1% at 70°F (21°C). Changes 2.2 ohms per 1 F°(0.5 C°) at 70°F (21°C). TS-8204 only: 1657 ohms
±0.1% at 300°F (149°C); changes 2.5 ohms per 1 F°(0.5 C°) at 300°F (149°C).
Note: TS-8204 is not compatible with internal setpoints of controllers (except for differential
control), TSP-8101 or TSP-8111 temperature transmitters. Order AT-8435, 200 to 400°F (93 to
204°C) when setpoint is required.
See Tables 1 and 2 for additional specifications.
ACCESSORIES
AT-208Duct mounting kit for TS-8201-105 (included with TS-8204).
AT-211Outdoor bulb shield.
AT-215Stainless steel bulb well for TS-9201, TS-8201-105 or TS-8204.
AT-225Stainless steel bulb well for TS-9201-106.
AT-226High pressure brass well.
AT-8435Remote setpoint adjuster, dual scale 200 to 400
required for all TS-8204 applications except differential control.
°F (93 to 204°C):
Printed in U.S.A. 11/10Copyright 2010 Schneider Electric All Rights Reserved.F-22668-7
Table-1 AMBIENT TEMPERATURE LIMITS.
Part Number
TS-8131
TS-8241
TS-8261
a
a
a
Shipping & Storage
TS-9201
TS-8201-105
TS-9201-106
(-40 to 121)
TS-8201-110
TS-9405
TS-9422
TS-8501
TS-8204
a
Humidity, 5 to 95% RH, non-condensing.
(-40 to 104)
(-40 to 204)
°F (°C)
-40 to 160
(-40 to 71)
-40 to 250
-40 to 220
-40 to 400
Operating
°F (°C)
-40 to 140
(-40 to 60)
-40 to 250
(-40 to 121)
-40 to 220
(-40 to 104)
200 to 400
(93 to 204)
Table-2 SPECIFICATIONS.
Part
Number
TS-8131Unitary
Description
a
TS-8201-105 Duct/Immersion
TS-9201Duct/Immersion
TS-9201-106Immersion
c
TS-8201-110Strap-onNylon Wire Tie
TS-8204Duct/Immersion
TS-8241Ceiling Diffuser
Combination
TS-8261
Light Fixtures &
Ceiling Diffuser
Mounting
Connection
7/32" (13.5 mm)
dia.
Mounting Hole
b
1/4" NPT Nut
b
Flange, 1/4” NPT
1/4" NPT Nut
1/4" NPT Nut
b
AT-208 included
7/16" (11.1 mm)
Mounting Hole
None
3/4 dia. x 1-1/4 long
b
c
d
e
1/4 dia. x 8 long
1/4 dia. x 6 long
b
1/4 dia. x 4 long
1/4 dia. x 2-1/4 long
1/4 dia. x 8 long
1-5/8 dia. x 1-3/4 long
1/4 dia. x 8-1/8 long
ElementWiring Enclosure
(19 x 32)
(6 x 203)
(6 x 152)
(6 x 102)
(6 x 57)
(6 x 203)
(41 x 44)
(6 x 206)
TS-9405Averaging (Duct)Flange5 ft(1.5 m) long2-7/8 H x 2-3/8 W x 1-1/2 D
TS-9422Averaging (Duct)Flange22 ft(6.7 m) long
TS-8501Outdoor1/2" Conduit
a
For mounting through fan coil of unit ventilator cabinet or similar application.
b
Immersion requires AT-215 or AT-226 bulb well.
c
Immersion requires AT-225 bulb well.
d
Factory supplied 2-1/2 x 2 in. (64 x 51 mm) foam insulation tape and 30 in. (762 mm) nylon wire tie for 1-1/2 thru 8 in. (38 thru 203 mm) diameter pipes.
e
AT-255 bulb well included.
1-1/8 dia. x 5 long
(29 x 127)
Dimensions in. (mm)
2-7/8 H x 2-3/8 W x 1-1/2 D
(73 x 60 x 38) wi
e
xtension to element; 1/2"
knockout (top)
(73 x 60 x 38) wi
e
xtension to element; 1/2"
knockout (top)
Wiring Connections
None1/4 in. Spade Connections
10 ft (3 m) Armored
None
Capillary with additional
6"(152 mm) leads
th 2-1/2 (64)
12 in. (305 mm) Black
Pigtail Leads
None
None
ne
No
None
th 2-1/2 (64)
12 in. (305 mm) Black
Pigtail Leads
16 in. (401 mm) Yellow
Pigtail Leads
20 ft (6.1 m) Black Pigtail
Leads
6 ft (1.8 m) Black Pigtail
Leads
12 in. (305 mm) Black
Pigtail Leads
None
3 ft (0.9 m) Black Pigtail
Leads
2Copyright 2010 Schneider Electric All Rights ReservedF-22668-7
INSTALLATION
1-3/16 (30)
Dimensions shown
are in inches (mm).
