Scotsman CME2006R SERVICE MANUAL

Introduction
CME2006R
This product manual contains the information needed for the setup, installation, initial start up, sanitation and maintenance of this ice machine. Keep it for future reference.
This machine incorporates advanced technology, including a scroll compressor.
Be certain that the information applies to the model in question. If no model is listed, the information applies to all models.
TABLE OF CONTENTS
Introduction ..................PAGE 1
Specifications .................PAGE 2
Condenser and Ice Machine Layouts .....PAGE 3
Pre-Installation .................PAGE 4
Location & Assembly .............PAGE 5
Bin Control: Installation ............ PAGE 6
This manual is organized in the same way as the expected use of the machine, it begins with specifications, goes thru unpacking and setup, shows where everything is; continues with initial start up, then describes how it works. Afterthat is the sanitation section, followed by service diagnosis and repair.
All Scotsman CM3models, like this one, feature Scotsman’s AutoIQ™ control system and ReliaClean™ water system cleaning process.
How The Electronic Cuber Works ...... PAGE23
Technicians Only: Freeze Cycle Sequence . PAGE 24 Technicians Only: Harvest Cycle & Notes . . PAGE 25
Sanitation and Cleaning ........... PAGE26
Additional Maintenance ........... PAGE27
Additional Maintenance: Water Distributors . PAGE 28
Bin Control ...................PAGE 7
Stacking ....................PAGE 8
Stacking ....................PAGE 9
For The Installer: Remote Condenser .....PAGE 10
Remote Condenser Location .........PAGE 11
Coupling Instructions .............PAGE 12
Electrical ....................PAGE 13
Plumbing ....................PAGE 14
After Utility Connections ............PAGE 15
Component Location and Function ......PAGE 16
System Controller ...............PAGE 17
Initial Start Up .................PAGE 18
Startup: Three Phase Compressor ......PAGE 19
Additional Maintenance: Water Valve Screen PAGE 29
Additional Maintenance: Ice Sensors, Cond. . PAGE 30
Service Diagnosis: Diagnostic Lights .... PAGE31
Service Diagnosis .............. PAGE32
Service Diagnosis: Components ....... PAGE33
Service Diagnosis .............. PAGE34
Operational Characteristics: CME2006R . . . PAGE 35
Suction Pressure ............... PAGE36
Removal and Replacement ......... PAGE37
Removal and Replacement ......... PAGE38
Removal and Replacement: Controller .... PAGE39
Removal and Replacement: ......... PAGE40
Removal and Replacement ......... PAGE41
Adjustments ..................PAGE 20
How To Operate The System Controller . . . PAGE 21
How The Electronic Cuber Works .......PAGE 22
Printed on recycled paper.
July 1998
Page 1
Refrigerant .................. PAGE42
Liquid Charging ............... PAGE43
Before Calling for Service .......... PAGE44
Service parts list & wiring diagrams located
in the middle of this manual.
Specifications
CME2006R
Both of these ice machines are designed to be installed indoors, in a controlled environment. They can operate satisfactorily under a wide variety of conditions. However, Do NOT operate the machine in temperatures it has not been designed for. Do NOT operate the machine above or below the voltage limits for the particular model. Do NOT operate the machine with too little or too much water pressure.
Operational Limits
Minimum Maximum
Air Temperature 50
Water Temperature 40oF. 100oF.
Water Pressure 20 psi 80 psi
Voltage (60 Hz) 197 253
Voltage note: The control system transformer in the control box of this ice machine has two primary taps, one for 208 volt power and one for 240 volt power. The machine ships with the power supply connected to the 208 volt tap. Change to the 240 volt tap when the voltage supplied to the unit is greater than 229 volts.
o
F. 100oF.
Bins:
All models will fit a standard, 48" wide or wider open top Scotsman Ice Storage Bin. Some examples are:
BH900
BH1100
BH1300
BH1600
In addition, there may be other bins that can be used, check Scotsman’s sales literature for application information.
