue to be powered until the power supply is restored. This is the case, for ex­ample, when measured data is being recorded or a com­munications link must be maintained. Uninterruptible power supplies (UPS) are required in such situation
SITOP power supplies with 24 V output voltage can be up­graded into a fully-fledged UPS. Two different UPS con­cepts are available corresponding to the mentioned re­quirements. They mainly differ in the type of energy store. One of them is based on lead or lithium batteries, the other on double-layer capacitors. All DC UPS modules have the same basic functionality with comprehensive monitor­ing functions and signaling contacts and are available with a USB interface. The battery based SITOP UPS1600 is also available with an Industrial Ethernet/PROFINET interface and communicates also over OPC UA. The free software tool SITOP Manager provides simple in­tegration into PC-based automation solutions. They sup­port further processing of status messages, safe shut­down, and correct restarting of the system. The UPS1600 with IE/PN interface can be configured via the TIA Portal or integrated in TIA (Totally Integrated Automation) with STEP 7 and WinCC
The energy storage makes the difference
Whether the capacitor-based or the battery-based concept is right for the respective application depends on the re­spective demands. If long buffer times are required, the UPS with batteries is the best choice. They can supply en­ergy for hours depending on the current requirements. Battery modules for the UPS1600 are available with capac­ities ranging from 1.2 Ah to 12 Ah. Connection in parallel allows for a flexible combination for the required capacity, up to 72 Ah. A UPS1100 battery module is equipped with electronics with specific parameters as well as for record­ing the current operating data that are read by the UPS1600 UPS module via a two-wire cable (Energy Storage Link). The UPS modules are available with rated output currents of 10 A, 20 A and 40 A. They also offer high overload ca­pability and can supply three times the rated current for 30 ms and 1.5 times the rated current for 5 s per minute.
In many cases, a plant can be brought into a safe status within minutes, and thus minimize the effects of a power failure. Many advantages for such time requirements are provided by the SITOP UPS500 based on double-layer ca­pacitors. These are also referred to as ultracaps, supercaps or super capacitors because of their high energy density. The innovative UPS for installation in control cabinets con­sists of a basic unit with energy storage of 2.5 or 5 kWs, and delivers an output current of up to 15 A. Add-on mod­ules of 5 kWs each permit configurations with up to 20 kWs. The type of energy storage is not only critical for the buffer time, is also decisive for the possible applications of the two types of SITOP UPS systems.
Available capacity of lead batteries is highly dependent on the temperature
Lead batteries are extremely temperature-sensitive, since the charging and discharging processes of a battery are the result of an electrochemical reaction. Aging depends on the electrolyte used (sulfuric acid) and the plates serv­ing as poles (lead and lead oxide) and is highly tempera­ture-dependent. Temperatures higher by 10 K reduce the service life by half. With an ambient temperature of 40 °C, for example, the service life is therefore only 1/4 of that at the rated operating temperature of 20 °C. A lead bat­tery with a service life of 4 years at the rated conditions must therefore be replaced after only one year when used at 40 °C. Special batteries with an increased thermal stability can also be used as an alternative to conventional lead batter­ies, but these are also more expensive. SITOP offers, for example, a high-temperature battery with pure lead plates for use at temperatures from -40 to +60 °C.
Page 4
Application Note | 24 V nonstop – even upon power failure
© Siemens 2020 4
Lithium based batteries with longer lifetime, even at high temperatures
Batteries using lithium, such as lithium iron phosphate (LiFePO4), bring together high temperature resilience and long lifetime. At 40°C, the lithium batteries are rated for 9 years, where traditional lead-acid batteries are rated for only 1 year. This dramatic difference makes the amortiza­tion of the valuable lithium technology possible over just a few years.
