External Battery Pack Installation

Inventory

(1) (1) (6) (4) (1)
(1) (2) (2) (2)

Safety and General Information

Read the Safety Guide included in the package before installation.
This unit is intended for indoor use only. Do not operate this unit in direct sunlight, in contact with fluids, or where there is excessive dust or humidity. Be sure the air vents on the external battery packs (XLBPs) are not blocked. Allow adequate space for proper
ventilation. The battery typically lasts for two to five years. Environmental factors impact battery life. Elevated ambient
temperatures, poor quality utility power, and frequent short duration discharges will shorten battery life. Always install the XLBPs at the bottom of the rack. The UPS must be installed above the XLBPs.

Specifications

For additional specifications, refer to the APC web site at www.apc.com.
Environmental
Operating 0° to 40° C (32° to 104° F)
Temperature
Maximum
Elevation Humidity
Storage -15° to 45° C (5° to 113° F)
charge UPS battery every six months
Operating 3,000 m (10,000 ft) Storage 15,000 m (50,000 ft)
0% to 95% relative humidity, non-condensing

Installation

su0
738
c
su0738d
su0574asu0574
b
su0584a
su0573a
Electrical Hazard: Before installing or replacing the batteries, remove jewelry such as
wristwatches and rings. High short-circuit current through conductive materials could cause severe burns.
• The Smart-UPS unit will recognize up to ten XLBPs using the display interface, however there is no limit to the number of XLBPs that can be used with the UPS.
• Always install the XLBPs below the UPS in a rack configuration.
• Connect all battery strings. Failure to do so may cause equipment damage.

Remove the Shipping Brackets

1 2

Remove the battery

Each battery weighs 23 kg (51 lbs). Remove the batteries before installation in a rack.

1 2
3 4
Smart-UPS X-Series XLBP2

Four-post rack installation

s
u
0
4
4
0
a
s
u
0
5
7
0
a
s
u
0
5
7
1
a
s
u
0
5
7
8
a
s
u
0
5
7
2
a
s
u
0
5
7
5
a
su0576a
Rack-mount brackets may differ by model.
1 2
Use the APC Four-Post Rail Kit.
3 4
5 6

Two-post rack

1 2
Smart-UPS X-Series XLBP 3