Scotsman CME456R Service Manual

Introduction
CME456R
This product manual contains the information needed for the setup, installation, initial start up, sanitation and maintenance of this ice machine. Keep it for future reference.
Be certain that the information applies to the model in question. If no model is listed, the information applies to all models.
Table of Contents
Specifications .............. Page 2
Condenser and Ice Machine Layouts . . Page 3
Pre-Installation .............. Page 4
Location & Assembly ........... Page 5
Bin Control: Optional Installation ..... Page 6
For The Installer: Remote Condenser . . Page 7
Remote Condenser Location ...... Page 8
Coupling Instructions ........... Page 9
Technicians Only: Harvest Cycle Sequence & Other
Notes .................. Page 22
Sanitation and Cleaning ........ Page 23
Additional Maintenance ......... Page 24
Additional Maintenance: Inlet Water Valve Screen
......................Page 25
Additional Maintenance: Ice Sensors, Condenser
......................Page 26
Service Diagnosis: Diagnostic Light Analysis .
......................Page 27
Fan Relay Kit .............. Page 10
Electrical ................ Page 11
Plumbing ................ Page 12
After Utility Connections ........ Page 13
Component Location and Function . . . Page 14
AutoIQ Controller ............ Page 15
Initial Start Up .............. Page 16
Adjustments .............. Page 17
How To Operate The AutoIQ Controller Page 18
How The Electronic Cuber Works . . . Page 19
How The Electronic Cuber Works . . . Page 20
Technicians Only: Freeze Cycle Sequence . . .
......................Page 21
Service Diagnosis ........... Page 28
Service Diagnosis: Components .... Page 29
Service Diagnosis ........... Page 30
Operational Characteristics: CME456R Page 31
Removal and Replacement ....... Page 32
Removal and Replacement: AutoIQ Controller .
......................Page 33
Removal and Replacement: Water Level Sensor
......................Page 34
Refrigerant ............... Page 35
Before Calling for Service ....... Page 36
Parts Lists and Wiring Diagrams are in the section at the center of this manual.
December 2000
Page 1
CME456R
Specifications
This ice machines is designed to be installed indoors, in a controlled environment. It can operate satisfactorily under a wide variety of conditions. However, Do NOT operate the machine in temperatures it has not been designed for. Do NOT operate the machine above or below the voltage limits for the particular model. Do NOT operate the machine with too little or too much water pressure.
Ice Machine Operational Limits
Minimum Maximum
Air Temperature 50oF. 100oF.
Water Temperature 40oF. 100oF.
Water Pressure 20 psi 80 psi
Voltage (60 Hz) 104 126
Remote Condenser Operational Limits
Minimum Maximum
Air Temperature -20oF. 120oF.
Voltage (60 Hz) 104 126
Scotsman reserves the right to make design changes and/or improvements at any time. Specifications and designs are subject to change without notice.
Scotsman assumes no liability or responsibility of any kind for products manufactured by Scotsman that have been altered in any way, including the use of any parts and/or other components not specifically approved by Scotsman.
Bins:
Designed to fit a standard, 22" wide or wider open top Scotsman Ice Storage Bin. Some examples are:
BH360: Direct Fit
HTB555 - use KBT27
Bins with short or no baffles require the
addition of thermostat kit KSTAT-22 to lower the ice level
Dispensers
ID150: Add adapter kit KBT42
HD22: Direct fit
Condensers
Single Circuit, 60 Hz: ERC111-1
Dual Circuit, 60 Hz: ERC211-1
Also, a Fan Relay Kit is needed when connecting two ice machines to one condenser:
KCMR120 relay kit used with 115 volt 60 Hz
units
In addition, there may be other bins and dispensers that can be used, check Scotsman’s sales literature for application information.
Precharged Tubing:
25’ RTE25
40’ RTE40
75’ RTE75
BASIC INFORMATION
Dimensions
Model Number
CME456RS-1C 22“ x 24" x 28" 115/60/1
WxDxH (w/o bin)
Basic Electrical (volts/Hz/phase)
Use Condenser
ERC111-1A (1 ice machine) or ERC211-1A (2 ice machines)
Use precharged tubing kits, RTE25 (25’) or RTE40 (40’) or RTE75 (75’). Select the length closest to the needs of the particular installation.
