Schneider Electric SER8300 Series, SE8300 Series Application Information

Fan Coil Unit Application Guide
SER8300/SE8300 Series Room Controllers
2
Schneider Electric | AG-SER83 00-SE8 300-FCU-A4.EN.01.2016.v6 January 2016
Table of Contents
SER8300 Room Controller and SC3000 Relay Packs 2 SE8300 Room Controller 2
SER8300 FCU Applications 4
HEATING/COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND 2-POSITION VALVES WITH WIRELESS DOOR SWITCH 4
COOLING AND ELECTRIC HEAT 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN, DEHUMIDIFICATION AND 2-POSITION VALVES 6
HEATING/COOLING WITH CHANGEOVER SENSOR 2-PIPE FAN COIL UNIT 3-SPEED FAN AND WIRELESSS WINDOW SWITCH 8
COOLING AND ELECTRIC HEAT 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN, DEHUMIDIFICATION AND 2-POSITION VALVES 10
HEATING/COOLING 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN, FRESH AIR DAMPER AND 2-POSITION VALVES 12
HEATING/COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND 2-POSITION VALVES WITH SLAVE RELAY PACK 14
COOLING AND ELECTRIC HEAT 2-PIPE FAN COIL 3-SPEED FAN AND 2-POSITION VALVES WITH WIRED WINDOW SWITCH 16
HEATING/COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND 2-POSITION VALVES WITH WIRED DOOR SWITCH 18
4-PIPE FAN COIL UNIT WITH 3-SPEED FAN, TRI-STATE FLOATING VALVES AND DEHUMIDIFICATION SEQUENCE FOR LOW VOLTAGE WITH WIRELESS DOOR SWITCH 20
4-PIPE FAN COIL UNIT WITH 3-SPEED FAN, 0-10 VDC ANALOG VALVES AND DEHUMIDIFICATION SEQUENCE FOR LOW VOLTAGE AND WIRELESS WINDOW SWITCH 22
4-PIPE FAN COIL UNIT WITH 3-SPEED FAN, 2-POSITION VALVES AND DEHUMIDIFICATION SEQUENCE FOR LOW VOLTAGE 24
2-PIPE FAN COIL UNIT WITH SINGLE SPEED FAN, 2-POSITION COOLING VALVE AND FRESH AIR DAMPER FOR LOW VOLTAGE 26
4-PIPE FAN COIL UNIT WITH 3-SPEED FAN, ANALOG COOLING VALVE AND N.C ON/OFF HEATING VALVE FOR LOW VOLTAGE 28
2-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND 0-10VDC ANALOG COOLING VALVE FOR LOW VOLTAGE 30
2-PIPE FAN COIL UNIT WITH 3-SPEED FAN, 2-POSITION VALVE AND ELECTRIC REHEAT FOR LOW VOLTAGE 32
2-PIPE FAN COIL UNIT WITH 3-SPEED FAN, 2-POSITION VALVE AND ELECTRIC REHEAT FOR LOW VOLTAGE 32
2-PIPE FAN COIL UNIT WITH 3-SPEED FAN, 2-POSITION VALVE AND ELECTRIC REHEAT FOR LOW VOLTAGE 32
SE8300 as Zone Controllers 34
HEATING ONLY ANALOG VALVE ACTUATOR, 2 PIPE 34
COOLING ONLY ANALOG VALVE ACTUATOR, 2 PIPE 36
HEATING COIL WITH TRI-STATE FLOATING VALVE ACTUATOR AND PWM ELECTRIC DUCT HEATER 38
HEATING WITH REHEAT, MODULATING DUCT HEATER, ELECTRIC PERIMETER 40
HEATING AND COOLING WITH CHANGEOVER SENSOR AND REHEAT, ANALOG VALVE ACTUATOR, 42
HEATING AND COOLING WITH CHANGEOVER SENSOR AND REHEAT, TRI-STATE FLOATING ACTUATOR, PWM DUCT HEATER AND WATER SENSOR FOR CHANGEOVER, 2 PIPE 44
HEATING AND COOLING WITH CHANGEOVER SENSOR AND REHEAT, ANALOG 0-10 VDC AIR DAMPER ACTUATOR, PWM DUCT HEATER AND AIR SENSOR FOR CHANGEOVER,
2 PIPE 46
HEATING AND COOLING WITH CHANGEOVER SENSOR AND REHEAT, FLOATING AIR DAMPER ACTUATOR, PWM DUCT 46
HEATER AND SUPPLY AIR SENSOR FOR CHANGEOVER, 2 PIPE 48
