Schneider Electric Smartlink SI B User Manual

Smartlink SI B

DOCA0123EN-04 09/2020
Smartlink SI B
User Manual
09/2020
DOCA0123EN-04
www.se.com
The information provided in this documentation contains general descriptions and/or technical character­istics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein. If you have any suggestions for improvements or amendments or have found errors in this publication, please notify us.
You agree not to reproduce, other than for your own personal, noncommercial use, all or part of this document on any medium whatsoever without permission of Schneider Electric, given in writing. You also agree not to establish any hypertext links to this document or its content. Schneider Electric does not grant any right or license for the personal and noncommercial use of the document or its content, except for a non-exclusive license to consult it on an "as is" basis, at your own risk. All other rights are reserved.
All pertinent state, regional, and local safety regulations must be observed when installing and using this product. For reasons of safety and to help ensure compliance with documented system data, only the manufacturer should perform repairs to components.
When devices are used for applications with technical safety requirements, the relevant instructions must be followed.
Failure to use Schneider Electric software or approved software with our hardware products may result in injury, harm, or improper operating results.
Failure to observe this information can result in injury or equipment damage.
© 2020 Schneider Electric. All rights reserved.
2 DOCA0123EN-04 09/2020

Table of Contents

Safety Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Chapter 1 Smartlink System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 2 Architecture of Smartlink System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Smartlink SI B Gateway. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Smartlink Communication System Pre-assembled Cables . . . . . . . . . . . . . . . . . . . . . . . . . .
Acti9 Devices with Ti24 Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Acti9 Devices without Ti24 Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PowerTag Wireless Communication Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Devices out of the Acti9 Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Devices with Analog Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 3 Technical Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Technical Characteristics of the Smartlink SI B Gateway . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Characteristics of the Devices with Ti24 Interface . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 4 Sizing the 24 Vdc Power Supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Definition of the 24 Vdc Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Protection Against a 240 Vac Fault on the Smartlink SI B Gateway Channels . . . . . . . . . . .
Electromagnetic Compatibility (EMC) Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 5 Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 6 Connection of Input/Output Channels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Acti9 Devices with Ti24 Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Volt-Free Low Level Indication Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Volt-Free Standard Indication Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Surge Arresters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contactor and Relay (Not in the Acti9 Range) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Direct Output Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Indirect Output Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Generating Summary Data Using iOF+SD24, OF+SD24, OF24, or SD24 . . . . . . . . . . . . . .
Analog Input Characteristics and Connection (Recommendation) . . . . . . . . . . . . . . . . . . . .
Recommendation for Cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 7 Getting Started with Smartlink SI B Gateway . . . . . . . . . . . . . . . . . . . . . . . 67
7.1 General Principle to Commission a Smartlink SI B Gateway System . . . . . . . . . . . . . . . . . .
Commissioning Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.2 Commissioning a Smartlink SI B Gateway System with EcoStruxure Power Commission
Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation of EcoStruxure Power Commission Software . . . . . . . . . . . . . . . . . . . . . . . . . . .
Commissioning with EcoStruxure Power Commission Software. . . . . . . . . . . . . . . . . . . . . .
7.3 Commissioning a Smartlink SI B Gateway with Webpages . . . . . . . . . . . . . . . . . . . . . . . . .
Discovering Smartlink SI B Gateway through Windows Explorer . . . . . . . . . . . . . . . . . . . . .
Login into Webpages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Webpage Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Firmware Upgrade. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Basic Commissioning of PowerTag Wireless Communication Energy Sensors . . . . . . . . . .
Commissioning the Modbus Meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 8 Setting Up Wireless Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Wireless Network Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wireless Communication Devices Selection and Configuration . . . . . . . . . . . . . . . . . . . . . .
11
16 19 21 22 23 25 26
28 31
34 36 37
40 46
50 51 52 53 54 57 58 59 60 62 63
68 68
69 70 71 73 74 76 77 78 79 81
84 86
DOCA0123EN-04 09/2020 3
Chapter 9 Setting Up Ethernet Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Ethernet Principle. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Set Up and Ethernet Addressing Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ethernet Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
IP Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
IP Network Services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Smartlink SI B Gateway Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 10 Setting Up Modbus Communication (Gateway Function). . . . . . . . . . . . . . . 97
Modbus Master Principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Possible Architecture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gateway Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Modbus Port Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 11 System Settings Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
General Network Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Modbus TCP/IP Filtering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Email Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
User Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 12 Monitoring, Control, and Diagnostics Webpages . . . . . . . . . . . . . . . . . . . . . 123
Monitoring and Control Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Alarms Page. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Communication Diagnostics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 13 Modbus Registers Tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
13.1 General Description of Modbus Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Modbus Table Format and Data Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
13.2 Summary and Detailed Modbus Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Modbus Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Summary of Digital Channels 1 to 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Details of Digital Channels 1 to 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Analog Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PowerTag Wireless Communication Energy Sensors Modbus Tables . . . . . . . . . . . . . . . . .
Embedded Configuration Registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
13.3 Modbus Tables for Connected Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
iOF+SD24 Indication Auxiliary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
OF+SD24 Indication Auxiliary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
iEM Meters or Meter with Pulse Output (IEC 62053-31 Standard) . . . . . . . . . . . . . . . . . . . .
iACT24 Auxiliary for iCT Contactor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
iATL24 Auxiliary for iTL Impulse Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contactor and Relay (Not in the Acti9 Range) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Acti9 RCA iC60 Remote Control with Ti24 Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Acti9 Reflex iC60 Integrated Control Circuit Breaker With Ti24 Interface . . . . . . . . . . . . . . .
Chapter 14 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167
Common Problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Appendices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Appendix A Details of Modbus Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171
Modbus TCP/IP Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Modbus TCP/IP Exception Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Function 8: Modbus Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
90 91 93 94 95 96
98 100 101 102 103
106 109 110 113 115 117
124 126 127 128
132 133 135 138 139 141 144 149 151 156 158 159 160 161 162 163 164 165 166
167 169
172 174 175
4 DOCA0123EN-04 09/2020
Function 43-14: Read Device Identification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Function 43–15: Read Date and Time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Function 43-16: Write Date and Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Function 100–4: Read n Non-Adjacent Words . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
177 179 180 181
Appendix B Data Availability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
Data Availability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
183
Appendix C Reset of Smartlink SI B Gateway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
187
DOCA0123EN-04 09/2020 5
6 DOCA0123EN-04 09/2020

