Siemens 21-115532-001 User Manual

Page 1
Installation / Operation / Maintenance
Instructions
JFR Distribution Step Voltage Regulator
21-115532-001 PR4018-06 SUPERCEDES
21-115532-001 PR4018-05
October 08
Page 2
Page 3
TABLE OF CONTENTS
Page
INTRODUCTION
Inspection for Damage in Shipment................... 2
Storage Prior To Installation............................. 2
Physical Considerations ...................................3
Line Terminals and Connections.......................3
Electrical Considerations .................................. 3
Installation Diagrams........................................4
Protective Measures ........................................5
Control Connections ........................................ 5
Connection Diagrams
Straight Design................................................6
Inverted Design................................................7
Series Transformers Design ............................. 8
Placing the Regulator in Service
Before Connecting ...........................................9
Connecting ......................................................9
Switching On-Line ............................................ 9
Checking Regulator Operation..........................9
Removing the Regulator From Service .............10
Maintenance
General Instructions ........................................11
Operational Checks.........................................11
Periodic Inspection..........................................12
Page
Special Features
Polarized Disconnect Switch
and Hinged Control Panel ......................................... 13
Remote Mounting of Control Equipment..................... 13
Vari-AMP
TM
Position Indicator................................... 13
Operation at Less Than Rated Voltage.........................14
Forced Air Cooling ................................................... 15
Subbase Assembly .................................................. 15
Parts List
Major Components................................................... 16
Position Indicator................................................... 17
Type TLG Dial Switch ............................................. 18
Type TLG Quick Break Mechanism ........................... 19
Type TLF Dial Switch ............................................... 20
Type TLF Quick Break Mechanism............................21
Bypass Arresters..................................................... 22
Bushings.................................................................23
For Emergency Service Call :
1-877-742-3309
Siemens Energy, Inc.
THESE INSTRUCTIONS DO NOT PURPORT TO COVER ALL DETAILS OR VARIATIONS IN EQUIPMENT, NOR TO PROVIDE FOR EVERY POSSIBLE CONTINGENCY TO BE MET IN CONNECTION WITH INSTALLATION, OPERATION OR MAlNTENANCE. SHOULD FURTHER INFOR­MATION BE DESIRED OR PROBLEMS ARISE WHICH ARE N OT COVERE D SUF ICIENT LY FOR T HE PURCHASER ’S PURPOSES , THE MATTER SHOULD BE REFERRED TO YOUR SIEMENS ENERGY, INC. REPRESENTATIVE.
THE CONTENTS OF THIS INSTRUCTION MANUAL SHALL NOT BEC OME PART OF OR MODIFY ANY PRIOR OR EXISTING AGREEMENT, COMMITMENT OR RELATIONSHIP. THE SALES CONTRACT CONTAINS THE ENTIRE OBLIGATION OF SIEMENS ENERGY, INC. THE WARRANTY CONTAINED IN THE CONTRACT BETWEEN THE PARTIES IS THE SOLE W ARRANTY OF SIEMENS ENERGY, INC. ANY STATEMENTS CONTAINED HEREIN DO NOT CREATE NEW WARRANTIES OR MODIFY THE EXISTING WARRANTY.
Page 4
Page 5
INTRODUCTION
Page 1
Type JFR single-phase step-voltage regulators are designed to give dependable service and to make installation, operation and maintenance as simple as possible.
Technology advances, especially in the realm of the control apparatus, make it efficient to provide a separate instruction manual for the Accu/StatTM control provided with this JFR Regulator. For specific control information, refer to the Accu/StatTM control manual included with the regulator.
Hazardous Voltag e. Death or serious injury from electrical shock, burns will result from misuse.
To prevent: Do not service or touch until you have de-energized
high voltage, grounded all terminals and turned off control voltage. Grounding terminals with line to ground capacitors may produce a small arc.
Only qualified personnel should work on or around this equipment after becoming thoroughly familiar with all warnings, safety notices, instructions and maintenance procedures contained herein.
The successful and safe oper ation of this equipment is dependent upon proper handling, installation, operation and maintenance.
QUALIFIED PERSON
FOR THE PURPOSE OF THIS MANUAL AND PRODUCT LABELS, A QUALIFIED PERSON IS ONE WHO IS FAMILIAR WITH THE INSTALLATION, CONSTRUCTION AND OPERA­TION OF THE EQUIPMENT, AND THE HAZARDS INVOLVED. IN ADDITION, HE HAS THE FOLLOWING QUALIFICATIONS:
(a) Is trained and authorized to de-energize, clear, ground and
tag circuits and equipment in accordance with established safety practices.
(b) Is trained in the proper care and use of protective
equipment such as rubber gloves, hard hat, safety glasses or face shields, flash clothing, etc., in accordance with established safety practices.