Note: Slope-front bins must have an internal baffle. Scotsman’s BH900 haas the required baffle. Baffle must be approximately in the position shown in the diagram below.
Baffle
Scotsman reserves the right to make design
12.0"
changes and/or improvements at any time. Specifications and designs are subject to change
4.0"
without notice.
Scotsman assumes no liability or responsibility of any kind for products manufactured by Scotsman that have been altered in any way, including the use of any parts and/or other components not specifically approved by Scotsman.
Side View
BASIC INFORMATION
Dimensions
Model Number
CME2006RS-32C 48 ½ “ x 24" x 28 208-230/60/1 ECR611-32A 336 oz 30 40
CME2006RS-3C same 208-230/60/3 ECR611-32A 336 oz 20 30
W x D x H (w/o bin)
Basic Electrical (volts/Hz/phase)
Use Condenser
* The remote condenser is designed to work in temperatures from -20oF. to 120oF.
Use precharged tubing kits, LRTE25 (25’) or LRTE40 (40’) or LRTE75 (75’). Select the length closest to the needs of the particular installation. NOTE: These line sets have a larger diameter discharge line than line sets for smaller Scotsman remote systems and are the only line sets that may be used with this product.
Refrigerant Charge R-404A
Minimum Circuit Ampacity
Maximum Fuse Size
The stacking kit required to place two like model cubers together is: KSCME6-LG-B.
November 2004
Page 2
Condenser and Ice Machine Layouts
c
55.3c
.88 DIA. ELECTRICAL INLET
DISCHARGE LINE 1/2" MALE CPLG.
29.50 in
74.9 cm
CME2006R
ERC611
.562 DIA. MOUNTING HOLES (4)
6.00 in
15.2 cm
CONDENSER FINS
32.16 in
81.7 cm
37.75 in
95.9 cm
MINIMUM FOR
UTILITY CONNECTIONS
2.75
38.47 in
97.7 cm
32.32 in
35.72 in
90.7 cm
15-0782-01CANCAUSE INJ URYOR DEAT H:DISCONNECTALLREMOTEELEC TR ICPOWERSUPP LIE S BEFORESERVICING.RISKOF ELECTRICSH OCK^MWARNING
2.84 in
7.2 cm
82.1 cm
28.07 in
71.2 cm
MINIMUM BIN TOP OPENING
PLAN VIEW
24.71 in
62.7 cm
7.60 in
19.3 cm
26.10 in
66.3 cm
11.50 in
29.2 cm
14.56 in
36.9 cm
27.56 in
70.0 cm
29.19 in
74.1
m
18.75 in
47.6 cm
.65 in
1.7 cm
LIQUID LINE 3/8" MALE CPLG.
AIR FLOW
ICE
OPENING
6.00 in
15.2 cm
MINIMUM FOR
AIR VENTILATION
REMOTE CONDENSER LIQUID LINE 3/8" MALE CPLG.
23.30 in
59.2 cm
22.65 in
57.5 cm
BACK VIEW
DUMP VALVE DRAIN 3/4" F.P.T.
REMOTE CONDENSER DISCHARGE LINE 1/2" MALE CPLG.
WATER INLET 3/8" FLARE
July 1998
4.20 in
10.7 cm ICE
OPENING
18.67 in
47.4 cm
Page 3
.88 DIA. KNOCKOUT ELECTRICAL INLET
15.77 in
40.1 cm
21.77 in m
10.15 in
25.8 cm
2.50 in
6.4 cm
5.87 in
14.9 cm
17.87 in
45.4 cm
2.46 in
6.2 cm
3.81 in
9.7 cm
.88 DIA. KNOCKOUT REMOTE CONDENSER FAN
23.87 in
60.6 cm
Pre-Installation
CME2006R
Other Applications:
Check sales literature for additional information.
Electrical:
Check the nameplate for electrical requirements. The nameplate is located on the back of the ice machine. If the information on the nameplate is different from other published information, go by the nameplate data.
While the model and serial number are on the nameplate, a serial number plate is located at the front of the machine, behind the left front panel and to the right of the purge valve.