Safety Information

Important Information
NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, service, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction and operation of electrical equipment and its installation, and has received safety training to recognize and avoid the hazards involved.
DOCA0123EN-04 09/2020 7
CYBERSECURITY SAFETY NOTICE
POTENTIAL COMPROMISE OF SYSTEM AVAILABILITY, INTEGRITY, AND CONFIDENTIALITY
Change default passwords at first use to help prevent unauthorized access to device settings,
controls, and information.
Disable unused ports/services and default accounts to help minimize pathways for malicious
attackers.
Place networked devices behind multiple layers of cyber defenses (such as firewalls, network
segmentation, and network intrusion detection and protection).
Use cybersecurity best practices (for example, least privilege, separation of duties) to help prevent
unauthorized exposure, loss, modification of data and logs, or interruption of services.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
WARNING
8 DOCA0123EN-04 09/2020
At a Glance
Document Scope
Validity Note
Online Information

About the Book

The purpose of this manual is to provide users, installers, and maintenance personnel with the technical information necessary to install and use the Smartlink SI B communication system.
The Smartlink SI B communication system can be easily integrated into any building management architecture.
It combines command and control, metering and protection functions designed for energy efficiency solutions. Based on the Modbus protocol, the Smartlink SI B communication system allows switchboard data to be exchanged in real time with a supervision system or a PLC.
This system's pre-wired cables can save time and prevent wiring errors during installation.
The information contained in this guide is likely to be updated at any time. Schneider Electric strongly recommends that you have the most recent and up-to-date version available on
www.se.com/ww/en/download
The technical characteristics of the devices described in this guide also appear online. To access the information online, go to the Schneider Electric home page at
.
www.se.com
.
Related Documents
Title of Documentation Reference Number
Smartlink Ethernet Communication System – User Manual
Smartlink Modbus Communication System – User Manual
iEM3000 Series - Energy Meters – User Manual
PM3200 Series – Power Meters – User Manual
Communication System Diagnostics – User Manual
Smartlink SI B Gateway – Release Note
PowerLogic EGX300 Ethernet Gateway – User Guide
EcoStruxure Power Commission – Installation Guide
Smartlink SI B Gateway – Instruction Sheet
Smartlink Modbus Gateway – Instruction Sheet
iACT24 - Low-level Control and Indication Auxiliary for iCT Contactors – Instruction Sheet
iATL24 - Low-level Control and Indication Auxiliary for iTL Impulse Relays – Instruction Sheet
RCA iC60 Remote Controls – Instruction Sheet
Watt-hour Meter - iEM2000T – Instruction Sheet
iEM3100 Series 63 A Watt-hour Meter (MID) – Instruction Sheet
iEM3200 Series 1 A/5 A Watt-hour Meter (MID) – Instruction Sheet
iEM3300 and iEM3350 125 A Watt-hour Meter (MID) – Instruction Sheet
iEM3310 125 A Watt-hour Meter (MID) – Instruction Sheet
PM3250 – PM3255 – Power Meter – Instruction Sheet
PowerTag M63 Energy Sensor – Instruction Sheet
PowerTag P63 Energy Sensor – Instruction Sheet
PowerTag F63 Energy Sensor – Instruction Sheet
PowerTag M250 Energy Sensor – Instruction Sheet
PowerTag M630 Energy Sensor – Instruction Sheet
RCA iC60 Remote Control - iC60 Circuit Breakers – Reference Manual
DOCA0073EN
DOCA0004EN
DOCA0005EN
DOCA0006EN
DOCA0042EN
DOCA0181EN
63230-319-216
DOCA0134EN
NVE12086
S1B33423
S1B3342101
S1B3342201
S1A4079001
S1A89364
NHA15789
NHA15801
HRB91204
HRB91202
S1B46607
EAV31628
QGH78639
QGH78642
QGH46815
QGH46820
A9MA01EN
DOCA0123EN-04 09/2020 9
Title of Documentation Reference Number
Reflex iC60 Integrated Control Circuit Breaker - iC60 Circuit Breakers – Reference Manual
Reflex iC60 - Integrated Remote Control Circuit Breakers – Reference Manual
Smartlink Device – Catalogue Page
A9MA03EN
S1B8674701
CA908033E
You can download these technical publications and other technical information from our website at
https://www.se.com/en/download
.
Trademark Notice
All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.
10 DOCA0123EN-04 09/2020