COOLING AND REHEAT, ANALOG 0-10 VDC AIR DAMPER ACTUATOR, ANALOG DUCT HEATER AND ELECTRIC PERIMETER 50
SE8300 Mixed-Voltage Applications 52
120 VDC RELAY HEATING/COOLING 4-PIPE FAN COIL UNIT WITH HIGH VOLTAGE 3-SPEED FAN, AND 0-10 VDC ANALOG VALVES AND DEHUMIDIFICATION SEQUENCE
FOR LOW VOLTAGE 52
240 VDC RELAY HEATING/COOLING 4-PIPE FAN COIL UNIT WITH HIGH VOLTAGE 3-SPEED FAN, AND 0-10 VDC ANALOG VALVES AND DEHUMIDIFICATION SEQUENCE
FOR LOW VOLTAGE 54
120 VDC RELAY HEATING/COOLING 4-PIPE FAN COIL UNIT WITH HIGH VOLTAGE 3-SPEED FAN, TRI-STATE FLOATING VALVES AND DEHUMIDIFICATION SEQUENCE
FOR LOW VOLTAGE 56
240 VDC RELAY HEATING/COOLING 4-PIPE FAN COIL UNIT WITH HIGH VOLTAGE 3-SPEED FAN, TRI-STATE FLOATING VALVES AND DEHUMIDIFICATION SEQUENCE
FOR LOW VOLTAGE 58
APPENDIX A - PASSIVE INFRA-RED SENSOR SPECIFICATIONS 60 APPENDIX B - OPTIONAL NETWORK SET-UP 61 APPENDIX C - SCHEMATIC OF CONTROLLERS OCCUPANCY SEQUENCE OF OPERATION 61 APPENDIX D - SER8300 CONTROLLER AND SC3000 RELAY PACK 62 APPENDIX E - SED SERIES FOR WIRELESS DOOR AND WINDOW SWITCH 63 APPENDIX F - TERMINAL CORRESPONDENCE 64
Schneider Electric | AG-SER83 00-SE8 300-FCU-A4.EN.01.2016.v6 January 2016
SER8300 ROOM CONTROLLER AND SC3000 AND RELAY PACKS
This new cost-effective solution for upgrading line-voltage fan coil unit thermostats requires only two components, the SER8300 Room Controller and the SC3000 Relay Pack. This solution allows existing line voltage wiring between the fan coil unit and Room Controller to be re-used, thereby reducing overall costs and installation time.
The SC3000 Relay Pack features an onboard universal voltage power supply and line-voltage relays which directly drive fractional horsepower fan motors and valves. This eliminates the need to install and wire costly pilot relays and transformers. The Relay Pack is not required for the SE8300 Series models.
Commercial and Hospitality Interface (Local Override and Degrees C/F Selection)
Power
Part Number Description Humidity PIR
Sensor
SER8300
A0BXX
BACnet® fan coil terminal equipment controller
No No BACnet
Communication
®
3
SER8300A5BXX
SER8350
SER8350
SER8350
A0BXX
A5BXX
A0BxxLTD
BACnet® fan coil terminal equipment controller
BACnet® fan coil terminal equipment controller
BACnet® fan coil terminal equipment controller
BACnet® fan coil terminal equipment controller
Transformer Relay Packs for Fan Coil Units
Power
Part Number Description
SC3500E5045 Transformer relay pack five relay fan outputs
SC3504E5045 Transformer relay pack five relay fan outputs, and four inputs
SC3514E5045 Transformer relay pack five relay outputs, smart VDC OCC output, and four inputs
SC3400E5045 Transformer relay pack four relay outputs and smart VDC output
SC3404E5045 Transformer relay pack four relay outputs, smart VDC output, and four inputs
SC3300E5045 Transformer relay pack three relay fan outputs
ZigBee Pro Module for SE(R)8300 Series
Part Number Description
Power
VCM8000V5045P Optional ZigBee Pro module for SE8300 Series room controllers.