5/32 (4.0)
1/4 (6)
1/2
(12)
13/16
(21)
1/2
(12)
3/64 x 3/16
(1.2 x 4.8)
Tabs (2)
Requires
17/32 (13.5) Dia.
Mounting Hole
Inspection
Visually inspect the carton for damage. If damaged, notify the appropriate carrier
immediately. If undamaged, open the carton and visually inspect the device for obvious
defects. Return damaged or defective products.
Required Installation Items
• Wiring diagrams
• Tools (not provided):
– DVM (digital volt/ohm meter)
– Appropriate screwdriver for mounting screws and terminal connections
– Appropriate drill and drill bit for mounting screws
• Appropriate accessories
• Mounting screws, (2) #10 x 3/4" sheet metal, provided for TS-9201, TS-9405 and
TS-9422 (TS-8204 contains mounting screws in AT-208 kit)
Caution: Installer must be a qualified, experienced technician. Make all connections in
accordance with the wiring diagram, and in accordance with national and local electrical
codes. Do not exceed the ratings of the device.
Mounting
Caution: Avoid locations where excessive vibration, moisture, corrosive fumes or vapors
are present.
TS-8131 Unitary
Sensor
TS-9201
Duct/Immersion
Sensor
1. Determine the sensor mounting location (Figure-1).
2. Drill 17/32" (13.5 mm) diameter mounting hole.
3. Insert gasket to base of sensor “button”.
4. Insert sensor with gasket into mounting hole.
5. Secure sensor to mounting flange or surface by inserting Tinnerman nut over back of
sensor.
6. Two crimp wire receptacles are provided for spade terminal connection to field wiring.
Figure-1 TS-8131 Mounting Dimensions.
Duct
Note: Hand tighten only - do not overtighten.
1. Determine the sensor mounting location on the duct (predetermine the knockout hole
F-22668-7Copyright 2010 Schneider Electric All Rights Reserved3
location for routing of conduit). The sensing element is located within 1 inch of the end of
the sensing probe, and it should be in the air stream at a location that is typical of the
temperature requiring sensing. Approximately 3" of length adjustment is available.
2. Use the mounting flange supplied as a template (or refer to Figure-2 for duct mounting
3-25/64
(86)
Dimensions shown
are in inches (mm).
13 (330)
1-5/8
(41)
2-5/16 (59)
1/4 (6) O.D.
8
(203)
2-1/2
(64)
2-1/2
(64)
Enclosure
Sensor Mounting Nut
Tee or Elbow for Mounting Well
Flow
Well
AT-225
8"
(203 mm)
1/4" (6 mm) dia.
dimensions) for mounting hole location.
3. Mount the sensor to the duct using the two #10 x 3/4” sheet metal screws provided.
Figure-2 TS-9201 Mounting Dimensions.
Immersion (Requires AT-215 Bulb Well)
1. Remove lock nut and duct mounting flange from sensor (Figure-3).
2. Thread the sensor into AT-215 bulb well that has been installed in a liquid line or tank.
TS-8201-105 Duct/
Immersion Sensor
4Copyright 2010 Schneider Electric All Rights ReservedF-22668-7
Note: The AT-215 bulb well should be filled with a temperature conductive grease (TAC part
number M-500) prior to element insertion, for optimum medium temperature sensing.
Figure-3 TS-9201 Immersion Mounting.
Duct (Requires AT-208 Duct Kit)
1. Determine the sensor mounting location on the duct. The sensing element is located
within 1 inch of the end of the sensing probe and it should be located in the air stream
typical of the temperature requiring sensing (see Figure-4).
Figure-4 TS-8201-105 Mounting Dimensions.
2. Drill insertion and mounting holes for AT-208 in the duct wall (see Figure-5).
3. Mount the sensor the duct using the AT-208 kit.
AT-208 Bracket, Gasket and Mounting Screws
1/2 (13) Dia.
1/8 (3.2) Dia.
TS-8201-110 Strap-on
Sensor
1/8 (3.2)
1 (25)
Full Scale - May be used as a template.
1 (25)
Dimensions shown
are in inches (mm).
Figure-5 AT-208 Mounting Dimensions.
Immersion (Requires AT-215 Bulb Well)
Thread the sensor into AT-215 bulb well that has been installed in a liquid line or tank.
