Schneider Electric Erie VM PopTop Series Modulating Valves Instruction Manual Supplement

Application
Spring Return
Non-Spring
Return
The Erie™ Modulating PopT op™ Series valve actuator assemblies are designed for closed hydronic heating and cooling systems. The Modulating PopTop is used to control fluid flow in fan coil units, VAV reheat, unit ventilators, AHUs and radiant applications.
The Modulating PopTop Proportional (P) type is compatible with any 0 to 10 Vdc or 4 to 20 mA signal with jumper selectable operating range and action resulting in precise positioning. The floating (T) type is compatible with any 24 Vac three-wire signal when three minute time-out logic resides in the valve actuator or system controller.
The Modulating PopTop valve assemblies allow the actuator to be snapped onto, or off from, the valve body. The actuator can be mounted after the valve body has been installed into the system without the need for linkages or calibration.
Available in standard (non-spring return) and spring return modulating actuators. The two-way spring return modulating actuators are provided in either normally open or normally closed operation. The three-way valves are available in normally closed operation only. Valve body reversal provides normally open flow for three-way valve bodies.
Erie VM PopTop Series
Modulating Valves
Floating "T" & Proportional "P"
Standard and Spring Return Modulating Valves
General Instructions
Features
Magnetic clutch to maxi mize the life of the motor and
gear train
Manual operating lever/position indicator facilitates
field setup
Easy to use lever terminal blocks
Actuator can be installed after the valve body
Three wire floating and 0 to 10 Vdc or 4 to 20 mA
proportional available
Spring return will return actuator to normal position
when the power is lost for more than two minutes.
Printed in U.S.A. 2-13 © Copyright 2013 Schneider Electric All Rights Reserved. F-27013-8
Applicable Literature
EN-205 Water and S team System Gu idelines, F-26080
Part Numbering System
Modulating Spring and Non-Spring Return Zone Valves
1
V M X X X X X X 3 A 00 X
Body Type
M = Modulating
Configuration
2 = 2-Way 3 = 3-Way
2 = 1/2" 3 = 3/4" 4 = 1" 5= 1-1/4"
Connection Type Availability
1 = Sweat 1/2", 3/4", 1", 1-1/4" 2 = Threaded NPT 1/2", 3/4", 1" 3 = Threaded Rp (Metric) 1/2", 3/4", 1" 5 = SAE Flare 1/2"
CV Size
1/2" 1, 2, 3, 5
1 = 1.0
1/2" 1, 2, 3, 5
2 = 2.0
3/4" 1, 2, 3
1/2" 1, 2, 3, 5
3 = 4.0
3/4" 1, 2, 3
1" 1
3/4" 1, 2, 3
7 =
1" 1, 2, 3
1-1/4" 1
7.5
8.0
T = Three-wire Floating P = Proportional, 0-10 Vdc, 0-5 Vdc, 5-10 Vdc or 4-20 mA, Jumper Selectable
Valve Size
Size Connection Type
Actuator Type
2
Options
Non-Spring Return Actuators
0 = No Options T = Three-Wire Signal Time-Out
Spring Return Actuators
T = Time-Out
Electrical Leads
00 = No leads
Voltage
A = 24 Vac Only
Temperature Ratings
3 = General Temperature
Action
1 = Spring Return Normally closed 2 = Spring Return Normally opened 3 = Non-Spring Return
1
When ordering valve body only: use the first six positions to configure the valve.
2
When ordering actuator only: use the last seven positions to configure the actuator. Prefex with the letter "A."
3
This feature is standard for spring return actuators. It must be included in the part number.
4
Should not be used with thermostats/ controllers unless they have a timeout feature.
3
Available Actuators
Part Number
AT13A00T AT23A00T AT33A000 AT33A00T AP13A000 AP23A000 AP33A000
2 © Copyright 2013 Schneider Electric All Rights Reserved. F-27013-8
Action
Spring Return
Spring Return Non-Spring Return Non-Spring Return
Spring Return
Spring Return Non-Spring Return
Position
N.C. N.O.
N.C. N.O.
Actuator Type
Three Wire Floating Three Wire Floating Three Wire Floating Three Wire Floating
Proportional Proportional Proportional
Option
With Time-Out With Time-Out
None
With Time-Out
None None None
4
SPECIFICATIONS Inputs
Floating Actuator Control Circuit, Max.
Powerup Inrush
a
Running
Series Action Vac mA VA VA VA
Total Actuator, Max.
