In the interests of user-safety (Required by safety regulations in some
countries) the set should be restored to its original condition and only
parts identical to those specified should be used.
Refrigerant; HFC-134a
Refer to "HFC-134a COOLING UNIT" Service Manual for handling this refrigerant.
T2G/T2A
T2G/T2A/T2W
T2G/T2A
This equipment complies with
the requirements of Directives
96/57/EC,89/336/EEC and
73/23/EEC as amended by
93/68/EEC.
DESTINATION ......................... 3
TABLE OF CONTENTS
page
ENERGY LABEL.............................................................................................................................................. 2
DESIGNATION OF VARIOUS PARTS............................................................................................................. 5
LIST OF ELECTRICAL PARTS........................................................................................................................ 6
THE FICHE ...................................................................................................................................................... 7
ASSEMBLING PROCEDURES OF MAIN PARTS AND CAUTIONS .............................................................13
MODIFICATION PROCEDURE OF THE DOOR OPEN SIDE ....................................................................... 21
COOLING UNIT ............................................................................................................................................. 24
REPLACEMENT PARTS LIST....................................................................................................................... 26
SHARP CORPORATION
1
SJ-58L-T2
SJ-63L-T2
SJ-68L-T2
ENERGY LABEL
Usage of "the ENERGY LABEL"
When displaying this refrigerator in the shop-window, attach the
"ENERGY LABEL" to it in the following procedure.
Fix the data part of
"ENERGY LABEL (DATA)"
on the data part of
"ENERGY LABEL (BASE)"
"ENERGY LABEL (DATA)"
(This label is in Operation manual)
E
A
B
C
D
E
F
G
G
Data part
"ENERGY LABEL (BASE)"
of each language
Refrigerator
INSTALLATION
Free standing type
To ensure adequate ventilation for this refrigerator, install with 6 cm space at the rear and both sides, with a
minimum space of 9 cm above the refrigerator.
9cm
6cm6cm
This refrigerator shall be used under the ordinary place condition between +5˚C and +43˚C of ambient
temperature, and also not be left under -10˚C for long days.
To be used this refrigerator within the range of the rated voltage ±6%.
2
CAUTIONS AND INFORMATIONS
In case of following troubles, the cause is not related with the failure of refrigerator.
Please mention the correct way to the customer for the use of refrigerator when the repairing.
1. Some foods freezed in the refrigerator compartment.
Do not place food directly in front of
cold air outlet.
This may lead to the food freezing.
SJ-58L-T2
SJ-63L-T2
SJ-68L-T2
cold air flow
IN
OUT
2. Some plastic parts were cracked or splitted.
Some household cleaning chemicals may affect the internal
food liner and plastic parts resulting in splitting or cracks
occurring.
When cleaning all plastic parts inside this refrigerator, only
use diluted dishwashing liquid(soapy water). Make sure that
all plastic parts are thoroughly rinsed with water after cleaning.
3. IT IS NORMAL for the refrigerator to produce the following sounds.
Cracking or crunching sound;
Sound produced by expansion and contraction of inner walls and internal parts during cooling.
Squeaking sound;
Sound produced by expansion and contraction of internal parts.
Sound of flowing fluid (gurgling sound, fizzing sound);
Sound of refrigerant flowing in pipes (sound may become louder from time to time).
1. ADJUSTABLE TEMPERATURE CONTROL
(1) Temperature control of freezer
Thermostat (senses freezer temperature) operates on ON/OFF switchover to control the compressor and
cool air circulating fan (F-fan motor) , and allows the freezer temperature to keep at a suitable temperature.
However adjust the freezer temp. control knob as follows depending upon the storing condition of foods.
MED
4
MIN
5
3
2
1
6
7
MAX
Coldest
KNOB
SETTING
MAX
(Coldest)
MED
FREEZER TEMP. CONTROL
Figure F-1.
MIN
(2) Temperature control of refrigerator
Damper-thermostat senses temperature of the refrigerator and changes the opening angle of the damper
automatically.
However, as the Damper-thermostat has no function to switch on or off the compressor and F-fan motor,
the freezer temperature control causes temperature in the refrigerator to vary to some extent.
However, adjust the refrigerator temp. control knob as follows depending upon the cooling condition.
FUNCTIONS
PURPOSE
For making ice rapidly or fast freezing.
When restocking with fresh food.
For normal freezing.
For storing frozen food for a short period (up to one month).
When frozen food or ice cream is not stored.
MED
4
3
2
5
6
CHILLED
ZONE
1
MIN
7 Coldest
REFRIGERATOR TEMP. CONTROL
Figure F-2.
KNOB
SETTING
CHILLED
ZONE
(Coldest)
MED
MIN
For keeping freshness of food longer.
