HEATING/COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND 2-POSITION VALVES WITH WIRELESS DOOR SWITCH 4
COOLING AND ELECTRIC HEAT 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN, DEHUMIDIFICATION AND 2-POSITION VALVES 6
HEATING/COOLING WITH CHANGEOVER SENSOR 2-PIPE FAN COIL UNIT 3-SPEED FAN AND WIRELESSS WINDOW SWITCH 8
COOLING AND ELECTRIC HEAT 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN, DEHUMIDIFICATION AND 2-POSITION VALVES 10
HEATING/COOLING 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN, FRESH AIR DAMPER AND 2-POSITION VALVES 12
HEATING/COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND 2-POSITION VALVES WITH SLAVE RELAY PACK 14
COOLING AND ELECTRIC HEAT 2-PIPE FAN COIL 3-SPEED FAN AND 2-POSITION VALVES WITH WIRED WINDOW SWITCH 16
HEATING/COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND 2-POSITION VALVES WITH WIRED DOOR SWITCH 18
4-PIPE FAN COIL UNIT WITH 3-SPEED FAN, TRI-STATE FLOATING VALVES AND DEHUMIDIFICATION SEQUENCE FOR LOW VOLTAGE WITH WIRELESS DOOR SWITCH20
4-PIPE FAN COIL UNIT WITH 3-SPEED FAN, 0-10 VDC ANALOG VALVES AND DEHUMIDIFICATION SEQUENCE FOR LOW VOLTAGE AND WIRELESS WINDOW SWITCH22
4-PIPE FAN COIL UNIT WITH 3-SPEED FAN, 2-POSITION VALVES AND DEHUMIDIFICATION SEQUENCE FOR LOW VOLTAGE24
2-PIPE FAN COIL UNIT WITH SINGLE SPEED FAN, 2-POSITION COOLING VALVE AND FRESH AIR DAMPER FOR LOW VOLTAGE 26
4-PIPE FAN COIL UNIT WITH 3-SPEED FAN, ANALOG COOLING VALVE AND N.C ON/OFF HEATING VALVE FOR LOW VOLTAGE28
2-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND 0-10VDC ANALOG COOLING VALVE FOR LOW VOLTAGE 30
2-PIPE FAN COIL UNIT WITH 3-SPEED FAN, 2-POSITION VALVE AND ELECTRIC REHEAT FOR LOW VOLTAGE32
2-PIPE FAN COIL UNIT WITH 3-SPEED FAN, 2-POSITION VALVE AND ELECTRIC REHEAT FOR LOW VOLTAGE32
2-PIPE FAN COIL UNIT WITH 3-SPEED FAN, 2-POSITION VALVE AND ELECTRIC REHEAT FOR LOW VOLTAGE32
SE8300 as Zone Controllers 34
HEATING ONLY ANALOG VALVE ACTUATOR, 2 PIPE34
COOLING ONLY ANALOG VALVE ACTUATOR, 2 PIPE36
HEATING COIL WITH TRI-STATE FLOATING VALVE ACTUATOR AND PWM ELECTRIC DUCT HEATER 38
HEATING WITH REHEAT, MODULATING DUCT HEATER, ELECTRIC PERIMETER 40
HEATING AND COOLING WITH CHANGEOVER SENSOR AND REHEAT, ANALOG VALVE ACTUATOR, 42
HEATING AND COOLING WITH CHANGEOVER SENSOR AND REHEAT, TRI-STATE FLOATING ACTUATOR, PWM DUCT HEATER AND WATER SENSOR FOR CHANGEOVER, 2 PIPE 44
HEATING AND COOLING WITH CHANGEOVER SENSOR AND REHEAT, ANALOG 0-10 VDC AIR DAMPER ACTUATOR, PWM DUCT HEATER AND AIR SENSOR FOR CHANGEOVER,
2 PIPE46
HEATING AND COOLING WITH CHANGEOVER SENSOR AND REHEAT, FLOATING AIR DAMPER ACTUATOR, PWM DUCT 46
HEATER AND SUPPLY AIR SENSOR FOR CHANGEOVER, 2 PIPE48
COOLING AND REHEAT, ANALOG 0-10 VDC AIR DAMPER ACTUATOR, ANALOG DUCT HEATER AND ELECTRIC PERIMETER 50
SE8300 Mixed-Voltage Applications 52
120 VDC RELAY HEATING/COOLING 4-PIPE FAN COIL UNIT WITH HIGH VOLTAGE 3-SPEED FAN, AND 0-10 VDC ANALOG VALVES AND DEHUMIDIFICATION SEQUENCE
FOR LOW VOLTAGE52
240 VDC RELAY HEATING/COOLING 4-PIPE FAN COIL UNIT WITH HIGH VOLTAGE 3-SPEED FAN, AND 0-10 VDC ANALOG VALVES AND DEHUMIDIFICATION SEQUENCE
