Schneider Electric BCPM User Manual

BCPM Series Panelboard Monitoring Systems
BCPME
User Guide
Panelboard Monitoring System with Ethernet Communication, Solid-Core Branch Current Sensors
Z206856-0D 04/2020
(other current sensor strip sizes available)
Branch Circuit Power Meter with Ethernet Communication
Safety Information
Important information
Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service or maintain it. The following special messages may appear throughout this bulletin or on the equipment to warn of potential
hazards or to call attention to information that claries or simplies a procedure.
The addition of either symbol to a “Danger” or “Warning” safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
DANGER indicates an hazardous situation which, if not avoided, will result in death or serious injury.
Z206856-0D
04/2020
DANGER
WARNING
Please note
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury.
Electrical equipment should be installed, operated, serviced and maintained only by qualied
personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
A qualied person is one who has skills and knowledge related to the construction, installation,
and operation of electrical equipment and has received safety training to recognize and avoid the hazards involved.
© 2020 Schneider Electric All Rights Reserved.
Z206856-0D
A qualified person is one who has skills and knowledge related to the construction and operation of this electrical equipment and installations, and has received safety training to recognize and avoid the hazards involved.
If this product is used in a manner not specified by the manufacturer, the protection provided by the product may be impaired. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
DANGER
04/2020
Safety Precautions
Branch Circuit Power Meter with Ethernet Communication
Safety Precautions
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices. See NFPA 70E in the USA, CSA Z462 in Canada, or applicable local codes.
• Read and understand the instructions before installing the product. Follow the instructions during installation.
• Installation, wiring, testing or service must be performed only by qualified persons in accordance with all applicable codes and regulations.
• Install the product in an appropriate electrical and fire enclosure per local regulations.
• Do not use the product for life or safety applications.
• Do not install the product in hazardous or classified locations.
• Do not exceed the product’s ratings or maximum limits.
• The product may use multiple voltage/power sources.
• Turn off ALL power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm that all power is off.
• Do NOT depend on the product for voltage indication.
• Products rated only for basic insulation must be installed on insulated conductors.
• Current transformer secondaries (current mode) must be shorted or connected to a burden at all times.
• Remove all wire scraps and tools, replace all doors, covers and protective devices before powering the equipment.
Failure to follow these instructions will result in death or serious injury.
© 2020 Schneider Electric All Rights Reserved.
NEC Article 100
i
Branch Circuit Power Meter with Ethernet Communication
Control system design must consider the potential failure modes of
1
Solid-State Controls or its equivalent in your specific country, language, and/or location.
Provide a disconnect device to disconnect the meter from the supply source. Place this device in close proximity to the equipment and within easy reach of the operator, and mark it as the disconnecting device. The disconnecting device shall meet the relevant requirements of IEC 60947-1 and IEC 60947-3 and shall be suitable for the application. In the US and Canada, disconnecting fuse holders can be used. Provide overcurrent protection and disconecting device for supply conductors with approved current limiting devices suitable for protecting the wiring.
For use in a Pollution Degree 2 or better environment only. A Pollution Degree 2 environment must control conductive pollution and the possibility of condensation or high humidity. Consider the enclosure, the correct use of ventilation, thermal properties of the equipment, and the relationship with the environment.
FCC PART 15 INFORMATION
NOTE: This equipment has been tested by the manufacturer and found
This Class A digital apparatus complies with Canadian ICES-003.
FCC Notice
control paths and, for certain critical control functions, provide a means to acheive a safe state during and after a path failure. Examples of critical control functions are emergency stop and over-travel stop.
WARNING
LOSS OF CONTROL
• Assure that the system will reach a safe state during and after a control path failure.
• Separate or redundant control paths must be provided for critical control functions.
• Test the effect of transmission delays or failures of communication links.
• Each implementation of equipment using communication links must be individually and thoroughly tested for proper operation before placing it in service.
Failure to follow these instructions may cause injury, death or equipment damage.
For additional information about anticipated transmission delays or failures of the link, refer to NEMA ICS 1.1 (latest edition). Safety Guidelines for the Application, Installation, and Maintenance of
1
Z206856-0D
04/2020
FCC Notice
ii
to comply with the limits for a class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reason­able protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. Modifications to this product without the express authorization of the manufacturer nullify this statement.
© 2020 Schneider Electric All Rights Reserved.