(c) Is trained in rendering first aid.
Distinctive signal words (DANGER, WARNING, CAUTION) are used in this instruction book to indicate degrees of hazard that may be encountered by the user. For the purpose of this manual and product labels these signal words are defined below.
DANGER Indicates an imminently hazardous situation
which, if not avoided, will result in death or serious injury
WARNING Indicates a potentially hazardous situation,
which, if not avoided, could result in death or serious injury.
CAUTION Indicates a potentially hazardous situation
which, if not avoided, may result in minor or moderate injury.
Page 6
INTRODUCTION
Page 2
INSPECTION FOR STORAGE PRIOR TO DAMAGE IN SHIPMENT INSTALLATION
Check each item with the shipping manifest immediately upon receipt of the regulator. Make a thorough visual in­spection of the regulator. Check for evidence of damage attributable to mishandling in shipment. Should any short­age or damage be found, notify the local agent of the ca rrier making the delivery and make appropriate notation on the freight bill. Any damage or shortage that is not noted on the freight bill becomes the recipients responsibility. A claim should be made immediately with the carrier. Please also notify your Siemens representative as soon as possible.
Assure that the control compartment enclosure is tightly closed, and regulator tank is sealed.
Page 7
INTRODUCTION
Page 3
PHYSICAL CONSIDERATIONS
Handling. Type JFR regulators are designed to be lifted either by a forklift at the base or by use of lifting hooks on the side of each tank. Each JFR regulator is provided with either 2 or 4 lifting hooks on the side of each tank. The number of hooks has been established to provide a margin of safety. Use all supplied lifting hooks when lifting.
WARNING
Improper use of lifting provisions can cause death, serious injury, or equipment damage.
To prevent: Do not use cover lifting eyes to lift complete unit.
Cover lifting eyes are for untanking only.
Location. Type JFR regulators are designed for outdoor installation. Any regulator may be platform or pedestal mounted. Regulators provided with hanger brackets are suitable for pole mounting. When the regulator is to be installed in a substation on a pedestal it is recom­mended that a minimum elevation to the live connection be established, as required by applicable codes.
LINE TERMINALS AND CONNECTIONS
Type JFR voltage regulators are routinely equipped with line bushing terminals per the following criteria.
Nameplate Line Current Rating
50A to 300A #2 to 477 MCM 301A to 668A #2 to 800 MCM 669A to 1200A 1.125- 12 UNF-2A 1201 A to 2000A 1.500- 12 UNF-2A
Clamp type terminals for use through 668 ampere are capable of accepting an aluminum or copper conductor.
Tank grounding provision consists of a 0.5-13NC tapped hole in a steel pad for regulators rated to 300 amperes. Above 300 ampere ratings, a stainless steel pad with two
0.5-13NC tapped holes is provided.
Conductor Size Range or Threaded Stud Size
ELECTRICAL CONSIDERATIONS
Type JFR regulators are commonly installed using any of four electrical configurations.
One regulator in single-phase application. (Figure 4A)
Hazardous voltage present at the line terminals of the bushings on the cover of the regulator.
Will cause serious injury or death. To prevent:
De-energize the regulator before servicing.
Elevation. When the regulator will be used at an elevation above 1000 meters (3300 feet) the kVA rating must be de­rated per ANSI C57.15 to assure operating temperature limits are not exceeded.
Three regulators in wye on a grounded-neutral three­phase system. (Figure 4D)
Two regulators in open delta on a three-phase ungrounded system. (Figure 4B)
Three regulators in closed delta on a three-phase ungrounded system. (Figure 4C)
Each of the four alternatives, when complete with switching provisions, will take the electrical configuration as shown on the next page.
The descriptions 'S', 'L', and 'SL' are embossed into th e cove r for user convenience at time of installation.
Page 8
INTRODUCTION
Page 4
INSTALLATION DIAGRAMS
Single Phase
Connection of one single phase JFR regulator on single
phase line.
Closed Delta
4C)
Open Delta
Connection of two single phase JFR regulators in open delta on a three phase, ungrounded line.
Wye Connected
Connection of three JFR regulators in closed delta on three phase, ungrounded system.
Connection of three single phase JFR regulators in wye on a three phase, grounded neutral system.
Page 9
INTRODUCTION
Page 5
PROTECTIVE MEASURES
Bypass Arrester. All JFR regulators are equipped with a properly sized arrester , connected externally between the 'S' and 'L' line terminals. The arrester is provided to protect the series winding of the regulator from line surges. By itself, the bypass arrester does not provide lightning protection for the regulator.