FOR LOW VOLTAGE54
120 VDC RELAY HEATING/COOLING 4-PIPE FAN COIL UNIT WITH HIGH VOLTAGE 3-SPEED FAN, TRI-STATE FLOATING VALVES AND DEHUMIDIFICATION SEQUENCE
FOR LOW VOLTAGE 56
240 VDC RELAY HEATING/COOLING 4-PIPE FAN COIL UNIT WITH HIGH VOLTAGE 3-SPEED FAN, TRI-STATE FLOATING VALVES AND DEHUMIDIFICATION SEQUENCE
FOR LOW VOLTAGE58
APPENDIX A - PASSIVE INFRA-RED SENSOR SPECIFICATIONS60
APPENDIX B - OPTIONAL NETWORK SET-UP61
APPENDIX C - SCHEMATIC OF CONTROLLERS OCCUPANCY SEQUENCE OF OPERATION61
APPENDIX D - SER8300 CONTROLLER AND SC3000 RELAY PACK62
APPENDIX E - SED SERIES FOR WIRELESS DOOR AND WINDOW SWITCH63
APPENDIX F - TERMINAL CORRESPONDENCE64
Schneider Electric | AG-SER83 00-SE8 300-FCU-A4.EN.01.2016.v6January 2016
SER8300 ROOM CONTROLLER AND SC3000 AND RELAY PACKS
This new cost-effective solution for upgrading line-voltage fan coil unit thermostats requires only two components, the
SER8300 Room Controller and the SC3000 Relay Pack. This solution allows existing line voltage wiring between the fan coil
unit and Room Controller to be re-used, thereby reducing overall costs and installation time.
The SC3000 Relay Pack features an onboard universal voltage power supply and line-voltage relays which directly drive
fractional horsepower fan motors and valves. This eliminates the need to install and wire costly pilot relays and transformers.
The Relay Pack is not required for the SE8300 Series models.
Commercial and Hospitality Interface (Local Override and Degrees C/F Selection)
Power
Part NumberDescriptionHumidity PIR
Sensor
SER8300
A0BXX
BACnet® fan coil terminal equipment controller
NoNoBACnet
Communication
®
3
SER8300A5BXX
SER8350
SER8350
SER8350
A0BXX
A5BXX
A0BxxLTD
BACnet® fan coil terminal equipment controller
BACnet® fan coil terminal equipment controller
BACnet® fan coil terminal equipment controller
BACnet® fan coil terminal equipment controller
Transformer Relay Packs for Fan Coil Units
Power
Part NumberDescription
SC3500E5045Transformer relay pack five relay fan outputs
SC3504E5045Transformer relay pack five relay fan outputs, and four inputs
SC3514E5045Transformer relay pack five relay outputs, smart VDC OCC output, and four inputs
SC3400E5045Transformer relay pack four relay outputs and smart VDC output
SC3404E5045Transformer relay pack four relay outputs, smart VDC output, and four inputs
SC3300E5045Transformer relay pack three relay fan outputs
ZigBee Pro Module for SE(R)8300 Series
Part NumberDescription
Power
VCM8000V5045POptional ZigBee Pro module for SE8300 Series room controllers.
NoYe sBACnet
YesNoBACnet
YesYe sBACnet
NoNoBACnet
4
Schneider Electric | AG-SER83 00-SE8 300-FCU-A4.EN.01.2016.v6January 2016
SE8300 ROOM CONTROLLERS
This new cost-effective solution for upgrading low-voltage fan coil unit thermostats requires only the SE8300 Terminal
Equipment Controller.
The SE8300 Terminal Equipment Controller can also be used along with a SC1300 or SC2300 Relay Pack for mixed-voltage
solutions, when control of both line-voltage and low-voltage end devices is required.