June 2004
Page 2
Refrigerant Charge R-404A
192 oz 20 20
Minimum Circuit Ampacity
Maximum Fuse Size
Condenser and Ice Machine Layouts
CME456R
Bin Stat Thru Hole
12.88 in
32.7 cm
3.75 in
9.5 cm
Bin Stat Bracket Mounting Holes
8.75 in
22.2 cm
Plan View
11.38 in
28.9 cm
1.25 in
3.2 cm
2.63 in
6.7 cm
4.00 in
10.2 cm
1.75 in
4.4 cm
16.7 in
42.4 cm
22.00 in
55.9 cm
Ice Opening
December 2000
Page 3
CME456R
Pre-Installation
Other Applications:
Check sales literature for additional information.
Note: Slope-front bins must have an internal baffle. Scotsman BH375 has the required baffle, and the BH260 does not need one. Baffle must be approximately in the position shown in the diagram below.
Baffle
12.0"
4.0"
Side View
Electrical:
Check the nameplate for electrical requirements. The nameplate is located on the back of the ice machine. If the information on the nameplate is different from other published information, go by the nameplate data.
Water:
There is no such thing as pure water. All water contains some impurities. There are two ways water carries the impurities: suspended and dissolved. Suspended solids can be filtered out. Dissolved solids must be diluted or treated. Water filters are recommended to remove suspended solids. Some filters also have treatment in them for dissolved solids. Check with a water treatment service for a recommendation.
Cube Ice machines use more water than what ends up in the bin as ice. While most water is used during ice making, a portion is designed to “rinse" out the water system to keep hard water scale from clogging up the machine. That water rinse, combined with water filters, prolongs the times between needed water system cleaning.
Service Technicians: All models covered here come set from the factory with at a “Standard” water rinse. Standard water rinse is designed to be compatible with typical water conditions. The machine may be adjusted to a different water rinse after start up. If the prior ice machine worked acceptably well with the local water conditions, leave the machine at the factory setting. If severe water conditions are present, and water filters do not solve the problem acceptably, adjust the machine to use more water. If water conditions are excellent, adjust the machine to use less water. See the Adjustments section.
While the model and serial number are on the nameplate, a
serial number plate is located at the front of the machine, behind the front panel and to the right
of the purge valve.
Nameplate, on back panel
Serial Number Plate, remove front
panel to locate.
Note: Water use adjustments are customer convenience adjustments; they are NOT factory defects and are NOT covered by warranty.
December 2000
Page 4
Location & Assembly
CME456R
Locate the ice machine indoors. A 6 inch minimum clearance on the back and sides is required for the proper operation and service of this machine.
Locate the remote condenser as close as possible to the ice machine. See page 11 for details.
Unpacking and Assembly:
Begin with unpacking the ice storage bin. Remove the carton, and using part of the carton as a cushion, tip the bin on its back to remove the skid and attach the legs or casters.
Note: This unit may not be stacked.
Return the bin to an upright position. Check the bin top gasket for gaps and tears, fill any in with food grade sealant prior to placing the ice machine on the bin.
Note: If recycling a prior bin, be sure that the bin top gasket is in good condition or seal the ice machine to the bin with food grade sealant.
Level the top edge of the bin front to back and left to right.
Cabinet Panel Removal:
1. Remove the front panel by removing the two screws connecting the top of the front panel to the machine, then pull out at the bottom.
2. Lift up at the front edge and push the top panel back until it releases from the tabs connecting it to the back panel.
If the ice machine has not been unpacked, do so now. Remove the carton from the skid. Remove shipping straps.
Remove the front panel and all packaging materials.
After all packing materials have been removed from the ice machine, lift or hoist the machine onto the bin. Align the sides and back of the machine with the sides and back of the bin.
Secure the ice machine to the bin with the two metal straps and 4 bolts provided.
3. Remove two screws at the front of each side panel, and pull them forward until they release from the tabs connecting them to the back panel.
December 2000
Page 5
CME456R
Bin Control: Optional Installation
The normal bin control is the ice sensor system. A bin thermostat may be required in some cases, It must be field installed after the ice machine has been placed on the bin.