Table 1: Service life and ambient temperature range of SITOP UPS1100 battery modules
How supercaps work and the advantages they offer
A chemical reaction does not take place in double-layer ca­pacitors. They store the charge in an electrochemical dou­ble layer (the so-called Helmholtz layer), where positive and negative ions of the electrolyte move through the electric field to the corresponding electrode. They are therefore more resistant to aging than lead batteries, with regard to both the charging cycles and the temperature. In the SITOP UPS500, the supercaps only lose approx. 20% of their capacity after eight years of operation and an ambient temperature of 50 °C. The UPS is therefore fully maintenance-free, and replacement of the energy storage is unnecessary. Even at an ambient temperature of 40 °C, the capacitor UPS is amortized in the second year of operation. The slightly higher cost is compensated by the second battery replacement for a conventional UPS. Even more costs can be saved regard to the control cabinet installation. Compared to lead batteries, the capacitors do not emit hydrogen and there is therefore no need to venti­late the control cabinet. An additional advantage provided by the energy storage is the short charging time of a few minutes (see table 2 "Buffering and charging times SITOP UPS500"). This guar­antees fast supply readiness following a power failure and also results in a high availability.
How is a DC UPS system configured?
The criteria for configuration of the UPS are the buffer time, the operating current, the peak current and the ambient temperature. The example below shows the configuration of a DC UPS, which is designed to protect an automation application with a 24 V industrial PC from a power failure.
The backup is intended for a Panel PC that is to save data and shut down normally in the event of a power failure. To retain or save the measured values, the sen­sors should also be supplied with 24 V via the DC UPS. To lower the load on the DC UPS, the actuators are not to be buffered and are connected directly to the 24 V output of the power supply
Figure 2: Application example for configuration of an uninter­ruptible 24 V power supply
Application conditions: Time required to save and shut down the system: 55 s, am­bient temperature: 40 °C, actuators are not buffered.
1) Calculation of current requirements and selection of power supply
a) Calculation of max. operating current requirement:
Buffered 24 V feeder: 3.4 A (PC 477E) + 0.5 A (sensors) + 2 A (UPS500S charging current, can be set to 1 or 2 A) =
5.9 A Non-buffered 24 V feeder: 3 A (actuators) Total operating current requirement: 5.9 A + 3 A = 8.9 A
b) Calculation of peak current requirement:
Buffered 24 V feeder: 6.5 A (PC 477E for 25ms) + 1 A (sensors) + 2 A (charging current) = 9.5 A Non-buffered 24 V feeder: Actuators: 4 A (starting torque) Total peak current requirement: 9.5 A + 4 A = 13.5 A
c) Selection of power supply for 8.9 A operating current
and 13.5 A peak current requirement
=> SITOP PSU6200 10 A (max. 15 A for 5 s)
2) Calculation of UPS output current, energy storage and se­lection of DC UPS
a) UPS output current at peak current requirement:
6.5 A (PC 477E for 25 ms) + 1 A (sensors) = 7.5 A
b) UPS output current for buffer mode:
3.4 A (PC 477E) + 0.5 A (sensors) = 3.9 A
c) Energy requirement + 25% due to 20% loss in capacity af-
ter approx. 8 years: 3.9 A x 24 V x 55 s x 1.25 = 6435 Ws Check in table for UPS500 "Buffering and charging times": Buffering time with 4 A operating current and 7.5 kWs: 61 sec = OK!
d) Selection of DC UPS for 7.5 A peak output current and
6.435 kWs => SITOP UPS500S 15A/ 2.5 kWs and add-on module SITOP UPS501S 5 kWs (total 15A/ 7.5 kWs)
Page 5
Application Note | 24 V nonstop – even upon power failure
© Siemens 2020 5
Table 2: Check in the table Buffering and charging times SITOP UPS500
TIA Selection Tool – convenient selection guide for power supply and DC UPS
The selection with the 24 V consumer view in the TIA Se­lection Tool is more convenient and detailed than the man­ual selection, especially for the more demanding dimen­sioning of a DC UPS with batteries. The selection guide of­fers the possible DC UPS solutions with a few mouse clicks, depending on the requirements, with capacitors or batter­ies. In addition to the criteria operating current and buffer time, you can also specify the ambient temperature, the minimum buffer voltage and new the target lifetime of the batteries. The minimum buffer voltage is the lowest input voltage at the load at which its function is still guaranteed. It influences the dimensioning of a DC UPS with battery. This is because if the battery voltage drops more, a longer buffer time is possible with the same battery capacity. The ambient temperature plays a crucial role for the service life of a battery, as described on page before.