Z206856-0D 04/2020
Specifications
Branch Circuit Power Meter with Ethernet Communication
Specifications
Table 1: Specifications
Type Description
Voltage Inputs
Measurement Voltage 90 to 300 Vac line-to-neutral, 50/60 Hz
Control Power 100 to 277 Vac line-to-neutral, 50/60 Hz, 15 VA max.
Frequency 50/60 Hz
Accuracy
Power/Energy IEC 62053-21 Class 1, ANSI C12.1-2008
Voltage ±0.5% of reading 90 to 277 V line-to-neutral
Current ±0.5% of reading
Minimum ON Current 50 mA
Operation
Sampling Frequency 2560 Hz
Update Rate Modbus: 1.8 seconds (both panels)
Ethernet Communication
Physical Interface RJ45 connector with 10/100 Mbit Ethernet
Protocols Supported Modbus TCP, BACnet IP, SNMP V2c
Serial Communication
Physical Interface 2-wire RS-485
Serial Protocols Supported Modbus RTU or BACnet MS/TP
Address Range 1 to 247 for Modbus RTU; 0 to 127 for BACnet MS/TP
Baud Rate 9600, 19200, 38400
Parity Modbus RTU: NONE, ODD, EVEN
Communication Format 8 data bits, 1 start bit, 1 stop bit
Termination 2x3 position connector
Wire Size Up to 16 AWG
Wire Size Range
Aux CT Terminals 24 to 14 AWG
Voltage Input and Control Power Connectors
Terminal Block Torque
Aux CT Terminals 3.5 to 4.4 in-lb (0.4 to 0.5 N-m)
Voltage Input and Control Power Connectors
Mechanical
Ribbon Cable Support 4 ft. (1.2 m) round cable ships standard; up to 20 ft. (6 m)
Environmental
Operating Temperature Range 0 to 60 °C (32 to 122 °F)
Storage Temperature Range -40 to 70 °C (-40 to 158 °F)
Altitude of Operation 3000 m
Compliance Information
Agency Approvals UL508 open type device*, IEC/EN61010-1
Installation Category Cat III, pollution degree 2
(1% system accuracy is for main board and branch CTs)
BACnet: 14 seconds SNMP: 20 seconds
BACnet MS/TP: NONE (xed)
22 to 12 AWG
4.4 to 5.3 in-lb (0.5 to 0.6 N-m)
round or at ribbon cables are available
(<95% RH, non-condensing)
© 2020 Schneider Electric All Rights Reserved.
1
Branch Circuit Power Meter with Ethernet Communication Introduction
Introduction
Z206856-0D
04/2020
Type Description
Conducted and Radiated Emissions FCC part 15 Class A, EN55011/EN61000-6-4 Class A (heavy
industrial)
Conducted and Radiated Immunity EN 61000-6-2 and EN 61326-1
Note: For indoor use only.
*BCPM internal circuitry (cables and CTs) are not circuits as dened by UL508A, as they do not extend beyond the BCPM itself without further safety/re isolation.
The PowerLogic™ BCPME is designed to measure the current, voltage, and energy consumption of up to 92 circuits (84 branch circuits, two 3-phase mains, two neutrals), enabling users to monitor two panelboards or an entire data center PDU with a single product. It increases the board’s current monitoring capability by combining the functions of two boards into one device. It also includes Ethernet capability, allowing communication in multiple protocols.
The BCPME consists of a data acquisition module and up to four current sensor strips, with eight auxiliary inputs. The strips have rows of solid-core CTs and are mounted on each side of the panel board along the termination points of
each breaker. The conductor passes through the appropriate current sensor before terminating at the breaker. Each strip transmits the current data to the
data acquisition board. The BCPME measures both current and power for the mains and branch circuits. The BCPME can easily accommodate different panel
congurations, including any combination of multi-phase breaker positions, voltage phase mapping, and breaker sizes. To congure the BCPME for operation, use the Schneider Electric ION Setup conguration software tool.
Get the latest version at https://schneider-electric.box.com/ionsetuplatest.
Data is transmitted via Ethernet with Modbus TCP, BACnet IP, or SNMP protocol, or via RS-485 with Modbus RTU or BACnet MS/TP protocols. Some protocols can be used simultaneously, and the Ethernet protocols all support access by multiple masters. Each data acquisition board requires two Modbus addresses, one for each set of two current sensor strips and four auxiliary inputs (two-strip models only require one Modbus address. As a circuit exceeds
the user-dened thresholds, the BCPME activates the event indicators. The communication interfaces and protocols require some conguration at the time
of installation.