No Ye s BACnet
Yes No BACnet
Yes Ye s BACnet
No No BACnet
4
Schneider Electric | AG-SER83 00-SE8 300-FCU-A4.EN.01.2016.v6 January 2016
SE8300 ROOM CONTROLLERS
This new cost-effective solution for upgrading low-voltage fan coil unit thermostats requires only the SE8300 Terminal Equipment Controller.
The SE8300 Terminal Equipment Controller can also be used along with a SC1300 or SC2300 Relay Pack for mixed-voltage solutions, when control of both line-voltage and low-voltage end devices is required.
Commercial and Hospitality Interface (Local Override and Degrees C/F Selection)
Power
Part Number Description Humidity PIR
Sensor
SE8300
U0BXX
BACnet® fan coil terminal equipment controller
No No BACnet
Communication
®
SE8300U5BXX
SE8350U0BXX
SE8350U5BXX
BACnet® fan coil terminal equipment controller
BACnet® fan coil terminal equipment controller
BACnet® fan coil terminal equipment controller
Mixed-voltage Relay Packs for SE8300 Series
Part Number Description
SC1300E5045
SC2300E5045
3 on/off outputs, 110/130V 3 speed
3 on/off outputs, 220/240V 3 speed
Wireless Accessories for SE(R)8300 Series
Power
Part Number Description
SED-DOR-P-5045 Wireless door switch
SED-WIN-P-5045 Wireless window switch
SED-CMS-P-5045 Wireless ceiling mounted motion sensor
No Ye s BACnet
Yes No BACnet
Yes Ye s BACnet
®
®
®
SED-WDS-P-5045 Wireless window and door switch
SED-WMS-P-5045 Wireless wall mounted motion sensor
Schneider Electric | AG-SER83 00-SE8 300-FCU-A4.EN.01.2016.v6 January 2016
SER83X0XXBXX WITH SC3500E5045 RELAY: HEATING/COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND 2-POSITION VALVES WITH WIRELESS DOOR SWITCH
5
SER8300
Onboard PIR Sensor
AND / OR
OR*
Fan
Airflow Direction
Cooling Coil
2 POSITION
COOLING VALVE
Heating Coil
2 POSITION
HEATING VALVE
SC3500E5045
Refer to the Schneider Electric Catalog for valves and actuators
Door Switch
SED-DOR-P-5045
Wired Remote PIR Sensor
Wireless Remote PIR Sensor
Configuration Parameter Name
Fan Menu L-M-H-A Fan cont. heat. On BI1 Motion NO or Motion NC (remote PIR sensor only) BI2 Door Dry Pulsed heating Off Pipe no. 4 Seq. operation Ht - Cl
Configuration Settings
* Wired remote sensor cannot be used at the same time as wireless remote sensor(s).
6
Schneider Electric | AG-SER83 00-SE8 300-FCU-A4.EN.01.2016.v6 January 2016
SER8300
7 VDC
Tx / Rx
Com
1
2
3
SC3500E5045
Tx/Rx
7 Vdc
Com
BACnet +
BACnet -
BACnet REF
BI 1
BI 2
Common
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve closed.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling valve closed.
Wireless Door Switch
Wireless door switch automatically toggles occupancy.
Options
Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
Can be configured for 2-pipe systems (without changeover).
Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, or remote night setback.
Schneider Electric | AG-SER83 00-SE8 300-FCU-A4.EN.01.2016.v6 January 2016
SER8350XXBXX WITH SC3404E5045 RELAY: COOLING AND ELECTRIC HEAT 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN, DEHUMIDIFICATION AND 2-POSITION VALVES
7
SER8300
Fan
Airflow Direction
Cooling Coil Electric Heating
2 POSITION
COOLING VALVE
SOLID STATE RELAY
SC3404E5045
Refer to Schneider Electric Catalog for valves and actuators.
