Sensaphone fGd-0007 Installation Instructions Manual

Page 1
®
Mounting Screws
Mounting Screw
SENSAPHONE
REMOTE MONITORING SOLUTIONS
Infrared MotIon detectIon SenSor • fGd-0007
InstallatIon InstructIons v.3.3
e Infrared Motion Detection Sensor is used to monitor the movement of warm bodies in a specic area. e range is a maximum of 40 feet directly ahead of, and approximately 20 feet to either side of, the detector at 40 feet distance (Figure 6). If motion is detected, the sensor will cause a dial-out to occur.
1. Remove front cover from sensor by placing a flat head screwdriver in slot located on side of sensor, then rotate the screwdriver.(Figure 1)
Screwdriver Slot
Figure 1: Removing the front cover
Warning: Do not face sensor toward the sun with the
cover off. This will damage the sensor.
2. Remove mounting screws from the holes in the PC board.
5. Mounting the back cover to the wall, using the accom­panying screws and the two knock-out slots for them in the back cover. The sensor must be mounted with the long dimension parallel to the floor and ceil­ing, with the sensor’s window to the left, not up. The detector can be mounted in either a surface wall mount position (Figure 3) or in a corner mount position (Figure 4). Recommended (most effective) mounting height is 4.5 feet.
WALL
Figure 3: Surface mounting the Sensor
WALL
Mounting Screw
WALL
3. Carefully remove the board from the pegs before attempting to screw the back plate to the wall.
4. Use a small screwdriver to punch out the cable-entry knock-out (indented circle) in the back cover of the Infrared Motion Detection Sensor.
Cable Entry
Knockout
Screw Mounting Holes
Figure 2: Cable entry knockout
Figure 4: Corner Mounting the Sensor
6. Run two wires through the cable knockout hole and connect them to the small terminal block (Output) on the side of the on the infrared circuit board opposite the reflector unit. (See Figure 5.)
Note: The sensor wiring is not polarity sensitive. It does not matter which wire goes to which screw ter­minal.
Page 2
Terminal
Side View
Block
(Output)
AA batteries
sPEcIFIcatIons
Normality: Normally closed
Range: Approximately 40 feet
Dimensions: 4” x 6” x 1.5”
JUMPER
Open for Lower
Sensitivity
Open for Multiple Events
Short for First Event
JUMPERJUMPER
Short for N/C Open for N/O
Figure 5: Circuit Board
7. Remount the circuit board on its three pegs and snap the front cover back on.
8. Run the two wires back to the Sensaphone unit. Connect one wire to any available alert input, the other to ground or common. The Infrared Motion Detection Sensor is a normally closed sensor.
9. Program the input normality as follows:
•For models 400, 800, 1400, 1800, 2800:
To be certain that the normal input state is closed,
take a piece of wire and attach it across the input terminals. This will force the input closed. Press Set, then Configure to set normality.
• For Sensaphone 2000, WEB600, SCADA 3000,
and Express II:
Program the input type as normally closed.
Consult your specific Sensaphone owner’s manual for further instructions.
40'
To p View
4.5'
40'
40'
Number per input: Multiple, wired in series.
WarrantY
1. WARRANTOR: Dealer, Distributor, Manufacturer
2. ELEMENTS OF WARRANTY: This Product is warranted to be free from defects in materials and craftsmanship with only the limitations and exclusions set out below.
3. WARRANTY AND REMEDY:
One-Year Warranty — In the event that the Product does not conform to this warranty at any time during the time of one year from original purchase, warran­tor will repair the defect and return it to you at no charge.
This warranty shall terminate and be of no further effect at the time the Product is (1) damaged by extraneous cause such as fire, water, lightning, etc. or not maintained as reasonable and necessary; (2) modified; (3) improperly installed; (4) repaired by someone other than warrantor; (5) used in a manner or purpose for which the Product was not intended; or (6) sold by original purchaser.
WARRANTORS’ OBLIGATION UNDER THIS WARRANTY IS LIMITED TO REPAIR OR REPLACEMENT OF THE PRODUCT. THIS WARRANTY DOES NOT COVER PAYMENT OR PROVIDE FOR THE REIMBURSEMENT OF PAYMENT OF INCIDENTAL OR CONSEQUENTIAL DAMAGES.
It must be clear that the warrantors are not insuring your premises or guaran­teeing that there will not be damage to your person or property if you use this Product.
The warrantors shall not be liable under any circumstances for damage to your person or property or some other person or that person’s property by reason of the sale of this product or its failure to operate in the manner in which it is designed. The warrantors’ liability, if any, shall be limited to the original cost of the Product. The warrantors assume no liability for installation of the Product and/or interruptions of the service due to strikes, riots, floods, fire, and/or any cause beyond Seller’s control.
4. PROCEDURE FOR OBTAINING PERFORMANCE OF WARRANTY: In the event that the Product does not conform to this warranty, the Product should be shipped or delivered freight prepaid to a warrantor with evidence of original purchase.
5. LEGAL REMEDIES: This warranty gives you specific legal rights, and you may also have other rights which vary from state to state to the extent allowed by law expressly in lieu of any other express or implied warranty, condition, or guarantee.
Figure 6: Distance Measurements
Note regarding Input Recognition Time: If your
equipment allows, set the input recognition time to 1 second. Most units default to 3 seconds, which may be too long to detect the alarm.
For technical support, call 877-373-2700
or email support@sensaphone.com
SENSAPHONE
®
901 Tryens Road Aston, PA 19014
www.sensaphone.com
LIT-0093 v3.3 3/13 © SenSaphone 2013