2
© 2020 Schneider Electric All Rights Reserved.
Z206856-0D 04/2020
Figure 1 Branch Circuit Power Meter with Ethernet Communication
Parts of the BCPME
Figure 2 shows the parts of the BCPME, while Table 2 describes these parts.
Branch Circuit Power Meter with Ethernet Communication
Introduction
Figure 2 BCPME Panel Board Monitoring System
1
4
7 7
2
8
3
9
65
10
© 2020 Schneider Electric All Rights Reserved.
3
Branch Circuit Power Meter with Ethernet Communication Introduction
Z206856-0D
Table 2: Parts Description of the BCPME
Part Description
1 Ethernet port Provides Ethernet connection for the gateway component.
2 Power LED Indicates power is applied to the meter.
3 2x3 RS-485 serial connection Used for Modbus, BACnet, and SNMP serial communications.
4 Protective ground connection Provides a grounding point for the device.
5 Voltage taps 1, 2, or 3 phase plus neutral connections. For voltage sensing and power calculations.
6 Control power connection Provides power to operate the meter.
7 Auxiliary CT inputs These 0.333 Vac inputs are used for monitoring the main breaker or other high amperage source.
8 50-pin ribbon cable connectors 48-inch (1220 mm) ribbon cables are provided for easy connection of the current sensor strips to this
9 Branch current sensors Each current sensor is capable of monitoring conductors rated up to a maximum of 100 amps.
10 50-pin ribbon cable connectors (branch current sensor
strips)
Dimensions
Inputs on the left are for panelboard 2; inputs on the right are for panelboard 1.
point of the data acquisition board. Other ribbon cable lengths are available (sold separately) The two connectors on the left are for panelboard 2; the two on the right are for panelboard 1. Connect current sensor strips to the correct ribbon cable connectors for each panel. The top connectors are for the strip labeled Panel B, and the bottom connectors are for the strip labeled Panel A.
Connects current signal from the current sensor strip to the main board via the ribbon connectors.
Figure 3 Data Acquisition Board and Mounting Bracket
04/2020
2.8”
(71 mm)
8.9”
(225 mm)
8.2”
(210 mm)
10.0”
(253 mm)
12.1”
(307 mm)
2x: 5.9”
(150 mm)
Note: The dotted lines indicate dimensions if the
two brackets are placed in
the alternate orientation. At
the factory, the brackets are
placed as shown with solid lines. See the Installation section for more information.
12.8”
(325 mm)
13.9”
(353 mm)
4
© 2020 Schneider Electric All Rights Reserved.
Z206856-0D 04/2020
Branch Circuit Power Meter with Ethernet Communication
Introduction
Figure 4 Current Sensor Strips
3/4" option, 21 CTs
1” option, 21 CTs
18 mm option, 21 CTs
18 mm option, 18 CTs
1.3”
(33 mm)
2.0”
(50 mm)
1.2”
(30 mm)
2.0”
(50 mm)
2.0”
(50 mm)
1.3”
(32 mm)
1.7”
(43 mm)
1.3”
(32 mm)
15.7” (399 mm)
0.4” (10 mm) opening
16.4” (417 mm)
0.4” (10 mm) opening
20.3” (516 mm)
0.4” (10 mm) opening
25.0” (635 mm)
0.4” (10 mm) opening
0.7” (18 mm) on center
0.7” (18 mm) on center
slot: 0.25” x 0.5”
(7 x 13mm)
0.75” (19 mm) on center
slot: 0.25” x 0.5”
(7 x 13mm)
1.0” (26 mm) on center
21.2”
(0.9 mm)
21.2”
(0.9 mm)
1.1”
(28 mm)
0.8”
(20 mm)
1.2”
(31 mm)
0.8”
(20 mm)
Data Output
0.4” (10 mm) opening
12.3” (312 mm)
0.7” (18 mm) on center
21.2”
(0.9 mm)
18 mm option, 12 CTs
1.7”
(43 mm)
1.3”
(32 mm)
The BCPME provides several types of measurements that give a comprehensive view of power consumption for every load on the panel:
• Real-time measurements: A live and up-to-date view of present power levels and the factors that affect them.
• Demand measurements: Averages of values measured over a
specied time interval. The time interval (typically 15 minutes) can
be set from 10 seconds to more than a day. The demand calculation
can be congured to use single intervals or the sliding average of up to 6 sub-intervals. Demand measurements are useful for tracking
or graphing load levels over time to correlate with total energy consumption.
