Schneider Electric Smart-UPS On-Line SRT Users Manual

Page 1
Operation Manual
Smart-UPS™ On-Line
SRT
SRT5KXLI
SRT5KRMXLI
SRT5KXLT
SRT5KXLT-IEC
SRT5KRMXLT-IEC
SRT5RMKXLW-HW
SRT6KXLI
SRT6KRMXLI
SRT6KXLT
SRT6KXLT-IEC
SRT6KRMXLT-IEC
208/220/230/240 Vac
Tower/Rack-Mount 3U/4U
Page 2
Page 3

Product Description

The APC™ by Schneider Electric Smart-UPS™ On-Line SRT is a high performance uninterruptible power supply (UPS). The UPS helps to provide protection for electronic equipment from utility power blackouts, brownouts, sags, surges, small utility power fluctuations and large disturbances. The UPS also provides battery backup power for connected equipment until utility power returns to safe levels or the batteries are completely discharged.
This user manual is available on the enclosed Documentation CD and on the APC web site, www.apc.com.

General Information

Safety Messages

Read the instructions carefully to become familiar with the equipment before attempting to install, operate, service or maintain the UPS. The following special messages may appear throughout this manual or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of this symbol to a Danger or Warning product safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed.
The addition of this symbol to a Warning or Caution product safety label indicates that a hazard exists that can result in injury and product damage if the instructions are not followed.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, can result in minor or moderate injury.
CAUTION
CAUTION addresses practi ces n ot rel ated to ph ysical in jury inc luding cert a in en vironmen t al ha zards , poten tial d amage or
loss of data.
1Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U
Page 4

Safety Information

• Adhere to all national and local electrical codes.
All wiring
C
hanges and modifications to this unit not expressly approved by APC could void the warranty.
•This UPS is intended for indoor use only.
•Do not operate this UPS in direct sunlight, in contact with fluids, or where there is excessive dust or humidity.
•Be sure the air vents on the UPS are not blocked. Allow adequate space for proper ventilation. For a UPS
• use surge protectors or extension cords.
Th
e battery typically lasts for two to five years. Environmental factors im pact battery life. Elevated ambien
tem
Th
e equipment is heavy. Always practice safe lifting techniques adequate for the weight of the equipment.
he batteries are heavy . Remo ve the batteries before ins talling the UPS and external battery packs ( XLBPs),
T
• in a rack.
•Always install XLBPs at the bottom in rack-mount configurations. The UPS must be installed above th XLBP
A
lways install peripheral equipment above the UPS in rack-mount configurations.
• Additional safety information can be found in the Safety Guide supplied with this unit.
must be performed by a qualified electrician.
with a factory installed power cord, connect the UPS power cable directly to a wall outlet. Do not
peratures, poor quality utility power, and frequent short duration discharges will shorten battery life.
s.
t
e
Deenergizing safety
The UPS contains internal batteries and may present a shock hazard even when disconnected from the branch circuit (mains). Before installing or servicing the equipment verify the following:
•XLBP battery modules are disconnected
s circuit breaker is in the OFF position
Main I
nternal UPS the batteries are removed
Electrical safety
• For models with a hardwired input, the connection to the branch circuit (mains) must be performed by a q
ualified electrician.
•230 V models only: In order to maintain compliance with the EMC directive for products sold in Europe o
utput cords attached to the UPS must not exceed 10 meters in length.
•The protective earth conductor for the UPS carries the leakage current from the load devices (compu eq
uipment). An insulated ground conductor is to be installed as part of the branch circuit that supplies th
U
PS. The conductor must have the same size and insulation material as the grounded and unground
ranch circuit supply conductor s. The con du cto r wi ll typi call y be green and wi th o r w it hou t a yel low str ipe.
b
•The UPS input ground conductor must be properly bonded to protective earth at the service panel. If the UPS input power is supplied by a separately derived system, the ground conductor must be properly bonded at the supply transformer or motor generator set.
,
ter
e
ed
Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U2
Page 5
Battery safety
• Before installing or replacing the batteries, remove jewelry such as wristwatches and rings. High short circuit current through conductive materials could cause severe burns.
•Do not dispose of batteries by burning them. The batteries may explode. Do
not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes, and may be toxic.
Hardwire safety
• Verify that all branch circuit (mains) and low voltage (control) circuits are deenergized, and locked out b
efore installing cables or making connections, whether in the junction box or to the UPS.
iring by a qualified electrician is required.
W
C
heck national and local codes before wiring.
•Strain relief is required for all hardwiring (not supplied). All op
enings that allow access to UPS hardwire terminals must be covered. Failure to do so may result in
personal injury or equipment damage. Select wire s
General information
• The UPS will recognize as many as 10 external battery packs connected to the UPS. However there is no limit to the number of XLBPs that can be used with the UPS.
Note: For each XLBP added, increased recharge time will be required.
The model and s
• is located on the chassis under the front bezel.
Always
•Recycle the package materials or save them for reuse.
recycle used batteries.
ize and connectors according to national and local codes.
erial numbers are located on a small, rear panel label. For some models, an additional label
3Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U
Page 6