SSR
(GENERIC)
Configuration parameter name
Pulsed heating On Pipe no. 2 Seq. operation Ht-Cl Fan menu L-M-H-A Fan cont. heat On
Configuration settings
8
Schneider Electric | AG-SER83 00-SE8 300-FCU-A4.EN.01.2016.v6 January 2016
SER8300
7 VDC
Tx / Rx
Com
1
2
3
4
5
6
7
8
9
10
SC3404E5045
Tx/Rx
7 Vdc
Com
RUI 1
SCom
RBI 2
SS
RS
Heat -
Heat +
SOLIDSTATE RELAY (4-32Vdc)
BACnet +
BACnet -
BACnet REF
BI 1
BI 2
Common
(-)
(+)
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature.
On Call for Heat
Electric heat operates to maintain room temperature. Cooling valve closes and dehumidification is disabled.
On a Demand for Dehumidification
Dehumidification achieved via cooling coil using reheat if necessary.
Dehumidification only allowed in COOL mode or if cooling is enabled in AUTO mode.
Dehumidification disabled if room temperature falls below low ambient lockout temperature, which is cooling setpoint minus configuration defined deadband value.
Options
Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
Remote wall mount or return duct sensor ready.
Can be configured for 2-pipe systems with changeover.
Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring.
Universal input can be configured for changeover sensor.
Schneider Electric | AG-SER83 00-SE8 300-FCU-A4.EN.01.2016.v6 January 2016
SER8300XXBXX WITH SC3504E5045 RELAY: HEATING/COOLING WITH CHANGEOVER SENSOR 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND WIRELESSS WINDOW SWITCH
Window Switch
Fan
Airflow Direction
Cooling / Heating Coil Supply Sensor
SED-WIN-P-5000
9
SER8300
Onboard PIR Sensor
2 POSITION
COOLING VALVE / HEATING VALVE
C/O
SENSOR
SENSOR
SC3504E5045
Changeover Sensor: 10K Ohm type 2
Supply Sensor: 10K Ohm type 2
Refer to Schneider Electric Catalog for valves and actuators.
Configuration Parameter Name
Fan Menu L-M-H-A Fan cont. heat On BI1 Window RUI1 COS Pipe No 2 Seq. operation Cool
Configuration Settings
10
Schneider Electric | AG-SER83 00-SE8 300-FCU-A4.EN.01.2016.v6 January 2016
SC3504E5045
SER8300
7 VDC
Tx / Rx
Com
1
2
3
4
5
6
7
8
Tx/Rx
7 Vdc
Com
RUI 1
SCom
RBI 2
SS
RS
BACnet +
BACnet -
BACnet REF
BI 1
BI 2
Common
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
If supply water temperature is less than 24°C (75F), valve opens to maintain room temperature, else valve closes.
On Call for Heat
If supply water temperature is greater than 25°C (77F), valve opens to maintain room temperature, else the valve closes.
Supply Air Sensor
Only used for monitoring. Shows automatically if sensor is
connected.
Wireless Window Switch
Wireless window switch automatically locks out heating/ cooling when window is opened.
Options
Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
Remote wall mount or return duct sensor ready.
Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring.
Schneider Electric | AG-SER83 00-SE8 300-FCU-A4.EN.01.2016.v6 January 2016
SER8350XXBXX WITH SC3400E5045 RELAY: COOLING AND ELECTRIC HEAT 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN, DEHUMIDIFICATION AND 2-POSITION VALVES
11
SER8300
Fan
Airflow Direction
Cooling Coil Electric Heating
2 POSITION
COOLING VALVE
SOLID STATE RELAY
SC3400E5045
Refer to Schneider Electric Catalog for valves and actuators.
SSR
(GENERIC)
Configuration parameter name
Configuration settings
Fan menu L-M-H-A Fan cont. heat. On Pulsed Heating On Pipe No 2 Seq. operation Ht-Cl
12
Schneider Electric | AG-SER83 00-SE8 300-FCU-A4.EN.01.2016.v6 January 2016
SC3400E5045
SER8300
7 VDC
Tx / Rx
Com
1
2
3
9
10
SOLIDSTATE RELAY (4-32Vdc)
BACnet +
BACnet -
BACnet REF
BI 1
BI 2
Common
(-)
(+)
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature.