Before starting, remove the front panel and any baffle in the bin.
1. Place thermostat in machine behind the high voltage box. Secure to existing holes with two screws. Locate bin thermostat bulb.
6. Fasten the bracket to the bottom of the ice machine with the two 3-pronged knobs supplied with the unit.
7. Pull excess capillary tubing into the machine.
2. Route bulb thru routing tube (located between the compressor and the reservoir).
3. Connect harness to bin thermostat and to controller.
4. Locate bin thermostat bracket.
Routing Hole
8. Return the baffle to the bin and continue with the installation.
Note: If the machine is located at an altitude higher than 2,000 ft., adjust the thermostat by removing the plastic cover and rotating the adjustment screw per the table.
Bin Thermostat Altitude Correction Table
CW Turns of Range Screw (under plastic cover)
Feet Turns Feet Turns
2000 55
4000 160
o
o
8000 340
9000 385
o
o
5. Carefully position the thermostat bulb on the bracket.
December 2000
Use This Table to Adjust Thermostat
Page 6
For The Installer: Remote Condenser
CME456R
Locate the condenser as near as possible to the interior location of the ice maker.
Note: The location of the condenser relative to the ice machine is LIMITED by the specification on the following page.
Select the best available location, one that protects the condenser from excessive dust, grease & sun.
Meet all applicable building codes.
Roof Attachment
Install and attach the remote condenser to the roof of the building, using the methods and practices of construction that conform to the local building codes, including having a roofing contractor secure the condenser to the roof.
Note: If using any other condenser besides the ERC111 or ERC211, its use must be approved by Scotsman, and a head pressure control valve must be connected to the condenser coil.
Line Routing
Do not connect the tubing until all routing and forming of the tubing is complete. See the Coupling Instructions for final connections.
3. Route the refrigerant tubes thru the roof opening. Follow straight line routing whenever possible.
If connecting two ice machines, be sure that the tubes from ice machine #1 are connected to one circuit of the condenser and the tubes from ice machine #2 are connected to the other.
Note: Excess tubing may EITHER be coiled up INSIDE the building OR cut out prior to connection to the ice maker and condenser.
If the excess tubing is cut out, after re-brazing the tubing must be evacuated prior to connection to the ice maker or condenser.
If the excess tubing is to be coiled, spiral it horizontally to avoid excess trapping in the lines.
Note: A 36" service loop may be placed behind the ice machine.
5. Have the roofing contractor seal the holes in the roof per local codes.
ERC111 Remote
Condenser
Electrical Power
Supply
If two CME456R ice machines are to be installed, mark one as Ice Machine #1 and the other as Ice Machine #2. Tag their refrigerant lines the same way.
1. Each set of pre-charged tubing lines
3
contains a
1
” diameter discharge line. Both ends of
2
“ diameter liquid line, and a
8
each line have quick connect couplings, the end without access valves goes to the ice maker.
Note: The openings in the building ceiling or wall, listed in the next step, are the minimum sizes recommended for passing the refrigerant lines through.
2. Have the roofing contractor cut a minimum hole for the refrigerant lines of 2“. Check local codes, a separate hole may be required for the electrical power supply to the condenser.
Caution: Do NOT kink the refrigerant tubing while routing it.
Coil Excess
Tubing
Horizontally
Within the
Building
December 2000
Page 7
Typical Installation
CME456R
Remote Condenser Location
Use the following for planning the placement of the condenser relative to the ice machine
Location Limits - condenser location must not exceed ANY of the following limits:
Maximum rise from the ice machine to the
condenser is 35 physical feet Maximum drop from the ice machine to the
condenser is 15 physical feet Physical line set maximum length is 100
feet. Calculated line set length maximum is 150.
Calculation Formula:
Drop = dd x 6.6 (dd = distance in feet)
Rise = rd x 1.7 (rd = distance in feet)
Horizontal Run = hd x 1 (hd = distance in
feet) Calculation: Drop(s) + Rise(s) + Horizontal
Run = dd+rd+hd = Calculated Line Length
Configurations that do NOT meet these requirements must receive prior written authorization from Scotsman.