The new option „target lifetime of the batteries” will di­mension the battery capacity to offset the natural aging process of the batteries for the specified lifetime. This im­plies that, for example, a customer selects a target lifetime of 3 years, the battery configuration will be dimensioned to provide the request buffer capacity after 3 years. This aging is modeled using the Arrenius’s Law and is compen­sates the capacity degradation by increasing the battery capacity. With these added features, TIA Selection Tool can model the real conditions even better, saving the ardu­ous calculations necessary to do such modeling manually.
The matching power supply as well as all the Add-on modules can be selected just as conveniently from the vast range of SITOP products. The tool compiles all re­quired CAD data, circuit diagram macros and appropriate documentation for the selected power supply and the DC UPS to enable quick configuration.
www.siemens.com/tst
Figure 3: After entering a few criteria, the TIA Selection Tool offers a selection of suitable DC UPS configurations.
Page 6
Application Note | 24 V nonstop – even upon power failure
© Siemens 2020 6
DC UPS
Communication
Control-
Engineering
Digital outputs
PLC
-
USB
PC
SITOP Manager
Digital outputs
PLC
-
USB
PC
PC
STEP 7, TIA Portal
How is the DC UPS integrated into the plant? The automation system must be informed about the
status of the DC UPS so that it can respond correctly to the situation. Communication takes place via digital outputs, USB or Ethernet/PROFINET interfaces.
ler
SITOP UPS500 (with ultracaps)
SITOP UPS1600 (with battery mod­ules)
Table 3: A free engineering tool is available for the DC UPS with interface and controller type that must be buffered; it can be used for easy configuration of the DC UPS and visualization of the operating state
Industr. Ethernet/ Profinet
PLC
tool
SITOP Manager
Digital outputs The most important status messages are displayed by
LEDs for all SITOP DC UPS modules and output via sig­naling contacts. The signals are evaluated by digital in­puts at the controller. Signaling and terminal assign­ment are identical for the DC UPS modules SITOP UPS500S and SITOP UPS1600 (see Table 4), which means engineering and wiring of both UPS systems is almost the same.
Tab le 4: The digital outputs of all SITOP DC UPS modules are the uniform in accordance to this terminal assignment.
The use of relay contacts is ideally suited for basic auto­mation applications without networking, such as ob­struction lighting, hydroelectric plants or thermal power stations. For these insular applications, the UPS1600 is especially equipped with the "Start from Battery" func­tion. When a plant is started without line voltage, the 24 V loads are supplied by the battery.
Figure 4: Backing up simple automation applications with sta­tus signaling via digital outputs.
The UPS settings are made on the front of the device. Among other things, you can set the voltage connection threshold, the buffer time and the operating current with DIP switches or rotary switches. For the coded UPS1100 battery modules, the operating current is pre­defined, depending on the temperature, via the 2-wire cable "Energy Storage Link" and therefore need not be set.
Interfaces for PC-based or PLC-based systems
For communication with PCs or PLCs, the SITOP DC UPS modules come equipped with an optional USB port or two Ethernet interfaces. Free engineering tools, which should be used according to Table 3, assist in the inte­gration of the DC UPS into the plant.
SITOP UPS500 with USB port on the PC
UPS modules with USB port are best suited for applica­tions with an automation computer and without further networking. The UPS500 responds via USB port to the same status messages that are also output via the con­tacts (see Table 4). The UPS 500 can be easily config­ured with the SITOP Manager from Version 1.1, which means it can be used to start applications at specific events, such as an emergency program in case of a power failure or buffer mode.
Page 7
Application Note | 24 V nonstop – even upon power failure
© Siemens 2020 7
Figure 5: Backing up a 24 V automation computer with com­munication via USB
The "Reset after Buffering" function is available for the versions with USB as well as Industrial Ethernet. Without this function, the computer remains switched off during shutdown when the power and therefore the 24 V sup­ply returns. With this function, the 24 V supply is inter­rupted for 5 seconds after shutdown (interface is not supplied with voltage) which makes the computer start up automatically again.
A general disadvantage of communication via USB is the restriction to a cable length of about 5 meters if no ad­ditional measures for signal amplification are taken.