Note: The AT-215 bulb well should be filled with a temperature conductive grease (TAC part
number M-500) prior to element insertion, for optimum medium temperature sensing.
1. Foam insulation tape should be placed over the sensor (Figure-6). Extend insulation
beyond the ends of the sensor.
2. Secure sensor and foam insulation tape to pipe with wire tie (factory supplied) or metal
hose clamp (not included).
Caution: Do not tighten clamp or nylon tie (or metal hose clamp) to the point of distorting
the sensor. Overtightening fasteners will cause a shift in sensed temperature.
Thread the sensor into AT-225 bulb well that has been installed in a liquid line or tank (see
Figure-7).
Note: The AT-225 bulb well should be filled with a temperature conductive grease (TAC part
number M-500) prior to element insertion, for optimum medium temperature sensing.
F-22668-7Copyright 2010 Schneider Electric All Rights Reserved5
Figure-7 TS-9201-106 Immersion Mounting.
Enclosure
Sensor Mounting Nut
Tee or Elbow for Mounting Well
Flow
Well
AT-225
Sensor Mounting Nut
Tee or Elbow for Mounting Well
Flow
Well
AT-225
TS-8204
Duct/Immersion
Sensor
Duct (Requires AT-208 Duct Kit)
1. Determine the sensor mounting location on the duct. The sensing element is located
within 1" of the end of the sensing probe and it should be located in the air stream typical
of the temperature requiring sensing (see Figure-8).
2. Drill insertion and mounting holes for AT-208 in the duct wall (see Figure-5).
3. Mount the sensor to the duct using the AT-208 kit.
Immersion (Requires AT-215 Bulb Well)
Thread the sensor into AT-215 bulb well that has been installed in a liquid line tank.
Note: The AT-215 bulb well should be filled with a temperature conductive grease (TAC part
number M-500) prior to element insertion, for optimum medium temperature sensing.
1/4
(6)
Figure-8 TS-8204 Mounting Dimensions.
8
(203)
Dimensions shown
are in inches (mm).
TS-8241 DuffuserThe sensor should be mounted to the face of the ceiling diffuser so that it projects downward
into the room (see Figure-10).
1. Drill a 7/16" (11.1 mm) diameter mounting hole in the diffuser face.
Figure-9 TS-8204 Immersion Mounting.
2. Insert the threaded end of the sensor into the mounting hole.
3. Secure the sensor to the diffuser face using the mounting nut and lock washer provided.
6Copyright 2010 Schneider Electric All Rights ReservedF-22668-7
If the diffuser has an adjustable pattern, the discharge air direction must be adjusted to a
Induced Room Air
Discharge Air
TS-8241
horizontal pattern. This horizontal pattern will insure a representative sample of room air
over the element (see Figure-11). The sensor will not perform satisfactorily if the discharge
is adjusted to a vertical pattern.
Figure-10 TS-8241 Sensor Mounted in Perforated Face Ceiling Diffuser.
TS-8261 Light Fixture
or Ceiling Diffuser
Sensor
Figure-11 Room Air Induced over Sensor by Discharged Air.
The sensor may be mounted in the return air grill of a light fixture or to the face of a ceiling
diffuser using field supplied fasteners (see Figure-12 and Figure-13).
Combination Light-Air
Diffuser Unit
Sensing Element
Room Air Entering Light Fixture through Return Grill
Access Door
Exhaust Air from
Light Fixture
Ceiling
Figure-12 TS-8261 Sensor Mounted in Light-Air Diffuser Unit.
Figure-13 TS-8261 Sensor Mounted in Perforated Ceiling Diffuser.
F-22668-7Copyright 2010 Schneider Electric All Rights Reserved7
TS-9405, TS-9422
3-25/64
(86)
4-3/4
1-5/8
(41)
2-5/16 (59)
2-1/2
(64)
Dimensions shown
are in inches (mm).
PartElement
NumberLength
TS-94055 ft.
TS-942222 ft.
Averaging Sensors
Note: Hand tighten only - do not overtighten.
1. Determine the sensor enclosure mounting location on the duct (see Figure 16)
(predetermine the knockout hole location for routing of conduit). The sensor should be
serpentined through the duct in a pattern that will expose it to all areas where variations
of temperature may occur. If duct can not be entered, wrap the element around a section
of conduit and place the conduit diagonally in the duct. Consider using part number
M-648 mounting clips when the inside of the duct can be accessed.
Caution: Do not make sharp bends in the element.
2. Use the mounting flange supplied as a template (or refer to Figure 14 for duct mounting
dimensions) for mounting hole location.