Lightning Protection. The number of lightning arresters used will be a discretionary decision on the part of the user, considering such factors as isokeraunic level and degree of risk of damage to be accepted. The minimum recommended lightning protection consists of a properly sized arrester between the 'S' or 'L' bushing and ground on a single phase or a wye connected system. A delta connection system requires the use of two arresters to accomplish minimum protection levels. Additional protection can be obtained with the use of arresters at both the 'S' and 'L' terminals in single phase or wye systems and on all three terminals on a delta system.
For best results, install lightning arresters on the mounting lugs adjacent to the bushings near the top of the tank. The lugs are 0.5 - 13NC located on 2.5 inch centers. Ground the arrester(s) and the regulator tank solidly to the same ground connection. Be careful to keep the ground lead connections as short as possible.
Thru Fault. Type JFR regulators are rated under condition of thru-faults per ANSI C57.15.
Figure 5A
For this purpose, it is necessary to use the nameplate drawing and control diagram found in the control enclosure.
1. Refer to the Nameplate. The P2 column indicates the
correct connection for lead P2 based on the system voltage. Using the applicable control diagram, the terminal designation of the nameplate can be cross referenced to the proper terminal on the 19-pin terminal block.
The user is advised to provide for additional source imped­ance, bus sectionalizing or other means of limiting the avail­able thru-fault current if these criteria are exceeded at the installation.
CONTROL CONNECTIONS
Many regulators can be used at several different nominal system voltages. It is therefore necessary to assure that the regulator is properly connected at the 19 pin upper terminal block for the system voltage on which the particular regul ator will be used.
2. Depending on the regulator, there may be a second
nameplate column indicating that lead U2 should also be connected. If so, the U2 column indicates the correct connection for lead U2 based on the system voltage Using the applicable control diagram, the “U” terminal designation of the nameplate can be cross referenced to the proper terminal on the 19-pin term i na l b lock.
3. For regulator equipped with fans for forced-air cooling,
another set of connections will be shown.
NOTE Matters specifically relating to the Accu/Stat
control used in conjunction with the regulator are not included in this manual. Refer to the appropriate control instruction manual.
TM
Page 10
CONNECTION DIAGRAMS
Page 6
STRAIGHT DESIGN (ANSI TYPE A)
Wiring diagram of a typical Type “A” regulator showing both internal and external connections without fan power.
SOURCE
S
Schematic diagram of a typical Type “A” JFR regulator with fan power circuit U3-U5.
Note: Other typical motor supply configurations below.
L SL
LOAD
Typical arrangement of windings and connections of Type “A” JFR regulators.
Note: Straight design units may or may not be
equiped with a balance winding. Refer to regulator nameplate.
Page 11
CONNECTION DIAGRAMS Page 7
INVERTED DESIGN (ANSI TYPE B)
S
SL
Wiring diagram of a typical Type “B” regulator showing both internal and external connections.
L
SOURCE
S
L
LOAD
SL
Schematic diagram of a typical Type “B” JFR regulator utilizing single potential source for motor and control circuit.
Typical arrangement of windings and connections of Type “B” JFR regulators.
Note: Inverted design units may or may not be
equiped with a balance winding. Refer to regulator nameplate.
Page 12
egulato
ate
CONNECTION DIAGRAMS
Page 8
SERIES TRANSFORMER DESIGN
S L
SL
Wiring diagram of a typical regulator with series transformer showing both internal and external connections.
SOURCE
S
Schematic diagram of a typical regulator with series transformer with fan power U3-U5.
*Note: Exciting Winding may not be fully tapped.
Refer to r
r namepl
L
.
LOAD
SL
Typical arrangement of windings and connections of Series JFR regulators, without fan power.
Note: Series Transformer design units may or may
not be equiped with a balance winding. Refer to regulator nameplate.
Page 13
PLACING THE REGULATOR IN SERVICE
The following checks will be useful in assuring the regulator is ready for use. The list cannot be all inclusive; careful at­tention on the part of a qualified operator remains imperative.
BEFORE CONNECTING
Check oil level at oil sight window. If low, add sufficient oil (ASTM D-3487 Type II) to bring to desired level.
Check oil dielectric strength per ASTM D 877. If found below 25kV, oil should be changed or reconditioned. Reference ANSI C57.106-2002. Note: Oil tests are not required for new equipment.
Perform insulation power factor test per ANSI C57.15. Maximum value is 2.0%.
Verify from the nameplate that the unit is connected for the proper output voltage, motor voltage and con trol panel voltage.
Assure that the regulator is on the neutral tap position. This should be accomplished by observing the position indicator pointer and by powering the control from a 120V external source and observing the Neutralite
illuminated.