SITOP UPS1600 with USB port or Industrial Ethernet interface on PC
If the UPS1600 backs up PC-based controllers, communica­tion can take place via USB or Industrial Ethernet (IE). Communication via the two 2 IE ports has the great ad­vantage that the UPS can be easily integrated into any LAN infrastructure and multiple PCs can be shut down accord­ing to the master-slave principle if a power failure occurs.
Figure 6: Backing up multiple 24 V PCs. Communication via Indus­trial Ethernet supports comprehensive diagnostics and targeted shutdown in the master-slave module in case of power failure
Parameters can be conveniently assigned via the SITOP Manager. Now with Version V1.1, all SITOP devices with USB or PN/IE communication can be configured and diag­nosed.
SITOP Manager runs on Windows 7 and 10 and offers:
Online- and Offline-Engineering
Commissioning and continuous monitoring
Monitoring and controlled shutdown of multiple PCs in
the event of a power failure, for example, by starting batch files and closing software applications
Online functions, such as firmware updates
Easy operation via web-based user interface
automatic scaling to window width
Remote access possible via mobile devices
Figure 7: With SITOP Manager, it is easy to parameterize and visu­alize the DC-UPS.
Download: Engineering Tool SITOP Manager
Remote visualization of the operating state and the param­eters is also possible via the integrated web server. The de­vice status along with the network connection can be eas­ily monitored in the SINEMA Server or SINEC NMS network management software.
SITOP UPS1600 with PROFINET at controller
For backing up SIMATIC controllers, the PROFINET connec­tion and the TIA Portal offer optimal options for easy and complete system integration. Function blocks for the SI­MATIC S7-300, 400, 1200 and 1500 enable processing of all UPS1600 operating data and therefore response to each state of the DC UPS. The state of the DC UPS can evaluated in detail especially when using the coded battery modules UPS1100. Up to six UPS1100 battery modules can be connected in parallel and evaluated individually.
Here is a selection of the UPS data that can be evaluated:
Voltage and input current
Output voltage and output current
Charging voltage and charging current
Temperature UPS1600 and UPS1100 battery modules
Capacity of the battery in total and individually
Remaining buffer time
Number of battery modules
Recommended battery replacement
Page 8
Application Note | 24 V nonstop – even upon power failure
© Siemens 2020 8
www.siemens.com/sitop
Subject to changes and errors. The information provided in this document contains descriptions or performance ways the products. The desired agreed in the contract. Availability and technical without notice. All product designations may be trademarks or product plier companies, the use violate the rights of the owners.
In addition, all device parameters can be read, for exam­ple, end-of-charge voltage, rated capacity, permissible temperature range, article number, serial number and ver­sion number.
Figure 8: Backing up an automation solution with PLC networked via PROFINET. Even multiple controllers can be brought to a de­fined state independent of each other
The operating status of the DC UPS can be easily visualized using ready-to-use faceplates. Faceplates for SIMATIC Pan­els and WinCC make for easier diagnostics in the area of production automation.
SITOP UPS with PROFINET on process control systems
A free UPS1600 library with software blocks and faceplates is also available for the SIMATIC PCS 7 process control sys­tem. Automatic information about operating status mes­sages such as power failure (buffer mode) or maintenance demanded as well as preventive battery replacement in­crease availability of the plant in process automation even more.
Figure 10: Faceplates for the SIMATIC PCS 7 enable easy diagnos­tics and maintenance of the DC UPS in the process industry
Download: SITOP library for integration in SIMATIC PCS 7 V8.2 and SIMATIC PCS 7 V9.0
Figure 9: Faceplates for WinCC help visualize comprehensive di­agnostics including trend charts and alarm messages
Download: SITOP UPS1600: Faceplates and STEP 7 communication blocks
Published by Siemens AG
Digital Industries Process Automation Östliche Rheinbrückenstr. 50 76187 Karlsruhe, Germany
apply as described or which may change as a result of further development of
characteristics which, in case of actual use, do not al-
performance characteristics are only binding if expressly
specifications are subject to change
names of Siemens AG or sup-
of which by third parties for their own purposes may
Loading...