Siemens 2200 Series Installation Instructions Manual

Series 2200 Relative Humidity and Temperature Room Units For APOGEE® Controllers
Product Description
These room units measure relative humidity and temperature in the occupied space in which they are installed. Models with display allow users to view the measured temperature value. A version with temperature setpoint adjustment is also offered.
These devices are intended for use with appropriate signal input on an APOGEE Controller. The effective sensing range is 32°F to 122°F (0°C to 50°C), and the setpoint range is 55°F to 95°F (13°C to 35°C).
These room units can be mounted on electrical boxes, stud-type mounting brackets, or drywall. Obtain the necessary mounting hardware and follow the appropriate mounting procedures for the type of installation required.
Installation Instructions
Document No. 129-104
October 1, 2013
Expected Installation Time
20 minutes
Required Tools
Sizes 1 and 2 Phillips screwdrivers
Small and medium flat-blade screwdrivers
1/16-inch hex key
Medium-duty electric drill
3/16-inch (4.8 mm) drill bit
One-inch (25 mm) hole saw
Small level
Tape measure
Marker or pencil
Product Numbers
QFA3212.FWSN QFA32SS.FWSN QFA3212.EWSN QFA32SS.EWSN
Accessories
AQA2200-INTL Room Unit Back Plate (10-pack)
AQA2200-2X4 Room Unit Back Plate (Single)
563-102 GSKT Kit Room Sensor Insulating Gasket (10-pack) (For hollow wall installations)
NOTE: If installing the Back Plate, discard the
metric screws provided with the Back Plate and utilize the Room Unit mounting screws.
Caution Notations
CAUTION
Item Number 129-104, Rev. HA
Equipment damage or loss of data may occur if you do not follow a procedure as specified.
Prerequisites
Review these instructions before beginning.
Installed: appropriate field wiring within the
maximum wiring run length for the individual equipment controller. The maximum recommended length is 750 feet (229 m) for 18 AWG; 300 feet (91 m) for 22 AWG.
All wiring must comply with National Electric Code (NEC) and local regulations.
Figure 1. Typical Temperature Room Unit.
Document No. 129-104 Installation Instructions October 1, 2013
Mounting Information
Always mount the room unit vertically. Locate the room unit:
according to design specifications and local regulations.
where the air circulates around it freely (not in recessed areas or behind doors).
allowing a minimum of 4 inches (10 cm) free space above and below for proper airflow, the front cover removal tool, and the computer communication cable.
away from drafts caused by doors, windows, outside walls, air registers, pipes, return air plenums, etc.
away from heat sources such as strong lights, fireplaces, direct sunlight, etc.
on an inside wall (preferably), about 5 feet (1.5 m) above the finished floor.
Drywall Mounting (No Rough-in), Typical
Figure 2. Insulating Gasket.
4. Pull about three inches (75 mm) of the cable through the hole in the base plate.
5. Mount the room unit base plate on the wall, noting the UP arrow:
NOTE: If required, position the Back Plate
behind the Room Unit Base, aligning the top and bottom mounting holes, prior to mounting to the wall:
a. Install the two mounting screws provided, but
do not tighten. b. Level the room unit base plate for appearance. c. Tighten the two mounting screws to the room
unit base plate.
Base Plate Mounting and Wiring
1. Mark the center (cable) hole and the mounting hole locations, using the room unit base plate as a template. See
2. Drill two 3/16-inch (4.8 mm) mounting holes and mount the two plastic wall anchors flush to below the wall surface for stable mounting of the device.
3. Cut a 1-inch (25 mm) center hole with a hole saw.
NOTE: It is recommended that you use the
Figure 3.
optional Insulating Gasket on the back of the Sensor Base for hollow wall installations.
When applying the adhesive-backed gasket to the back of the Sensor Base, orient the gasket so that the cut-out
ow portion of the gasket is in the
arr upper lefthand quadran Base. The Sensor Base has an UP arrow molded into the surface in the same quadrant location (see
t of the Sensor
Figure 6).
6. Cut the cable, leaving about three inches (75 mm) on the room unit side of the drywall. Ensure that pin Number 1 connects to the same wire at each end of the cable.
NOTE: See Figure 2 for details on optional Gasket
application.
Page 2 of 5 Siemens Industry, Inc.
Figure 3. Drywall Mounting (No Rough-in), Typical.
Loading...
+ 3 hidden pages