TM
to be
Follow instructions to place into service:
1. Place the Auto/Manual switch in the By-Pass position
2. Place the Raise/Lower switch in "Off"
3. Make certain regulator is in neutral (N) position
4. Turn voltage power source switch to "Off"
5. Remove power fuse
6. Close, sequentially, the source and load switches
7. Open the bypass switch
8. Visually observe that bypass circuit has opened
9. Replace power fuse
10. Place voltage power source switch to "Normal."
Improper By-Pass operation will result in explosion and fire hazard. Will cause serious injury, death or equipment damage.
To Prevent: Do NOT install OR remove from
service unless Tap Changer is in neutral position AND Control Panel is properly disabled to prevent tap changes while in By-Pass configuration. Read Operators Manual before attempting to By­Pass this Regulator.
Page 9
BEFORE CONNECTING
Identify 'S', 'L' and 'SL' bushings on the cover. Make elec- trical connections per the appropriate installation diagrams, page 4, first connecting 'SL' bushing.
TM
Set Vari-Amp See Page 11.
Set Accu/Stat instruction manual.
limits on position indicator, if necessary.
TM
Control as desired. See Accu/StatTM
SWITCHING “ON-LINE”
Improper by-pass operation will result in explosion and fire hazard. Will cause serious injury, death or equipment damage.
Do NOT place into service unless tap-changer is in neutral position AND control panel is properly disabled.
CHECKING REGULATOR OPERATION
1. Refer to applicable Accu/StatTM Control instruction manual.)Turn the Tap Control switch to MANUAL.
2. Run the tapchanger in the lower direction, at least until the control is observed to go out of band "LOW".
3. Turn the Tap Control switch to AUTO. After a time delay, the regulator will return to an "IN" band condition.
4. Turn the Tap Control switch to MANUAL.
5. Run the tapchanger in the raise direction, at least until the control is observed to go out of band "HIGH".
6. Turn the Tap Control switch to AUTO. After a time delay, the regulator will return to an "IN" band condition.
Page 14
REMOVING THE REGULATOR FROM SERVICE
Page 10
SWITCHING “OFF LINE”
Improper by-pass operation will result in explosion and
fire hazard. Will cause serious injury, death or equipment damage.
Do NOT remove from service unless tap-changer is in
neutral position AND control panel is properly disabled.
If the regulator being removed is in a closed delta bank,
it is necessary to bypass and isolate all regulators in the bank.
Improper By-Pass operation will result
Follow instructions to remove from service:
1. Place the Auto/Manual switch in the By-Pass position
2. Place the Raise/Lower switch in "Off"
3. Make certain regulator is in neutral (N) position. If independent checks of the position indicator and NeutraliteTM indicator do not confirm the neutral position, bypassing must not be attempted. In such event, de­energize the system to remove the regulator from service
4. Turn voltage power source switch to "Off"
5. Remove power fuse
6. After assuring the voltage regulator is on neutral, close the bypass switch
7. Open sequentially, the load and source switches
8. (a) For a single phase or grounded wye connection, make sure that the high voltage disconnect switches are opened (b) For a closed delta connection, be sure all regulators in the bank are bypassed and isolated
9. Exercise appropriate care in the removal of the regulator. High voltage will still be present at the bypass switch and the source and load switch terminals. Remove the ground connection last.
in explosion and fire hazard. Will cause serious injury, death or equipment damage.
To Prevent: Do NOT install OR remove from
service unless Tap Changer is in neutral position AND Control Panel is properly disabled to prevent tap changes while in By-Pass configuration. Read Operators Manual before attempting to By-Pass this Regulator.
Page 15
MAINTENANCE
Page 11
GENERAL INSTRUCTIONS
This manual does not represent an exhaustive survey of maintenance steps necessary to ensure safe operation of the regulator. Particular applications may require further pro­cedures. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred to the local Siemens sales representative.
WARNING
Failure to properly maintain the regulator can result in serious injury, death, or equipment damage. The instructions contained herein should be carefully reviewed, understood and followed.
To prevent: The following maintenance procedures should be
performed regularly:
1. Operational checks.
2. Periodic inspection.
OPERATIONAL CHECKS
Basic regulator operation can be checked while the regulator remains in service. The output voltage can be monitored from the control panel display under the <METER> menu on the “Vld” screen.
• Check the calibration by following the steps in the Basic Troubleshooting section of the Accu/Stat control panel instruction manual.
• Run the tapchanger several steps in one direction in the manual mode until the output voltage is outside of the bandwidth. Return the control to automatic mode. After the predetermined time delay, the tapchanger motor will be observed to return the output voltage in-band. Repeat this operation, running the tapchanger in the opposite direction.
• Check the Vari-Amp tapchanger beyond the position to which the switches are set. The limit switches should function to open the circuit. Note: If the limit switch is set at the maximum 10% range and fails to function, the tapchanger w ill stall again st a mechanical stop. The motor is designed to stall continuously without damage.
