Schneider Electric Smart-UPS VT Technical Data

Page 1
Smart-UPS VT
“Compact, high-performance power protection with scalable runtime”
10 / 15 / 20 / 30 kVA – Three-phase
>
Performance 3 Phase Power Protection in Optimized Footprint with Hot Scalable Runtime for Small Data Centers and Other Business Critical Applications
> High Efficiency in Class (96%) > Small Footprint > Scalable runtime > Parallel Capable > Network Manageability
Page 2
Smart VT Features
High Availability
The Smart-UPS VT includes dual-mains inputs, automatic and maintenance bypasses, and scalable runtime with hot-swappable batteries which are quick and easy to replace for increased availability.
Its compatibility with the market-leading remote management applications, coupled with intuitive LCD user interface and LED status indicators ensures the utmost availability for business critical applications.
A versatile product
The Smart-UPS VT is available in a wide choice of configurations to best fit each specific installation need.
> 10 / 15 / 20 / 30 kVA > 2 different enclosures: wide or narrow tower f or optimized footprint > Flexible runtime capacity :
> Compatibility with generators, transformers, etc..
- with hot-swappable batteries and extended run enclosures
- with up to 4 internal battery strings and external
extended runtime enclosures
Reduced Total Cost of Ownership
Smart-UPS VT intelligent design leads to a significant reduction of the TCO and makes it the ideal choice over time.
> Best-in-class efficiency even at low load levels minimizes energy losses and operating costs >
Compact, small footprint for floor space optimization
> Input power factor correction reduces installation costs > Reduction of electrical infrastructure rating requirements (wire, transformers, generators…)
Page 3
Smart-UPS VT Features & Options
High performance
> Up to 96% efficiency even at low load levels > Large input voltage tolerance for
compatibility with low-quality power grids > Low input / output signal distortion > Parallel capability up to 4 units for
redundant configurations or capacity
extension
Comprehensive Services offering
The Smart-UPS VT product design backed up by APC by Schneider Electric world­class Services organization provides the serenity required by any business-critical application. > On-site audits > Maintenance contracts > Battery replacement > Remote monitoring for maximized up-time
Easy maintenance
The product design allows quick maintenance in case of failure, leading to higher availability for the load. > slide-in/out concept for the power module
for a quick comeback to normal state
> hot-swappable batteries for quick and
easy replacement
Manageability
The built-in features of the Smart-UPS VT combined with APC’s leading management solutions make it easy to manage and monitor, both proactively or upon failure. This significantly improves control over the energy supply and ensures high availability for the loads. > Remote management of the UPS over
network or telephone lines
> Centralized management via
InfraStruXure Manager
Options
Smart-UPS VT product offering provides a list of options > Service Bypass Panel Stand-alone > Service Bypass Panel with distribution > Circuit breaker panel > Power Availability > 1 year repair or replace
Page 4
Technical characteristics
UPS Rating kVA/KW (PF = 0.8) 10/8 15/12 20/16 30/24
AC power supply input
Input voltage (V) 208V (3 Phase) Frequency (Hz) 40-70 Hz (auto-sensing) Power Factor <0,98 Input current total harmonic distortion Less than 5% for full load
Output
Output voltage (V) 120V, 208V Frequency (Hz) 57 - 63 Hz for 60 Hz nominal Power Factor 0.8 Overload 150% 1 minute, 125% 10 minutes Output voltage total harmonic distortion Less than 5% for full load
Performance
Efficiency (at full load) 95,7% 95,7% 95,3% 96,4% Operating temperature 0-40°C Paralleling up to 4 units Spec feature For either redundancy or capacity
Dimensions (HxWxD) mm
Wide Tower 1500x523x854 Narrow Tower (10 /15 kVA) 1500x352x854
Environmental conditions and noi s e
Audible Noise (dBA) 64dB (57dB at 70% load) Operating Temperature 0°C to 40°C (32 to 104 °F) Operating Relative Humidity 0 to 95%
N/A
Wide Tower (10/15/20/30 kVA)
Narrow Tower (10/15 kVA)