Product Overview

Specifications

For additional specifications refer to the APC web site, www.apc.com.
Environmental
Temperature
Operating Storage Operating
Maximum Elevation
Storage Humidity Protection Class
Note: Charge the battery modules every six months during storage.
Environmental factors impact battery life. Elevated ambient temperatures, high humidity, poor quality mains power, and frequent short duration discharges will shorten battery life.
0% to 95% relative humidity, non-condensing
IP 20 rating
0º to 40º C (32º to 104º F)
-15º to 45º C (5º to 113º F) 0 - 3,000 m (0 - 10,000 ft) 0 - 15,000 m (50,000 ft)
Physical
SRT5K model
The UPS is heavy. Follow all lifting guidelines.
Lifting guidelines >55 kg (>120 lb)
Unit weight batteries included, without packaging
Unit weight batteries included, with packaging
Unit dimensions without packaging Height x Width x Depth
Unit dimensions with packaging Height x Width x Depth
The model and serial numbers are on a small label located on the rear panel.
54.6 kg (120 lb)
Rack-Mount models: 63.6 kg (140 lb) Tower models: 67 kg (147.4 lb)
130 mm x 432 mm x 719.4 mm 5 in x 17 in x 28.3 in
330 mm x 610 mm x 960 mm 13 in x 24 in x 37.8 in
SRT6K model
The UPS is heavy. Follow all lifting guidelines.
Lifting guidelines >55 kg (>120 lb)
Unit weight batteries included, without packaging 60 kg (132 lb) Unit weight batteries included, with packaging 67 kg (147.4 lb) Unit dimensions without packaging
Height x Width x Depth Unit dimensions with packaging
Height x Width x Depth
The model and serial numbers are on a small label located on the rear panel.
Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U4
174 mm x 432 mm x 719.4 mm
6.9 in x 17 in x 28.3 in 370 mm x 610 mm x 960 mm
14.6 in x 24 in x 37.8 in
Page 7
Battery
Battery type Replacement battery module
This UPS has hot swappable battery modules. Replacement is a safe procedure, isolated from electrical hazards.
Refer to the appropriate replacement battery user manual for installat ion instruc t ions.
Contact your dealer or go the APC web site, www.apc.com for information on replacement batteries.
Number of battery modules 2 battery modules Voltage for each battery module
Total voltage for the UPS Ah rating
XLBP cable length 500 mm (19.7 in)
Maintenance free, leak proof, sealed, lead acid APCRBC140
96 VDC 192 VDC
5.1 Ah per battery module
Electrical
Models Rating
SRT5KXLT SRT5KRMXLT SRT5KXLT-IEC SRT5KRMXLT-IEC SRT5KXLI
SRT5KRMXLW-HW SRT6KXLT SRT6KRMXLT SRT6KXLT-IEC SRT6KRMXLT-IEC SRT6KXLI SRT6KRMXLI
5 kVA/4.25 kW
5 kVA/4.5 kWSRT5KRMXLI
6 kVA/6 kW
Output
Output Frequency 50 Hz/60 Hz ± 3 Hz Nominal Output Voltage SRT5KRMXLW-HW: 208V, 220V, 230V, 240V
SRT5K/6KXLI, SRT5K/6KRMXLI: 220V, 230V, 240V SRT5K/6KXLT/XLT-IEC, SRT5K/6KR M XLT/RMXLT-IEC: 208V, 240V
Input
Input Frequency 40 Hz-70 Hz ± 3 Hz Nominal Input Voltage SRT5KRMXLW-HW: 208 V, 220 V, 230 V, 240 V
SRT5K/6KXLI, SRT5K/6KRMXLI: 220 V, 230 V, 240 V SRT5K/6KXLT/XLT-IEC, SRT5K/6KR MXLT/RMXLT-IEC: 208 V, 240 V
5Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U
Page 8

Front panel features

Display interface panelUPS battery connectorsBattery compartmentBezel
a
7
7
8
0
u
s
Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U6
Page 9

Rear panel features

G
R
O
U
P
2
1
6
A
M
P
M
A
X
O
u
t
p
u
t
:
5
0
/
6
0
H
z
2
2
0
/
2
3
0
/
2
4
0
V
A
C
GROUP 1
20 AMP MAX
G
R
O
U
P
2
3
0
A
M
P
M
A
X
Note: Refer to the table “Key to identify rear panel features” on page 10, that provides a key to the callout numbers for the rear panel graphics depicted in this manual.
SRT5KXLI/SRT5KRMXLI
GROUP 1
10 AMP MAX
su0878a
SRT5KXLT/SRT5KRMXLT
su0879a
z H
C
0
A
6
V
/ 0
0
5
4
:
2
t
/
/
u
8
p
t
0
u
2
O
7Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U
Page 10
SRT5KXLT-IEC/SRT5KRMXLT-IEC
O
u
t
p
u
t
:
5
0
/
6
0
H
z
2
0
8
/
2
4
0
V
A
C
GROUP 1
15 AM P MAX
X
2
A M
P U
P
O
M
R
A
G
0 2
su0880a
SRT5KRMXLW-HW
su0881a
Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U8
Page 11
SRT6KXLI/SRT6KXRMXLI
GROUP 1
10 AMP MAX
G
R
O
U
P
2
1
6
A
M
P
M
A
X
O
u
t
p
u
t
:
5
0
/
6
0
H
z
2
2
0
/
2
3
0
/
2
4
0
V
A
C
GROUP 3
16 AMP MAX
G
R
O
U
P
2
3
0
A
M
P
M
A
X
O
u
t
p
u
t
:
5
0
/
6
0
H
z
2
0
8
/
2
4
0
V
A
C
GROUP 1
20 AMP MAX
GROUP 3
30 AMP MAX
su0884a
GROUP 1
15 AMP MAX
G
R
O
U
P
2
2
0
A
M
P
M
A
X
O
u
t
p
u
t
:
5
0
/
6
0
H
z
2
0
8
/
2
4
0
V
A
C
G
R
O
U
P
3
2
0
A
M
P
M
A
X
su0882a
SRT6KXLT/SRT6KRMXLT
su0883a
SRT6KXLT-IEC/SRT6kRMXLT-IEC
9Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U
Page 12
Key to identify rear panel features
SmartSlot The SmartSlot can be used to connect optional management accessories.
External battery
power and communication connector
Chassis ground
screws
Hardwire output
box
EPO terminal The Emergency Power Off (EPO) terminal allows the user to connect the UPS to a central EPO
Serial Com The Serial Com port is used to communicate with the UPS.
USB port The USB port is used to connect either a server for native operating system communications, or
Universal I/O port Use to connect:
Use the external battery cable on the XLBP to connect the UPS and XLBP. XLBPs provide extended runtime during power outages. The UPS will automatically recognize up to 10 external battery packs.
The UPS and XLBPs have ground screws for connecting the grou nd lead s. Prior to connecting a ground lead, disconnect the UPS from mains power.
SRT5KRMXLW-HW, SRT6KXLI, SRT6KRMXLI, SRT6KXLT, SRT6KRMXLT, SRT6KXLT-IEC, SRT6KRMXLT-IEC models are equipped with a hardwire output box. Refer to “Wiring Specifications” on page11 for hardwire specifications.
Remove the knockouts. Snap-In strain reliefs are recommended (not supplied).
system.
Use only interface kits supplied or approved by APC by Schneider Electric. Any other serial interface cable will be incompatible with the UPS connector.
for software to communicate with the UP S. Note: Serial and USB communication should not be used simultaneously. Use either the Serial Com or the USB port.
• Temperature sensor AP9335T (supplied)
• Temperature/humidity sensor AP9335TH (not supplied)
• Relay input/output connector AP9810 (not supplied), supports two input contacts and one output relay
Console port Use the Console port to configure the network management features.
Network po r t Use the Network port to connect the UPS to the network.
Reset button Use the Reset button to restart the Network Management Interface.
Note: A restart of the Network Management Interface does not affect UPS operation.
AC input
power cable or hardwire input box
Controllable outlet
group 1
Controllable outlet
group 2
Controllable outlet
group 3
Circui t breaker In the event an overload condition occurs, disconnect nonessential equipment.
• SRT5KXLT, SRT5KRMXLT, SRT5KXLT-IEC, SRT5KRMXLT-IEC models have factory installed input power cables.
• All other models are equipped with a hardwire input box. Refer to “Wiring Specifications” on page 11. Remove the knockouts. Snap-In strain reliefs are recommended (not supplied).
Connect electronic devices to these outlets.
Connect electronic devices to these outlets.
Connect electronic devices to these outlets.
Then reset the circuit breaker.
Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U10
Page 13