Do NOT:
Route a line set that rises, then falls, then
rises. Route a line set that falls, then rises, then
falls.
Calculation Example 1:
The condenser is to be located 5 feet below the ice machine and then 20 feet away horizontally.
5 feet x 6.6 = 33. 33 + 20 = 53. This location would
be acceptable
Calculation Example 2:
The condenser is to be located 35 feet above and then 100 feet away horizontally.
35 x 1.7 = 59.5. 59.5 +100 = 159.5. 159.5 is
greater than the 150 maximum and is NOT acceptable.
rd
22.87"
dd
17.15"
Max 35’
Max 15’
Remote
Condenser
Located ABOVE
Ice Machine
Remote
Condenser
Located BELOW
Ice Machine
hd
40.35"
Condenser Distance &
Location Schematic
December 2000
Page 8
Coupling Instructions
CME456R
The couplings on the ends of the pre-charged line sets are self-sealing when installed properly. Follow these instructions carefully.
These steps must be performed by an EPA Certified Type II or higher technician.
Initial Connections
1. Remove the protector caps and plugs. Wipe the seats and threaded surfaces with a clean cloth to remove any possible foreign matter.
2. Thoroughly lubricate the threads, o-rings, diaphragms and all internal coupling surfaces with polyolester refrigerant oil.
Clean and Lubricate Couplings
3. Position the fittings on the correct connections on the condenser and ice machine.
1
The
“ discharge line (schrader valve end)
2
goes to the remote condenser fitting marked “discharge line”.
3
The
“ liquid line (schrod valve end) goes to
8
the remote condenser fitting marked “liquid line”.
1
The
“ discharge line goes to the ice maker
2
fitting marked “discharge line”.
3
The
“ liquid line goes to the ice maker
8
fitting marked “liquid line”.
4b. Using two wrenches, one to rotate the swivel nut and one to hold the tubing in place, tighten each coupling.
It is CRITICAL that ONLY the NUT on the pre-charged tube be turned, or the diaphragms will be torn by the piercing knives and become loose in the refrigeration system causing severe operational problems.
Tighten Swivel Nut
Note: As the coupling is tightened, the diaphragms in the quick connect couplings will begin to be pierced. As that happens, there will be increased resistance to tightening the swivel nut.
4c. Continue tightening the swivel nut until it bottoms out or a very definite increase in resistance is felt (no threads should be showing). Do NOT overtighten.
5. Use a marker or pen to mark a line on the coupling nut and unit panel. Then tighten the coupling nut an additional one-quarter turn. The line will show the amount that the nut turns.
6. After all connections have been made, and after the liquid line valve has been opened (do not open yet), check the couplings for leaks.
Note: The system charge is contained in the receiver tank of the ice machine. Only “holding" charges are present in the “pre-charged" tubing or the condenser.
Final Connections:
4a. Begin to tighten the couplings together by hand. Continue to turn the swivel nuts by hand until it is certain that the threads are properly engaged.
December 2000
Rotate Swivel Nut ¼ Turn More
Page 9
CME456R
Fan Relay Kit
When two CME456Rs are located near each other and are connected to the same ERC211 remote condenser, a fan relay kit, KCMR120 is required to operate the condenser’s fan motor.
1. Attach the relay box of the KCMR120 to a location that is convenient for installation and future service.
2. Attach a solid earth ground wire to the ground screw.
Electrical Shock Hazard
Disconnect Electrical Power Before Beginning
3. Route the connecting wires from the first ice machine's fan wires to the relay kit terminal strip posts marked: No. 1 Ice Machine.
Put the Hot (line) wire on Terminal 1 and the
Neutral wire on Terminal 2.
4. Route the connecting wires from the second machine's fan wires to the relay kit terminal strip posts marked: No. 2 Ice Machine.
Put the Hot (line) wire on Terminal 3 and the Neutral wire on Terminal 4
5. Attach wires at the fan relay kit terminal strip marked: To Remote Fan, and route them to the remote condenser electrical connection.
Terminals 2 and 4 must be connected to a
common leg (such as N).