Nameplate
Serial Number Plate
Water:
There is no such thing as pure water. All water contains some impurities. There are two ways water carries the impurities: suspended and dissolved. Suspended solids can be filtered out. Dissolved solids must be diluted or treated. Water filters are recommended to remove suspended solids. Some filters have treatment in them for suspended solids. Check with a water treatment service for a recommendation.
Cube Ice machines use more water than what ends up in the bin as ice. While most water is used during ice making, a portion is designed to “rinse" out the water system to keep hard water scale from clogging up the machine. That water rinse, combined with water filters, prolongs the times between needed water system cleaning.
Service Technicians: All models covered here come set from the factory with at a “Standard” water rinse. Standard water rinse is designed to be compatible with typical water conditions. The ReliaClean™ water system provides an adjustment method so the amount of water rinsed out of the machine per cycle can be changed. If the prior ice machine worked acceptably well with the local water conditions, leave the machine at the factory setting. If severe water conditions are present, and water filters do not solve the problem acceptably, adjust the machine to use more water. If water conditions are excellent, adjust the machine to use less water. See the Adjustments section.
Note: Water use adjustments are customer convenience adjustments; they are NOT factory defects and are NOT covered by warranty.
July 1998
Page 4
Location & Assembly
CME2006R
Locate the ice machine indoors. A 6 inch minimum clearance on the back and left sides is required for the proper operation and service of this machine.
Locate the remote condenser as close as possible to the ice machine. See page 11 for details.
Unpacking and Assembly:
Begin with unpacking the ice storage bin. Remove the carton, and using part of the carton as a cushion, tip the bin on its back to remove the skid and attach the legs or casters. Note: Stacked
applications may not use casters.
Return the bin to an upright position. Check the bin top gasket for gaps and tears, fill any in with food grade sealant prior to placing the ice machine on the bin.
Note: If recycling a prior bin, be sure that the bin top gasket is in good condition or seal the ice machine to the bin with food grade sealant.
Level the top edge of the bin front to back and left to right.
Cabinet Panel Removal:
1. Remove the front panels by removing the four screws connecting the front panels to the machine.
2. Lift up at the front edge and push the top panel back until it releases from the tabs connecting it to the back panel.
If the ice machine has not been unpacked, do so now. Remove the carton from the skid. Remove shipping straps.
Remove the left side and front panels. Remove all packaging materials including the compressor shpping brackets..
After all packing materials have been removed from the ice machine, lift or hoist the machine onto the bin. Align the sides and back of the machine with the sides and back of the bin.
Secure the ice machine to the bin with the two metal straps and 4 bolts provided.
3. Remove two screws at the front of each side panel, and pull them forward until they release from the tabs connecting them to the back panel.
Evaporator Cover:
To Remove
Evaporator Cover:
Push Up and Tilt Out
November 2003
Page 5
Bin Control: Installation
CME2006R
The bin control is a thermostat. It must be field installed after the ice machine has been placed on the bin.
Before starting, remove the left front panel and any baffle in the bin.
1. Locate bin thermostat bulb.
2. Route bulb thru routing tube (located between the compressor and the reservoir).
3. Locate bin thermostat bracket.
4. Carefully position the thermostat bulb on the bracket (see the diagram on the next page).
5. Fasten the bracket to the bottom of the ice machine with the two 3-pronged knobs supplied with the unit.
6. Pull back into the ice machine any excess capillary tubing.
7. Return the baffle to the bin and continue with the installation.
Note: If the machine is located at an altitude higher than 2,000 ft., adjust the thermostat by removing the plastic cover and rotating the adjustment screw per the table.