Wiring Specifications

CAUTION
DAMAGE TO EQUIPMENT OR PERSONNEL
• Adhere to all national and local electrical codes.
• Wiring should be performed by a qualified electrician.
• Strain reliefs are not provided with this unit. Snap-In strain reliefs are recommended. Refer to the Installation Guide for knockout panel sizes.
• The UPS must be wired into a branch circuit, equipped with a circuit breaker rated as specified in the tables below.
• Actual wire size must comply with required amp capacity and national and local electrical codes.
• Recommended input terminal screw torque: 16 lbf-in (2 Nm).
Failure to follow these instructions can result in equipment damage and minor or moderate injury
SRT5K/6KXLT, SRT5K/6KXLT-IEC models
Input connections Wire to L1, L2,
Output connections Wire to L1, L2,
System Wiring Voltage Current full
SRT5KXLT SRT5KRMXLT SRT5KXLT-IEC SRT5KRMXLT-IEC
SRT6KXLT SRT6KRMXLT SRT6KXLT-IEC SRT6KRMXLT-IEC
Input
208/240 Vac 24 A 30 A/2-pole Not applicable
Output
Input
208/240 Vac
Output
SRT5KXLI/SRT6KXLI models
Input connections Single phase: Wire to L, N,
Output connections Wire to L, N
System Wiring Voltage Current full
SRT5KXLI SRT5KRMXLI
SRT6KXLI SRT6KRMXLI
Input
Output
Input
Output 28 A
220/230/240 Vac 24 A 40 A/2-pole 10 mm
220/230/240 Vac
load, nominal
33 A 29 A
load, nominal
32 A
External input
Wire size,
circuit breaker,
(typical)
50 A/2-pole 6 AWG
External input
circuit breaker,
(typical)
50 A/2-pole 16 mm
typical
Wire size,
typical
2
2
11Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U
Page 14
SRT5KRMXLW-HW
Input connections Single phase: Wire to L, L2/N,
Output connections Wire to L1, L2/N
System Wiring Voltage Current full
SRT5KRMXLW-HW
Input
Output
208/220/
230/240 Vac
load, nominal
26 A 24 A
External input
circuit breaker,
(typical)
40 A/2-pole
Wire size,
typical
2
10 mm
(8 A WG)
Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U12
Page 15

Connect Equipment

CAUTION
DAMAGE TO EQUIPMENT OR PERSONNEL
• Disconnect the mains input circuit breaker before installing or servicing the UPS or connected equipment.
• Disconnect internal and external batteries before installing or servicing the UPS or connected equipment.
• The UPS contains internal and external batteries that may present a shock hazard even when disconnected from the
mains.
• UPS AC hardwired and pluggable outlets may be energized by remote or automatic control at any time.
• Disconnect equipment from the UPS before servicing any equipment.
Failure to follow these instructions can result in equipment damage and minor or moderate injury.
Note: The UPS batteries will charge to 90% capacity in the first three hours of normal operation. Do not expect
full battery runtime capability during this initial charge period.
1. Connect equipment to the outlets on the rear panel of the UPS. Refer to “Controllable Outlet Groups” on page 21.
2. Connect the UPS to the building utility power.

Turn the UPS On/Off

The first time the UPS is turned on the Setup Wizard screen will run. Follow the prompts to configure UPS settings. R efer to “Config uration” on page 17.
T o turn on the UPS and all conn ected equipment, press the Power prompts to either turn the UPS on immediately or after a delay, then press OK. NOTE: When there is no input power and the UPS is off, the cold start feature can be used to turn on the UPS and connected equipment using battery power. To perform a cold start press the Power ON/OFF button. The display panel will illuminate and the Power ON/OFF button will illuminate red. To turn on the output power press the Power ON/OFF button again. Select the prompt Turn ON with NO AC and press OK.
To turn output power off, press the Power immediately or after a delay, then press OK. NOTE: Once the AC power has been turned off the UPS will continue operating on battery power for a short period of time. To remove power completely pr ess the Power O N/OFF button. Follow the prompt to select Internal Power Off, then press OK.
ON/OFF button. Follow the prompts to either turn the UPS off
ON/OFF button on the display panel. Follow the
13Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U
Page 16