Overview

Introduction
Smartlink SI B Smartlink System DOCA0123EN-04 09/2020

Smartlink System

Chapter 1
Smartlink System
The Smartlink system is used to control and monitor the final distribution boards to any supervision system.
Modular devices in the Smartlink system is used to monitor, measure, and control electrical distribution boards via a Modbus serial line or Modbus TCP/IP communication network.
The Smartlink system concentrates the data from electrical distribution boards in real time, thus contributing to achieve energy efficiency targets.
The Smartlink system collects data from any meter (including kilowatt-hour, water, air, gas, or steam meters).
This system consists of:
Smartlink SI B gateway and the test kit.iOF+SD24, OF+SD24, iOF/SD24 indication auxiliaries.iACT24 and iATL24 auxiliaries for contactors and impulse relays.Acti9 RCA iC60 remote control module with Ti24 interface.Acti9 Reflex iC60 integrated control circuit breaker with Ti24 interface.iEM2000T, iEM3110, iEM3155, iEM3210, iEM3255, iEM3310, iEM3350, and iEM3355 pulse meters
and Modbus meters.
PowerTag energy sensors such as:
PowerTag M63 (for iC60 offer)PowerTag P63 (for DT40 and iC40 offers)PowerTag F63 (for other devices such as VigiBlock and specific installations)PowerTag M250/M630 (for ComPact NSX, ComPact INS, and ComPact INV)
The PowerTag energy sensors are wireless devices that are directly mounted on a protective device and are connected to Smartlink SI B gateway through a wireless communication. The circuit breaker auxiliary allows you to monitor and control the devices and collects not only energy, but also power and alarm events on the voltage loss. PowerTag energy sensors are mounted upstream or downstream of the device.
Pre-wired cables.
This system offers the following advantages and services:
Calculation functions.Telemetering applications.Monitor load unbalance.Monitor power and voltage loss.Alarm temperature, humidity, and luminescence.Energy management and regulations.Scheduled control of electrical distribution with any building systems.
The Smartlink system is an open system:
Smartlink SI B gateway can be used as a standard I/O distributed module.Smartlink SI B gateway is equipped with seven digital channels. Each channel is represented by a Ti24
interface consisting of:
Two power supply terminals: 0 V and 24 VdcTwo 24 Vdc logic inputs (I1 and I2)One 24 Vdc logic output (Q)
Each Ti24 interface is compatible with Miniconnect Phoenix standard connectors (at intervals of
3.81 mm) or equivalent.
Smartlink SI B gateway is equipped with one analog channel having:
Two power supply terminals: 0 V and 24 VdcTwo analog inputs (4...20 mA or 0...10 V)
DOCA0123EN-04 09/2020 11
Smartlink System
Smartlink SI B gateway is compatible with any type of counter (pulse output) compliant with standard
IEC 62053-21 (minimum pulse width of 30 ms):
The pulse weight must be configured (written in a Modbus register).Smartlink SI B gateway calculates consumption and flow.
Smartlink SI B gateway is compatible with any type of device equipped with low-level inputs and outputs
(24 Vdc).
The Smartlink system is simple to use:
The pre-wired cables of the Smartlink system reduce complexity and wiring time by allowing connection
on a Smartlink SI B gateway of the Smartlink system components and 24 Vdc compatible products.
The functions of the Smartlink system can be created by sending messages (Modbus protocol) to
Smartlink devices (Modbus slave or Ethernet server) that act on devices via Ti24 interfaces.
Smartlink SI B Communication System Block Diagram
12
The Smartlink SI B communication system can manage a gateway function (Modbus TCP/IP to Modbus RS485). It can support up to eight Modbus RS485 slave devices (address from 1 to 149). The default address of the Modbus master port is 255.
The Smartlink SI B communication system also manages webpage to configure the settings or to monitor and control the devices.
DOCA0123EN-04 09/2020
Smartlink System
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
It is recommended not to use Smartlink SI B gateway to remotely control the circuits or loads requiring visual attendance.
Failure to follow these instructions will result in death or serious injury.
WARNING
POTENTIAL COMPROMISE OF SYSTEM AVAILABILITY, INTEGRITY, AND CONFIDENTIALITY
Change the default passwords to help prevent unauthorized access to device settings and information.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
DOCA0123EN-04 09/2020 13
Smartlink System
14
DOCA0123EN-04 09/2020
Smartlink SI B Architecture of Smartlink System DOCA0123EN-04 09/2020

Architecture of Smartlink System

Chapter 2
Architecture of Smartlink System
What Is in This Chapter?
This chapter contains the following topics:
Smartlink SI B Gateway 16
Smartlink Communication System Pre-assembled Cables 19
Acti9 Devices with Ti24 Interface 21
Acti9 Devices without Ti24 Interface 22
PowerTag Wireless Communication Devices 23
Devices out of the Acti9 Range 25
Devices with Analog Output 26
Topic Page
DOCA0123EN-04 09/2020 15
Architecture of Smartlink System