Bin Thermostat Altitude Correction Table
CW Turns of Range Screw (under plastic cover)
Feet Turns Feet Turns 2000 55 4000 160 6000 250
o
o
o
8000 340 9000 385 10000 405
Use This Table to Adjust Thermostat
o
o
o
Bin
Thermostat
Body
Bin Thermostat Bulb
Thermostat Bulb
Routing Tube
Route Bin Thermostat Bulb Into Bin
July 1998
Page 6
Bin Control
Bin Thermostat
Bracket
CME2006R
Bin Thermostat Capillary Tube
Mount Bulb Here
Minimize Excess
Tube in Bin
Attach Thermostat Bulb to Bracket
Three-Pronged Knob
Thermostat and
Bracket
Attach Bracket to Bottom of Ice Machine
July 1998
Page 7
Stacking Kit - KSCME6-LG-B
CME2006R
Only like models may be stacked. Begin after the bottom unit has been placed on the ice storage bin and secured. Stacking requires heavy duty leg kits. Casters are NOT recommended.
Note: Instructions are for either model.
Bottom Machine:
1. Remove front panel, left side panel, and top panel.
2. Remove & discard top cover from over the freezing compartment.
3. Install gasket materials to freezing compartment:
Cut about 22" of gasket material from the roll in the kit. Apply it to the back side top edge of the freezing compartment.
Cut two lengths of gasket material to fit the right side top edge of the freezing compartment and apply them.
4. Place a bead of food grade sealant to the top of the back wall’s gasket.
5. Place the shield bracket (has a large hole in the center) from the kit over the center of the freezing compartment.
Insert the tabs of the bracket into slots on the back of the unit.
6. Secure bracket at the front with screws from the kit.
7. Hang the plastic shields from the bracket installed in the prior step. Use the slots in the shields to hang them from the stainless steel hooks.
Note: The notch in the bottom of the shield goes to the front.
11. Remove two existing screws and secure the bracket to the: freezing compartment, back panel and front channel with the 2 existing screws and 1 large and 4 small screws from the kit.
Both Machines:
12. Place the top ice machine onto the bottom one. Secure together with hardware from the top machine. Remove left front and left side panels.
13. At the back of the ice machines, on the compressor end, remove the upper knock-out from the bottom machine and the lower knock out from the upper machine.
14. Place a strain relief (from the kit) into each hole.
15. Insert wire harness from kit thru strain-relief and hole in upper corner of the lower ice machine’s back panel.
NOTE: Harness is marked which end goes to which machine.
Bottom Machine:
16. Remove harness from controller terminal 7 and bin thermostat.
17. Route wire harness in lower ice machine to the controller. Connect to terminal #7. Plug the two free wires onto the thermostat terminals #1 and #2.
18. Return left side panel to its original position on the lower ice machine.
Top Machine:
19. Remove harness from controller terminal 7.
20. Route wire harness thru upper unit’s lower knock-out hole and strain relief and continue internally to the controller. Plug wire onto terminal 7 of the controller.
Note: The tabs on the shields must fit inside the ice outlet port.
8. Check the position of the shields. They must move freely and be vertical.
Note: The suction line may need to be moved slightly so the tubing clears the bracket & shields.
9. Place a bead of food grade sealant onto the top left edge of the freezing compartment.
10. Install the front-to-back support bracket over the left edge of the freezing compartment.
May 2001
21. Return all panels and covers to their normal positions.
22. Complete the balance of the installation.
Service Notes:
A. The shields must be positioned so they hang vertically and move freely left to right. Their purpose is to guide the ice past the bottom machine’s evaporators and into its cube port.
B. The drain lines from each ice machine must be kept separate.
Page 8
Stacking
CME2006R
Gasket on Plastic
Walls of Lower Unit
Gasket for Metal Edges of Bottom
Unit
Front-To-Back
Mounting Straps
and Hardware
Bracket
Shield Hanger
Bracket
Shield
May 2001
Page 9
For The Installer: Remote Condenser
CME2006R
Locate the condenser as near as possible to the interior location of the ice maker.
Note: The location of the condenser relative to the ice machine is LIMITED by the specification on the following page.
Select the best available location, one that protects the condenser from extremes of dust, grease and sun.
Meet all applicable building codes.
Roof Attachment
Install and attach the remote condenser to the roof of the building, using the methods and practices of construction that conform to the local building codes, including having a roofing contractor secure the condenser to the roof.