UPS Display Interface

Output
230.0
v
LOA D
LOAD
POWER ON/OFF button
Button illumination indicat i ons :
-No illumination, the UPS and the output power are off
-White illumination, the UPS and the output power are on
-Red illumination, the UPS is on and the output power is off
Load icon
Disable/mute audible alarm icon UPS status information
Operation mode icons
ESCAPE button
OK button
UP/DOWN buttons
Controllable outlet group status icons
On-Line
12
su0870b
Battery status icons
.
The icons on the LCD display interface screen may vary depending on the installed firmware version.
Load icon: The approximate load capacity percentage is indicated by the number of load bar sections illuminated. Each bar represents 16% of the load capacity.
Mute icon: Indicates the audible alarm is disabled/mute.
UPS Status Informati on
The status information field provides key information on the status of the UPS. The Standard menu will allow the user to select one of the following screens. The Advanced menu will scroll through the following five screens.
Input Voltage Output Voltage Output Frequency Load Runtime
In the case of a UPS event, status updates will be displayed defining the event or condition that has occurred. The display screen illuminates amber to indicate a Warning and red to indicate an Alert depending on the severity of the event or condition.
Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U14
Page 17
Operation Mode Icons
On-Line mode: The UPS is supplying conditioned mains power to connected equipment.
Bypass mode: The UPS is in Bypass mode and the connected equipment will receive mains
power as long as the input voltage and frequency are within the configured limits.
Green mode: When in Green mode mains power is sent directly to the load. In the event of a mains power outage, there will be an interruption in power to the load of up to
8 ms while the UPS switches to On-Line or Battery mode. When enabling Green mode consideration should be given to devices that m ay be sensitive to
power fluctuations.
Battery mode: The UPS is supplying battery power to connected equipment.
Controllable Outlet Group Icons
Controllable Outlet Group Power Available: The number next to the icon identifies the
specific outlet groups that have available power.
Controllable Outlet Group Power Not Available: The number next to the icon identifies specific outlet groups that do not have available power.
Battery Status Icons
Battery Charge Status: Indicates the battery charge status.
Battery Charge In Progress: Indicates the battery is charging.
UPS Display Interface operation
Use the UP/DOWN buttons to scroll through the options. Press the OK button to accept the selected option. Press the
ESC button to return to the previous menu.
Menu overview
The UPS Display Interface has Standard and Advanced menu screens. The preferen ce for Standard or Advanced menu selections is made during initial installation and can be changed at any time through the Configuration menu.
The Standard menus include the most commonly used options. The Advanced menus provide additional options. Note: Actual menu screens may differ by model and firmware version.
15Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U
Page 18
LCD display interface angle adjustment
The angle of the LCD display interface can be adjusted for ease in viewing the displayed messages.
1. Remove the front bezel.
2. Locate the button on the bottom of the display interface panel.
3. Press the button and slide the bottom of the LCD display interface screen out. An audible click will be heard when the screen reaches the maximum angle.
a
6
2
9
0
u
s
Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U16
Page 19
Configuration Menus Overview
Main Menu Status Control Configuration Test A nd Diag nostics Log About
Accessory Network Management Interface Information*
Config Menu UPS Battery Outlets* Communication Display
Status Menu UPS Battery Accessory***
Control Menu** UPS Bypass Outlet Group 1* Outlet Group 2* Outlet Group 3* Clear Alarms
Test and Diagnostics Menu Self Test Runtime Test Alarm T e st
Event Log
Battery Battery Status Information
UPS** Efficiency Output Power, V A, W a tts, % Output Voltage, Current, Frequency Energy Usage Battery State Of Charge, Runtime
Input Voltage, Frequency Bypass Voltage, Frequency Self Test Runtime Test
Outlet Group
Tu rn On / Off / Reb o o t*
UPS Bypass**
Go into Bypass
Go out of Bypass
UPS**
Tu rn On / Off / Reb o o t
Outlets Outlet Group 1
Outlet Group 2 Outlet Group 3
Main Outlet
Display Language Beeper Vo lume LCD Backlight Menu type - Standard / Advanced
Green mode Enable / Disable Output Voltage / Frequency Settings Bypass Settings Battery Settings Self Test Schedule Default Setting Reset Energy Meter*
Battery Install Date Replace Notification Replace Battery Alarm
Communication
Network IP Addr ess / Boot Mode
MODBUS Address*
Part Number Serial Number Manufacture Date Firmware Version Date and Time
A
MAC Address IP Address Firmware Version
About Menu UPS Battery Accessory
Part Number Install And Replace Date Firmware Version*
Menus are subject to change depending on the ins ta lled firmware v ers ion
Options displayed will v ary
Options displayed will v ary based on c onnected acc es s ories.
* Available on the Advanced Menu Screens ** based on UPS state. ***
Log
UPS
UPS
Battery
ccessory
Page 20

Configuration

Language
Francais Italiano
Setup Wizard
V o ltage AC Setting
220 VAC 240 VAC
Menu Type
Advanced