• Historic maximum measurements: These measurements store the
largest value recorded for a specic measurement since the last time they were cleared. They are useful for identifying peak levels critical to
equipment sizing or demand limits in utility agreements.
• Accumulated energy measurements: Ongoing totals of cumulative energy used since the last time the value was cleared. Energy values provide the informational basis for billing, cost allocation, carbon offset, BTU equivalent calculations, and other applications of overall energy use.
© 2020 Schneider Electric All Rights Reserved.
5
Branch Circuit Power Meter with Ethernet Communication Introduction
Z206856-0D
04/2020
• Energy snapshots: Energy totals that only change when the demand intervals are updated. They are samples of the free-running energy
accumulators at the end of each demand interval, as congured by the
user. These provide energy readings that are easily correlated to the
demand values to simplify the tasks of sub-billing and cost allocation.
• Over-threshold Events (previously referred to as Alarms): Provide a warning of excessively high or low current on each branch and aux channel. The user can set two high-level and two low-level thresholds, and a delay time for latching events. Events are reported as both non-latched events and latched events. Non-latching events are active while the current exceeds the threshold, but go inactive if the current
returns to a level within the specic thresholds. Latching events
become active when the current exceeds the threshold for a time
period greater than the specied delay and remain active until they
are cleared remotely. Event status can be polled via any protocol. Via
BACnet, Subscribe_COV can be used to generate event notications. Via SNMP, they drive SNMP event notications.
Advanced Features - The BCPME supports a number of advanced features.
Some are always active, and others are congured manually via Modbus
register 62017, BACnet object AV164, or SNMP MIB variable “spanels/
panel1/p1Conguration/p1Setup/p1UserDenedSettings” (OID .1.3.6.1
.4.1.3833.1.30.1.1.6.3.4.0). For models with 42 channels or more, these
features are congured independently for each panel.
Logical meter support: The BCPME can be congured to map any set of 1, 2 or 3 channels that are adjacent in the panel to a logical meter, referred to in the point map as a logical circuit, that provides accurate multi-phase measurement totals. Map these logical circuits by writing the desired logical circuit number into a set of registers/data objects provided for each branch and aux channel (per panel).
• The channels assigned to each logical circuit must be adjacent in
the panel (usually used for multi-phase breakers), but there are no
limitations on where those adjacent channels are aligned in the panel
(any position where a multi-phase breaker can be installed). This
functionality is always active, but a user selection affects the how the data can be accessed via Modbus. Measurement data via Modbus for logical circuits is presented in two ways, arranged either by logical
circuit number (looks more like a collection of individual meters) or by
measurement type (arranged similar to the single-phase data section of the point map).
• Legacy point map or alternate logical circuit point map: The BCPME
can be congured to select a preferred version of the Modbus
registers in the address range 4000 to 9999. If enabled (default), the logical circuits by measurement type is active. Otherwise, the legacy
point maps for 2-phase and 3-phase breakers used in BCPM models with a rmware version earlier than 1.023 is active. The logical circuits
functionality can also be accessed via the “Logical Circuits by Circuit” section of the point map (address range 10000 to 45000), regardless of the state of this selection.
• Phase angle measurements: The BCPME measures the phase angle of every voltage and current input and presents these measurements (in degrees) in additional data registers/objects. These values are used to verify that current inputs are assigned to the proper voltage phases and to help determine how power factor variations are
inuenced by current phase changes vs. harmonic distortion. Phase
angle measurements are instantaneous and always active.
• User CT phase assignment: In the default mode, the BCPME assigns each channel to the corresponding phase that most 3-phase panels implement, so that the user does not have worry about it. The user can opt to replace this self-assignment paradigm with a mode that
6
© 2020 Schneider Electric All Rights Reserved.
Z206856-0D 04/2020
Branch Circuit Power Meter with Ethernet Communication
Introduction
allows explicit specication of the phase assignment for each channel.
The explicit assignments set by the user are stored by the BCPME in non-volatile memory.
• Phase angle reference: The BCPME measures the phase angle of every current and voltage input. The user can select whether the phase angles are stated relative to an absolute reference (the phase angle of voltage input V1) or relative to the voltage phase assigned to
that specic current input channel.