3. Mount the sensor enclosure to the duct using the two #10 x 3/4” sheet metal screws
provided.
TS-8501 Outdoor Air
Sensor
Figure-14 TS-9405/9422 Mounting Dimensions.
Figure-15 TS-9405/9422 Typical Mounting.
Mount sensor to waterproof conduit box using the 1/2" conduit connection (see Figures 17
and 18).
Use optional shield if required by application (see Figure 19).
8Copyright 2010 Schneider Electric All Rights ReservedF-22668-7
Figure-16 TS-8501 Mounting Dimensions.
3/4
(19)
5
(127)
Fitting included for 1/2 in. Conduit
2 Leads
3 ft. (0.9 m) length
Dimensions shown
are in inches (mm).
TS-8501 Sensor
Outside Wall
Waterproof Conduit Box
(outside)
Knockouts
Figure-17 TS-8501 Typical Mounting.
TS-8501 Sensor
Figure-18 TS-8501 Mounted with Shield.
Mounting Duct
Sensor Using Existing
Mounting Plate
F-22668-7Copyright 2010 Schneider Electric All Rights Reserved9
Table-3 APPLICABLE MODELS.
New Part NumberOld Part Number
TS-9201
TS-9201-106
TS-9405
TS-9422
TS-8201
TS-8201-106
TS-8405
TS-8422
When a duct sensor is being replaced at a location where an existing mounting hole size
exceeds the coverage of the adaptor flange, use the existing mounting plate as follows:
1. Remove the existing unit from the duct. Note location of the unit’s conduit hole.
2. Remove (and set aside for later use) the conduit nut securing the mounting plate to the
sensor.
3. Remove the mounting plate from the old sensor.
4. Place the mounting plate on the new sensor and secure with the conduit nut removed
from the old sensor. Do not include the plastic adaptor flange.
5. When mounting the sensor to the duct, be sure the conduit hole is located appropriately.
WIRING
Conduit Nut
Mounting Plate
Adaptor Flange
Figure-19 Mounting Duct Sensor Using Existing Mounting Plate.
Two separate twisted pair wires (six turns per foot). Class II, low voltage, are suitable for the
sensor leads except as stated below.
Caution: Shielded cable must be used when it is necessary to install the sensor lead in the
same conduit with power wiring, or when it is known that high RFI/EMI generating devices
are near. System ground the shield at the controller only on the COM (-) terminal or blue (-)
lead. Do not use an earth ground. Do not use the enclosure as a junction box for other
control circuits.
It is generally advisable to use flexible conduit to connect enclosure to rigid conduit.
To Energy Management
System Sensor Input
1/4" Spades
(TS-8131)
Two Leads
Figure-20 Sensor Connections.
Restrict element lead to shortest length practical (see Table-4).
Table-4 SENSOR WIRING LENGTHS.
Length of Run - ft. (m)
Wire Gauge
22-125 (38)
181000 (305)300 (91)
162250 (686)-
144000 (1219)-
TS-8xxx and TS-9xxx
Sensor to Controller
(except TP-810x)
TS-8xxx and TS-9xxx
Sensor to TP-810x
Table-5 TS-8000 & TS-9000 SERIES BALCO TEMPERATURE SENSORS.
1. Material: Balco wire calibrated for 1000 ohms ± 1% at 70 °F.
2. Temperature coefficient: 4300 (± 150) ppm °C between 25 and 100°C.
3. Relationships:
R (resistance)= 0.00161T2 + 1.961T + 854.841
Temperature = (SQRT ((.00644 x R) - 1.6597) - 1.961) / .00322
F-22668-7Copyright 2010 Schneider Electric All Rights Reserved11
MAINTENANCE
FIELD REPAIR
4. Storage Temperature Specification:
Minimum = -40 °F
Maximum = 160 °F
5. Operation Temperature Specification:
Minimum = -40 °F
Maximum = 240 °F
Ta b l e N ot e s:
1. Temperature (T) in °F
2. Resistance (R) in ohms
3. Temperature coefficient is positive
Regular maintenance of the total system is needed to assure sustained optimum
performance. Sensors should be periodically inspected for dirt or blockage of air over the
elements.
These sensors are not field repairable.
On October 1st, 2009, TAC became the Buildings business of its p arent company Schneide r Electric. This document reflects the visual identity of Schnei der Electric,
however there remains references to T AC a s a corporate bran d in the body copy. As each document is updated, the body copy will be changed to ref lect appropriate
corporate brand changes.
Copyright 2010, Schneider Electric
All brand names, trademarks and registered
trademarks are the property of their respective
owners. Information contained within this
document is subject to change without notice.
F-22668-7
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.