When the refrigerator does not provide sufficient cooling.
For normal operation.
When the refrigerator provides excessive cooling.
PURPOSE
When the temperature of the refrigerator is higher, R-fan thermo. senses the temperature and the
refrigerator is cooled efficiently by running of R-fan motor.
R-fan thermo. heater energizes when the door is opened intend to promote to running of R-fan motor.
NOTE:The refrigerator temperature is affected also by the freezer temperature. If the freezer temp.
control knob is set at the position "MAX", the temperature tends to be lower than the following
values, and if set at near the position "MIN", temperature tends to be higher.
If the refrigerator is operated for a long time with the freezer temperature control sets the "MAX"
position, foods stored in the refrigerator compartment may also freeze.
When refrigerator temperature control sets to the "CHILLED ZONE", some foods stored may
freeze.
In this case adjust control set back to the "MED" position.
When refrigerator temperature control sets to the "CHILLED ZONE", some foods stored in chilled
case may also become frozen.
(3) Reference value of temperature
SETTING OF
FREEZER TEMP.
CONTROL KNOB
Freezer
temperature
MAX
(Coldest)
Approx.
-21 C
MEDMIN
Approx.
-18 C
Approx.
-15 C
SETTING OF
REFRIGERATOR TEMP.
CONTROL KNOB
Refrigerator
temperature
Chilled room
temperature
CHILLED
ZONE
(Coldest)
Approx.
0 C
Approx.
-3 C
MEDMIN
Approx.
3 C
Approx.
1 C
Approx.
Approx.
6 C
4 C
The values shown above refer to the case where the
freezer temp. control knob is set at "MED".
The values shown above refer to the measurement carried out center area and 1/3 of overall height from the bottom
at each of the refrigerator and the freezer after machine has been operated at an ambient temperature of 30˚C with no
food stored and the door closed until the temperature is stabilized.
The values vary depending upon frequency of opening and closing the door, ambient temperature, amount of stored
foods and manner of storing foods.
10
2. DEFROSTING
OperationElectric diagramDescription
1. Cooling
(Normal)
2. Defrosting
(Time 20 to 30 min.)
3. Drain
(Time approx. 5 min.)
4. Restart
(Time approx. 5 min.)
The integration timer integrates running
time of the compressor. When it reaches
cycle time of defrost timer, the timer
contact is changed to start defrosting.
When the defrost thermostat becomes
OFF, the timer motor starts running.
During the operation time (delay time
of defrost time)
defrosted water is
drained outside the refrigerator.
Timer contact is changed to cooling
operation and the compressor starts
running and the timer motor stops.
Defrost thermostat contact becomes ON
when it’s cooled. And the timer motor
starts running. (Figure F-3.)
Figure F-3.
Figure F-4 .
Figure F-5.
Figure F-6.
TMCOMP
Defrost thermostat ONCompressor running
Timer motor running
Timer contact
Defrost
thermostat (ON)
Defrost heater
Thermo. fuse
Compressor
Timer motor
SOURCE
TMCOMP
Defrost thermostat OFFCompressor running
Timer motor stops
ThermostatTimer contact
Defrost
thermostat (OFF)
Defrost heater
Thermo. fuse
Compressor
Timer motor
SOURCE
TMCOMP
Defrost thermostat OFFCompressor stops
Timer motor running
ThermostatTimer contact
Defrost
thermostat (OFF)
Defrost heater
Thermo. fuse
Compressor
Timer motor
SOURCE
TMCOMP
Defrost thermostat ONCompressor stops
Timer motor stops
ThermostatTimer contact
Defrost
thermostat (ON)
Defrost heater
Thermo. fuse
Compressor
Timer motor
SOURCE
Thermostat
The timer contact is changed to start
defrosting, the timer motor stops, and
power is supplied to the defrost heater.
It takes about 20 to 30 min. to defrost.
When little frosted, the defrosting takes
little time. When much frosted, the defrosting takes much time.
(1) No defrosting operation is necessary
No defrosting operation is necessary.
As this machine is so designed that a built-in
evaporator cools air and a fan circulates cooled
air, neither the freezer nor the refrigerator is
frosted, though the evaporator is frosted.
(2) Where is melted frost brought
1. Melted frost is brought into the evaporating
pan at the bottom of the set and is evaporated
here by the heat of sub condenser.
2. Be sure that the evaporating pan is inserted
correctly and is level.
The frosted evaporator is defrosted automatically
due to the function of defrosting timer and heater,
requiring no defrosting operation.
(3) The following circuit diagrams in the table show automatic defrosting function of the refrigerator with
timer and defrost thermostat.
SJ-58L-T2
SJ-63L-T2
SJ-68L-T2
11
Loading...
+ 25 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.