Model 1104/08 Owner’s Manual Addendum
Sensaphone BusinessSitter
How to use this Addendum
This is a supplement to the Sensaphone 1104/08 Owner’s Manual.
Review the entire manual before reading this addendum. This
addendum does not explain the Sensaphone setup, configuration,
or operation. The purpose of this addendum is to instruct you on
the use of the external relay functions of your Sensaphone to turn
on devices when an alarm occurs. These devices include an
audible sounder, strobe light, or even an X10 device in
conjunction with the use of the X10 Powerflash module, not
included. Use of X10 technology may aid in allowing the
activation of building lights or a VCR to capture and record alarm
events.
Sensaphone 1104/08 BusinessSitter Feature
The Sensaphone 1104/08 BusinessSitter allows you to monitor
and check on the status of your facility from any cellular or
ordinary telephone. The Sensaphone 1104/08 BusinessSitter turns
a device on when an alarm occurs. You can also inquire about the
status of the device during a voice status report.
This Sensaphone contains a relay contact on the rear of the unit
(see Figure 1). The relay contact supports a normally open relay.
When the Sensaphone detects an alarm condition, it closes this
relay, which then activates the device attached to the relay. The
relay remains closed throughout the alarm process, even while the
Sensaphone is making its alarm-response telephone calls out to
you. Reset of the alarm relay may occur either locally or remotely
via the telephone. This is discussed further in following sections.
The Sensaphone relay is a low voltage relay. Only voltages less
than 30 volts AC 2AMPS, or 30 volts DC 2 AMPS may be
switched. For higher voltages, an additional high-voltage relay
would be required.
Always enlist the services of a licensed electrician
when working with high voltages. Improper wiring
can cause harm to you or your property.
NOTE: For safety reasons it is highly recommended that the unit
only be used to switch low voltage signals (30 volts or less). If
Sensaphone®Model 1104/1108 User’s Manual
A-1

BusinessSitter Addendum
A-2
you intend to control higher voltages you must install the unit in an
NEC approved electrical panel or enclosure and have wiring
performed by a qualif ied electrician.
Switching the Output using the Keypad
To switch the output ON from the keypad:
1. Press STATUS.
2. Press 6.
To switch the output OFF from the keypad:
1. Press STATUS.
2. Press 3.
Switching the Output over the Telephone
1. Call the Sensaphone. When the unit answers it will begin
reciting a status report. At any time during the call, press a
touch-tone. The unit will respond with“OK.” The Sensaphone
is now ready to accept touch-tone commands.
2. On your phone, press # 6 to turn ON the output. The
Sensaphone will respond “ON.”
+
3. Press # 3 to turn OFF the output. The Sensaphone will respond
“OFF.”
3
INTERCALL
TIME
STATUS
CONFIGURE
6
CALIBRATE
STATUS
CONFIGURE

+
4. To check the present state of the relay press # 2.
+
This initiates a full recitation of the Status Report. At the
end of the status report, the Sensaphone will say, “Number
five On/Off” for the Model 1104 BusinessSitter, or
“Number nine On/Off” for the Model 1108 BusinessSitter.
Figure 1: Activating a Sounder or Strobe on Alarm
GND GND GND GND
1234
ALARM
RELAY
12–24 VA C or
12–24 VDC
Power Supply
–
+
Strobe Light
Sounder
Sensaphone®Model 1104/1108 User’s Manual
A-3

BusinessSitter Addendum
A-4
Relay Output Specifications
Rated Load: 2 A at 30 VAC
2 A at 30 VDC
Max. Operating Voltage: 30 VAC
30 VDC
Max. Operating Current: 2 A
Max. Switching Capacity: 60 VA
60 W
Every effort has been made to ensure that the information in this
document is complete, accurate and up-to-date. SENSAPHONE,
INC. assumes no responsibility for the results of errors beyond its
control. SENSAPHONE, INC. also cannot guarantee that changes
in equipment made by other manufacturers, referred to in this
addendum, will not affect the applicability of the information
herein.
Addendum © 2002 by Phonetics, Inc.
Written and produced by SENSAPHONE, INC. Please address all
comments on this publication to:
SENSAPHONE, INC.
901 Tryens Road
Aston, PA 19014
www.sensaphone.com
Sensaphone®is a registered trademark of Phonetics, Inc.
Touch-Tone™ is a registered trademark of AT&T.

Sensaphone®Model 1104/1108 User’s Manual
A-5