On Call for Heat
Electric heat operates to maintain room temperature. Cooling valve closed and dehumidification is disabled.
On a Demand for Dehumidification
Dehumidification achieved via cooling coil using reheat if necessary.
Dehumidification only allowed in COOL mode or if cooling is enabled in AUTO mode.
Dehumidification disabled if room temperature falls below low ambient lockout temperature, which is cooling setpoint minus configuration defined deadband value.
Options
Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring.
Schneider Electric | AG-SER83 00-SE8 300-FCU-A4.EN.01.2016.v6 January 2016
SER8300XXBXX WITH SC3514E5045 RELAY: HEATING/COOLING 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN, FRESH AIR DAMPER AND 2-POSITION VALVES
13
SER8300
Fresh Air
DAMPER
Return Air
Fan
Airflow Direction
SC3514E5045
Cooling / Heating Coil Supply Sensor
2 POSITION
COOLING VALVE / HEATING VALVE
C/O
SENSOR
Supply Sensor: 10K Ohm type 2.
Changeover Sensor: 10K Ohm type 2.
Refer to Schneider Electric Catalog for valves and actuators.
SENSOR
Configuration Parameter Name
Fan menu L-M-H-A Fan cont. heat On RUI1 COS Pulsed Heating Occ Out Pipe no. 2 Seq. operation Cool
Configuration Settings
14
Schneider Electric | AG-SER83 00-SE8 300-FCU-A4.EN.01.2016.v6 January 2016
SER8300
Tx / Rx
7 VDC
Com
7Vdc RELAY COIL
1
2
3
4
5
6
7
8
9
SC3514E5045
Tx/Rx
7 Vdc
Com
RUI 1
SCom
RBI 2
SS
RS
OCC -
BACnet +
BACnet -
BACnet REF
BI 1
BI 2
Common
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating. The occupancy output opens fresh air damper to minimum position.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling. The fresh air damper closes.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
If supply water temperature is less than 24°C (75F), cooling valve opens to maintain room temperature, else the valve closes.
On Call for Heat
If supply water temperature is greater than 25°C (77F), heating valve opens to maintain room temperature, else the valve closes.
Supply Air Sensor
Only used for monitoring. Shows automatically if sensor is connected.
Options
Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
Remote wall mount or return duct sensor ready.
Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring.
Schneider Electric | AG-SER83 00-SE8 300-FCU-A4.EN.01.2016.v6 January 2016
SER8300XXBXX WITH SC3500E5045 AND SC3300E5045 RELAYS: HEATING/COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND 2-POSITION VALVES WITH SLAVE RELAY PACK
Airflow Direction
Fan
Cooling Coil
Heating Coil
15
SER8300
SC3300E5045
Configuration Parameter Name
Fan menu L-M-H-A Fan cont. heat On Pipe No 4 Seq. operation Ht-Cl
Configuration Settings
2 POSITION
COOLING VALVE
SC3500E5045
2 POSITION
HEATING VALVE
Refer to Schneider Electric Catalog for valves and actuators.
16
Schneider Electric | AG-SER83 00-SE8 300-FCU-A4.EN.01.2016.v6 January 2016
SER8300
7 VDC
Tx / Rx
Com
SC3300E5045
1
2
3
SC3500E5045
1
2
3
BACnet +
BACnet -
BACnet REF
BI 1
BI 2
Common
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve closes.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling valve closes.
Options
Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
Can be configured for 2-pipe systems without changeover.
Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring.
Schneider Electric | AG-SER83 00-SE8 300-FCU-A4.EN.01.2016.v6 January 2016
SER83X0XXBXX WITH SC3504E5045 RELAY: COOLING AND ELECTRIC HEAT 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND 2-POSITION VALVES WITH WIRED WINDOW SWITCH
17
SER8300
Onboard PIR Sensor
Fan
Airflow Direction
Cooling / Heating Coil Supply Sensor
2 POSITION
COOLING VALVE / HEATING VALVE
C/O
SENSOR
SC3504E5045
Changeover Sensor: 10K Ohm type 2
Supply Sensor: 10K Ohm type 2
Refer to Schneider Electric Catalog for valves and actuators.