Precharged Line Routing
If the excess tubing is cut out, after re-brazing the tubing must be evacuated prior to connection to the ice maker or condenser.
If the excess tubing is to be coiled, spiral it horizontally to avoid excess trapping in the lines.
Note: A 36" service loop may be placed behind the ice machine.
5. Have the roofing contractor seal the holes in the roof per local codes.
ERC611 Remote
Condenser
Electrical Power
Supply
Do not connect the precharged tubing until all routing and forming of the tubing is complete. See the Coupling Instructions for final connections.
1. Each set of pre-charged tubing lines contains a
3
" diameter liquid line, and a " diameter
8
5
8
discharge line. Both ends of each line have quick connect couplings, the end without access valves goes to the ice maker.
Note: The openings in the building ceiling or wall, listed in the next step, are the minimum sizes recommended for passing the refrigerant lines through.
2. Have the roofing contractor cut a minimum hole for the refrigerant lines of 2". Check local codes, a separate hole may be required for the electrical power supply to the condenser.
Caution: Do NOT kink the refrigerant tubing while routing it.
3. Route the refrigerant tubes thru the roof opening. Follow straight line routing whenever possible.
Coil Excess
Tubing
Horizontally
Within the
Building
Note: Excess tubing may EITHER be coiled up INSIDE the building OR cut out prior to connection to the ice maker and condenser.
July 1998
Page 10
Typical Installation
Remote Condenser Location
CME2006R
Use the following for planning the placement of the condenser relative to the ice machine
Location Limits - condenser location must not exceed ANY of the following limits:
Maximum rise from the ice machine to the
condenser is 35 physical feet
Maximum drop from the ice machine to the
condenser is 15 physical feet
Physical line set maximum length is 100 feet.
Calculated line set length maximum is 150.
Calculation Formula:
Drop = dd x 6.6 (dd = distance in feet)
Rise = rd x 1.7 (rd = distance in feet)
Horizontal Run = hd x 1 (hd = distance in
feet)
Calculation: Drop(s) + Rise(s) + Horizontal
Run = dd+rd+hd = Calculated Line Length
Configurations that do NOT meet these requirements must receive prior written authorization from Scotsman.
Do NOT:
Route a line set that rises, then falls, then
rises.
Route a line set that falls, then rises, then
falls.
Calculation Example 1:
The condenser is to be located 5 feet below the ice machine and then 20 feet away horizontally.
5 feet x 6.6 = 33. 33 + 20 = 53.
be acceptable
Calculation Example 2:
The condenser is to be located 35 feet above and then 100 feet away horizontally.
35 x 1.7 = 59.5. 59.5 +100 = 159.5.
greater than the 150 maximum and is NOT acceptable.
Operating a machine with an unacceptable configuration will void the refrigeration system warranty.
This location would
159.5 is
rd
dd
Max 35’
22.87"
17.15"
Max 15’
Remote
Condenser
Located ABOVE
Ice Machine
Remote
Condenser
Located BELOW
Ice Machine
hd
40.35"
Condenser Distance &
Location Schematic
July 1998
Page 11
Coupling Instructions
CME2006R
The couplings on the ends of the pre-charged line sets are self-sealing when installed properly. Follow these instructions carefully.
These steps must be performed by an EPA Certified Type II or higher technician.
Initial Connections
1. Remove the protector caps and plugs. Wipe the seats and threaded surfaces with a clean cloth to remove any possible foreign matter.
2. Thoroughly lubricate the threads, o-rings, diaphragms and all internal coupling surfaces with polyolester refrigerant oil.
Clean and Lubricate Couplings
3. Position the fittings on the correct connections on the condenser and ice machine.
The " discharge line (schrader valve end)
5
8
goes to the remote condenser fitting marked “discharge line".
The " liquid line (schrader valve end) goes
3
8
to the remote condenser fitting marked “liquid line".
The " discharge line goes to the ice maker
5
8
fitting marked “discharge line".
The " liquid line goes to the ice maker
3
8
fitting marked “liquid line".