UPS Settings

There are four ways to select UPS configuration options.
1. The first time the UPS is turned on the Setup Wizard screen will open . On each menu s creen select the des i red
settings. Press OK after each UPS setting is selected.
Note: The UPS will not turn on until all of the settings have been configured.
2. Main Menu/Configuration/UPS/Load Default. This screen allows the user to reset the UPS to factory default
settings. Press OK after the UPS setting is selected. Refer to “Configuration” on page 17 and “Menu overview” on page 17.
3. Configure settings using an external interface, such as the Network Management Web interface.
Startup configuration
Function Description
Select the language required for the display interface. Language options will vary by model and firmware version. Options:
• English
• Francais
• Italiano
•Deutch
•Espanol
• Portugues
•Russian Select the output voltage.
Options:
• 208 Vac
• 220 Vac
• 230 Vac
• 240 Vac
Setup Wizard
The Standard menu options are the most commonly used options . The Advanced menu options will be used by IT professionals who need detailed
configuration and reporting information.
Setup Wizard
17Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U
Page 21
General settings
Configure these settings at any time, using the display interface, or the Network Management Web Interface.
Parameters Default Value Options Description
Config
Menu
UPS
Green Mode
AC Setting
Output Lower Acceptable Voltage
Output Upper Acceptable Voltage
Output Frequency
Output Frequency Slew Rate
Bypass Lower Acceptable Voltage
Bypass Upper Acceptable Voltage
Disabled Disable
Enable
User Choice 230 V, 220 V, 240 V,
184 V for 208 V output 198 V for 220 V output 207 V for 230 V output 216 V for 240 V output
220 V for 208 V output 242 V for 220 V output 253 V for 230 V output 264 V for 240 V output
Auto 50/60 ± 3Hz Auto 50/60 ± 3 Hz
1 Hz/Sec 0.5 Hz/Sec
160 V 208 V - 160 to 184 V
250 V for 208 V output 255 V for 220 V output 265 V for 230 V output 270 V for 240 V output
208 V
208 V - 169 to 184 V 220 V - 186 to 198 V 230 V - 195 to 207 V 240 V - 204 to 216 V
208 V - 220 to 235 V 220 V - 242 to 253 V 230 V - 253 to 265 V 240V - 264 to 270 V
50 ± 0.1 Hz 50 ± 3.0 Hz 60 ± 0.1 Hz 60 ± 3.0 Hz
1 Hz/Sec 2 Hz/Sec 4 Hz/Sec
220 V - 160 to 198 V 230 V - 160 to 207 V 240V - 160 to 216 V
208 V - 220 to 250 V 220 V - 242 to 264 V 230 V - 253 to 270 V 240 V - 264 to 270 V
Disable or enable Green mode operation
Set the output voltage for the UPS. This setting can only be changed when the UPS output is off.
These settings may vary depending on the UPS model.
If the UPS input voltage is between the lower acceptable voltage and the higher acceptable voltage, the UPS will operate in Green mode when enabled.
If the output voltage goes outside the acceptable range the UPS will switch from Green mode to On- Line mode or to Battery mode.
Set the output frequency for the UPS.
Select the rate of change for output frequency in Hertz per second.
If the UPS input voltage is between the lower acceptable voltage and the higher acceptable voltage, the UPS can enter Bypass mode when enabled.
Bypass Mode
Low Runtime Warning
Self Te st Schedule
Default Setting
Reset Energy Meter
Allow Wider Frequency Allow Wider Frequency
Follow Frequenc y Setting
150 seconds 0 to 1800 seconds The UPS will emit an audible alarm when the
Startup + every 14 days since last test
No Yes/No Allows the user to restore the UPS factory default
No Yes/No The Energy Meter stores information on UPS
Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U18
Never Startup Startup + 14 days Startup + 7 days
The setting Allow Wider Frequency, enables Bypass mode operation for an input frequency range of 47-63 Hertz.
remaining runtime has reached this threshol d.
This is the interval at which the UPS wi ll execute a Self Test.
settings.
output energy usage. The Reset feature allows the user to reset the
Energy Meter to 0 kWh.
Page 22
Parameters Default Value Options Description
Config
Menu
Battery
Config
Menu
Display
Install Date
Replacement Notification Time
Replacement Battery Alarm Time
Language
Beeper Volume
Battery Installation Date Month-Year Enter the installation date of the RBCs. 180 days 0-360 days To set the Near End of Life alarm, select the
14 days 0-180 days The Near End of Life alarm can be muted.
English English
Francais Italiano Deutch Espanol Portugues Russian
Loud Disable
Enable
•Soft
•Medium
•Loud
number of days before the estimated battery end of life. When this date is reached the UPS will emit an alarm and a message will appear on t he display interface screen.
Example: Using the default value, the Near End of Life alarm will occur 180 days before the estimated end of life date.
Enter the number of days between the time a Near
End of Life alarm is acknowledged and the next Near End of Life alarm occurs.
Select the language required for the display interface.
Language options will vary by model and firmware version.
When audible alarms are disab led, the UPS will never emit an audible alarm.
Select the volume level for alarms when Enable is selected.
LCD Back Light
LCD Setting
Menu Type
Auto Dim Always On
Auto Dim Auto Off
Optimal Values Color
Brightness Contrast
User Choice Standard
Advanced
To conserve energy, the LCD back light illumination dims or turns off when no events are active.
Full display interface illumination returns when the UPS changes status as a result of an event or when any button on the display interface is pressed.
Adjust the brigh tness and contrast indi vidually for each LCD back light color.
The Standard menus include the mo st commonly used options.
The Advanced menu options include all parameters.
19Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U
Page 23
Parameters Default Value Options Description
Config
Menu
Outlets
Power On Delay
Power Off Delay
Reboot Duration
Minimum Return Runtime
Loadshed On Battery
Loadshed Time On Battery
Loadshed On Runtime
Loadshed Runtime
0 seconds 0-1800 seconds Select the amount of ti me the controllable outlet
90 seconds 0-32767 seconds Select the amount of time the controllable outlet
8 seconds 4-300 seconds Select the amount of time the controllable outlet
0 seconds 0-32767 seconds Select the amount of battery runtime that must be
Disable Disable
Enable
5 seconds 5-32767 seconds Select the amount of ti me the controllable outlet
Disable Disable
Enable
0 seconds 0-3600 seconds When the selected runtime threshold is reached the
groups will wait between receiving the command to turn on and actual startup.
groups will wait between receiving the command to shutdown and actual shutdown.
groups will remain off before the UPS will restart.
available before the controllable outlet groups will turn on using battery power, after a shutdown.
To conserve battery power the UPS can disconnect power from controllable outlet groups not in use.
To configure the disconnect delay time for this feature use the Loadshed Time On Battery setting.
groups will be allowed to functi on on ba ttery po wer before shutdown.
To conserve battery power the UPS can disconnect power from controllable outlet groups when the Loadshed Runtime threshold i s reached.
UPS will shutdown the controllable outlet groups.
Config
Menu
Network
Manage
Loadshed Overload
IP Address Mode
IP Address
Disable Disable
Enable
Manual, DHCP, BOOTP
Program IP, Subnet, Gateway
To conserve energy in the event of an overload condition greater than 105% output, the controllable outlet groups will immediately turn off. The controllabl e outlet groups will only t urn on again with a manual restart command onc e th e overload condition has bee n cor rected.
Refer to the Network Management Utility CD.
Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U20
Page 24

Controllable Outlet Groups

Controllable Outlet Groups provide battery backup power to conn ected equ ipm en t.
Overview
The controllable outlet groups can be configured using the Advanced menu options. Refer to “General settings” on page 18.
The controllable outlet groups can be con fi gur ed t o indep e nden tly turn off, turn on, shutdown, switch to Sleep mode, and reboot connected equipment.
Turn Off: Disconnect output p ower t o conn ected eq uipmen t either immed i ately us ing the Turn Off Immediately feature or after a configured delay using the Turn Off With Delay feature. NOTE: Controllable outlet groups can be turned on only using the Turn On feature.
Turn On: Connect output power to connected equipment either immediately using the Turn On Immediately feature or after a configured delay using the Turn On With Delay feature.
Shutdown: Disconnects the power to connected equipment either immediately or after a configured delay. Equipment reconnects after a configured delay when mains power becomes available and other configured conditions are met. Each controllable outlet group can be configured separately to allow power sequencing for equipment connected to any controllable outlet group.
Reboot: Disconnect the power to connected equipment either immediately or after a configured delay. Reconnect equipment after a configured delay when either mains or battery power becomes available and other configured conditions are met. Each controllable outlet group can b e con figu red sepa ra tely to allow power sequencing for loads conn ecte d to any controllable outlet group.
Sleep: This mode is a reboot with an extended duration where a outlet(s) remain turned off. Disconnect the power to connected equipment either immediately or after a configured delay. Reconnect equipment after a configured delay when either mains or battery power becomes available and other configured conditions are met. Each controllable outlet group can be configured separately to allow power sequencing for equipment connected to any controllable outlet group. To configure Sleep mode use an external interface, such as the Network Management Web interface.
Automatically turn off or shutdown when certain conditions occur, based on user configurations set using the Config Menu Outlets menus. Refer to “Configuration” on page 17
Connect controllable outlet groups
• Connect critical equipment to one controllable outlet group.
• Connect peripheral equipment to the other controllable outlet groups.
– To conserve battery runtime during a power outage, nonessential equipment can be configured to shut down.
Use Loadshed Time on Battery Enable/Disable and Loadshed Time on Battery Setting defined in the General Settings section. Refer to “General settings” on page 18.
– If equipment has dependent peripherals that must restart or shut down in a specific sequence, such as an
ethernet switch that must restart before a connected server can be restarted, connect the devices to diff erent outlet groups. Each controllable outlet group can be configured independently of the other groups.
• Use the Configuration menus to configure how the controllable outlet groups will react in the event of a power outage.
21Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U
Page 25