Window Switch
SENSOR
Configuration Parameter Name
Fan menu L-M-H-A Fan cont. heat On BI1 Window RUI1 COS Pipe no. 2 Seq. operation Cool
Configuration Settings
18
Schneider Electric | AG-SER83 00-SE8 300-FCU-A4.EN.01.2016.v6 January 2016
SC3504E5045
SER8300
Tx / Rx
7 VDC
Com
1
2
3
4
5
6
7
8
Tx/Rx
7 Vdc
Com
RUI 1
SCom
RBI 2
SS
RS
BACnet +
BACnet -
BACnet REF
BI 1
BI 2
Common
BI1 (Window)
SCom
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
If supply water temperature is less than 24°C (75F), cooling valve opens to maintain room temperature, else the valve closes.
On Call for Heat
If supply water temperature is greater than 25°C (77F), heating valve opens to maintain room temperature, else the valve closes.
Supply Air Sensor
Only used for monitoring. Shows automatically if sensor is connected.
Wired Window Switch
The window switch automatically locks out heating/cooling when window opens.
Options
Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
Models available with factory installed PIR sensor.
Remote wall mount or duct sensor ready.
Can be configured for 2-pipe systems with changeover.
Binary inputs can be configured to control occupancy via door or window contact, remote night setback, or provide alarms for service or filter monitoring.
Universal input can be configured for changeover sensor.
19
Schneider Electric | AG-SER83 00-SE8 300-FCU-A4.EN.01.2016.v6 January 2016
SER8300XXBXX WITH SC3500E5045 RELAY: HEATING/COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND 2-POSITION VALVES WITH WIRED DOOR SWITCH
SER8300
Onboard PIR Sensor
AND / OR
OR*
Fan
Airflow Direction
Cooling Coil
2 POSITION
COOLING VALVE
Heating Coil
2 POSITION
HEATING VALVE
SC3500E5045
Refer to Schneider Electric Catalog for valves and actuators.
Wired Window Switch
Wired Remote PIR Sensor
Wireless Remote PIR Sensor
Configuration Parameter Name
Fan menu L-M-H-A Fan cont. heat On BI1 Motion NO or Motion NC (remote PIR sensor only) BI2 Door Dry Pipe No 4 Seq. Operat Ht-Cl
Configuration Settings
20
Schneider Electric | AG-SER83 00-SE8 300-FCU-A4.EN.01.2016.v6 January 2016
SC3500E5045
SER8300
7 VDC
Tx / Rx
Com
1
2
3
Tx/Rx
7 Vdc
Com
BACnet +
BACnet -
BACnet REF
BI 1
BI 2
Common
BI2 (Door)
SCom
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve closes.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling valve closes.
Door Switch
Door switch automatically toggles occupancy.
Options
Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
Models available with factory installed PIR sensor.
Can be configured for 2-pipe systems without changeover.
Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring.
Schneider Electric | AG-SER83 00-SE8 300-FCU-A4.EN.01.2016.v6 January 2016
SE8350UXBXX HEATING/COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN, TRI-STATE FLOATING VALVES AND DEHUMIDIFICATION SEQUENCE FOR LOW VOLTAGE WITH WIRELESS DOOR SWITCH
21
Fan
SE8300
Onboard PIR Sensor
AND / OR
Wired Remote PIR Sensor
Airflow Direction
OR*
Wireless Remote PIR Sensor
Cooling Coil
TRI-STATE
COOLING VALVE
Heating Coil
TRI-STATE
HEATING VALVE
Door Switch
SED-WDS-P-5045
Refer to Schneider Electric Catalog for valves and actuators
Configuration Parameter
Configuration Settings
Name
Fan menu L-M-H-A Control Type Floating UI16 Motion NO or Motion NC (remote PIR sensor only) UI17 Door Dry Pipe no. 4 Seq. operation Cool / Heat
* Wired remote sensor cannot be used at the same time as wireless remote sensor(s).
Loading...