Commercial and Hospitality Interface (Local Override and Degrees C/F Selection)
Schneider Electric | AG-SER83 00-SE8 300-FCU-A4.EN.01.2016.v6January 2016
SER83X0XXBXX WITH SC3500E5045 RELAY: HEATING/COOLING 4-PIPE FAN COIL
UNIT WITH 3-SPEED FAN AND 2-POSITION VALVES WITH WIRELESS DOOR SWITCH
5
SER8300
Onboard
PIR Sensor
AND / OR
OR*
Fan
Airflow Direction
Cooling Coil
2 POSITION
COOLING VALVE
Heating Coil
2 POSITION
HEATING VALVE
SC3500E5045
Refer to the Schneider Electric Catalog for valves and actuators
Door Switch
SED-DOR-P-5045
Wired Remote
PIR Sensor
Wireless Remote
PIR Sensor
Configuration
Parameter Name
Fan MenuL-M-H-A
Fan cont. heat.On
BI1Motion NO or Motion NC (remote PIR sensor only)
BI2Door Dry
Pulsed heatingOff
Pipe no. 4
Seq. operationHt - Cl
Configuration Settings
* Wired remote sensor cannot be used at the same time as wireless remote sensor(s).
6
Schneider Electric | AG-SER83 00-SE8 300-FCU-A4.EN.01.2016.v6January 2016
SER8300
7 VDC
Tx / Rx
Com
1
2
3
SC3500E5045
Tx/Rx
7 Vdc
Com
BACnet +
BACnet -
BACnet REF
BI 1
BI 2
Common
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and
heating.
Stand-by Mode (only available when PIR motion detector
sensor is used)
Setpoints revert to those defined by stand-by cooling and
heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and
cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by
“ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating
valve closed.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling
valve closed.
Wireless Door Switch
Wireless door switch automatically toggles occupancy.
Options
•Wireless adapter modules for BACnet models are
available. (see Appendix B for network wiring).
•Can be configured for 2-pipe systems (without
changeover).
•Binary inputs can be configured to control occupancy via
door or window contact, remote motion sensor, or remote
night setback.
Schneider Electric | AG-SER83 00-SE8 300-FCU-A4.EN.01.2016.v6January 2016
SER8350XXBXX WITH SC3404E5045 RELAY: COOLING AND ELECTRIC HEAT 2-PIPE FAN COIL UNIT
WITH 3-SPEED FAN, DEHUMIDIFICATION AND 2-POSITION VALVES
7
SER8300
Fan
Airflow Direction
Cooling CoilElectric Heating
2 POSITION
COOLING VALVE
SOLID STATE RELAY
SC3404E5045
Refer to Schneider Electric Catalog for valves and actuators.
SSR
(GENERIC)
Configuration
parameter name
Pulsed heatingOn
Pipe no. 2
Seq. operationHt-Cl
Fan menuL-M-H-A
Fan cont. heatOn
Configuration settings
8
Schneider Electric | AG-SER83 00-SE8 300-FCU-A4.EN.01.2016.v6January 2016
SER8300
7 VDC
Tx / Rx
Com
1
2
3
4
5
6
7
8
9
10
SC3404E5045
Tx/Rx
7 Vdc
Com
RUI 1
SCom
RBI 2
SS
RS
Heat -
Heat +
SOLIDSTATE
RELAY
(4-32Vdc)
BACnet +
BACnet -
BACnet REF
BI 1
BI 2
Common
(-)
(+)
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and
heating.
Stand-by Mode (only available when PIR motion detector
sensor is used)
Setpoints revert to those defined by stand-by cooling and
heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and
cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by
“ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature.
On Call for Heat
Electric heat operates to maintain room temperature. Cooling
valve closes and dehumidification is disabled.
On a Demand for Dehumidification
Dehumidification achieved via cooling coil using reheat if
necessary.
Dehumidification only allowed in COOL mode or if cooling is
enabled in AUTO mode.
Dehumidification disabled if room temperature falls below
low ambient lockout temperature, which is cooling setpoint
minus configuration defined deadband value.
Options
•Wireless adapter modules for BACnet models are
available. (see Appendix B for network wiring).
•Remote wall mount or return duct sensor ready.
•Can be configured for 2-pipe systems with changeover.
•Binary inputs can be configured to control occupancy via
door or window contact, remote motion sensor, remote
night setback, or provide alarms for service or filter
monitoring.
•Universal input can be configured for changeover sensor.