Emergency Power Off

Overview
The Emergency Power Off (EPO) option is a feature that will immediately disconnect all connected equipment from mains power. The UPS will immediately shut down and will not switch to battery power.
Connect each UPS to the EPO switch. In configurations where multiple units are connected in parallel, each UPS must be connected to the EPO switch.
The UPS must be restarted for power to return to connected equipment. Press the UPS.
ON/OFF button on the front panel of the
CAUTION
RISK OF DAMAGE TO EQUIPMENT OR PERSONNEL
• Adhere to all national and local electrical codes.
• Wiring must be performed by a qualified electrician.
• Always connect the UPS to a grounded outlet.
Failure to follow these instructions can result in equipment damage and minor or moderate injury.
Normally open contacts
1. If the EPO switch or relay contacts are normally open, insert the wires from the switch or contacts at pins 1 and 2 of the EPO terminal block. Use 16-28 AWG wire.
2. Secure the wires by tightening the screws.
If the contacts are closed, the UPS will turn OFF and power will be removed from the load.
Normally closed contacts
1. If the EPO switch or relay contacts are normally closed, insert the wires from the switch or contacts at pins 2 and 3 of the EPO terminal block. Use 16-28 AWG wire.
2. Insert a wire jumper between pins 1 and 2. Secure the wires by tightening the three screws at positions 1, 2, and 3.
If the contacts are opened, the UPS will turn OFF and power will be removed from the load.
Note: Pin 1 is the power source for the EPO circuit, it provides a few milliampere of 24 V power.
If the normally closed (NC) EPO configuration is used, the EPO switch or relay should be rated for “dry” circuit applications, the rating should be for low voltage and low current applications. This normally implies the contacts are gold plated.
The EPO interface is a Safety Extra Low Voltage (SELV) circuit. Connect the EPO interface only to other SELV circuits. The EPO interface monitors circuits that have no determined voltage potential. SELV circuits are controlled by a switch or relay properly isolated from mains power. To avoid damage to the UPS, do not connect the EPO interface to any circuit other than a SELV circuit.
Use one of the following cable types to connect the UPS to the EPO switch.
• CL2: Class 2 cable for general use.
• CL2P: Plenum cable for use in ducts, plenums, and other spaces used for environmental air.
• CL2R: Riser cable for use in a vertical run in a floor to floor shaft.
• CLEX: Limited use cable for use in dwellings and for use in raceways.
• Installation in Canada: Use only CSA certified, type ELC, (extra low voltage control cable).
• Installation in countries other than Canada and the USA: Use standard low voltage cable in accordance with national
and local regulations.
Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U22
Page 26

Network Management Interface

Introduction

The UPS has a network port and console port that can be used to access the Network Management Interface. The Network Management Interface is very similar to an AP9630 Network Management Ca rd (NMC) that is integrated into a UPS with one universal input/output port.
The Network Management Interface and the AP9630 NMC have the same firmware, operation modes and interaction with other APC products such as PowerChute Network Shutdown.
Refer to the Network Management Card utility CD supplied with this product.

Features

The Network Management Interface allows the UPS to function as a Web based, IPv6 ready product. The Network Management Interface can manage the UPS using multiple open standards such as:
Hypertext Transfer Protocol (HTTP) Secure SHell (SSH) Simple Network Management Protocol versions 1
and 3 (SNMPv1, SNMPv3) File Transfer Protocol (FTP) Secure Copy (SCP) Telnet Syslog RADIUS
The Network Management Interface:
• Provides UPS control and Self Test scheduling f eatures.
• Provides data and event logs.
• Enables you to set up notifications through event logging, e-mail, and SNMP traps.
• Provides support for PowerChute Network Shutdown.
• Supports using a Dynamic Host Configuration Protocol (DHCP) or BOOTstrap Protocol (BOOTP) server to provide the network (TCP/IP) values.
• Supports use of Remote Monitoring Service (RMS).
• Provides the ability to export a user configuration (.ini) file from a configured UPS, to one or more unconfigured UPS without conversion to a binary file.
• Provides a selection of security protocols for authentication and encryption.
• Communicates with StruxureWare Central and InfraStruxure Manager.
• Supports one universal input/output port for connection to a:
– Temperature probe, AP9335T (supplied) – Temperature/humidity sensor, AP335TH (optional) – Relay input/output connector that su pports two input cont acts and on e output relay, AP9810 Dry Contact I/O
Accessory (optional)
Hypertext Transfer Protocol over Secure Sockets layer (HTTPS)
23Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U
Page 27

Related Documents

The Network Management Card Utility CD contains the following documentation:
• UPS Network Management Card 2 User’s Guide
• Network Management Card Upgrade Utilities
• Security Handbook
• PowerNet Management I nformation Base (MIB) Refe rence Guide

IP Address Configuration

The default TCP/IP configuration setting DHCP, assumes that a properly configured DHCP server is available to provide TCP/IP settings to the Network Management Interface.
If the Network Management Interface obtains an IPv4 address from a DHCP server, use the display interface menus About/ Interface, to see the address.
T o setup a static IPv4 address use the display interface Config menu. Set the IP address Subnet Mask and Gateway fr om th e Config menu.
See the User’s Guide on the Network Management Card Utility CD for user information about the Network Management Interface and for setup instructions.
Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U24
Page 28