Smartlink SI B Gateway

Introduction
The Smartlink SI B gateway has seven digital channels (24 Vdc) and one analog channel (4...20 mA or
0...10 Vdc) and can be connected to the devices in the Acti9 range equipped with a Ti24 interface. The data can be transmitted from the Smartlink SI B gateway to a PLC or a supervision system via a Modbus TCP/IP protocol.
The Smartlink SI B gateway channels can also be used to transmit standardized I/O. The Smartlink SI B gateway can also therefore communicate with devices (not in the Acti9 range) with or without a Ti24 link.
The devices which can be connected to the Smartlink SI B gateway include:
Acti9 products: control switch for iACT24 contactors and iATL24 impulse relays, iC60 iOF+SD24
indication auxiliary, C60 OF+SD24 indication auxiliary, RCA iC60 remote control with Ti24 interface, Reflex iC60 integrated control circuit breaker with Ti24 interface.
Meters: iEM2000T or other meters (Schneider Electric or other manufacturers) in compliance with IEC
62053-21 (minimum pulse 30 ms).
Any product (not in the Acti9 range) that has command and control information: 2 discrete 24 V outputs
and 1 discrete 24 V input.
PowerTag energy sensors.Any product using analog output (4...20 mA or 0...10 V).
The Smartlink SI B gateway is an intermediary between the supervisor and various electrical appliances. It can therefore be used to retrieve and process data received from devices and also control them. The functions available depend on the type of connected devices.
The functions of Smartlink SI B gateway are described in Smartlink SI B Function
(see page 96)
.
Description
A 7 digital input/output channels B 1 analog channel with two inputs C 1 x 24 V power connector D Status LEDs (including Wireless LED) E Ethernet LEDs F Reset button G Ethernet communication port H 1 Modbus connector: 4-way
Smartlink SI B Gateway Acting as a PowerTag Concentrator
The PowerTag auxiliaries provide compact and high density metering solution with rich and accurate data for building systems (that can send energy, power, current, voltage, and power factor to Smartlink concentrator every 5 seconds). Tagging a circuit breaker with PowerTag allows you to monitor any electrical device with high flexibility (for example, you can add PowerTag energy sensors after the last­minute changes in the distribution board).
The PowerTag energy sensors provide an advanced alarm on load level of each phase to monitor and balance the loads, and sends an alarm if the electrical device is down.
The Smartlink SI B gateway behaves as a data concentrator to collect information from digital, analog, wireless auxiliaries, and downstream Modbus devices. The Smartlink SI B gateway provides monitoring and control of the digital switchboard over Modbus TCP for upstream software and via embedded webpages. The addition of new wireless auxiliaries provides affordable metering with panel size optimization.
16
DOCA0123EN-04 09/2020
Digital Input/Output Channels
The figure below shows the terminals for each channel.
A Channels from 1 to 7
Description of terminals for each channel (Ti24 interface):
Terminal Description
24V 24 V of the 24 Vdc power supply
Q Control output
I2 Input number 2
I1 Input number 1
0V 0 V of the 24 Vdc power supply
Communication LED
Architecture of Smartlink System
COM LED Description
Yellow: During communication with the Modbus serial port, the LED is Off if there is no Modbus communication
Blinking green: While pressing the reset button between 5 and 10 seconds, the IP settings are reconfigured to DHCP mode
Wireless Status LED
Operating Mode WIRELESS LED Description
Initialization
Startup Blinking amber: Looking for wireless device
Operation Flash green every five seconds: Networking complete (normal operation)
Degraded
Disabled
Solid amber: Not configured
Blink green and red (one second): Downgraded in Boot mode
No light: Wireless disabled
Status LED
Operating Mode STATUS LED Description
Initialization / Operation Green light: Device operates normally
Start-up
Reset (level 1)
Reset (level 2) Red blink (Fast, 2 blinks/sec): While pressing the Reset button for more than10 seconds.
Duplicate IP address Red blink (1 blink per second): System has detected duplicate IP address. Check and
Degraded Flashing orange light: Power supply of the product is degraded
Failure Red light: Out of service or hardware failure
DOCA0123EN-04 09/2020 17
Alternate green and red light every second: Device is starting
Green blink: Reset button acknowledgment (pressed between 5 to 10 seconds). IP settings are reconfigured to DHCP mode.
The LED stops blinking after the device restarts. Do not switch off the device until the LED stops blinking in RED for at least 30 seconds, as the product restarts.
change the IP address of the Smartlink SI B gateway.
Architecture of Smartlink System
Ethernet Status LED
LK/10-100/ACT LED Description
Network Status LED
NETWORK STATUS LED Description
Alternate yellow and white: Activity at 10 Mbps
Alternate green and white: Activity at 100 Mbps
No light: No power, invalid IP address
Green: Connected, valid IP address
Amber: Factory setting IPv4 address
Red: Duplicated IP address/IP error
Flashing green and red light: Self-test
18
DOCA0123EN-04 09/2020
Architecture of Smartlink System