Schneider Electric | AG-SER83 00-SE8 300-FCU-A4.EN.01.2016.v6January 2016
SER8300XXBXX WITH SC3504E5045 RELAY: HEATING/COOLING WITH CHANGEOVER SENSOR
2-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND WIRELESSS WINDOW SWITCH
Window Switch
Fan
Airflow Direction
Cooling / Heating CoilSupply Sensor
SED-WIN-P-5000
9
SER8300
Onboard
PIR Sensor
2 POSITION
COOLING VALVE / HEATING VALVE
C/O
SENSOR
SENSOR
SC3504E5045
Changeover Sensor: 10K Ohm type 2
Supply Sensor: 10K Ohm type 2
Refer to Schneider Electric Catalog for valves and actuators.
Configuration
Parameter
Name
Fan MenuL-M-H-A
Fan cont. heatOn
BI1Window
RUI1COS
Pipe No 2
Seq. operationCool
Configuration Settings
10
Schneider Electric | AG-SER83 00-SE8 300-FCU-A4.EN.01.2016.v6January 2016
SC3504E5045
SER8300
7 VDC
Tx / Rx
Com
1
2
3
4
5
6
7
8
Tx/Rx
7 Vdc
Com
RUI 1
SCom
RBI 2
SS
RS
BACnet +
BACnet -
BACnet REF
BI 1
BI 2
Common
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and
heating.
Stand-by Mode (only available when PIR motion detector
sensor is used)
Setpoints revert to those defined by stand-by cooling and
heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and
cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by
“ToccTime” parameter.
On Call for Cool
If supply water temperature is less than 24°C (75F), valve
opens to maintain room temperature, else valve closes.
On Call for Heat
If supply water temperature is greater than 25°C (77F), valve
opens to maintain room temperature, else the valve closes.
Supply Air Sensor
Only used for monitoring. Shows automatically if sensor is
connected.
Wireless Window Switch
Wireless window switch automatically locks out heating/
cooling when window is opened.
Options
• Wireless adapter modules for BACnet models are
available. (see Appendix B for network wiring).
• Remote wall mount or return duct sensor ready.
• Binary inputs can be configured to control occupancy via
door or window contact, remote motion sensor, remote
night setback, or provide alarms for service or filter
monitoring.
Schneider Electric | AG-SER83 00-SE8 300-FCU-A4.EN.01.2016.v6January 2016
SER8350XXBXX WITH SC3400E5045 RELAY: COOLING AND ELECTRIC HEAT 2-PIPE FAN COIL UNIT
WITH 3-SPEED FAN, DEHUMIDIFICATION AND 2-POSITION VALVES
11
SER8300
Fan
Airflow Direction
Cooling CoilElectric Heating
2 POSITION
COOLING VALVE
SOLID STATE RELAY
SC3400E5045
Refer to Schneider Electric Catalog for valves and actuators.
SSR
(GENERIC)
Configuration
parameter name
Configuration settings
Fan menuL-M-H-A
Fan cont. heat.On
Pulsed HeatingOn
Pipe No 2
Seq. operationHt-Cl
12
Schneider Electric | AG-SER83 00-SE8 300-FCU-A4.EN.01.2016.v6January 2016
SC3400E5045
SER8300
7 VDC
Tx / Rx
Com
1
2
3
9
10
SOLIDSTATE
RELAY
(4-32Vdc)
BACnet +
BACnet -
BACnet REF
BI 1
BI 2
Common
(-)
(+)
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and
heating.
Stand-by Mode (only available when PIR motion detector
sensor is used)
Setpoints revert to those defined by stand-by cooling and
heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and
cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by
“ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature.
On Call for Heat
Electric heat operates to maintain room temperature. Cooling
valve closed and dehumidification is disabled.
On a Demand for Dehumidification
Dehumidification achieved via cooling coil using reheat if
necessary.
Dehumidification only allowed in COOL mode or if cooling is
enabled in AUTO mode.
Dehumidification disabled if room temperature falls below
low ambient lockout temperature, which is cooling setpoint
minus configuration defined deadband value.
Options
• Wireless adapter modules for BACnet models are
available. (see Appendix B for network wiring).
• Binary inputs can be configured to control occupancy via
door or window contact, remote motion sensor, remote
night setback, or provide alarms for service or filter
monitoring.
Schneider Electric | AG-SER83 00-SE8 300-FCU-A4.EN.01.2016.v6January 2016
SER8300XXBXX WITH SC3514E5045 RELAY: HEATING/COOLING 2-PIPE FAN COIL UNIT WITH
3-SPEED FAN, FRESH AIR DAMPER AND 2-POSITION VALVES
13
SER8300
Fresh Air
DAMPER
Return Air
Fan
Airflow Direction
SC3514E5045
Cooling / Heating CoilSupply Sensor
2 POSITION
COOLING VALVE / HEATING VALVE
C/O
SENSOR
Supply Sensor: 10K Ohm type 2.