AT13A00T AT23A00T 24 0.6 1.9
Spring
Return
24 Vac
24 0.6
10
1.9
+25%/-15%
A T33A000
AT33A00T 1.2 1.2
a Transformer must be sized for Powerup Inrush
Non- Spring
Return
50/60 Hz
–– 1.0 1.0
To tal Actuator, Max.
Proportional Actuator Control Circuit, Max.
Powerup Inrush
a
Running
Series Action VAC Range Rin VA VA
AP13A000 AP23A000
AP33A000
a Transformer must be sized for Powerup Inrush b Factory supplied. Actual range is 1-9 Vdc.
Spring Return
Non-Spring
Return
24 Vac
+25%/-15%
50/60 Hz
b
0-10 VDC
or
0-5 VDC or
5-10 VDC or
4-20 mA
>200K >200K >200K
300
10
1.7
1.7
Outputs
Timing:
Nominal Stroke
Series Mode Action
Time
60 Hz 50 Hz 60 Hz 50 Hz
AT13A00T AT23A00T AT33A000
Floating
Spring
Return
3 min.
Non-Spring
AT33A00T
AP13A000 AP23A000
AP33A000
Modulating
Return
Spring
Return
Non-Spring
Return
2 min. 30
sec.
3 min.
3 min.
± 30 sec.
2 min.
45 sec.
Mechanical:
Action, T series: Direct acting.
P series: Direct acting (valve opens port B with increase in signal.) Field
selectable reverse acting.
Manual Override, Allows manual positioning. Operating Pressure Limits, 400 psi (2758 kPa) static pressure. Material,
Actuator: High temperature plastic. Valve: Body: Forged brass; stem: nickel- plated/chrome-plated brass; seat:
brass, plug/paddle: high temperature thermoplastic/rubber.
Flow Characteristic, 1.0 to 4.0 Cv: equal percentage. 7.0/8.0 Cv: linear.
Total Run Time
3 min.
36 sec.
no delay
na
3 min.
18 sec.
F-27013-8 © Copyright 2013 Schneider Electric All Rights Reserved. 3
Environment
Ambient Temperature Limits:
Shipping & Storage, -40 to 158°F (-40 to 70°C) Operating, 35 to 125°F (2 to 52°C).
Fluid, 32 to 200× F (0× to 93× C) (not steam rated). Humidity: 5 to 95% RH, non-condensing. Seat Leakage: ANSI class IV (0.01%) Shipping Weight: 1.9 lbs (860 g), actuator and valve body. Location: NEMA Type 1.
Agency Listings (Actuator Only):
UL873: Underwriters Laboratories (File #E9429 Category Tempera tu re Indicating and
Regulating Equipment) Class 2. CUL: UL Listed for use in Canada by Underwriters Laboratory. Canadian Standards C22.2
No. 24.
European Community: CE Approved. Australia: This product meets the requirements to bear the C-Tick Mark according to the
terms specified by the Communications Authority under the Radio Communications Act of
1992.
T ab le-1 Flow Coefficients & Maximum Close-Off Differential Pressu r e.
Valve
Size in.
Connection Type
Flow Coefficient
Cv (kv)
Non-Spring
Operating Mode
(Driven Close)
Maximum Close-Off DP, PSI (kPa)
Spring Return
Operating Mode
(Driven Closed)
Spring Return
Power Failure Mode*
(Spring Close) PSID
1/2 NPT, SW, SAE, Rp 1.0 (0.9) 50 (344) 50 (344) 50 (344) 1/2 NPT, SW, SAE, R p
2.0 (1.8) 50 (344) 50 (344) 20 (138)
3/4 NPT, SW, Rp 1/2 NPT, SW, SAE, R p
4.0 (3.5) 35 (241) 35 (241) 20 (138)3/4 NPT, SW, SAE, R p
1SW
3/4 NPT, SW, Rp 7.5 (6.5) 35 (241) 35 (241) 15 (103)
1SW, Rp
8.0 (6.9) 35 (241) 35 (241) 15 (103)
1-1/4 SW
*If valve is driven closed before a power failure, the "operating mode" close- off pressures apply. Valve Body Legend
NPT — Threaded SW — Sweat SAE — Society Automotive Engineers. Rp—"Metric" Threaded
4 © Copyright 2013 Schneider Electric All Rights Reserved. F-27013-8
Loading...
+ 8 hidden pages