Smartlink Communication System Pre-assembled Cables

Description
The Smartlink communication pre-assembled cables are a quick way to connect all the Smartlink communication system components and compatible products (24 Vdc) to the Smartlink SI B gateway channels.
The pre-assembled cables are:
Product Reference Description Length (mm)
A9XCAS06 Set of six pre-assembled cables with two Ti24 connectors 100
A9XCAM06 Set of six pre-assembled cables with two Ti24 connectors 160
A9XCAL06 Set of six pre-assembled cables with two Ti24 connectors 870
A9XCAH06 Set of six pre-assembled cables with two Ti24 connectors 450
A9XCAU06 Set of six pre-assembled cables with one Ti24 connector 870
A9XCAC01 One pre-assembled cable with one Ti24 connector 4,000
A9XC2412 Set of 12 connectors with 5-pin spring -
Each Ti24 interface (I/O channel) is compatible with Miniconnect Phoenix standard connectors (at intervals of 3.81 mm) or equivalent.
NOTE: The connectors in each pre-assembled cable have a flat surface where a self-adhesive label can be placed to identify the channel number used. Self-adhesive labels are not supplied by Schneider Electric.
DOCA0123EN-04 09/2020 19
Architecture of Smartlink System
NOTE:
Do not connect two wires in each of the Ti24 connector terminals (A9XC2412).
Do not connect a wire with cable end in each of the Ti24 connector terminals.
The following figure gives the characteristics of cables that can be used with the A9XC2412 connector:
Description of the Connector at the Ti24 Interface End
Terminal Description
24 V 24 V of the 24 Vdc power supply
Q Control output
I2 Input number 2
I1 Input number 1
0 V 0 V of the 24 Vdc power supply
20
DOCA0123EN-04 09/2020

Acti9 Devices with Ti24 Interface

Description
Devices that can be connected to the Smartlink SI B gateway are listed in the table below:
Device Product Reference Description
iACT24 auxiliary for iCT contactor A9C15924 The iACT24 auxiliary:
Can be used to control a contactor (iCT) via its Y1, Y2, and Y3 inputs.
The Y3 (24 Vdc) input can be controlled by one of the Smartlink SI B gateway channels.
Is used to find out the contactor status (O/C status).
iATL24 auxiliary for iTL contactor A9C15424 The iATL24 auxiliary:
Can be used to control an (iTL) impulse relay via its Y1, Y2, and Y3
inputs. The Y3 (24 Vdc) input can be controlled by one of the Smartlink SI B gateway channels.
Is used to find out the impulse relay status (O/C status).
iOF/SD24 indication auxiliary for iC60 and RCBO
iOF+SD24 indication auxiliary for iC60, iC65, MCB, and iDPN
OF+SD24 indication auxiliary for C60, C120, C60H-DC, and iDPN circuit breakers
Acti9 RCA iC60 remote control with Ti24 interface
Acti9 Reflex iC60 integrated control circuit breaker with Ti24 interface
A9A19804 OF24 allows you to monitor the Open/Close status of the breaker. This is
chosen mechanically at device level. Based on your choice, you will configure the OF24 object on input. SD24 allows you to monitor the Trip/No Trip status of the breaker. This is chosen mechanically at device level. Based on your choice, you will configure the SD24 object on input.
A9A26897 The iOF+SD24 indication auxiliary is used to find out the status of a iC60,
iC65 (OF and states) and iDPN circuit breaker (sold in China).
A9N26899 The OF+SD24 indication auxiliary is used to find out the status of a C60,
C120, C60H-DC (OF and ) and iDPN circuit breaker (sold in all the countries except China).
A9C7012• The Acti9 RCA iC60 remote control:
Should have a Ti24 interface (with product references A9C70122 and
A9C70124).
Can be used to control an iC60 circuit breaker via input Y3 of its Ti24
interface. Input Y3 (24 Vdc) can be controlled by one of the Smartlink SI B gateway channels.
Can be used to find out the OF and status of the circuit breaker
associated with the Acti9 RCA iC60 remote control.
A9C6•••• The Acti9 Reflex iC60 integrated control circuit breaker:
Should have a Ti24 interface (with product references A9C6••••).Can allow the device to be controlled via input Y3 of its Ti24 interface.
The Y3 (24 Vdc) input can be controlled by one of the Smartlink SIB gateway channels.
Can be used to communicate its O/C and auto/OFF status.
Architecture of Smartlink System
NOTE: All the devices in the above table can be connected to channel N (1 ≤ N ≤ 7) of the Smartlink SI B gateway with A9XCAS06 pre-wired cable (or A9XCAM06 or A9XCAL06 or A9XCAH06).
DOCA0123EN-04 09/2020 21
Architecture of Smartlink System

Acti9 Devices without Ti24 Interface

Description
Devices that can be connected to the Smartlink SI B gateway are listed in the table below:
Designation Product Reference Description
iEM2000T A9MEM2000T Single-phase energy meter without display
iEM3110 A9MEM3110 Three-phase energy meter with display
iEM3155 A9MEM3155 Three-phase energy meter with display
iEM3210 A9MEM3210 Three-phase energy meter with display
iEM3255 A9MEM3255 Three-phase energy meter with display
iEM3310 A9MEM3310 Three-phase energy meter with display
iEM3355 A9MEM3355 Three-phase energy meter with display
iPRD (Type 2) A9L••••1 Withdrawable surge arresters with remote indication contact
iPRD65r/iPRD40r/iPRD20r/iPRD8r
iPRD 40r PV (Type 2) A9L40271
A9L40281
iPRF1 12.5r (Type 1 + Type 2; Type B+C)
PRD1 25r (Type 1 + Type 2) 16329
PRD1 Master (Type 1) 16360
iQuick PRD (Type 2) A9L16292
A9L16632 A9L16633 A9L16634
16330 16331 16332
16361 16362 16363
A9L16293 A9L16294 A9L16295 A9L16296 A9L16297 A9L16298 A9L16299 A9L16300
Withdrawable surge arresters with remote indication contact
Monobloc surge arresters with remote indication contact
Withdrawable surge arresters with remote indication contact
Withdrawable surge arresters with remote indication contact
Withdrawable surge arresters with integrated backup MCB and remote indication contact
NOTE: The connection of these devices can be done with a pre-wired cable: molded connector (at Smartlink SI B gateway end), and with five wires (at device end).
The table below describes products that need a low level interface relay in order to be connected to Smartlink SI B gateway:
Designation Product Reference Description
IH, IHP see catalog Timer switches with RBN type low level relays or equivalent
IC see catalog Light sensitive switches with RBN type low level relays or equivalent
TH, THP see catalog Thermostats with RBN type low level relays or equivalent
22
DOCA0123EN-04 09/2020