TM
limit switches by attempting to run the
Hazardous voltages. Will cause serious injury, death, or equipment damage.
To prevent: Always de-energize and ground the equipment before
maintenance requiring access to high voltage parts.
WARNING
The use of unauthorized parts in the repair of the equipment, tampering by unqualified personnel, or faulty repair and adjustments can result in dangerous conditions which can cause serious injury, death, or equipment damage.
To prevent: Follow all safety instructions contained herein, and contact
your local Siemens sales representative for replacement parts.
CAUTION
Operation of the regulator at extreme tap positions could produce line voltages outside of operating limits that could result in property damage.
To prevent: Operate the regulator only to judiciously determined
voltage extremes.
WARNING
Regulator may have High Internal Pressure. Can cause serious injury, death, or equipment damage.
To prevent:
Use pressure relief valve to vent regulator before untanking.
Page 16
A
A
MAINTENANCE
Page 12
PERIODIC INSPECTION
A sample of oil from the regulator should be subjected to dielectric breakdown test, per ASTM D-877. If found below 25kV, the oil should be changed or reconditioned. Refer to ANSI C57.106-2002. Other tests, especially Neutralization Number, Interfacial Tension and Power Factor are also useful and may be preferred by particular users.
The oxidation inhibitor in the oil will be depleted over a per iod of a few years and should be replaced. The inhibitor is 2, 6­ditertiary-butyl-para-cresol (DBPC) at a concentration level of
0.2 to 0.3%. The time interval between internal inspections will depend
upon frequency of tapchanger operation and the load on the regulator. Regulators subjected to numerous overloads and a high load factor may require more frequent inspections than those carrying normal loads. While internal inspection is not a necessity, preventive maintenance inspections will help assure the continuity of service.
When inspecting, check to be certain all hardware and con­nections are tight. The principal point of the internal inspection will be the condition of the arcing contacts on the tapchanger. Since numerous factors influence the rate of contact tip wear, no one criteria can be stated to recommend when a contact should be changed.
The following figure shows the possible condition of contact wear after a period of operation. If the contact surface is less than 1/8 inch wide, the contact should be replaced. (See the Figure below)
Contacts, both movable and stationary, show normal burning and wear once placed in service. If for any reason A1 dimensions exceed 4/5 of A, the stationary contact should be replaced. (See the Figure below)
To untank a JFR regulator, proceed as folllows:
1. Remove the regulator from service as described on
Page10.
Hazardous voltages. Will cause serious injury, death, or equipment damage.
To prevent: Always de-energize and ground the equipment before
maintenance requiring access to high voltage parts.
2. Place the regulator in a position where energized overhead lines will not interfere.
3. Operate pressure relief valve to vent regulator before un­tanking
4. Remove the mounting bolts holding the control box onto the main tank.
5. Remove all cover bolts.
6. The regulator can now be pulled from the main tank by the cover lifting eyes.
1
UPPER FILTER PRESS SEALING
If cover top cap is removed, make certain the cap is properly sealed when replaced on cover. Siemens recommends applying pipe sealant (Loctite PST or equivalent) around the threads of the adapter. Furthermore, it is recommended that the seal be tested by applying 5 psig pressure through the pressure relief valve fitting for 5 minutes, with no loss in pressure. Failure to assure seal may allow moisture to be pulled into the unit during a cool-down cycle.
FAN MAINTENANCE
Cooling fans (if equipped), require minimum attention. Fans with plain sleeve bearings or least once a year with SAE 10-W engine oil which does not thicken in cold weather. Oil must be added to sleeve bearings before starting motor for the first time after installation.
Fans equipped with ball bearing motors are packed with grease before shipment and should be greased at least once a year with a soda-soap, ball-bearing grease of medium consistency furnished by a reliable supplier.
Oil-Lite sleeve bearings should be oiled at
Page 17
SPECIAL FEATURES Page 13
POLARIZED DISCONNECT SWITCH VARI-AMP (JACK PLUG) AND HINGED CONTROL PANEL
The Accu/StatTM control panel is hinged and may be re­moved completely from the regulator control box by removing the wing nuts on the polarized jack plug and pulling the jack from its fixed position. Th is will automatically de-energize the control. It is not necessary to bypass or de-energize the regulator to remove the control.
A spring-loaded shorting bar in the plug automatically short circuits the current transformer secondary when the jack is removed.
The Vari-Amp regulator at increased load by decreasing the range of op­eration. It provides operator flexibility by allowing the range of regulation to be adjusted in 1¼ percent increments. The various regulation ranges together with the corresponding current capacities for standard regulators are listed on the next page. All that is necessary to adjust the range of regulation anywhere from ±5 percent to ±10 percent is to turn the adjusting knobs until the proper range of regulation is shown on the side of the position indicator. The upper and lower limits need not be the same.