Changeover Sensor: 10K Ohm type 2.
Refer to Schneider Electric Catalog for
valves and actuators.
SENSOR
Configuration
Parameter
Name
Fan menuL-M-H-A
Fan cont. heatOn
RUI1COS
Pulsed HeatingOcc Out
Pipe no. 2
Seq. operationCool
Configuration Settings
14
Schneider Electric | AG-SER83 00-SE8 300-FCU-A4.EN.01.2016.v6January 2016
SER8300
Tx / Rx
7 VDC
Com
7Vdc
RELAY
COIL
1
2
3
4
5
6
7
8
9
SC3514E5045
Tx/Rx
7 Vdc
Com
RUI 1
SCom
RBI 2
SS
RS
OCC -
BACnet +
BACnet -
BACnet REF
BI 1
BI 2
Common
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and
heating. The occupancy output opens fresh air damper to
minimum position.
Stand-by Mode (only available when PIR motion detector
sensor is used)
Setpoints revert to those defined by stand-by cooling and
heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and
cooling. The fresh air damper closes.
Occupied Override Mode
System reverts to occupied mode for duration determined by
“ToccTime” parameter.
On Call for Cool
If supply water temperature is less than 24°C (75F), cooling
valve opens to maintain room temperature, else the valve
closes.
On Call for Heat
If supply water temperature is greater than 25°C (77F),
heating valve opens to maintain room temperature, else the
valve closes.
Supply Air Sensor
Only used for monitoring. Shows automatically if sensor is
connected.
Options
• Wireless adapter modules for BACnet models are
available. (see Appendix B for network wiring).
• Remote wall mount or return duct sensor ready.
• Binary inputs can be configured to control occupancy via
door or window contact, remote motion sensor, remote
night setback, or provide alarms for service or filter
monitoring.
Schneider Electric | AG-SER83 00-SE8 300-FCU-A4.EN.01.2016.v6January 2016
SER8300XXBXX WITH SC3500E5045 AND SC3300E5045 RELAYS: HEATING/COOLING 4-PIPE FAN
COIL UNIT WITH 3-SPEED FAN AND 2-POSITION VALVES WITH SLAVE RELAY PACK
Airflow Direction
Fan
Cooling Coil
Heating Coil
15
SER8300
SC3300E5045
Configuration
Parameter Name
Fan menuL-M-H-A
Fan cont. heatOn
Pipe No 4
Seq. operationHt-Cl
Configuration Settings
2 POSITION
COOLING VALVE
SC3500E5045
2 POSITION
HEATING VALVE
Refer to Schneider Electric
Catalog for valves and
actuators.
16
Schneider Electric | AG-SER83 00-SE8 300-FCU-A4.EN.01.2016.v6January 2016
SER8300
7 VDC
Tx / Rx
Com
SC3300E5045
1
2
3
SC3500E5045
1
2
3
BACnet +
BACnet -
BACnet REF
BI 1
BI 2
Common
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and
heating.
Stand-by Mode (only available when PIR motion detector
sensor is used)
Setpoints revert to those defined by stand-by cooling and
heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and
cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by
“ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating
valve closes.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling
valve closes.
Options
• Wireless adapter modules for BACnet models are
available. (see Appendix B for network wiring).
• Can be configured for 2-pipe systems without
changeover.
• Binary inputs can be configured to control occupancy via
door or window contact, remote motion sensor, remote
night setback, or provide alarms for service or filter
monitoring.
Schneider Electric | AG-SER83 00-SE8 300-FCU-A4.EN.01.2016.v6January 2016
SER83X0XXBXX WITH SC3504E5045 RELAY: COOLING AND ELECTRIC HEAT
2-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND 2-POSITION VALVES WITH WIRED WINDOW SWITCH
17
SER8300
Onboard
PIR Sensor
Fan
Airflow Direction
Cooling / Heating CoilSupply Sensor
2 POSITION
COOLING VALVE / HEATING VALVE
C/O
SENSOR
SC3504E5045
Changeover Sensor: 10K Ohm type 2
Supply Sensor: 10K Ohm type 2
Refer to Schneider Electric Catalog for valves and actuators.