• Demand/snapshot time interval source: The BCPME offers two mechanisms for driving the demand/snapshot time interval, an interval
timer or an RTC (real-time clock). The legacy mode (default) uses an
interval timer that does not need to be set to an absolute time. When using the interval timer the demand/snapshot interval can be set from 10 to 32767 seconds (over 9 hours). An alternate mode utilizes an
RTC set to a specic date and time to synchronize the results with a larger system. The RTC must rst be set in order to run and capture
demand values and energy snapshots. When power is interrupted, the RTC resets to a default date and time and must be set again in order to run. When using the RTC, the demand/snapshot interval can be set from 10 to 3600 seconds (1 hour).
Table 3: Data Outputs Table
Monitoring of Mains
Current: multi-phase average and per phase
Current phase angle
Real power (kW): multi-phase total and per phase
Real Time Measurements
Demand Measurements
Historic Maximums
Accumulated Energy Energy (kWh): multi-phase total and per phase
Energy Snapshots Energy (kWh): multi-phase total and per phase
Apparent power (kVA): multi-phase total and per phase
Power factor: multi-phase average and per phase
Voltage - L-L: multi-phase average and per phase
Voltage - L-N: multi-phase average and per phase
Frequency (phase A)
Current present demand: multi-phase average and per phase
Real Power (kW) present demand: multi-phase average and per phase
Maximum instantaneous current: multi-phase average and per phase
Maximum current demand: multi-phase average and per phase
Maximum real power demand: multi-phase total and per phase
Monitoring of Branch Circuits
Current: multi-phase average and per phase
Real Time Measurements
Demand Measurements
Historic Maximums
Accumulated Energy Energy (kWh): multi-phase total and per phase
Energy Snapshots Energy (kWh): multi-phase total and per phase
Current phase angle per branch
Real power (kW): multi-phase total and per phase
Apparent power (kVA): multi-phase total and per phase
Power factor: multi-phase average and per phase
Current present demand: multi-phase average and per phase
Real power (kW) present demand: multi-phase average and per phase
Maximum instantaneous current: multi-phase average and per phase
Maximum current demand: multi-phase average and per phase
Maximum real power demand: multi-phase total and per phase
© 2020 Schneider Electric All Rights Reserved.
7
Branch Circuit Power Meter with Ethernet Communication
A qualified person is one who has skills and knowledge related to the construction and operation of this electrical equipment and installations, and has received safety training to recognize and avoid the hazards involved.
If this product is used in a manner not specified by the manufacturer, the protection provided by the product may be impaired. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
DANGER
Installation
Solid Core Branch Current Sensors
Installation
Modbus Events
Voltage over/under
Events
Branch current over/under
Mains current over/under
Table 4: Branch Current Sensor Specs
100 A Solid-Core Branch Current Sensors
Voltage Rating 300 Vac
Measurement Range 120 A*
Temperature 0 to 60 °C (32 to 122 °F)
Agency EN61010-1
*Momentary.
Z206856-0D
04/2020
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices. See NFPA 70E in the USA, CSA Z462 in Canada, or applicable local codes.
• Read and understand the instructions before installing the product. Follow the instructions during installation.
• Installation, wiring, testing or service must be performed only by qualified persons in accordance with all applicable codes and regulations.
• Install the product in an appropriate electrical and fire enclosure per local regulations.
• Do not use the product for life or safety applications.
• Do not install the product in hazardous or classified locations.
• Do not exceed the product’s ratings or maximum limits.
• The product may use multiple voltage/power sources.
• Turn off ALL power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm that all power is off.
• Do NOT depend on the product for voltage indication.
• Products rated only for basic insulation must be installed on insulated conductors.
• Current transformer secondaries (current mode) must be shorted or connected to a burden at all times.
• Remove all wire scraps and tools, replace all doors, covers and protective devices before powering the equipment.
Failure to follow these instructions will result in death or serious injury.
8
NEC Article 100
© 2020 Schneider Electric All Rights Reserved.
Z206856-0D 04/2020
Branch Circuit Power Meter with Ethernet Communication
Observe precautions for handling static sensitive devices to avoid damage to the circuitry that is not covered under the factory warranty.
Installation
The protective ground connection on the housing should be used if the device will not be mounted to a suitably grounded surface. Assure conductivity to the protective ground.
