Schneider Electric SEZ7260X5x45B Installation Guide

SEZ7260X5x45B

Installation Guide for BACnet MS/TP Zone Controller

CONTENTS

Installation

2

 

Location

2

 

Installation

2

 

Typical Applications

4

 

Main outputs wiring

5

 

Wiring examples

8

 

CO2 Sensor wiring

8

 

Configuring and Status Display Instructions

9

 

Status display

9

 

User interface

10

 

User configuration menu

10

 

Occupied setpoint adjustments

10

 

Unoccupied and Stand-By setpoints adjustments

10

 

Local keypad interface

10

 

 

 

 

 

 

 

Schneider Electric SEZ7260X5x45B Installation Guide

2

INSTALLATION

Remove security screw on bottom of Room Controller cover.

Open unit by pulling on bottom side of Room Controller (Figure 1).

Remove wiring terminals from sticker.

Read FCC ID and IC label installed in cover.

Location

1.Should not be installed on outside wall.

2.Must be installed away from any direct heat source.

3.Should not be installed near air discharge grill.

4.Should not be affected by direct sun radiation.

5.Nothing should restrict vertical air circulation to Room Controller.

Installation

1.

Swing open Room Controller PCB to left by pressing PCB locking tabs

Figure-1 Opening the Cover

 

(Figure 2).

 

2.

Pull out cables 6” out from wall. Ensure wall surface is flat and clean.

 

 

4.Insert cable in central hole of base.

5.Align base and mark location of two mounting holes on wall ensuring proper side of base is up.

6.Install anchors in wall.

7.Insert screws in mounting holes on each side of base (Figure 2).

8.Gently swing back circuit board on base and push until tabs lock.

9.Strip each wire 1/4 inch from end.

10.Insert each wire according to wiring diagram.

11.Gently push excess wiring back into hole (Figure 3).

12.Re-Install wiring terminals in correct locations (Figure 3).

13.Re-install cover (top side first) and gently push extra wire length back into hole in wall.

14.Install security screw.

When replacing an existing Room Controller, label the wires before removal of the Room Controller.

Electronic controls are static sensitive devices. Discharge yourself properly before manipulating and installing the Room

Controller.

A short circuit or improper wiring may permanently damage the Room Controller or the equipment.

All SEZ7000 series Room Controllers are designed for use as operating controls only and are not safety devices. These instruments have undergone rigorous tests and verification prior to shipping to ensure proper and reliable operation in the field. Whenever a control failure could lead to personal injury

and or loss of property, it becomes the responsibility of the user or installer or electrical system designer to incorporate safety devices (such as relays, flow switch, thermal protections, etc…) and or an alarm system to protect the entire system against such catastrophic failures. Tampering with the devices or unintended application of the devices will result in a void of warranty.

Figure-2 Opening the PCB

Figure-3 Terminal Block Reinstall

Schneider Electric | II-SEZ7260X-A4.EN.12.2015.v2

December 2015

3

TERMINAL, IDENTIFICATION AND FUNCTION

Wiring

 

Terminal

Terminal

 

Terminal Use

Identification

Identification

Description

 

SEZ7260F

SEZ7260C

 

4 - 24 V ~ Hot

24V ~ Hot

24V ~ Hot

Power supply of controller, hot side

(Delivered from the RTU)

 

0V~Com

0V~Com

Power supply of controller, common side.

5 - 0 V ~ Com

Also used as reference for the analog

 

 

 

outputs when used

6- On-Off Rht

BO5

BO5

Local isolated triac reheat output when used

7- On-Off Rht

BO5

BO5

Local isolated triac reheat output when used

8- Primary Rht

Not used

BO3

24 VAC triac reheat output (open)

 

 

 

For SEZ7260F: Local analog 0 - 10 VDC

9 – Primary Rht

AO2

BO4

reheat output when used

For SEZ7260C: 24VAC triac reheat output

 

 

 

 

 

 

(close)

 

 

 

For SEZ7260F: Local VAV analog 0 - 10

10 – VAV

AO1

BO1

VDC

 

Damper

For SEZ7260C: 24VAC triac VAV output

 

 

 

 

 

 

 

 

(open)

11 – VAV

Not used

BO2

24VAC triac reheat output (close)

Damper

 

 

 

12 – BI1

BI1

BI1

Configurable extra digital input. See

parameter section for more information

 

 

 

13 - A14

A14

A14

0-10VDC analog input for remote CO2 or

other sensor (airflow, etc...)

 

 

 

14 - Scom

Scom

Scom

Reference input for BI 1, BI 2, UI3 and RS

 

 

 

Remote room sensor input when used.

15 - RS

RS

RS

Input auto-detects a remote sensor and will

automatically by-pass the internal sensor

 

 

 

 

 

 

when used.

 

UI3

UI3

Non-configurable extra analog input for

16 – UI3 / SS

monitoring local discharge or supply

 

 

 

temperatures over the network.

BACnet™ Network Connections

BACnet™ Network Connections

BACnet™ Com

Com +

BACnet™ communication bus + connection.

BACnet™ Com

Com -

BACnet™ communication bus – connection.

 

 

Communication bus reference terminal.

Ref

Ref

• DO NOT USE FOR OTHER THAN SERVICING ISSUES

 

 

• DO NOT WIRE SHIELD TO THIS TERMINAL

Schneider Electric | II-SEZ7260X-A4.EN.12.2015.v2

December 2015

4

TYPICAL APPLICATIONS

Main outputs wiring

VAV Damper Wiring

VAV Damper and Analog Reheat Wiring

24 V~ Hot

 

 

 

 

 

24 V~ Hot

 

 

 

24 V~ Com

 

 

 

 

 

 

 

 

VAV Damper

 

 

24 V~ Com

Com

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Reheat Valve or SCR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0-10 VDC

 

 

 

 

 

 

Motor

 

 

AO 2

24 VAC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Com

 

 

 

 

 

 

 

 

 

 

Com

 

VAV Damper Motor

 

 

 

 

 

 

0-10 VDC

 

 

 

 

 

 

 

 

 

 

0-10 VDC

 

AO 1

24 VAC

 

 

 

 

AO 1

24 VAC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VAV Damper Wiring

 

 

 

VAV Damper and Analog Reheat Wiring

24 V~ Hot

 

 

 

 

 

24 V~ Hot

 

 

 

24 V~ Com

VAV Damper

 

 

24 V~ Com

Open

 

 

 

 

 

 

 

 

 

BO 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Com

Reheat Valve

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor

 

 

BO 4

Close

 

 

 

 

 

 

 

 

Open

 

 

 

 

 

 

 

 

 

 

 

 

BO 1

 

BO 1

 

 

 

 

 

Com

 

 

 

 

 

 

 

 

Com

VAV Damper Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Open

 

 

BO 2

Close

BO 2

Close

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Schematic

 

Wiring

 

 

Settings

 

 

 

 

 

 

 

Pressure dependent VAV cooling only system

 

 

Analog VAV Actuator

 

 

 

 

 

 

 

 

Mandatory

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RehtConf= 0 None

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0 to 10

VDC

 

UI3

 

0 V~ Com

 

24 V~ Hot

Room Temperature Control

AO1

 

Minimum & Maximum Position

 

Adjusted at Controller

 

Floating VAV Actuator

Mandatory

 

RehtConf = 0 None

Open

Close

UI3

0 V~ Com

24 V~ Hot

BO1

Room Temperature Control BO2

Minimum & Maximum Position

Adjusted at Controller

Schneider Electric | II-SEZ7260X-A4.EN.12.2015.v2

December 2015