B. After initial start up, test with a volt meter (compressors must be ON).
1. Switch on ice maker #1, then ice maker #2.
2. Test with a volt meter between the terminals and ground.
3. List the voltages and compare them to what they should be.
Tested Voltage Should Be
Terminal #1 to ground: 104 to 126 volts
Terminal #2 to ground: near zero
Terminal #3 to ground: 104 to 126 volts
Terminal #4 to ground: near zero
Tested Voltage Was:
Terminal #1 to ground: _____
Terminal #2 to ground: _____
Terminal #3 to ground: _____
Terminal #4 to ground: _____
If the voltages are not correct:
A. Switch off ice maker number 2, and then switch off ice maker number 1.
B. After the units have stopped, disconnect the
electrical power. Do all wiring with the electrical power disconnected to BOTH ice makers at the source.
C. Reverse the connections at the KCMR120 terminal strip that measured incorrectly.
6. Make the proper electrical connection at the junction box.
Conform to all applicable codes.
of the KCMR120 kit has been accomplished, a check of the electrical phasing is required.
If the power is not connected properly the relay will fail in a cycle or two and there may be an electrical overload.
A. Before initial start up. Compare the illustration of the KCMR120 terminal strip to the connections at the KCMR120:
Terminals 1 and 3 must be connected to a common leg (such as L1).
December 2000
D. Reconnect electrical power.
KCMR120 RELAY BOX
Page 10
Electrical
CME456R
All models must be installed with the correct wire size and type per the National Electric Code. Locate the nameplate on the back of the cabinet and find the numbers for Voltage, Phase, Minimum Circuit Ampacity and Maximum Fuse Size. Either fuses or HACR type circuit breakers may be used.
The ice maker is designed to operate on its own electrical circuit and must be individually fused. Voltage variation must not exceed the limits listed on page 2.
The remote condenser is designed to be powered from the ice machine. A separate knockout hole has been provided in the ice maker electrical junction box.
Remote
Condenser
Note: Central Condensers connected to more than one refrigeration system will likely have a wiring scheme to control the fan motor. Follow those directions for condenser wiring.
Electrical connections are made in the junction box in the back of the cabinet.
1. Remove the junction box cover.
2. Knock out both holes for a field supplied strain relief.
3. Install wires and strain reliefs per code. Note: Condenser fan motor wires are tagged.
4. Connect to wires and secure ground wire to ground screw inside junction box.
All external wiring should conform to the national, state and local electrical code requirements. Usually an electrical permit and the services of a licensed electrician will be required.
Interconnecting
Wires
Power
Supply
Power IN
Power OUT
December 2000
Page 11
CME456R
Plumbing
All models require an adequate potable water supply and a gravity drain. The recommendations for tubing are:
Water supply to be
Drain to be
3
" OD.
4
3
" OD.
8
Note: When replacing a prior ice machine, do not take a short cut and reuse the old inlet and drain system. INSTALL A NEW SYSTEM.
Supply:
3
All models have 1 water supply connection, a
"
8
male flare at the back of the cabinet. Connect to cold potable water that has adequate pressure.
Note: Using water supply tubing smaller than
3
"
8
will cause severe operational issues.
Water Filters:
The water filters must flow at least 1.25 GPM or they will cause severe operational issues. Check with the filter manufacturer. When replacing a prior ice machine, do NOT assume that the water flow capacity of the filter will be adequate.
All Drain Tubing Material must be RIGID. Flexible tubing will eventually cause a restricted drain.
Drain:
3
All models have 1 gravity drain connection, a
"
4
FPT fitting at the back of the cabinet. Use only RIGID TUBING. Flexible tubing may be easily kinked or become cracked.
The drain tube must be vented at the back of the cabinet. Use an 18" high vent.
The ice storage bin will have a drain out the back or base, depending upon the model.
The drain for the ice machine and the ice storage bin must be SEPARATE or the ice machine’s drain water may run into the bin and MELT THE ICE.
Insulation is recommended for the ice machine reservoir and bin drains.
Follow all applicable codes
Bin Drain
Electrical OUT to
Condenser Fan
Electrical IN
Water IN
Water OUT
December 2000
Page 12
Loading...
+ 26 hidden pages