PowerTag Wireless Communication Devices

Description
Wireless communication devices that can be connected to the Smartlink SI B gateway are listed in the following table:
Designation Product Reference Description
PowerTag M63 Wireless Communication Energy Sensor 1P
PowerTag M63 Wireless Communication Energy Sensor 1P+N Top
PowerTag M63 Wireless Communication Energy Sensor 1P+N Bottom
PowerTag M63 Wireless Communication Energy Sensor 3P
PowerTag M63 Wireless Communication Energy Sensor 3P+N Top
PowerTag M63 Wireless Communication Energy Sensor 3P+N Bottom
PowerTag P63 Wireless Communication Energy Sensor 1P+N Top
PowerTag P63 Wireless Communication Energy Sensor 1P+N Bottom
PowerTag P63 Wireless Communication Energy Sensor 1P+N Bottom
PowerTag P63 Wireless Communication Energy Sensor 3P+N Top
PowerTag P63 Wireless Communication Energy Sensor 3P+N Bottom
PowerTag F63 Wireless Communication Energy Sensor 1P+N
PowerTag F63 Wireless Communication Energy Sensor 3P+N
PowerTag M250 Wireless Communication Energy Sensor 3P
PowerTag M250 Wireless Communication Energy Sensor 4P
PowerTag M630 Wireless Communication Energy Sensor 3P
PowerTag M630 Wireless Communication Energy Sensor 4P
A9MEM1520 One-phase wireless communication energy sensor (installation on
top or bottom of a protective device).
A9MEM1521 One-phase and neutral wireless communication energy sensor
(installation on top of a protective device).
A9MEM1522 One-phase and neutral wireless communication energy sensor
(installation on bottom of a protective device).
A9MEM1540 Three-phase wireless communication energy sensor (installation
on top or bottom of a protective device).
A9MEM1541 Three-phase and neutral wireless communication energy sensor
(installation on top of a protective device).
A9MEM1542 Three-phase and neutral wireless communication energy sensor
(installation on bottom of a protective device).
A9MEM1561 One-phase and neutral wireless communication energy sensor
(installation on top of a protective device).
A9MEM1562 One-phase and neutral wireless communication energy sensor
(installation on bottom of a protective device).
A9MEM1563 One-phase and neutral wireless communication energy sensor
(installation on bottom of a protective device).
A9MEM1571 Three-phase and neutral wireless communication energy sensor
(installation on top of a protective device).
A9MEM1572 Three-phase and neutral wireless communication energy sensor
(installation on bottom of a protective device).
A9MEM1560 One-phase and neutral wireless communication energy sensor
(installation on top or bottom of a protective device).
A9MEM1570 Three-phase and neutral wireless communication energy sensor
(installation on top or bottom of a protective device).
LV434020 Three-phase wireless communication energy sensor (installation
on top or bottom of a device).
LV434021 Four-pole wireless communication energy sensor (installation on
top or bottom of a device).
LV434022 Three-phase wireless communication energy sensor (installation
on top or bottom of a device).
LV434023 Four-pole wireless communication energy sensor (installation on
top or bottom of a device).
Architecture of Smartlink System
NOTE: While using PowerTag M250/630 energy sensors, the power and energy will be signed correctly if the device is mounted on the circuit breaker at the bottom position with a Top feeding. Any other configuration can lead to inverted value.
Principle of Wireless Device Installation
The Smartlink SI B gateway is installed in such a manner that the PowerTag energy sensors are distributed around the concentrator. It is recommended to install the Smartlink SI B gateway in the center of the switchboard for maximum data quality.
For example, when the switchboard is partitioned, and if you have three-column switchboard with PowerTag energy sensors in each column, then install the Smartlink SI B gateway in the central cubicle. For more than three columns of 650 mm in the same switchboard, add one Smartlink SI B gateway for every three sections.
The system is compatible with Prisma Plus enclosure (form1 and form2), Prisma iPM form 1, Pragma, and plastic final distribution enclosures. The distance between the concentrator and PowerTag energy sensors should be smaller than 3 meters.
NOTE: For a good quality of radio frequency signal, it is recommended to install the PowerTag energy sensors in the same switchboard.
DOCA0123EN-04 09/2020 23
Architecture of Smartlink System
Maximum Number of PowerTag Energy Sensors in an Electrical Room
The wireless network configuration is used for special applications like data centers and high density metering applications. In standard building applications, use the default settings.
At data centers, thousands of PowerTag energy sensors are placed in the same environment. Therefore, it is necessary to consider the radio plan and bandwidth, in order to:
dispatch all the PowerTag energy sensors among the 16 available radio channels. It is recommended
to dispatch the Smartlink SI B gateways among the 16 channels using the manual channel selection in this section.
use as many PowerTag energy sensors as possible in the same radio channel to increase the number
of points without decreasing the radio quality. Following are the recommendations to slow down the communication period of the PowerTag energy sensors that are in the same channel, to avoid overloading the bandwidth:
Up to 100 PowerTag energy sensors by radio channel: communication period to be set to 5 secondsUp to 200 PowerTag energy sensors by radio channel: communication period to be set to 10 secondsUp to 400 PowerTag energy sensors by radio channel: communication period to be set to 20 secondsUp to 600 PowerTag energy sensors by radio channel: communication period to be set to 30 secondsUp to 1200 PowerTag energy sensors by radio channel: communication period to be set to 60
seconds
Any modification to the communication period has to be done after the commissioning of the PowerTag energy sensors is completed to avoid slowdown of the commissioning process.
NOTE: Modification in communication period does not slowdown the alarms. The voltage loss is sent immediately on demand. The communication period is used to send regular metering data (P, U, I, E, PF), not voltage loss alarms.
NOTE:
The radio channel is chosen in the wireless settings of Smartlink SI B gateway and is applied to all the
PowerTag energy sensors that are commissioned with Smartlink SI B gateway.
An Smartlink SI B gateway can manage up to 20 PowerTag energy sensors.Several Smartlink SI B gateways can use the same radio channel to communicate with PowerTag
energy sensors.
A set of Smartlink SI B gateways has to be installed and commissioned to concentrate all the needed
PowerTag energy sensors.
24
DOCA0123EN-04 09/2020