1. Always use a properly rated voltage sensing device to conrm power is off.
2. Determine where you will mount the BCMPE measurement unit. The
preferred location is inside the enclosure of the panelboard being
monitored. If sufcient space is not available there, then mount the unit in
an appropriate enclosure nearby. Decide whether to mount it vertically or
horizontally. The meter is shipped with the brackets placed on the two sides for vertical mounting. If desired, you can move the brackets from the sides
to the ends of the housing. Loosen the screws on the sides of the BCPME
that hold the brackets in place (do not fully remove the screws from the
housing). Loosen the screws on the two ends of the housing (do not fully
remove the screws from the housing), and set the brackets into their new
positions. Tighten all screws to 25 in-lb (2.8 N-m).
Figure 5 Brackets positioned for vertical and horizontal mounting
Vertical Mounting Horizontal Mounting
Install the BCPME in the panel. A grounding connection is located on the housing (see below).
Figure 6 BCPME Ground stud
Ground
3. Install the branch current sensor strips into the panel. Select one of the four
circuit congurations shown below and arrange the CTs strips accordingly.
For more detailed installation diagrams and help identifying what circuit
conguration setting to use, refer to the appendix titled: Panel Conguration Diagrams and Selection Matrix. Adjust conguration of the circuit numbers in the eld during commissioning by writing to Modbus Register 6 (or
the corresponding BACnet object or SNMP variable) or use ION Setup
conguration software. Most of the examples in this graphic show the 21 current sensor strips. The same conguration options are available for the
18 and 12 current sensor strips.
© 2020 Schneider Electric All Rights Reserved.
9
Branch Circuit Power Meter with Ethernet Communication Installation
Top Feed Bottom Feed
Z206856-0D
04/2020
Figure 7 Current sensor strip configuration selections (must be
set during commissioning - default is "Top Feed")
B
A
2
1
4
3
6
5
8
7
10
9
12
11
14
13
16
15
18
17
20
19
22
21
24
23
26
25
28
27
30
29
32
31
34
33
36
35
38
37
40
39
42
41
Panel 1Panel 2 Panel 1Panel 2
Register 6
B
A
2
1
4
3
6
5
8
7
10
9
12
11
14
13
16
15
18
17
20
19
22
21
24
23
26
25
28
27
30
29
32
31
34
33
36
35
38
37
40
39
42
41
Value = 0
B
A
2
1
4
3
6
5
8
7
10
9
12
11
14
13
16
15
18
17
20
19
22
21
24
23
26
25
28
27
30
29
32
31
34
33
36
35
38
37
40
39
41
42
Register 6
Value = 1
(Default)
Single Row: Sequential Single Row: Odd/Even
A
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
B
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
Panel 1Panel 2 Panel 1Panel 2
Register 6
Value = 2
A
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
B
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
A
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
2
B
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
Register 6
Value = 3
B
A
2
1
4
3
6
5
8
7
10
9
12
11
14
13
16
15
18
17
20
19
22
21
24
23
26
25
28
27
30
29
32
31
34
33
36
35
38
37
40
39
42
41
A
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
2
B
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
10
4. Verify that the serial numbers printed on the branch current sensor strips
and on the BCPME match. The board and the strips are sold as a calibrated set.
5. Connect the current sensor ribbon cables to the 50-pin connectors on
the BCPME. The label on the strip indicates which connector to use (e.g. connect the strip labeled “Panel 1A” to the bottom right connector on the
board). Orient the cables so that the plastic key on the BCPME connector aligns with the keyhole cutout on the ribbon cable connector, as shown
below.
© 2020 Schneider Electric All Rights Reserved.
Z206856-0D 04/2020
Branch Circuit Power Meter with Ethernet Communication
Installation
Figure 8 Connector orientation
Align ribbon
cable key with
connector
keyhole.
Aux CT Installation
Panel 2,
Strip B
Panel 2,
Strip A
Panel 1, Strip B
Panel 1, Strip A
1. Connect 0.333 Vac current transformers (CTs) to the mains or other
conductors, observing local codes regarding bending radius. Refer to the appropriate CT installation instructions for further information.
Figure 9 CT connection
Panel 2 Panel 1
E30 CURRENT SENSOR STRIP
E30 CURRENT SENSOR STRIP
E30 CURRENT SENSOR STRIP
E30 CURRENT SENSOR STRIP
© 2020 Schneider Electric All Rights Reserved.
NOTE: The BCPME measures and reports the phase angle of each voltage input and each CT (when there is active current through the primary of that CT).
11
Branch Circuit Power Meter with Ethernet Communication
DANGER
Installation
Wiring
Z206856-0D
04/2020
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• While removing or installing panels and covers, assure that they do not contact an energized bus.