It is not necessary to remove the regulator from service to make this adjustment. The switches are, however, in the motor power circuit so the motor should not be runnin g while the switches are being set.
TM
TM
POSITION INDICATOR
feature provides a method of operating the
REMOTE MOUNTING OF CONTROL EQUIPMENT
The Accu/StatTM control may be remotely mounted. Remote cable is available in standard lengths of 18, 25 and 30 feet incorporating oil and moisture resistant, color-coded conductors.
Page 18
SPECIAL FEATURES
Page 14
OPERATION AT LESS THAN
RATED VOLTAGE
JFR regulators may be operated at less than the voltage for which they were de­signed. All system voltages for which control system taps have been provided are shown on the nameplate. When this is to be accomplished it may be neces­sary to reconnect particular leads at the upper 19-pin terminal block as illustrated on page 5. When operating the regulator at reduced voltage it must be noted t hat the regulator carries a maximum current rating which rules regardless of the voltage (see table at right). It may therefore be necessary to operate the regulator at less than its nameplate kVA rating.
Units with catalog number starting with: 10 are self cooled
11 are forced-air cooled
VARI-AMPTM RANGE AND CURRENT RATINGS AVAILABLE
±10% ±8 3/4% ±7 1/2% ±6 1/4% ±5%
10-02.5-050.0 200 220 240 270 320 10-02.5-075.0 300 330 360 405 480
10-02.5-100.0 400 440 480 540 640 10-02.5-167.0 668 668 668 668 668 10-02.5-250.0 1000 1000 1000 1000 1000 10-02.5-333.0 1332 1332 1332 1332 1332 11-02.5-416.3 1665 1665 1665 1665 1665
10-05.0-050.0 100 110 120 135 160 10-05.0-100.0 200 220 240 270 320
10-05.0-167.0 334 367 401 451 534 10-05.0-250.0 500 550 600 668 668 10-05.0-333.0 668 668 668 668 668 11-05.0-416.3 835 835 835 835 835
10-07.6-038.1 50 55 60 68 80 10-07.6-057.2 75 83 90 102 120 10-07.6-076.2 100 110 120 135 160
10-07.6-114.3 150 165 180 203 240 10-07.6-167.0 219 241 263 296 351 10-07.6-250.0* 328/347 361/381 394/416 443/468 525/555 10-07.6-333.0* 437/463 481/509 524/556 590/625 668/668 10-07.6-416.3* 546/578 601/636 656/668 668/668 668/668 10-07.6-500.0 656 668 668 668 668 10-07.6-667.0 875 875 875 875 875
11-07.6-889.0 1167 1167 1167 1167 1167 10-13.8-069.0 50 55 60 68 80
10-13.8-138.0 100 110 120 135 160 10-13.8-207.0 150 165 180 203 240 10-13.8-276.0 200 220 240 270 320
Regulators can be modified at factory for 50 Hz operation with appropriate de-rating of voltage.
*Capable of carrying current corresponding to rated kVA when operated at 7200/12470 volts ground wye.
10-14.4-072.0 50 55 60 68 80 10-14.4-144.0 100 110 120 135 160 10-14.4-288.0 200 220 240 270 320
10-14.4-333.0 231 254 277 312 370 10-14.4-432.0 300 330 360 405 480 10-14.4-576.0 400 440 480 540 640 11-14.4-720.0 500 550 600 668 668 10-14.4-833.0 578 636 668 668 668
10-19.9-100.0 50 55 60 68 80 10-19.9-200.0 100 110 120 135 160
10-19.9-333.0 167 184 201 226 268 10-19.9-400.0 200 220 240 270 320 10-19.9-667.0 335 368 402 452 536 11-19.9-833.0 418 459 502 565 668
Page 19
SPECIAL FEATURES Page 15
FORCED AIR COOLING
Certain regulators may be equipped for forced-air cooling and include fans mounted on the radiators. The fans are usually automatically controlled by means of the change in oil temperature (see Connection Diagram). The thermometer located in the top transformer oil contains two identical switches which control fan operation when fan control switch is
in “Auto” position.
The switches are normally set to start the fans at 65°C and to stop them at 55°C top oil temperature, but may be adjusted plus or minus 5°C.
A thermal overload relay is mounted on each fan motor. Any fan that develops trouble will be auto matica lly disconne cted from the line without affecting the other fans of the system. One fan can be removed from the radiators without affecting the operation of the others. When fans are out of service, care must be exercised to prevent overloading the regulator.