Devices out of the Acti9 Range

Description
The devices that can be connected to the Smartlink SI B gateway are:
Meter with a pulse output and compliant with standard IEC 62053-31.Volt-Free Low Level Indication Contact.Volt-Free Standard Indication Contact.Contactor and Relay.Indication device or PLC input can be directly connected to the output (Q) of Smartlink SI B gateway
channel. The connected device should have the following characteristics:
To be powered with 24 Vdc.The consumption must be less than 100 mA.
Any device (for example: motor) that needs a command circuit of more than 100 mA can be controlled
by the output (Q) of a channel of Smartlink SI B gateway. The electrical diagram must be indirect between Smartlink SI B gateway and this device: a low level relay must be installed between the command of this device and Smartlink SI B gateway.
NOTE: The connection of these devices can be done with an A9XCAU06 or A9XCAC01 pre-wired cable: molded connector (at Smartlink end), and with five wires (at device end). All sensors (compliant with IEC 61000-6-2 and IEC61000-6-3 standards) using one output (compatible with
4...20 mA or 0...10 V) can be directly connected to analog inputs of Smartlink SI B gateway (the cable for analog channel is delivered with the product).
Architecture of Smartlink System
DOCA0123EN-04 09/2020 25
Architecture of Smartlink System

Devices with Analog Output

Overview
All sensors (compliant with IEC 61000-6-2 and IEC61000-6-3 standards) using 24 Vdc as power supply input and 0...10 V or 4...20 mA output can be connected to the Smartlink SI B gateway analog inputs (female analog connector is delivered with the product).
26
DOCA0123EN-04 09/2020
Smartlink SI B Technical Characteris tics DOCA0123EN-04 09/2020

Technical Characteristic s

Chapter 3
Technical Characteristics
What Is in This Chapter?
This chapter contains the following topics:
Technical Characteristics of the Smartlink SI B Gateway 28
Technical Characteristics of the Devices with Ti24 Interface 31
Topic Page
DOCA0123EN-04 09/2020 27
Technical Characteristics