Smart Battery Management

Definitions
• Battery Module: A string of battery cells arranged to produce a battery assembly with a connector.
• Replaceable Battery Cartridge (RBC): An APC battery cartridge consisting of two battery modules. Replacement RBCs can be ordered from the APC web site, www.apc.com.
• Smart External Battery Pack (XLBP): An enclosure that contains RBC(s) and battery management electronics.
• User Interface (UI): Any interface by which a user can interact with the system. This may include a UPS display interface, a network management interface or PowerChute™ Network Shutdown software.
NOTE: Do not use a battery that is not APC approved. The system will not detect the presence of a non APC approved battery and may adversely affect the operation of the system. Use of a non APC approved battery will void the manufacturer warranty.
Features
Smart Battery Management provides the following features:
• Monitors and informs the user of the health of each RBC.
• Monitors and shows on the UPS Display Interface screen, the date for the end of useful life for each RBC.
• The UPS emits an alarm and shows a message on the UPS Display Interface screen to indicate the estimated battery end of life. On the UPS Display Interface screen the user can set the number of days before the alarm is heard and the message appears on the UPS Display Interface screen.
• Automatically detects the addition or removal of XLBPs and RBCs.
• Monitors the internal temperature of each XLBP and automatically adjusts the battery charging.
Maintenance
RBC maintenance: The APC RBC uses sealed lead acid battery cells and does not require maintenance.
Runtime Test (Calibration): This should be performed anytime the steady state load is changed significantly, for example a new server is added to or removed from the UPS load.
Battery health monitoring: The battery energy output and voltage are monitored to assess the health of the installed batteries when the UPS is operating on battery. Battery health monitoring is done during a UPS Self Test, a Runtime Calibration Test, and when the UPS is operating on battery power. The UPS can be configured to perform periodic, automatic Self Tests.
End of useful life
Near end of life notification: A warning message will appear on the UPS display interface screen when each RBC is approaching the end of its useful life. For configuration details refer to Replacement Notification Time and Replacement Battery Alarm Time. The estimated replacement date for each RBC is available through the UI.
Needs replacement notification: The UPS display interface screen shows when RBC replacement is required. The RBC must be replaced as soon as possible. When an RBC requires replacement, the UPS display interface may recommend that additional RBCs be replaced if they will soon reach the end of their useful life.
CAUTION: Continued operation after end of useful life notification may cause damage to the batteries.
Recycling: Remove the RBC from the XLBP. Recycle the RBC. Do not disassemble an RBC.
25Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U
Page 29
Replace the RBCs in a UPS
An RBC should only be disconnected or removed from the UPS temporarily as part of the battery replacement procedure.
• Disconnect all connected battery modules in the UPS. Slide the RBCs out of the UPS.
• Slide the new RBCs into the UPS and connect the battery modules to the UPS.
• Securely connect each battery module. Press the battery connector into the UPS until it is firmly connected. A battery that is not fully connected will cause erratic UPS operation, abnormal error messages and connected equipment may not receive battery power during power outages.
• After installing the RBC, the UPS display interface may prompt the user to verify the status of the replaced battery modules. If the battery module is new, respond
YES. If the battery module is not new, respond NO.
Recommended actions after installing new RBCs
• Verify that the UPS is connected to input power and the output power is turned on. Refer to the Operation section in this manual for instructions.
• Verify that the UPS load is greater than 400 watts. This will appear on the UPS display interface screen.
• Perform a UPS Self Test.
• Verify on the UPS display interface that the installation dates for the replaced RBCs are set to the current date. The installation dates can be changed manually on the UPS display interface. If all RBCs have been replaced at the same time, all installation dates can be changed simultaneously. For configuration details refer to Battery Install Date on page 19 of this manual.
• Allow the system to charge for 24 hours to ensure full runtime capability.
XLBP installation and replacement
Refer to the External Battery Pack Installation Guide for installation and replacement instructions.
Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U26
Page 30

Troubleshooting

Use the table below to solve minor installation an d operation problems . Refer to the APC web site, www.apc.com for assistance with complex UPS problems. The UPS features firmware that can be upgraded. Go to the APC web site, www.apc.com/Support, or contact your local Customer Care Center for more information.
Problem and Possible Cause Solution UPS will not turn on or there is no output
The UPS is not connected to mains power.
The UPS display interface screen shows very low or no mains power.
There is an internal UPS alert or warning. The UPS Display Interface screen will show a message to identify the alert or
Be sure the power cable is securely connected to the UPS and to the mains power supply.
Check the mains power supply to verify acceptable power quality.
warning and corrective action.
UPS emits an audible alarm
Normal UPS operation when running on battery power.
The UPS emits an audible alarm and has a red or amber back light on the UPS Display Interface screen.
The UPS is operating on battery power. Refer to the status of the UPS as shown on the UPS Display Interface screen.
Press any key to mute all alarms.
An Alarm or Warning condition exists. Refer to the display interface screen for information.
UPS does not provide expected backup time
The UPS batteries are weak due to a recent power outage or they are near the end of service life.
Charge the batteries. Batteries require rechar ging after ex tended outages and wear out faster when put into service often or when operated at elevated temp eratures. If the batteries are near the end of service life, consider r eplacing the batteries even if the Replace Battery message is not displayed.
The UPS is experiencing an overload condition.
The connected equipment exceeds the specified maximum load. R efer to the APC web site, www.apc.com for product specifications.
The UPS will emit a sustained audible alarm until the overload condition is corrected.
Disconnect nonessential equipment from the UPS to correct the overload condition.
27Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U
Page 31
Problem and Possible Cause Solution UPS operates on battery power while connected to mains power
The input circuit breaker has tripped. Reduce the load on the UPS. Disconnect nonessential equipment and reset the
circuit breaker. Check the circuit breaker rating for the connected equipment.
There is very high, very low, or distorted input line voltage.
The UPS Display Interface screen shows the message Waiting for Minimum Runtime.
Navigate to the UPS Display Interface screen that shows input voltage. Verify that the input voltage is within specified operating limits.
If no input voltage is indicated on the UPS Display Interface screen, contact Customer Support through the APC web site, www.apc.com.
The UPS has been configured to operate for a specified period of runtime. The setting can be changed through the Config/UPS menus.
UPS Display Interface Status screen shows Overload and the UPS emits a sustained audible alarm
The UPS is experiencing an overload condition.
The connected equipment exceeds the maximum load rating for the UPS. The UPS will emit a sustained audible alarm until the overload condition is
corrected. Disconnect nonessential equipment from the UPS to correct the overload
condition.
UPS Display Interface Status screen shows UPS is operating in Bypass mode
The UPS received a command to operate in Bypass mode
The UPS has automatically switched to Bypass mode due to an internal UPS alert or warning.
No action is required.
The UPS Display Interface screen will show a message to identify the alert or warning and corrective action.
UPS Display Interface is red or amber and shows an alert or warning message The UPS emits a sustained audible alarm
The UPS has detected a problem during normal operation.
The UPS Display Interface screen shows the message Disconnected Battery .
The UPS Display Interface screen shows the message Replace Battery.
Follow the instructions on the UPS Display Interface screen. Press any key to mute all alarms.
Be sure the battery cables are securely connected. Perform a UPS Self Test to be sure the UPS detects all connected batteries. To perform a UPS Self Test use the UPS Display Interface menu option Test and
Diagnostics.
Allow the battery to recharge for 24 hours. To perform a Runtime test use the UPS Display Interface menu option Test and
Diagnostics.
If the problem persists, replace all of the batteries.
Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U28
Page 32
Problem and Possible Cause Solution
Output Off
Output Overload
Bypass
The UPS display turns red or amber, displays an alert message, and emits a sustained audible alarm Red illumination indicates a UPS alarm that requires immediate attention Amber illumination indicates a UPS alarm that requires attention
There is an internal UPS alert or warning. Do not attempt to use the UPS. Turn the UPS of f and have it serviced immediately.
1/1
Power Sys Error - 00100 Contact Customer Support
123
The UPS is experiencing an overload condition.
Reduce the load on the UPS. Disconnect nonessential equipment.
1/1
123
The Replace Battery alert is displayed
The battery has a weak charge. Allow the battery to recharge for at least four hours. Then, perform a
UPS Self Test. If the problem persists after recharging, replace the battery.
The replacement battery is not properly connected.
Be sure the battery cable is securely connected.
UPS reports; Battery Sys Error 0800 or Needs Firmware Update
UPS reports; Battery Sys Error 0800 or Needs Firmware Update
The UPS system firmware must be updated to correct this problem.
To update the UPS system firmware go to www.apc.com/support. Select Search the Knowledge Base and search for FA164737.
Follow the instructions to upgrade the firmware.
29Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U
Page 33

