Securitron EcoPower EPS-05, EcoPower EPS-05B Owner's Manual

1 500-33530, Rev B
EcoPower™ Power Supply
Owner’s Manual
Table of Contents
Warranty....................................................................................................2
Models.......................................................................................................3
Structure....................................................................................................3
Block Diagram...........................................................................................4
Specifications............................................................................................4
Environmental ....................................................................................... 4
Mechanical ............................................................................................ 5
Electrical ................................................................................................ 5
Regulatory Certifications ....................................................................... 6
Regulatory Compliance ......................................................................... 7
UL294 Access Control Performance Levels for Model EPS-05
Power Supply ........................................................................................ 7
Status Signaling .................................................................................... 8
Access Control and FAI Operations
..........................................................8
Installing the EcoPower Power Supply...................................................11
Install the EcoPower Power Supply using the included enclosure
box (flush with the wall stud and wall surface) .................................... 11
Install the EcoPower Power Supply using the included enclosure
box and surface mounted .................................................................... 15
Install the EcoPower Power Supply flush with the stud in an
existing 2-gang junction box ................................................................ 17
Warranty
The EcoPower™ Power Supply is covered by the MagnaCare® lifetime replacement no fault warranty. No registration is required. Product will be replaced forever, for any reason, including but not limited to installation error, vandalism, or act of God. Replacement product is shipped at Securitron’s expense next day air if needed.
For more information, visit www.securitron.com
3 500-33530, Rev B
Models
EPS-05 EcoPower Power Supply in Enclosure
EPS-05B EcoPower Power Supply PCB only
Structure
4 500-33530, Rev B
Block Diagram
Specifications
Environmental
Parameter Value
Operating Ambient Temperature 0 to +49° Celsius (C) Design Product Life 10 years, +49°C ambient,
continuous full load Storage Temperature -25 to +85°C Operating Humidity 5 to 90%, non-condensing
Mechanical
Parameter Value
Enclosure Polycarbonate, UL294 Level 1 Enclosure dimensions 4 1/8” X 4 1/8” X 3 13/16” AC input wiring 3-wire with strain relief DC1, LOCK, BAT, FAI, ACC wiring 10-position terminal strip
Electrical
Parameter Value
Input Voltage Range 100–240 VAC, ±10% Input Frequency 50–60 Hz Input Surge Resistance 6000 Vpk Access Control Input Dry Contact, NO or NC; 32
VDC, 0.02A minimum Fire Alarm Interface Input Dry Contact, NO or NC; 32
VDC, 0.02A minimum Hi-Pot Test 2500 VAC or 3535 VDC Leakage Current < 0.5 mA Output Voltage at No Load Set to 14.0 VDC, ± 0.2% Number of Outputs Two (2) Outputs:
DC1 (Reader): 12 VDC nominal (9.4–14.6 VDC for compatibility) LOCK: 12 VDC nominal (9.4–
14.6 VDC for compatibility) If the battery is discharged below 9.4V, the lock output is de-energized
Total Peak Output Current 0.5A (Total current from both outputs for at least 1 second)
Total Continuous Output Current 0.1A (Total continuous current from both outputs)
Charging Current (BAT) 12 VDC nominal, 0.1A maximum continuous, 0.34A peak (< 2 seconds)
Standby Power < 20 mW at 230V, < 10mW at115V
Load Regulation < 2.5% at 100 mA Line Regulation < 0.2%
Output Voltage Ripple and Noise < 0.14 Vpp (20 MHz bandwidth limit measurement)
Output Surge Resistance 2400 Vpk Output Over Voltage Protection Under any single point
condition, output voltage shall not exceed 120% of nominal voltage
Battery Type and Capacity Sealed Lead Acid (SLA), 12V,
0.8 Ah Battery Standby Time 20.5 hours dependent on lock
type (FSA or FSE) and usage. Battery standby time is designed for EcoFlex lock with optional H1 controller only (not for 100 mA load). H1 controller draws an average of 5 mA. The two total current draw is about 20 mA.
Total Load Current 0.8 Ah Battery Backup Time
20 mA 20.5 hours 50 mA 6.5 hours
100 mA 2 hours
Regulatory Certifications
UL294, "Access Control System Unit," 6th Edition
UL603, "Power supply for use with Burglar Alarm System," 5th
Edition
CAN/ULC-S533, "Egress Door Securing and Releasing Devices,"
3rd Edition
GreenCircle Certified (99% Energy Savings)
NOTE: 50% - battery discharge time from fully charged
condition.
Loading...