• NEVER bypass external fusing.
• NEVER short the secondary of a potential transformer.
• Before closing covers and doors, carefully inspect the work area and remove any tools, wire scraps or other objects that may have been left inside the equipment.
Failure to follow these instructions will result in death or serious injury.
NOTE: For all steps in this section, when tightening terminals, apply the correct torque: Aux Inputs: 3.5 to 4.4 in-lb (0.4 to 0.5 N-m); all other terminals: 4.4 to 5.3 in-lb (0.5 to 0.6 N-m).
1. Wire the (optional) 0.333 V Aux CTs to the BCPME (see Figure 10), observing local codes regarding bending radius. Refer to the appropriate CT installation instructions for further information.
Figure 10 Aux CT wiring
CT Input
(0 to 0.333 Vac)
X1 X1 X1 X1
N 3 2 1
X2 X2 X2 X2
CT Input
(0 to 0.333 Vac)
X2 X2 X2 X2
1 2 3 N
X1 X1 X1 X1
2. Connect 2-wire 100 to 277 Vac power to the control power terminals. Observe polarity. Connect voltage lines to the voltage inputs. Provide overcurrent protection and disconnecting means to protect the wiring. Use
EMFP1, EMFP2, EMFP3 fuse packs, or equivalent. Suggested: 0.5 A, time
delay fuses.
12
© 2020 Schneider Electric All Rights Reserved.
Z206856-0D
3-wire (ungrounded)
Corner-grounded
4-wire
3-wire
2-wire
Single-phase
120/240V High-Leg
L2
04/2020
Branch Circuit Power Meter with Ethernet Communication
Installation
Figure 11 Connect to voltage inputs
Voltage taps are shared by both panels.
Delta
L3
N
N
L1 L2 L1
120 V/240 V Delta High Leg (where the center tap of one of the three phase-to-phase transformers is grounded): the BCPME supports these applications, as long as the line-to neutral voltage [especially of the High Leg] does not exceed 300 Vac (as in North American 120/240 V High Leg Delta
congurations).
Voltage Inputs
90 to 300 V 50/60 Hz
N V3 V2 V1
L-N V1 V2/NL-L
Figure 12 Wiring configurations
Delta
L3 L3
X
Delta
L2 L1
Control Power
100 to 277 V 50/60 Hz 15 VA
V1 V2/N
Wye
L3
N
L2 L1
Split-phase
L2
L1
N
N
L1
© 2020 Schneider Electric All Rights Reserved.
In 3-wire (ungrounded) Delta applications, the BCPME supports these applications with the following caveats:
Control Power for the meter cannot exceed 277 Vac. In applications where the L-L voltage is 277 Vac or less (e.g. 208 V line-to-line) it can be connected to two of the phases being monitored without exceeding the limit. For higher voltages (e.g. 480 V line-to-line), this must be supplied from a source that is 277 Vac or less. It could be a separate source or a transformer can be used to step it down from two of the phases being measured.
All of the CT inputs (both branches and Aux inputs) are neutral-referenced. One side of each CT is essentially connected directly to the neutral voltage
input. If this is left oating, the solid-core CT strips, split-core CT adapter boards and all CTs will oat at the same potential (while the panel is energized). This does not present a risk to the equipment as long as it is
within 300 V of ground, but should be considered from a safety perspective in the overall application. The BCPME will provide measurements in this
application with the accuracy specied, with the exception of line-to-neutral
13
Branch Circuit Power Meter with Ethernet Communication Installation
Z206856-0D
04/2020
voltages, which will be calculated and reported, based on a derived virtual neutral voltage, even though they are not relevant.
Corner-grounded delta: the BCPME does not support these applications at any voltage level.
The BCPME supports measurement of all 4-wire Wye, 3-wire split-phase and
2-wire single phase and congurations that operate between 90 and 300 Vac
line-to neutral.
3. Connect the 2-wire Modbus RS-485 network.
Figure 13 RS-485 connection
RS-485
S
+
S
+
4. Mechanically secure the RS-485 cable(s) where they enter the electrical panel.
5. If using Modbus RTU or BACnet MS/TP protocol, connect a serial cable(s) from the RS-485 loop to the serial connector on the BCPME. Connect all RS-485 devices in a daisy-chain, and properly terminate the chain.
Figure 14 Daisy chain connection
120 Ω terminator where specied
RS-485
S
+
S
+
RS-485 cable
by the applicable standard
Two sets of connections are provided to simplify daisy-chain connections and enable retention of each wire.