Window Switch
SENSOR
Configuration Parameter
Name
Fan menuL-M-H-A
Fan cont. heatOn
BI1Window
RUI1COS
Pipe no. 2
Seq. operationCool
Configuration Settings
18
Schneider Electric | AG-SER83 00-SE8 300-FCU-A4.EN.01.2016.v6January 2016
SC3504E5045
SER8300
Tx / Rx
7 VDC
Com
1
2
3
4
5
6
7
8
Tx/Rx
7 Vdc
Com
RUI 1
SCom
RBI 2
SS
RS
BACnet +
BACnet -
BACnet REF
BI 1
BI 2
Common
BI1 (Window)
SCom
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and
heating.
Stand-by Mode (only available when PIR motion detector
sensor is used)
Setpoints revert to those defined by stand-by cooling and
heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and
cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by
“ToccTime” parameter.
On Call for Cool
If supply water temperature is less than 24°C (75F), cooling
valve opens to maintain room temperature, else the valve
closes.
On Call for Heat
If supply water temperature is greater than 25°C (77F),
heating valve opens to maintain room temperature, else the
valve closes.
Supply Air Sensor
Only used for monitoring. Shows automatically if sensor is
connected.
Wired Window Switch
The window switch automatically locks out heating/cooling
when window opens.
Options
• Wireless adapter modules for BACnet models are
available. (see Appendix B for network wiring).
• Models available with factory installed PIR sensor.
• Remote wall mount or duct sensor ready.
• Can be configured for 2-pipe systems with changeover.
• Binary inputs can be configured to control occupancy via
door or window contact, remote night setback, or provide
alarms for service or filter monitoring.
• Universal input can be configured for changeover sensor.
19
Schneider Electric | AG-SER83 00-SE8 300-FCU-A4.EN.01.2016.v6January 2016
SER8300XXBXX WITH SC3500E5045 RELAY: HEATING/COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED
FAN AND 2-POSITION VALVES WITH WIRED DOOR SWITCH
SER8300
Onboard
PIR Sensor
AND / OR
OR*
Fan
Airflow Direction
Cooling Coil
2 POSITION
COOLING VALVE
Heating Coil
2 POSITION
HEATING VALVE
SC3500E5045
Refer to Schneider Electric Catalog for valves and actuators.
Wired Window Switch
Wired Remote
PIR Sensor
Wireless Remote
PIR Sensor
Configuration
Parameter
Name
Fan menuL-M-H-A
Fan cont. heatOn
BI1Motion NO or Motion NC (remote PIR sensor only)
BI2Door Dry
Pipe No 4
Seq. OperatHt-Cl
Configuration Settings
20
Schneider Electric | AG-SER83 00-SE8 300-FCU-A4.EN.01.2016.v6January 2016
SC3500E5045
SER8300
7 VDC
Tx / Rx
Com
1
2
3
Tx/Rx
7 Vdc
Com
BACnet +
BACnet -
BACnet REF
BI 1
BI 2
Common
BI2 (Door)
SCom
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and
heating.
Stand-by Mode (only available when PIR motion detector
sensor is used)
Setpoints revert to those defined by stand-by cooling and
heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and
cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by
“ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating
valve closes.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling
valve closes.
Door Switch
Door switch automatically toggles occupancy.
Options
• Wireless adapter modules for BACnet models are
available. (see Appendix B for network wiring).
• Models available with factory installed PIR sensor.
• Can be configured for 2-pipe systems without
changeover.
• Binary inputs can be configured to control occupancy via
door or window contact, remote motion sensor, remote
night setback, or provide alarms for service or filter
monitoring.
Schneider Electric | AG-SER83 00-SE8 300-FCU-A4.EN.01.2016.v6January 2016
SE8350UXBXX HEATING/COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN, TRI-STATE FLOATING
VALVES
AND DEHUMIDIFICATION SEQUENCE FOR LOW VOLTAGE WITH WIRELESS DOOR SWITCH
21
Fan
SE8300
Onboard
PIR Sensor
AND / OR
Wired Remote
PIR Sensor
Airflow Direction
OR*
Wireless Remote
PIR Sensor
Cooling Coil
TRI-STATE
COOLING VALVE
Heating Coil
TRI-STATE
HEATING VALVE
Door Switch
SED-WDS-P-5045
Refer to Schneider Electric
Catalog for valves and actuators
Configuration
Parameter
Configuration Settings
Name
Fan menuL-M-H-A
Control TypeFloating
UI16Motion NO or Motion NC (remote PIR sensor only)
UI17Door Dry
Pipe no.4
Seq. operationCool / Heat
* Wired remote sensor cannot be used at the same time as wireless remote sensor(s).