Transport

1. Shut down and disconnect all connected equipment.
2. Disconnect the unit from mains power.
3. Disconnect all internal and external batteries (if applicable).
4. Follow the shipping instructions outlined in the Service section of this manual.

Service

If the unit requires service, do not return it to the dealer. Follow these steps:
1. Review the Troubleshooting section of the manual to eliminate common problems.
2. If the problem persists, contact APC Customer Support through the APC web site, www.apc.com.
a. Note the model number and serial number and the date of purchase. The model and serial
numbers are locate d on th e rear panel of t he unit and a re availabl e thr ough the LCD d ispla on sel
ect models.
b. Call APC Suppo rt and a tech nicia n will attempt t o solve th e probl em over the phon e. If thi s
is not possible, the technician will issue a Returned Material Authorization Number (RMA#).
y
c. If the unit is under warranty, the repairs are free
Service procedures and returns may vary internationally. Refer to the APC web site fo
d.
co
untry specific instructions.
3. Pack the unit properly to avoid damage in transit. Never use foam beads for packaging. Damage sustained
in transit is not covered under warranty.
a. Note: When shipping within the United States, or to the United States always
DISCONNECT O Department of Transportation (DOT) and IAT A r egul ations . The intern al batteries ma
emain in the UPS.
r
b. Batteries may remain connected in the XBP during shipment. Not all units utilize XLBPs.
4. Write the RMA# provided by Customer Support on the outside of the package.
5. Return the unit by insured, prepaid carrier to the address provided by Customer Support.
NE UPS BATTERY before shipping in compliance with U.S.
.
r
y
Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U30
Page 34

Limited Factory Warranty

Schneider Electric IT Corporation (SEIT), warrants its products to be free from defects in materials and workmanship for a period of three (3) years excluding the batteries, which are warranted for two (2) years from the date of purchase. The SEIT obligation under this warranty is limited to repairing or replacing, at its own sole option, any such defective products. Repair or replacement of a defective product or part thereof does not extend the original warranty period.
This warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase. Products may be registered online at warranty.apc.com.
SEIT shall not be liable under the warranty if its testing and examination disclose that the alleged defect in the product does not exist or was caused by end user or any third person misuse, negligence, improper installation, testing, operation o r use of th e product con trary to S EIT recommendati ons of sp ecifications . Further , SEIT shall not be liable for defects resulting from: 1) unauthorized attempts to repair or modify the product, 2) incorrect or inadequate electrical voltage or connection, 3) inappropriate on site operation conditions, 4) Acts of God, 5) exposure to the elements, or 6) theft. In no event shall SEIT have any liability under this warranty for any product where the serial number has been altered, defaced, or removed.
EXCEPT AS SET FORTH ABOVE, THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OF LAW OR OTHERWISE, APPLICABLE TO PRODUCTS SOLD, SERVICED OR FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH.
SEIT DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABI LITY, SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE.
SEIT EXPRESS WARR ANTIES WILL NOT BE ENLARGED, DIMINISHED, OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF, SEIT RENDERING OF TECHNICAL OR OTHER ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS.
THE FOREGOING WARRANTIE S AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES. THE WARRANTIES SE T FORTH ABOVE CONSTITUTE SEIT’S SOLE LIABILITY AND PURCHASER EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES. SEIT WARRANTIES EXTEND ONLY TO ORIGINAL PURCHASER AND ARE NOT EXTENDED TO ANY THIRD PARTIES.
IN NO EVENT SHALL SEIT, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT, SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT OF THE USE, SERVICE OR INSTALL ATION OF THE PRODUCTS, WHETHER SU CH DAMAGES ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT, NEGLIGENCE OR STRICT LIABILITY OR WHETHER SEIT HAS BEEN ADVISED IN ADV ANCE OF THE POSSIBILITY OF SUCH DAMAGES. SPECIFICALLY, SEIT IS NOT LIABLE FOR ANY COSTS, SUCH AS LOST PROFITS OR REVENUE, WHETHER DIRECT OR INDIRECT, LOSS OF EQUIPMENT, LOSS OF USE OF EQUIPMENT, LOSS OF SOFTWARE, LOSS OF DATA, COSTS OF SUBSTITUANTS, CLAIMS BY THIRD PARTIES, OR OTHERWISE.
NOTHING IN THIS LIMITED WARRANTY SHALL SEEK TO EXCLUDE OR LIMIT SEIT LIABILITY FOR DEATH OR PERSONAL INJURY RESULTING FROM ITS NEGLIGENCE OR ITS FRAUDULENT MISREPRESENTATION OF TO THE EXT ENT THAT IT C ANNOT BE EXCLUDED OR LIMITED BY APPLICABLE LAW.
To obtain service under warranty you must obtain a Returned Material Authorization (RMA) number from customer support. Customers with warranty claims issues may access the SEIT worldwide customer support network through the APC web site: www.apc.com. Select your country from the country selection drop down menu. Open the Support tab at the top of the web page to obtain information for customer support in your region. Products must be returned with transportation charges prepaid and must be accompanied by a brief description of the problem encountered and proof of date and place of purchase.
31Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U
Page 35
Page 36
© 2014 APC by Schneider Electric. APC, the APC logo, PowerChute, and Smart-UPS are owned by
Schneider Electric Industries S.A.S. or their affiliated companies. All other trademarks are property of their
respective owners.
12/2014EN 990-4505B
Loading...