SUBBASE ASSEMBLY
Subbase assemblies are available in 4-inch high increments from 21 through 49 inches for most JFR regulators. The proper height is selected by picking the elevation that will provide required clearance from foundation to the li ve part o f the regulator bushing.
Page 20
A
PARTS LIST
Page 16
MAJOR COMPONENTS PARTS LIST
Instructions For Ordering Part
When ordering parts give the quantity of parts required, the regulator serial number, parts list item number, complete description, and method of shipping. State whether for emergency repair, maintenance, spare part, etc.
ll shipments will be made F.O.B Factory
Item
01-11
5050A 5079 5081 5083 5084 5085 5087 5088 5092 5094B 5095 5246 5287
17 80 81A 90A
Control Compartment Gasket Position Indicator Main Cover Gasket Pressure Relief Valve Terminal Box Gasket Nameplate Sampling Device Grounding Lug Terminal (not shown) Terminal Block Clamp Terminal Block Studs Terminal Block Gasket Motor Capacitor TLG Motor Capacitor TLF Drain Valve Oil Sight Glass Oil Sight Gauge Gasket Bolts - Stainless Steel
Description
Page 21
PARTS LIST
TYPE TLG DIAL SWITCH
Page 17
Item
01-11
5320 5317A
5321 5322 5323 5324 5325 5326 5327
Description
Panel Reversing Main Shaft Main Stationary Contacts Reversing Stationary Contact R Reversing Stationary Contact L Neutral Stationary Cont act Collector Ring Collector Hub Reversing Switch Arm
Item
01-11
5328A
5328B 5329 5330
5331
5332
5333
5334
5336
Description
Reversing Switch Finger Assembly Reversing Switch Hub Finger Assembly Drive Arm Hub Finger Support Ring Finger Support Main Moving Finger Assembly Hub Finger Assembly Ring Finger Assembly Phenolic Drive Pin
Page 22
p
PARTS LIST
Page 18
TYPE TLG QUICK BREAK MECHANISM
Item
01-11
5201G 5202 5207
5212 5213
5214 *5216A *5216B *5216C
5217
5229 5231 5233A 5234
5237
Description
Mounting Frame Assembly Motor Drive Spring Assembl y Latch Assembly
Latch Spring (not shown) Latch Pin (not shown) Reversing Switch Drive A rm - Phenolic Reversing Switch Drive A rm - Phenolic Rev. Switch Drive Arm – Glass P henolic
Interlock Disk And Drive Assembly Main Shaft w/Sleeve Bearing Motor Mounting Bracket Operation Counter Switch Assembly Roller Chain Position I ndicator Reversing Switch Shaft
Item
01-11
5238
5240 5241 5242
5243A
5244 5245A
5246
5247 5248 5250
5273
5600 5600A
Description
Reversing Switch Assembly
Spring Spring Tube Position Indicator Dri ve Mechanism Neutral Switch Index Plate Motor Sprocket Capacitor for Motor Sprocket Assembly Main Drive Chain Assembly Drive Pin
Phenolic S Flexible Shaft
Flexible Shaft O-Ring
acer
Page 23
PARTS LIST
TYPE TLF DIAL SWITCH
Page 19
Item
01-11
5351 5352 5353 5354 5355 5356 5357
5358A
5359
5360A
Description
Panel Stationary Contact Neutral Stationary Cont act Stationary Contact - LH Stationary Contact - RH Collector Ring Shaft Assembly Main Finger Assembly (each) Contact Finger Assembly Co llector Ring
Contact Finger Assembly Co llector Hub
Item
01-11
5363
5364 5365
5366
5367 5368 5369 5370 5373
FIGURE 20A
Description
Drive Plate
Contact Finger Assembly - Rev. S witch Contact Support Assembly Reversing Drive Pin Reversing Shaft Spacer Contact Finger Support Contact Finger Support Reversing Switch Stop
Page 24
PARTS LIST
Page 20
TYPE TLF QUICK BREAK MECHANISM
Item
01-11
5233A 5243B 5251 5252 5256 5257 5259 5260 5262 5263 5264 5265
Description
Counter Switch Assembly Neutral Switch Mounting Frame Motor Drive Spring Tube Drive Spring Spacer Notched Index Plat e Latch Latch Spring Latch Pin
Reversing Switch Drive Arm
Item
01-11
5266 5267 5275 5276 5278 5285 5286
5287 5288 5289 5290 5291 5600
5600A
Figure 21A
Description
Interlock Disc and Drive Sprocket Assem bly Quick Break Mechanism Shaft Actuating Arm Assembly Spacer A-Frame Drive Chain for Positi on Indicator Motor Sprocket Motor Capacitor (may be located in control box)
Actuating Disc and Sprocket Main Drive Chain Position Indicator Dri ve Mechanism Reversing Switch Spring Assembly
Flexible Shaft Flexible Shaft O-Ring
Page 25
PARTS LIST
BYPASS ARRESTERS
Page 21
Item
01-11
5429
Include regulator serial number when ordering replacement parts
Description Volts
5423
Bypass Arrester Assembly 3 kV MOV 2,500, 5,000, 7,620 Mounting Bracket Assembly
5425
Bypass Arrester Assembly, 3 kV MOV 12,000-13,80 0-14,400
5423
Mounting Bracket Assembly
5425
Bypass Arrester Assembly, 6 kV MOV 19,920
5428
Mounting Bracket Assembly
Figure 22A
Figure 22B
Polymer arresters now used on voltage regulators. Supersedes previous porcelain arresters.