Final Connections:
4a. Begin to tighten the couplings together by hand. Continue to turn the swivel nuts by hand until it is certain that the threads are properly engaged.
4b. Using two wrenches, one to rotate the swivel nut and one to hold the tubing in place, tighten each coupling.
Tighten Swivel Nut
It is CRITICAL that ONLY the NUT on the pre-charged tube be turned, or the diaphragms will be torn by the piercing knives and become loose in the refrigeration system causing severe operational problems.
Note: As the coupling is tightened, the diaphragms in the quick connect couplings will begin to be pierced. As that happens, there will be increased resistance to tightening the swivel nut.
4c. Continue tightening the swivel nut until it bottoms out or a very definite increase in resistance is felt (no threads should be showing). Do NOT overtighten.
5. Use a marker or pen to mark a line on the coupling nut and unit panel. Then tighten the coupling nut an additional one-quarter turn. The line will show the amount that the nut turns.
Note: The system charge is contained in the receiver tank of the ice machine. Only “holding" charges are present in the “pre-charged" tubing or the condenser.
Rotate Swivel Nut ¼ Turn More
6. After all connections have been made, and after the liquid line valve has been opened (do not open yet), check the couplings for leaks.
July 1998
Page 12
Electrical
CME2006R
All models must be installed with the correct wire size and type per the National Electric Code. Locate the nameplate on the back of the cabinet and find the numbers for Voltage, Phase, Minimum Circuit Ampacity and Maximum Fuse Size. Either fuses or HACR type circuit breakers may be used.
The ice maker is designed to operate on its own electrical circuit and must be individually fused. Voltage variation must not exceed the limits listed on page 2.
The remote condenser is designed to be powered from the ice machine. A separate knockout hole has been provided in the ice maker electrical junction box.
Remote Condenser
Power Connection
Electrical connections are made in the junction box in the back of the cabinet.
1. Remove the junction box cover.
2. Knock out both holes for a field supplied strain relief.
3. Install wires and strain reliefs per code. Note: Condenser fan motor wires are tagged.
4. Connect to wires and secure ground wire to ground screw inside junction box.
All external wiring should conform to the national, state and local electrical code requirements. Usually an electrical permit and the services of a licensed electrician will be required.
Interconnecting
Wires
Power Supply
July 1998
Page 13
Plumbing
CME2006R
All models require an adequate potable water supply and a gravity drain. The recommendations for tubing are:
Water supply to be
Drain to be
3
⁄4" OD.
3
⁄8" OD.
Note: When replacing a prior ice machine, do not take a short cut and reuse the old inlet and drain system. INSTALL A NEW SYSTEM.
Supply:
3
All models have 1 water supply connection, a
⁄8"
male flare at the back of the cabinet. Connect to cold potable water that has adequate pressure.
Note: Using water supply tubing smaller than3⁄8" will cause severe operational issues.
Water Filters:
The water filters must flow at least 2.7 GPM or they will cause severe operational issues. Check with the filter manufacturer. When replacing a prior ice machine, do NOT assume that the water flow capacity of the filter will be adequate.
All Drain Tubing Material must be RIGID. Flexible tubing will eventually cause a restricted drain.
Drain:
All models have 1 gravity drain connection, a
3
⁄4"
FPT fitting at the back of the cabinet. Use only RIGID TUBING. Flexible tubing may be easily kinked or become cracked.
The drain tube must be vented at the back of the cabinet. Use an 18" high vent.
The ice storage bin will have a drain out the back or base, depending upon the model.
The drain for the ice machine and the ice storage bin must be SEPARATE or the ice machine’s drain water may run into the bin and MELT THE ICE.
Insulation is recommended for the ice machine reservoir and bin drains.
Follow all applicable codes
Refrigerant and
Electrical Lines to
Condenser
Potable Water
Inlet - 3/8"
Male Flare
Field Supplied
Water Filter
Potable
Water
Source
Vented
Drain
Ice
Machine
Drain
Bin Drain
July 1998
Page 14
Floor Drain
Loading...
+ 30 hidden pages