Technical Characteristics of the Smartlink SI B Gateway

General Characteristics
Characteristic Value
Product marking CE
Temperature Operation (horizontal) –25...+60°C
Operation (vertical) –25...+50°C
Storage –40...+85°C
Tropicalization Execution 2 (relative humidity of 93% at 40°C)
Resistance to voltage dips 10 ms, class 3 according to IEC 61000-4-29
Degree of protection IP 20
Level of pollution 3
Overvoltage category OVC II
Conforming to SELV specifications Yes
Altitude Operation 0...2,000 m
Storage 0...3,000 m
Immunity to vibration IEC 60068-2-6 1 g/± 3.5 mm, 5...300 Hz, 10 cycles
Immunity to mechanical shock 15 g/11 ms
Immunity to electrostatic discharge IEC 61000-4-2 Air: 8 kV
Contact: 4 kV
Immunity to radiated electromagnetic interference
Immunity to fast transients IEC 61000-4-4 1 kV for the I/O, Modbus and Ethernet communication.
Surge IEC 61000-4-5 Power supply: 0.5 kV
Immunity to conducted magnetic fields IEC 61000-4-6 10 V from 150 kHz to 80 MHz
Immunity to magnetic fields at line frequency
Conducted emissions IEC 61131-2, CISPR Class A (0.15...30 MHz)
Radiated emissions IEC 61131-2, CISPR Class A (30...1000 MHz)
Resistance to corrosive atmospheres IEC 60721-3-3 Level 3C2 on H²S/SO²/NO²/Cl²
Fire withstand For live parts 30 s at 960°C. IEC 60695-2-10 and IEC 60695-2-11
Salt mist IEC 60068-2-52 Severity 2
Environment Conforms to RoHS directives
Installation position Horizontal or vertical
Mean time between failures More than 1 M hours
IEC 61000-4-3 10 V/m – 80 MHz to 3 GHz
2 kV for the 24 Vdc - 5 kHz - 100 kHz power supply
Modbus and Ethernet: 1 KV
IEC 61000-4-8 30 A/m continuous
100 A/m pulse
For other parts 30 s at 650°C. IEC 60695-2-10 and IEC 60695-2-11
Integrated Functions
Characteristic Value
Counter Number of counters Up to 14 (14 inputs)
Maximum frequency 16.667 Hz, IEC 62053-31
Period stored in backup memory 10 years
Mechanical Characteristics
Characteristic Value
Dimensions Length 359 mm
Height 22.5 mm
Depth 42 mm
Weight 180 g
28
DOCA0123EN-04 09/2020
Technical Characteristics
Communication Module
Characteristic Value
Type of interface module Modbus RTU, RS485 serial connection
Modbus TCP/IP Ethernet
Transmission Modbus RS485 Transfer rate: 9,600...19,200 Baud
Medium: Double shielded twisted pair Impedance 120 Ω
Ethernet Transfer rate: 10/100 Mbps
Structure Type Modbus, Ethernet
Method Master/Slave
Device type Modbus Master
Ethernet Server
Turnaround time Modbus 10 ms
Ethernet 1 ms
Maximum length of cable Modbus 1000 m
Ethernet 100 m
Type of bus connector Modbus 4-pin connector
Ethernet RJ45 (Shielded)
Power supply Nominal Non-isolated 24 Vdc with protection against negative voltages up to
Voltage limits 19.2... 28.8 Vdc with ripple
Current consumption, no-load 110 mA
Maximum input intensity 1.5 A
Maximum current inrush 3 A
Isolation Between the Modbus serial connection
and 24 Vdc Ti24 I/O interfaces
Between the Ethernet serial connection and 24 Vdc Ti24 I/O interfaces
Number of digital I/O channels 7
Number of analog input channels 1
Number of Ethernet ports 1
Medium: Shielded, STP or S/FTP, Cat5e or 6, straight cable, RJ45 connector
-28.8 Vdc
1.9kVdc for 1minute
1.9kVdc for 1minute
Radio Frequency Characteristics
Characteristic Value
Radio communication ISM band 2.4...2.4835 GHz
Number of channels 11...26 (IEEE 802.15.4)
Equivalent isotropic radiated power (EIRP) 0 dBm
Number of radio frequency devices up to 20
RF standard compliance ETSI / EN 300328 v1.9.1
ETSI / EN 301489-17 v2.2.1
Digital Inputs
Characteristic Value
Number of logic inputs 14 (2 per channel)
Rated input voltage 24 Vdc
Input type Current sink, type 1
IEC 61131-2
Weight (0 V) 1 for 2 inputs (1 per channel)
Input voltage limits 19.2...28.8 Vdc
Rated input current 2.5 mA
DOCA0123EN-04 09/2020 29
Technical Characteristics
Characteristic Value
Maximum input current 5 mA
Filter time 2 ms
Acquisition time 10 ms
Isolation No isolation between the Ti24 interfaces
Negative voltage protection Yes
Maximum length of cables and cordsets
500 m (conductor c.s.a. of at least 0.5 mm
Digital Outputs
Characteristic Value
Number of logic outputs 7 (1 per channel)
Logic output Current source, 24 Vdc 0.1 A
Weight (0 V) 1
Rated output voltage Voltage 24 Vdc
Maximum current 100 mA
Filter time 1 ms
Voltage drop (voltage at state 1) 1 V max.
Maximum current inrush 500 mA
Leakage current 0.1 mA
Overvoltage protection 33 Vdc
Short-circuit protection Yes
Overload protection Yes
Current limiting Yes
Maximum length of cables and cordsets
IEC 61131-2
500 m (conductor c.s.a. of at least 0.5 mm
2
)
2
)
Analog Inputs
Characteristic Value
Number of analog inputs 2
Type of each input Voltage/Current: IEC 61131 - 2 compliant
Rated input voltage 0...10 V
Rated input current 4...20 mA
Input impedance Current mode 140 Ω
Voltage mode 50 KΩ
Resolution 12 bits
Accuracy ≤ ± 1% of the full scale
Refresh time 500 ms
Isolation None
Type of cable Twisted shielded pair and screened cable
Cable length
Channel 8 (Analog inputs) maximum sourcing current at 24 V to power
< 30 m maximum
200 mA for each analog sensor
(1)
the sensors
Conversion time/Refresh time 100 ms
Connector type Screw type (4-pin), 3.5 mm pitch
(1)
NOTE:
Wrong wiring or wrong configuration can cause the analog input damage.
Introduce analog isolators (with 0.5 to 1% accuracy) when the cables go outside the switchboard where Smartlink SI B gateway is mounted.
30
DOCA0123EN-04 09/2020
Loading...
+ 162 hidden pages