Page 26
PARTS LIST
Page 22
BUSHINGS
01-11
5400P
5400R
5400S
5401P
5401R
5401S 5410 5419 5411 5418 5426
5430
5427 4034
Item
Bushing Assembly for 15 kV 50 5000
38.1 thru 76.2 7620 69 thru 138 13,800
Bushing Assembly for 15 kV 50 2500
100 5000
114.3 thru 167 7620 Bushing Assembly for 15 kV 75 2500 414 13,800 Bushing Porcelain for 15 kV 50 5000
38.1 thru 76.2 7620
69 thru 138 13,800
Bushing Porcelain for 15 kV 50 2500 100 5000 Bushing Porcelain for 15 k V 114.3 thru 167 7620
Clamping Ring for 5400 and R Ratings 75 2500 Clamping Ring for 5400S Rating 414 13800 Cushion Spring Cap Screw
Bushing Cap Line Terminal for
5400P Rating
Bushing Cap Line Terminal for 5400R and S Ratings
Gasket Gasket
Description kVA Volts
Figure 23A
Page 27
PARTS LIST
BUSHINGS
z
Page 23
Item
01-11
5400T Bushing Assembly 15 kV 100 thru 167 2500
167 500
250 thru 509 7620 5400U Bushing Assembly, 15 kV 207-276 13,800 5400V Bushing Assembly, 23 kV 72 thru 144 14,400
100 thru 200 19,920
5400W Bushing Assembly 15 kV 333 thru 416.3 2500
250 thru 416.3 5000 5400X Bushing Assembly, 23 kV 576 thru 833 14,400 5400Y Bushing Assembly, 23 kV 288 14,400
333 thru 400 19,920
5400YY Bushing Assembly, 15 kV 333 12,000
5400Z Bushing Assembly, 23 kV 333 thru 432 14,400
5400AB Bushing Assembly, 23 kV 667 thru 833 19,920 5400AC Bushing Assembly, 15 kV 667-889 7620
5401T Bushing Porcelain, 15 kV 100 thru 167 2500
167 5000
250 thru 509 7620 5401U Bushing Porcelain, 15 kV 207-276 13,800 5401V Bushing Porcelain, 23 kV 72 thru 144 14,400
100 thru 200 19,920
5401W Bushing Porcelain, 15 kV 250 thru 416.3 2500
250 thru 416.3 5000 5401X Bushing Porcelain, 23 kV 576 thru 833 14,400 5401Y Bushing Porcelain, 23 kV 288 14,400
333 thru 400 19,920
5401YY Bushing Porcelain, 15 kV 333 12,000
5401Z Bushing Porcelain, 23 kV 333 thru 432 14,400
5401AB Bushing Porcelain, 23 kV 667 thru 833 19,920 5401AC Bushing Porcelain, 15 kV 7620
4025 Clamping Ring for 5400T
4026
4028
4030 4027 Gasket 4032 Gasket 4034 Gasket 4035 *Bushing Cap Line Terminal
5430
5426 5418
*Units rated 250 kVA and above, 2500 and 5000 volts are not supplied with line terminals
X, Z and AB Ratings Clamping Ring for 5400U
V, W (SL Bushing only), Y and YY Ratings
Clamping Ring for 5400W
Rating S and L Bushings only
Cushion Spring
for 5400T X, YY and AB Ratings
*Bushing Cap Line Terminal for
5400U, Y and Z ratings
*Bushing Cap Line Terminal for 5400V Rating Cap Screw
Description kVA Volts
Page 28
s
Siemens Energy, Inc. P.O. Box 6289 Jackson, MS 39288-6289 Phone: 601-939-0550 Fax: 601-939-3606
ACCU/STAT, DATA/PAK, NEUTRALITE and VARI­AMP are trademarks of Siemens Energy, Inc.
PR4018-06 PR4018-05 PR4018-04
October 08 PRINTED IN U.S.A.
Loading...