14
© 2020 Schneider Electric All Rights Reserved.
Z206856-0D 04/2020
Branch Circuit Power Meter with Ethernet Communication
Installation
Follow all applicable wiring and termination connection guidelines for the standard in use. Note that while both the Modbus RTU and BACnet MS/ TP standards identify requirements for RS-485 line polarization/bias and termination, the value and placement of these resistors varies for each standard. The BCPME does not implement any RS-485 line polarization/ bias or termination internally. Shield the RS-485 cable using twisted-pair wire. Use cable that is voltage-rated for the installation. The shield is not internally connected to Earth Ground. Connect the shield to Earth Ground somewhere on the RS-485 bus (single point connection only).
6. Connect an Ethernet cable to a local PC. Secure a ferrite lter (included) around the Ethernet cable to ensure the device meets emission
requirements. Use the PC to congure the gateway (next section of this
document). Note: 100 to 277 Vac must be added to control power inputs to
supply power to the gateway during conguration.
Figure 15 Ethernet port location
7. Once congured, disconnect the local PC. If desired (and the device is congured for operation on the network), connect the BCPME directly to the network for ongoing access to the GUI even if primarily using a serial
protocol to access and control the BCPME.
© 2020 Schneider Electric All Rights Reserved.
15
Branch Circuit Power Meter with Ethernet Communication
A qualified person is one who has skills and knowledge related to the construction and operation of this electrical equipment and installations, and has received safety training to recognize and avoid the hazards involved.
If this product is used in a manner not specified by the manufacturer, the protection provided by the product may be impaired. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
DANGER
Installation
Gateway Configuration
Z206856-0D
04/2020
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices. See NFPA 70E in the USA, CSA Z462 in Canada, or applicable local codes.
• Read and understand the instructions before installing the product. Follow the instructions during installation.
• Installation, wiring, testing or service must be performed only by qualified persons in accordance with all applicable codes and regulations.
• Install the product in an appropriate electrical and fire enclosure per local regulations.
• Do not use the product for life or safety applications.
• Do not install the product in hazardous or classified locations.
• Do not exceed the product’s ratings or maximum limits.
• The product may use multiple voltage/power sources.
• Turn off ALL power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm that all power is off.
• Do NOT depend on the product for voltage indication.
• Products rated only for basic insulation must be installed on insulated conductors.
• Current transformer secondaries (current mode) must be shorted or connected to a burden at all times.
• Remove all wire scraps and tools, replace all doors, covers and protective devices before powering the equipment.
Failure to follow these instructions will result in death or serious injury.
Accessing the Graphical User Interface (GUI)
16
NEC Article 100
Note: The screen captures in this section were taken using Windows 7; other operating systems will look different.
If the BCPME IP address parameters are already congured to work on the network and is being accessed from a PC on that same network, then open a web browser and enter the IP address of the BCPME into the address/URL eld on the browser. Press enter. On the rst time login to the device GUI, follow the
instructions in the section "Accessing the GUI for the rst time with rmware
version 1.027 or higher" to congure the web server's security settings and log in. If already congured, the GUI login page appears. Enter the username and password and click Login. The GUI launches and appears, as shown, in the
browser window below.
Note: Devices with rmware version 1.026 and earlier will not have a login page
and will not require a password.
© 2020 Schneider Electric All Rights Reserved.
Z206856-0D 04/2020
Branch Circuit Power Meter with Ethernet Communication
Installation
If the IP address parameters are not congured for the network, connect a PC
directly and access the GUI from it as follows:
1. Connect a standard Ethernet cable between a PC and BCPME if not
already connected. Secure a ferrite lter (included) around the Ethernet
cable to ensure the device meets emission requirements.
2. Temporarily change the IP address of the PC to a static value on the same subnet as the BCPME. For example: If the BCPME is set to its factory default IP address of 192.168.1.24, set the PC to an unused static IP address on the 192.168.1.xxx subnet (where xxx is any value between 1 and 255, except 24). Set the subnet mask to 255.255.255.0.
a. Open the Control Panel:
b. In the Control Panel, select Network and Sharing Center. In the Sharing
Center, select Change Adapter Settings in the list at the upper left corner.
c. Select the connection for the network that the BCPME is connected to.
© 2020 Schneider Electric All Rights Reserved.
17
Loading...
+ 49 hidden pages